Service Bulletin 3-01

Transcription

Service Bulletin 3-01
SERVICE REMINDER
INSTALLATION
NUMBER:
DATE:
SERVICE
Tampa Sales District
The Trane Company
9208 Palm River Road
Suite 301
Tampa, FL 33619
(813) 621-707 0
3-01
10/11/01
TO: ALL AUTHORIZED TRANE DEALERS AND SERVICERS
SUBJECT:
SINGLE STAGE INTEGRATED FURNACE CONTROLS (IFC) SOLDER TERMINAL
FAILURES (CNT02789, CNT02891, CNT03076)
MODELS AFFECTED: SEE TABLE BELOW
PART NUMBER
MODEL FAMILY
CNT02789 (CNT02183 Repl.)
TDE-A-K2 thru L0
CNT02789
TUE-A-K2 thru L0
CNT03076
TDD-C-D-D0 thru E0
CNT03076
TUD-C-J0, J1
CNT02854 / CNT03076
TDX/TUX-C-C0 thru C2
CNT02891 (CNT02183 Repl.)
TDC/TUC-C-B6, B7
DATE CODE RANGE
M47 - R19
M43 - R29
P15 - R22
P15 - R22
N30 - R22
N31 - R31
INTRODUCTION: Since the beginning the 2nd quarter of 1999, field complaints reported failures of the “K1” relay powering the
circulating blower on the furnace controls CNT02789 (particularly in downflow models). More recently, similar
reports have been received on other single stage furnace models (see list above). The failure appears as burned
solder joints of the relay pins on the backside of the PC board (See photos on last page).
The symptom will be intermittent or no circulating blower operation.
DISCUSSION:
The cause of failure was determined to be thermal stress induced by high temperature swings during
cycling. This is prevalent on downflow furnaces but has been witnessed on upflow furnaces.
CORRECTIVE ACTION
FACTORY:
1. The use of CNT02789 has been suspended in downflow TDE models.
(See FURN-TRN-SB-11). The downflow units have been built with CNT02183. New model number
TDE-A-L1 identifies this change.
2.
FIELD:
IFC’s CNT02789, CNT02891 and CNT03076 have been redesigned to withstand the thermal stresses
mentioned above. The date codes on the controls for improved design are 0019 for the CNT03076 and
0023 for CNT02789 and CNT02891. See the table in the heading of this bulletin for the corresponding
furnace production date codes. Effective with date code Z373 (9/12/01), TDE-A-L1 will again use
CNT02789.
For upflow models, this is a “Fix-On-Fail Only” bulletin. Because of the higher level of failures
experienced in downflow models, the control may be replaced prior to failure where customer
satisfaction is at risk.
In case of CNT02789 or CNT02891 failure, the current replacement will be CNT02183. This will change in the
near future (back to the original IFC). Special instructions for replacement of the control on the TDE-A-L0 are
included in General Service Bulletin FURN-TRN-SB-11. See the table on P.2 for proper control selection.
Special Notes:
1. All controls replaced “in warranty” must be returned to the parts distribution outlet to obtain credit.
Also, “out of warranty” controls exhibiting the fault described above must be returned to obtain
credit under this bulletin.
2.
ISSUED BY:
All material and labor claims for this fault must be cleared with the local Field Service
Representative. No claims are to be made against this bulletin for anything other than the failure
described in the text above and photo on p.3.
AFTER SALES SUPPORT - TRENTON
IFC-TO-FURNACE MODEL FAMILY CROS S REFERENCE
MODEL FAMILY
Approximate First
Production Date
(Date Code)
TRANE P/N
W-R P/N
Trane DWG#
IGN
TYPE
ONE STAGE IFC
FCA/FUA-A-A0…A1 & CUD-A-A1…A3
*DE/*UE-A-K0…K1 & FCA/FUA-A-E0 &
KIT03793
*DE/*UE-K2 and later & CUB
XE-80 *DD/*UD-C-A1…B0
XE-80 *DD-C-C0...C1 & *UD-C-H0…H1
XE-80 *DD-C-C3...C4 & *UD-C-H3…H4
XE-80 *DD-C-E0 and later & *UD-C-J0 and later
XE-90
XE-90
XE-90
XE-90
XE-90
XE-90
*DC/*UC-C-A, *DX/*UX-C-A
*DC/*UC/*DX/*UX-C-BO …B2
*DC/*UC/*DX/*UX-C-B
*DC/*UC/*DX/*UX-C-B and later
*DX/*UX-C-C0
*DX/*UX-C-C1 and later
1991
Mar, 11, '96
CNT01309
CNT02181
50A50-405
50A50-571
D340035P01 SiC
D330927P01 SiC
Nov. '97 (M47 )
1991
July '95
April 29, '96 (L17)
FW15-99 (P15)
CNT02789
CNT01309
CNT01848
CNT02182
**CNT03076
50A55-571
50A50-405
50A50-471
50A50-473
50A65-475
D341122P01
D340035P01
D340774P01
D330930P01
D341396P01
SiC
SiC
SiC
SiC
SiNi
Nov. '92
July '95
April 29, '96 (L17)
July, '98 (N31)
July, '98 (N30)
April '99 (P17)
CNT01616
CNT01849
*CNT02183
**CNT02891
CNT02854
**CNT03076
50A50-406
50A50-472
50A50-474
50A55-474
50A65-474
50A65-475
D340354P01
D340790P01
D330934P01
D341235P01
D341213P01
D341396P01
SiC
SiC
SiC
SiC
SiNi
SiNi
STAGE IFC ( STANDARD
MODELS )
TWO
XL-80 *DD/*UD-R
XL-80 *DD/*UD-R
XL-80 *DD/*UD-R
1991
April 29, '96 (L17)
Sept. '99 (P38)
CNT01308 50A51-405
CNT02184 50A51-495
**CNT03077 50M61-495
TWO STAGE IFC ( VARIABLE
XV-80 *DD/*UD-R9V-A1
XV-80 *DD-R9V-B0...C3 & *UD-R9V-A1...H0
XV-80 *DD-R9V-C4 & *UD-R9V-H4
XV-80 *DD-R9V-D0 & *UD-R9V-J0 and later
XV-90 *DY/*UY-R9V-A0…A3
XV-90 *DY-R9V-A4, *UY-R9V-H4
XV-90 *DY/*UY-R9V-V
XL-90 *DX/*UX-R-V
1992
Oct. '95 (K43)
Sept. '96
Sept. '99 (P38)
Aug. '94
Sept. '96
Aug. '97
Oct. '98
CNT01523
CNT01819
CNT02223
**CNT03078
CNT01819
**CNT02223
**CNT02536
**CNT02871
D340021P01 SiC
D330937P01 SiC
D341418P01 SiNi
SPEED MODELS )
50A51-505
50A51-506
50A51-507
50V61-507
50A51-506
50A51-507
50A61-605
50V65-495
D340236P01
D340641P01
D340949P01
D341420P01
D340641P01
D340949P01
C341033P01
D341232P01
*Universal replacement for 1 stg SiC IFC's (Also used in KIT05216 Radiant Sense to Flame Rectification Conversion)
**Current replacement part (CNT02789 and CNT02891 are currently superseded to CNT02183)
SiC
SiC
SiC
SiNi
SiC
SiC
SiNi
SiNi
Open solder joint on K1 relay on back of PC Board - can occur on either terminal.
Labor:
A labor claim will be accepted for one hour at the servicer’s normal rate for
each individual affected furnace. If multiple repairs are made on the same installation, one hour will be
allowed for the first repair and _ hour for each additional furnace on the same installation. Labor claims
are to be submitted via Field Repair Invoice (FRI) routine. If an extended warranty is in effect on the
furnace repaired, an additional hour will be accepted (_ hour diagnostics, and _ hour travel). The
Extended Warranty contract number must be written on the FRI. Do not submit claims through the
Extended Warranty System.
IS S UED BY: Tom Menard, Field S ervice Representative.