Chapter10 Cabin system
Transcription
Chapter10 Cabin system
CHAPTER 10 CABIN SYSTEM CABIN SYSTEM 1. STRUCTURE 1.1 HEATER C45WA01A (1) Radiator union (7) Heater Switch (2) Heater Hose (In-line) (8) Warm Air Outlet (3) Heater Hose (Out-line) (9) Battery (4) Heater system (10) Slow Blow Fuse (5) Duct Hose (11) Main Switch (6) Grill (12) Fuse • The heater components are as shown in the illustration. • Use the engine coolant and release hot air outside the cabin through the heater unit. • When using the air conditioner, close the heater valve. DC45-W00 Nov. 2004 10-3 CHAPTER 10 DK45S(DK451) 1.2 AIR-CONDITIONER C45WA02A (10) Compressor Relay (1) Compressor (6) Air-con Control Switch (2) Receiver Driver (7) Warm Air Outlet (11) Compressor Relay (3) Condensor (8) Fuse (12) Main Switch (4) Air-con Unit (9) Pressure (13) Thermostat (5) Air-con Duct 10-4 DC45-W00 Nov. 2004 CABIN SYSTEM An air-conditioner inside the cabin is operated in a ventilation method. In cold weather, the air that is warmed by the pipe getting the heat from the engine is supplied through the heater unit to the cabin. If the temperature outside air is excessively high (for example in summer), driving in the cabin is uncomfortable and so the air-conditioning system of the compressor begins to operate, lowering the temperature inside the cabin. Refrigerant in the air-conditioner unit circulates around the closed circuit with the pressure loaded. R134a (HFC) is used as refrigerant here. This refrigerant undergoes the change of pressure and temperature at the specified point in the circuit. The compressor is driven through the engine by means of the belt, keeping the upper side of the vaporizer that draw in vapor in low pressure, compressing the refrigerant in gas state obtained thereby, and leading it via the condenser finally to the air-conditioner unit. As the air passage crosses the condenser located in the front of engine’s radiator, the refrigerant is cooled and condensed between them. The refrigerant in liquid state will be then filtered in the receiver drier. Thereby humidity and impurities are removed from the receiver drier. The receiver drier is also used as a temporary repository of refrigerant. R134, liquid refrigerant under high pressure is led to the expansion valve controlling the flow rate, and its pressure will fall down here radically to vaporizable state. This low-pressure fluid starts to vaporize and condense in the heat exchanger, that is, the vaporizer. The air of high temperature and humidity in the cabin will be sent to the vaporizer by the fan, and be forced to return into the cabin after being cooled by contacting the vaporizer. Humidity in the air is compressed outside the vaporizer, and discharged in the state of water through the drainage hose attached to the vaporizer’s discharge fan, resulting in the reduction of humidity in the cabin. Gaseous refrigerant returns to the compressor, which now completes the cycle. Main components of an air-conditioning system are as follows: • Refrigerant • Vaporizer • Compressor • Condenser • Receiver Drier • Expansion Valve DC45-W00 Nov. 2004 10-5 CHAPTER 10 DK45S(DK451) 2. TROUBLE SHOOTING You can simply find the troubles by visual and sound check during daily inspection and season-in inspection. The early finding of troubles and proper repair enable to extend the lifetime of equipment. A. VISUAL AND AUDIO CHECK 1. Noise caused by loosened V-belt When the friction noise is generated by loosened or worn out V-belt, adjust the velt tension. 2. Abnormal noise around compressor Check the compressor bolts and mounting bracket bolts for loosened and retighten them if needed. 3. The abnormal noise inside the compressor results from the broken suction valve. Disassemble, Repair, or replace it. 4. Mud or dust adhered to the condenser As the mud or dust reduce the radiation performance remarkably which affects the cooling capacity, it is required to wash out the mud or dust with water. Make sure not to damage the condenser fins. 5. Contamination on the connecting area of piping and condenser The contaminated area by oil indicates the refrigerant leaks with oil. If the contaminated area is found, check with leak tester and retighten or replace as necessary. Carefully check the gasket, O-ring, and shaft seal in condenser. 6. Noise from blower fan motor If the fan blower motor generates the noise or do not rotate properly, replace it with new one. The foreign material inside the blower or insufficient tightening may cause this noise; so carefully check before starting repair work. 10-6 DC45-W00 Nov. 2004 CABIN SYSTEM B. TROUBLE DIAGNOSIS Insufficient Cooling Check discharging air flow Air flow is insufficient or no air flow Discharging air flow normal Check the fan motor's operation Inspect discharging air temperature Motor does not operate Only air flow is insufficient FUSE wiring short Check motor control circuit Air temperature normal Air temperature high abnormally Check insulation state Check H/T COMP rotation abnormal Check belt Tension normal Check the magnetic clutch EVAP Frozen There is a foreign material in the suction grille Unfreeze EVAP (Turn A/C S/W OFF into FAN 3) Remove the foreign material Inspect the refrigerant in the sight glass Check THERMO AMP Check COMP rotation COMP rotation abnormal Check SIGHT, GLASS There is no air bubble Measure pressure Tension Loosen Adjust tension There is no air bubble Measure pressure Faulty clutch Abnormal rotation of COMP Inspect the clutch engagement There is a air bubble Charge refrigerant There is a air bubble Check refrigerant capacity and air mix state Inspect wiring connection Faulty electric system in MAGNET Inspect battery voltage drop, control switch and earth Both high & low pressure normal A/C SYSTEM malfunction Faulty A.C mix door Faulty VENT, intake door Both high & low pressure is high Excessive refrigerant Foreign material in COND. FAN Excessive oil in the pipe Inlet temperature of COMP. is low Airtightness and close adhereness is bad in EVAP. thermostatic unit Noise High pressure is low & low pressure is high Inspect temperature of EVAP. outlet & COMP. inletCOMP. inlet No temperature difference & Fast pressure balance COMP. discharging defference malfunction Inspect the point where occurred COMP Excessive oil Faulty bearing Faulty clutch DC45-W00 Belt Other Faulty Belt Faulty belt line alignment Check belt tension Nov. 2004 10-7 CHAPTER 10 DK45S(DK451) C. ADVANCED TROUBLESHOOTING a . Poor Cooling (A) Fan motor doesn’t rotate Causes Checking Methods Action Blown Fuse Check the A/C fuse Replace Open wiring or poor contact Check the ground and missing of key boss Repair the failure or connect properly Fan Motor Failure Check two leads from motor with circuit tester. Failure if no current Replace Open in Resistor Check the continuity of resistor with circuit tester. Failure if no continuity Replace Fan Switch Failure Check the fan revolution in each stage. Replace (B) Fan motor is normal but airflow is not sufficient Causes Checking Methods Action Obstacles in the inlet of suction of vaporizer Contamination of vaporizer Removal of obstacles and cleaning Air leakage Check the assembly status of cooling unit case Modification or adjustment Poor thermo-switch Check whether the vaporizer is frozen with a circuit tester Replac (C) Airflow is sufficient and compressor runs normally but cooling is poor Causes 1. Excessive/insufficient refrigerant Checking Methods Action Touch the high and low pressure pipes by hand after 5~10 minutes from turning on A/C. Check the refrigerant flows and level by monitoring sight glass. 2. Insufficient refrigerant The difference of temperature is too Repair the leakage area and small. Bubbles or foggy flows can be charge to specified level. seen through sight glass. 3. Excessive refrigerant The high pressure is too high and Discharge the refrigerant cannot be seen any bubbles through gradually till you can see bubble sight glass even when cooling the through sight glass. condenser with water. 4. Normal pressure High pressure: 14~15 kg/cm 2G Low pressure: 1.5~2.0 kg/cm 2G Ambient temperature: 30~35 ¡ÆC Engine speed: approx. 2000 rpm 10-8 DC45-W00 Nov. 2004 CABIN SYSTEM Causes Checking Methods Action 4-1. Low pressure is too high 1) Faulty thermo switch Magnetic clutch is off before the extracted Adjust or replace air temperature fully falls down. 2) Faulty compressure gasket or valve When magnetic clutch is off, the high Repair or replace and low gauge pressure is balanced immediately. 3) Poor contact of thermal case in expansion valve Frost is generated on connecting area Adhere the thermal case to low of compressor and its temperature is pressure pipe lower than that of outlet pipe. 4) Too widely open expansion Same as above. No changes in pres- Replace sure regardless of thermal case’s valve existence. 5) Clogged compressure suction filter The low pressure hose is not cold and Clean filter only connecting area of compressor is cold. 4-2. Low pressure is too low 1) Insufficient refrigerant Refer to “Insufficient refrigerant”. Add refrigerant 2) Clogged receiver drier The difference of temperature between Replace receiver drier outlet ports is significant. Frost is generated on the tank. 3) Clogged expansion valve The inlet port of expansion valve is cold Replace expansion valve and frost is generated on the tank. 4) Gas leaks from thermal The outlet port of expansion valve is not case in expansion valve cold and low pressure gauge indicates Replace expansion valve negative pressure. 5) Clogged and damaged pipings When the pipings are clogged, low Clean or replace pipings pressure may be low or the gauge may indicate negative pressure. 6) Faulty thermo switch Frozen vaporizer Adjust or replace Contaminated condenser or clogged, Wash, repare or replace the fan 4-3. The high pressure is too high 1) Poor cooling of condenser faulty cooling fan, blown fuse, open wiring and poor contact 2) Excessive refrigerant Refer to “excessive refrigerant”. Adjust refrigerant level Vacuuming, recharge refrigerant 3) Air intrusion into cycle 4-4. The high pressure is too low 1) Insufficient refrigerant DC45-W00 Nov. 2004 Refer to “Insufficient refrigerant”. Add refrigerant 10-9 CHAPTER 10 DK45S(DK451) (D) The compressor does not rotate or hard to rotate Causes Checking Methods Action 1. Loosened belt Too large belt vibration Adjust belt tension 2. Internal failure of compressor Slippery belt Repair or replace 3-1. Nattery boltage drop Slipping when rotating Charge the battery 3-2. Layer short of coil Slipping when rotating Replace magnetic clutch 3-3. Oil intrusion into clutch Slipping due to contaminated magnetic Replace or clean the clutch clutch area surface Contact each other when pushing the Adjust the clearance or replace 3. Magnetic clutch problem surface 3-4. Too large clearance between clutch plate and clutch plate clutch wheel 3-5. Open coil Cannot contact when pushing the clutch Replace compressor and circuit tester doesn’t move when checking the lead of ports. 3-6. Open wiring or poor contact to ground 3-7. Check the wiring parts Cannot contact regardless operation, Repair check the ground and connecting area Check the continuity of pressure switch, Replace thermo switch and relay b. Poor Heating (A) Fan motor doesn’t rotate: refer to step 1 in section 2-(1) (B) Fan motor doesn’t rotate: refer to step 1 in section 2-(1) Causes 1. Too large ventilation resis- Checking Methods Action Check the duct for clogged or damaged Repair Check the duct connecting area, Check Repair tance 2. Air leaks at duct connecting the duct seal and assembled conditions area (C)Airflow is sufficient but hot air cannot be generated Causes 1. Too low coolant temperature Checking Methods Check the coolant temperature after Action Replace thermostat heating operation 2. Too low coolant level Check the coolant level in radiator Add coolant 3. Too low coolant circulating Check the pipings for clogged Air bleeding, repair Check the operation of air mix door and Adjust or replace control cable, seal condition check the seal volume 4. Clogged heater core (D)Airflow is sufficient but hot air cannot be generated Causes Checking Methods Action 1. Faulty seal Check the leaks from heater core, core, Replace or repair 2. Too large play in connecting connecting area, hose, and pipings Replace or repair area Same as above 3. Porous heater core Check heater core 10-10 Replace DC45-W00 Nov. 2004 CABIN SYSTEM D. TROUBLESHOOTING BY MANIFOLD GAUGE The manifold gauge is used to check the high and low pressure in cooling cycle, and troubles in certain cycle can be found by reading the measured value. a. Normal Condition 1. Connect the manifold gauge to high and low pressure connectors. 2. Exhaust the air from charging hose at manifold gauge connecting area. * CONDITION Ambient temperature: 30°C ~ 35°C (86°F ~ 95°F) Engine speed: 2000 rpm Blower fan: HI (Maximum speed) Thermo switch (Coldest) * REFERENCE Low pressure side: 1.5 ~ 2.0 kgf/cm 2 (0.15 ~ 0.19 Mpa, 21.3 ~ 28.4 psi) High pressure side: 14.5 ~ 15 kgf/cm2 (1.42 ~ 1.47 Mpa, 206.2 ~ 213.3 psi) C45WA03A b. Insufficient Refrigerant 1. Status: Not cool 2. Symptoms: - The pressure of high/low pressure side is low. - The bubble in sight glass is seen. - Discharging temperature doesn’t fall down. 3. Cause: Refrigerant leakage 4. Action: Check with gas leak tester and repair the leaking part and add to specified level. * REFERENCE Low pressure side: 0.8 kgf/cm 2 (0.08 Mpa, 11.37psi) High pressure side: 8 ~ 9 kgf/cm2 (0.78 ~ 0.88 Mpa, 113.8 ~ 128.0 psi) C45WA04A c. Excessive Refrigerant, Poor Condenser Cooling 1. Status: Not cool 2. Symptoms: - The pressure of high/low pressure side is high. 3. Cause: - Increased pressure due to excessive charging the refrigerant - Poor cooling performance of condenser - Loosened A/C belt 4. Action: - Clean the condenser - Check and adjust the fan belt and condenser motor - Check the refrigerant level CAUTION • Discharge the refrigerant slowly from the low pressure side of manifold gauge while checking the refrigerant level by monitoring the pressure gauge and sight glass. This may caused by contamination of radiator. DC45-W00 Nov. 2004 C45WA05A * REFERENCE Low pressure side: 2.5 kgf/cm2 (0.24 Mpa, 35.5 psi) High pressure side: 20 kgf/cm2 (1.96 Mpa, 284.5 psi) 10-11 CHAPTER 10 DK45S(DK451) d. Air Intrusion into Cycle 1. Status: Not cool 2. Symptoms: - The pressure of high/low pressure side is high. - The low pressure pipe is not cold. 3. Cause: - Air intrusion into cooling cycle - The measured value is shown in left figure. 4. Action: - Read the measured value in charginf process while vacuuming - Replace the receiver drier after long operation with air intruded. - Check the contamination of refrigerant and oil. C45WA06A * REFERENCE Low pressure side: 2.5 kgf/cm2 (0.24 Mpa, 35.5 psi) High pressure side: 23 kgf/cm2 (2.25 Mpa, 327.1 psi) e. Faulty expansion valve 1. Status: Not cool 2. Symptoms: - The pressure of high/low pressure side is high. 3, Cause: - Poor expansion valve, poor refrigerant flow control due to improper assembly of thermal case 4. Action: - Check the assembled conditions, position and adiabatic in thermal case. if normal, replace the expansion valve. * REFERENCE C45WA07A Low pressure side: 2.5 kgf/cm2 (0.24 Mpa, 35.5 psi) High pressure side: 19 ~ 20 kgf/cm 2 (1.86 ~ 1.96 Mpa, 270.2 ~ 284.5 psi) f. Poor Compression 1. Status: Not cool 2. Symptoms: - The pressure of low pressure side is high while the pressure of high pressure side is very low. - When stopping the operation, the pressure of high/ low pressure shall be the same immediately. 3. Cause: - Poor compressor gasket, poor compressor caused by the broken suction valve. 4. Action: - Disassemble and repair the compressor. C45WA08A - Replace the compressor assembly. * REFERENCE Low pressure side: 4~6 kgf/cm2 (0.39 ~ 0.59 Mpa, 56.9 ~ 85.3 psi) High pressure side: 7~10 kgf/cm2 (0.69 ~ 0.98 Mpa, 99.6 ~ 142.2 psi) 10-12 DC45-W00 Nov. 2004 CABIN SYSTEM g. Moisture Intrusion Into Cooling Cycle 1. Status: Sometimes cool, sometimes not cool 2. Symptoms: - The pressure of low pressure side is sometimes negative or sometimes returning normal. 3. Cause: - The moisture inside cooling cycle is frozen which makes the cycle closed in the expansion valve and return to the normal by melting of ice. 4. Action: - Replace the receiver drier. - Repeat the vacuum working 2 ~ 3 times. Charge the proper amount of refrigerant. * C45WA09A REFERENCE Low pressure side: Vacuum High pressure side: 7 ~ 15 kgf/cm 2 (0.69 ~ 1.47 Mpa, 99.6 ~ 213.3 psi) h. Poor Recirculation of refrigerant 1. Status: Nots cool (sometimes cool) 2. Symptoms: - The pressure of low pressure side is negative and the pressure of high pressure sidde shows the pressure 5 ~ 6 kgf/cm 2 (0.49 ~ 0.59 Mpa, 71.1 ~ 85.3 psi) - Frost or dew forming in the receiver drier or the front/rear pipe connecting section of expansion valve. 3. Cause: - The cycle is closed by moisture freezing or dust in cooling cycle. C45WA10A - The cycle is blocked due to the poor thermal case of expansion valve. 4. Action: - Stop the operation once to check the clogging by moisture or dust. - If moisture has been found, perform the vacuuming. - Detach the expansion valve and remove the dust by compressed air. - Replace the receiver drier. * REFERENCE Low pressure side: Vacuum High pressure side: 6 kgf/cm 2 (0.59 Mpa, 85.3 psi) DC45-W00 Nov. 2004 10-13 CHAPTER 10 DK45S(DK451) 3. INSPECTION AND ADJUSTMENTS WARNING 1. Do not release refrigerants to the outside. 2. The refilling of air conditioner gas deals with high pressure gas, and because of the dangers, it should only be performed by specialists. 3. To prevent accidents like the loss of sight during work, you must wear protective glasses, gloves etc. 4. Store the service container in a cool dry place, and do not drop or knock it. 5. The air conditioner gas and equipment must exclusively use HFC-134a, and never use R12. 6. Use the UCON 488 compressor oil (265cc) 7. Do not work where there is poor ventilation. 8. Air conditioner gas in non-hazardous and non-toxic, but if it comes into contact with high temperatures it breaks down and forms harmful substances. 10.Over refilling of gas is a cause for bad cold air, overheating etc. 11. Do not turn the service container up side down. 12.Each refill hose connections must be firmly attached by hand. (Do not attach with pliers and the like) 13.When you connect the refill hose to the service container, check for damages in the packing. IMPORTANT • After disassembling the pipe and it is left out for more than a week, change the receiver. • When disassembling the pipe or hose of the cooler, gas leakages and dust penetration must be prevented by plug or cap mounting attachments. When connecting the pipe, compressor oil must be applied to the O ring. • When replacing condensers, evaporators, receivers, dryers etc. the compressor oil must be replenished with the following amount. 10-14 DC45-W00 Nov. 2004 CABIN SYSTEM A. LEAKAGE TEST 1. Using an extraction detector, check for leakages in each section. 2. If a gas leakage is detected, refer to the next gas emission stage (reference page…) and repair the leakage section as outlined. IMPORTANT • When disassembling parts, they must be thoroughly cleaned and sealed. (When assembling) • Apply refrigerant lubrication oil to the O ring of the connection area. • For gas vacuuming and refilling (reference page ), refer to the relevant section and perform as outlined, and after checking for leakages complete the refilling. C45WA11A (1) Leak Tester B. DISCHARGING SYSTEM IMPORTANT • Do not discharge refrigerants to the outside. • HFC-134a equipments must be used exclusively. • Check if the service hose is properly connected. WARNING You must wear protective glasses and gloves. 1. Attach the manifold gavage and the recycling machine to the refrigerant lines as shown. CAUTION • Be careful not to switch the connections for the low and high pressure valves. C45WA12A (1) Low Pressure (2) Low Pressure (3) Recycling Machine 2. Open the high pressure valve slowly to release the refrigerant to the recycling machine. CAUTION • Open the valve slowly, while checking to see that refrigerant is not leaking out. 3. When the manifold gauge dial falls below 3.5 kg/ cm 2 (50 psi), slowly open the low pressure valve. 4. Open both the high and low pressure valves slowly until the manifold gauge dials indicates 0 kg/cm 2 (0 psi). DC45-W00 Nov. 2004 10-15 CHAPTER 10 DK45S(DK451) C. EVACUATING 1. Connect the manifold low pressure service hose (red) and the high pressure service hose (blue) to the compressor low pressure end and high pressure end of the service valve. 2. Connect the manifold center hose (green) to the vacuum pump. 3. Open the low pressure & high pressure valves, and operate the vacuum pump in accordance with the instructions to perform vacuuming. 4. Perform for about 15 minutes and when the low pressure gauge reaches the lowest safe vacuum level (750mmHg) stop the vacuum pump, close the manifold low pressure, high pressure valves and leave it for at least 5 minutes and check that the gauge does not reach 0. 5. If the gauge reaches close to 0, there is a leak somewhere, so after checking and repairing the pipe connections, re-perform the vacuuming and check that there are no gas leakages. 10-16 C45WA13A (1) Low pressure (3) Vacuum pump (2) High pressure (4) Air (A) Open DC45-W00 Nov. 2004 CABIN SYSTEM D. CHARGING. IMPORTANT • Refill the gas after gas has been released and vacuuming has been performed. • When refilling gas, do not start the engine and perform from the high pressure end first, and then start the engine and put in the prescribed amount. WARNING • When refilling gas on the high pressure end, do not start the engine. This could cause rupture from the back flow and as there are no refrigerants it could cause damage to the compressor. C45WA14A (1) High Pressure Gauge (2) Low Pressure Gauge 1. Open the high pressure valve and put in about……. of refrigerant. 2. Close the high pressure valve and check for any gas leakages. (3) Refrigerant (A) High pressure (open) (B) Low pressure (close) WARNING • Because the engine is turned on when refrigerant is put into the low pressure end, do not open the high pressure valve. • When replacing the service can, release the air from the charging hose (green). 3. After checking that the high pressure valve is closed, start the engine and take it to about 2000rpm. 4. Open the interior door and adjust the temperature control lever to cool, and the fan switch to high. 5. Open the low pressure valve and put in refrigerant until the bubbles disappear from the receiver window. 6. When the refrigerant has been filled, close the low pressure valve and stop the engine. 7. Perform refrigerant leakage tests. - Refrigerant insertion quantity : 700g (1.54 lbs) - Manifold gauge pressure {when the exterior temperature in 30 degrees (86°F)} - High pressure : 14.5 ~ 15 kgf/cm2 (1.42 ~ 1.47 Mpa, 206.2 ~ 213.3 psi) - Low pressure : 1.5 ~ 2.0 kgf/cm2 (0.15 ~ 0.19 Mpa, 21.3 ~ 28.4 psi) DC45-W00 Nov. 2004 10-17 CHAPTER 10 DK45S(DK451) E. DISASSEMBLING AND CHECK a . Draining Coolant CAUTION • Never open radiator cap when the coolant’s temperature reaches boiling point. • When opening the cap, turn the cap slightly to let off pressure and then open it. 1. Stop the engine and cool the water fully. 2. Open the drain cock and radiator cap to drain the water completely. 3. Lock the drain cock, after the coolant drained completely. (1) Drain Cock (Filling) • C45WA15A (2) Radiator Cap Fill water up the point between “Full” and ”low” mark on the recovery water tank. Coolant capacity 8.6 (2.3 U.S.gal) C45WA16A (1) Recovery Tank (A) FULL (B) LOW b. Disassembling Hood, Side Cover and Battery 1. Open the hood and disconnect battery (-)cable. 2. Disconnect the headlamp wiring (3). 3. Remove the hood (1). 1 3 4. Remove the side cover (4). 4 REFERENCE: • 2 When disconnecting battery cable, (-) cable at first, but link (+) cable at first when assembling. C45WA17A 10-18 (1) Hood (3) Head Lamp Wiring (2) Battery (-) Cable (4) Side Cover DC45-W00 Nov. 2004 CABIN SYSTEM c. Disassembling Air Conditioner Hose, Heater Hose, Steering Hose, Wire, And Hood Wiring Assembly 1. Remove the steering hose T, P, L, R. 2. Remove the PTO hydraulic pipe1 and 4 from connector. 3. Remove the pipe bracket 2. 4. Remove the air conditioner hose valve A and B under cabin, and then detach hose. 5. Remove the heater hose. 6. Remove the governor wire. 7. Remove the pipe band and separate suction hose and suction pipe 3. C45WA18A (1) Steering Hose (L) (8) Air Conditioner Vlave (Assembling) (2) Steering Hose (R) (9) Heater Hose 1 • (3) Steering Hose (P) (10) Heater Hose 2 (4) Steering Hose (T) (11) Accelator Cable (5) Hydraulic Pipe (3) (12) Suction Hose (6) Hydraulic Pipe (4) (13) Suction Pipe 3 When assembling PTO hydraulic pipe 1 and 4, apply pipe sedent (LOCTITE #577 or equivalent). Assembling torque of steering hose T, P, L, R 24.5 N·m 2.5 kgf·m 18.1 lbf·ft Assembling torque of PTO hydraulic pipe 1 and 4 1/6~1/3 revolution after the point of rapid increasing torque of nut. Assembling torque of air conditioner coupler Pipe band tightening torque 9.8 N·m DC45-W00 Nov. 2004 (7) Pipe Bracket 1 kgf·m 7.2 lbf·ft 10-19 CHAPTER 10 DK45S(DK451) d. Disassembling cabin 1. Remove the mat. 2 2. Loosen the bolt and separate seat assy and bottom plate. 3. Pull of joystick lever from support and push it out of cabin. 4. Remove the main shift lever. 5. Remove the range shift lever. C45WA20A (1) Mat (4) Main Shift Lever (2) Seat Assy (5) Range Shift Lever (3) Joystick Lever 6. Remove the PTO shift lever rod. 7. Remove the differential pedal rod. 8. Remove the MLS valve rod. 9. Remove the hydraulic control lever rod (position, draft control lever). 10.Remove the double action valve lever rods. C45WA21A (1) PTO Shift Lever Rod (2) Differential Pedal Rod (3) MLS Valve Rod (4) Double Action Valve Lever Rods 11. Remove the brake rod(LH / RH). 12.Remove the clutch rod. 13.Remove the rubber cover 2 and disconnect the suttle lever and cabin wiring. C45WA22A (1) Brake Rod (3) Rubber Cover 2 (2) Clutch Rod 10-20 DC45-W00 Nov. 2004 CABIN SYSTEM 15.Support the cabin hanging on hoist with nylon rope. 16.Unlock the bolt assembling cabin. 17.Remove the cabin from tractor. REFERENCE: • Disassemble cabin slowly checking if there is any obstacle. (Assembling) • Assemble washer, cabin rubber, etc. at the original place. Torque of bolt and nut assembling cabin 123.6 ~ 147.1 N·m 12.6 ~ 15.0 kgf·m 91.1 ~ 108.5 lbf·ft C45WA23A F. DISASSEMBLING THE COMPRESSOR 1. Open the hood. 2. Release the air conditioner gas.(refer to page 1015) 3. Remove the air conditioner hose. Seal with a stopper when detaching. 4. Disassemble the wiring. 5. Remove the compressor belt. 4. Loosen the bolt and remove the compressor. (When assembling) • Set the compressor belt tension (refer to page 129) & refill the air conditioner gas (refer to page 10-17). C45WA24A - Compressor oil quantity : 150 cc - Tightening torque of air conditioner hose : 4.9 ~ 5.7 kgf·m (48.1 ~ 55.9 N·m, 35.4 ~ 41.2 lb·ft) - Tightening torque of compressor : M8 : 2.4 ~ 2.8 kgf·m (23.6 ~ 27.4 N·m, 17.4 ~ 20.2 lb·ft) M10 : 4.9 ~ 5.7 kgf·m (48.1 ~ 55.9 N·m, 35.4 ~ 41.2 lb·ft) DC45-W00 Nov. 2004 10-21