Service Bulletin 3-01
Transcription
Service Bulletin 3-01
SERVICE REMINDER INSTALLATION NUMBER: DATE: SERVICE Tampa Sales District The Trane Company 9208 Palm River Road Suite 301 Tampa, FL 33619 (813) 621-707 0 3-01 10/11/01 TO: ALL AUTHORIZED TRANE DEALERS AND SERVICERS SUBJECT: SINGLE STAGE INTEGRATED FURNACE CONTROLS (IFC) SOLDER TERMINAL FAILURES (CNT02789, CNT02891, CNT03076) MODELS AFFECTED: SEE TABLE BELOW PART NUMBER MODEL FAMILY CNT02789 (CNT02183 Repl.) TDE-A-K2 thru L0 CNT02789 TUE-A-K2 thru L0 CNT03076 TDD-C-D-D0 thru E0 CNT03076 TUD-C-J0, J1 CNT02854 / CNT03076 TDX/TUX-C-C0 thru C2 CNT02891 (CNT02183 Repl.) TDC/TUC-C-B6, B7 DATE CODE RANGE M47 - R19 M43 - R29 P15 - R22 P15 - R22 N30 - R22 N31 - R31 INTRODUCTION: Since the beginning the 2nd quarter of 1999, field complaints reported failures of the “K1” relay powering the circulating blower on the furnace controls CNT02789 (particularly in downflow models). More recently, similar reports have been received on other single stage furnace models (see list above). The failure appears as burned solder joints of the relay pins on the backside of the PC board (See photos on last page). The symptom will be intermittent or no circulating blower operation. DISCUSSION: The cause of failure was determined to be thermal stress induced by high temperature swings during cycling. This is prevalent on downflow furnaces but has been witnessed on upflow furnaces. CORRECTIVE ACTION FACTORY: 1. The use of CNT02789 has been suspended in downflow TDE models. (See FURN-TRN-SB-11). The downflow units have been built with CNT02183. New model number TDE-A-L1 identifies this change. 2. FIELD: IFC’s CNT02789, CNT02891 and CNT03076 have been redesigned to withstand the thermal stresses mentioned above. The date codes on the controls for improved design are 0019 for the CNT03076 and 0023 for CNT02789 and CNT02891. See the table in the heading of this bulletin for the corresponding furnace production date codes. Effective with date code Z373 (9/12/01), TDE-A-L1 will again use CNT02789. For upflow models, this is a “Fix-On-Fail Only” bulletin. Because of the higher level of failures experienced in downflow models, the control may be replaced prior to failure where customer satisfaction is at risk. In case of CNT02789 or CNT02891 failure, the current replacement will be CNT02183. This will change in the near future (back to the original IFC). Special instructions for replacement of the control on the TDE-A-L0 are included in General Service Bulletin FURN-TRN-SB-11. See the table on P.2 for proper control selection. Special Notes: 1. All controls replaced “in warranty” must be returned to the parts distribution outlet to obtain credit. Also, “out of warranty” controls exhibiting the fault described above must be returned to obtain credit under this bulletin. 2. ISSUED BY: All material and labor claims for this fault must be cleared with the local Field Service Representative. No claims are to be made against this bulletin for anything other than the failure described in the text above and photo on p.3. AFTER SALES SUPPORT - TRENTON IFC-TO-FURNACE MODEL FAMILY CROS S REFERENCE MODEL FAMILY Approximate First Production Date (Date Code) TRANE P/N W-R P/N Trane DWG# IGN TYPE ONE STAGE IFC FCA/FUA-A-A0…A1 & CUD-A-A1…A3 *DE/*UE-A-K0…K1 & FCA/FUA-A-E0 & KIT03793 *DE/*UE-K2 and later & CUB XE-80 *DD/*UD-C-A1…B0 XE-80 *DD-C-C0...C1 & *UD-C-H0…H1 XE-80 *DD-C-C3...C4 & *UD-C-H3…H4 XE-80 *DD-C-E0 and later & *UD-C-J0 and later XE-90 XE-90 XE-90 XE-90 XE-90 XE-90 *DC/*UC-C-A, *DX/*UX-C-A *DC/*UC/*DX/*UX-C-BO …B2 *DC/*UC/*DX/*UX-C-B *DC/*UC/*DX/*UX-C-B and later *DX/*UX-C-C0 *DX/*UX-C-C1 and later 1991 Mar, 11, '96 CNT01309 CNT02181 50A50-405 50A50-571 D340035P01 SiC D330927P01 SiC Nov. '97 (M47 ) 1991 July '95 April 29, '96 (L17) FW15-99 (P15) CNT02789 CNT01309 CNT01848 CNT02182 **CNT03076 50A55-571 50A50-405 50A50-471 50A50-473 50A65-475 D341122P01 D340035P01 D340774P01 D330930P01 D341396P01 SiC SiC SiC SiC SiNi Nov. '92 July '95 April 29, '96 (L17) July, '98 (N31) July, '98 (N30) April '99 (P17) CNT01616 CNT01849 *CNT02183 **CNT02891 CNT02854 **CNT03076 50A50-406 50A50-472 50A50-474 50A55-474 50A65-474 50A65-475 D340354P01 D340790P01 D330934P01 D341235P01 D341213P01 D341396P01 SiC SiC SiC SiC SiNi SiNi STAGE IFC ( STANDARD MODELS ) TWO XL-80 *DD/*UD-R XL-80 *DD/*UD-R XL-80 *DD/*UD-R 1991 April 29, '96 (L17) Sept. '99 (P38) CNT01308 50A51-405 CNT02184 50A51-495 **CNT03077 50M61-495 TWO STAGE IFC ( VARIABLE XV-80 *DD/*UD-R9V-A1 XV-80 *DD-R9V-B0...C3 & *UD-R9V-A1...H0 XV-80 *DD-R9V-C4 & *UD-R9V-H4 XV-80 *DD-R9V-D0 & *UD-R9V-J0 and later XV-90 *DY/*UY-R9V-A0…A3 XV-90 *DY-R9V-A4, *UY-R9V-H4 XV-90 *DY/*UY-R9V-V XL-90 *DX/*UX-R-V 1992 Oct. '95 (K43) Sept. '96 Sept. '99 (P38) Aug. '94 Sept. '96 Aug. '97 Oct. '98 CNT01523 CNT01819 CNT02223 **CNT03078 CNT01819 **CNT02223 **CNT02536 **CNT02871 D340021P01 SiC D330937P01 SiC D341418P01 SiNi SPEED MODELS ) 50A51-505 50A51-506 50A51-507 50V61-507 50A51-506 50A51-507 50A61-605 50V65-495 D340236P01 D340641P01 D340949P01 D341420P01 D340641P01 D340949P01 C341033P01 D341232P01 *Universal replacement for 1 stg SiC IFC's (Also used in KIT05216 Radiant Sense to Flame Rectification Conversion) **Current replacement part (CNT02789 and CNT02891 are currently superseded to CNT02183) SiC SiC SiC SiNi SiC SiC SiNi SiNi Open solder joint on K1 relay on back of PC Board - can occur on either terminal. Labor: A labor claim will be accepted for one hour at the servicer’s normal rate for each individual affected furnace. If multiple repairs are made on the same installation, one hour will be allowed for the first repair and _ hour for each additional furnace on the same installation. Labor claims are to be submitted via Field Repair Invoice (FRI) routine. If an extended warranty is in effect on the furnace repaired, an additional hour will be accepted (_ hour diagnostics, and _ hour travel). The Extended Warranty contract number must be written on the FRI. Do not submit claims through the Extended Warranty System. IS S UED BY: Tom Menard, Field S ervice Representative.