DCG Commercial - Daikin Comfort
DCG Commercial 7½ - 12½ Ton Packaged Gas/ Electric Up to 11.3 EER / 80% AFUE Cooling Capacity: 88,000 — 144,000 BTU/h Heating Capacity (Output): 168,000 BTU/h ■ Contents Nomenclature......................................... 2 Product Specifications............................ 4 Expanded Cooling Data.......................... 8 Airflow Data.......................................... 16 Dimensions........................................... 20 Wiring Diagrams .................................. 24 – for Models with DDC Controls............... 36 Accessories........................................... 43 ■ Standard Features • • • • • • • • • • • • ■ Cabinet Features TuffTube™ tubular heat exchanger • Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish High-efficiency scroll compressors • Full perimeter rail Two-stage heating and cooling • Sloped drain pan Copper tube / aluminum fin coils • Easy to service Power block for field wiring High-capacity, steel-cased filter drier Single-point entry 24-volt terminal strip Convertible airflow orientation Built-in filter rack with standard 2" filters Complies with California Low NOx emissions standards Units meet the performance outlined in Table 6.8.1A of ASHRAE Standard 90.1-2010 • AHRI Certified; ETL Listed *Complete warranty details available from your local dealer or at www.daikincomfort.com. SS-DCG7 www.daikincomfort.com 6/16 Supersedes 3/16 Nomenclature D 1 C 2 G 3 090 4,5,6 210 7,8,9 3 10 B 11 * 12 * 13 * 14 A * 15 16 Revision Levels Major & Minor Brand D Daikin Configuration C Commercial T High Efficiency (3-5 Tons) Application C Cooling3 G Gas Heat H Heat Pump3 Nominal Cooling Capacity 036 3 Tons 102 048 4 Tons 120 060 5 Tons 150 072 6 Tons 180 090 7½ Tons 240 8½ Tons 10 Tons 12½ tons 15 Tons 20 Tons 300 25 Tons Nominal Heating Capacity Gas/Electric A/C H/P Factory-Installed Electric Heat 045 45,000 BTU/h XXX No Heat 090 90,000 BTU/h 010 10 kW 030 30 kW 115 115,000 BTU/h 015 15 kW 031 30 kW 140 140,000 BTU/h 016 15 kW 045 45 kW 210 210,000 BTU/h 018 18 kW 046 45 kW 350 350,000 BTU/h 020 20 kW 060 60 kW 400 400,000 BTU/h 025 25 kW See product specifications for heat size(s) available for each capacity. Voltage 1 208-230/1/60 3 208-230/3/60 4 7 460/3/60 575/3/60 Supply Fan/Drive Type/Motor B Belt Drive (single speed) V Two-Speed Belt Drive (also designates 6-Ton D Direct Drive (3-5 Tons) with two-stage compressor) Factory-Installed Options A Ultra Low-Leak Downflow Economizer1 B DDC-BACnet protocol F Ultra Low-Leak Downflow Economizer1; DDC-BACnet protocol H Disconnect Switch (non-fused) J Ultra Low-Leak Downflow Economizer1; Disconnect Switch (non-fused) M Disconnect Switch (non-fused); DDC-BACnet protocol R Ultra Low-Leak Downflow Economizer1; DDC-BACnet protocol; Disconnect Switch (non-fused) V Low-Leak Downflow Economizer2 W Low-Leak Downflow Economizer2 Disconnect Switch (non-fused) X No Options Note: Not all options available for all products. 2 Factory-Installed Options No Options Non-powered convenience outlet Powered convenience outlet Low-ambient kit Return air smoke detector Supply air smoke detector Non-powered convenience outlet; Low-ambient kit G Non-powered convenience outlet; Return air smoke detector H Non-powered convenience outlet; Supply air smoke detector J Non-powered convenience outlet; Return & Supply air smoke detectors K Non-powered convenience outlet; Low-ambient kit; Supply air smoke detector L Non-powered convenience outlet; Low-ambient kit Return & Supply air smoke detectors M Powered convenience outlet; Low-ambient kit N Powered convenience outlet; Return air smoke detector O Powered convenience outlet; Return & Supply air smoke detectors P Powered convenience outlet; Supply air smoke detector Q Powered convenience outlet; Low-ambient kit; Return air smoke detector R Powered convenience outlet; Low-ambient kit; Supply air smoke detector T Powered convenience outlet; Low-ambient kit; Return & Supply air smoke detectors U Non-powered convenience outlet; Low-ambient kit; Return air smoke detector V Low-ambient kit; Return air smoke detector W Low-ambient kit; Supply air smoke detector Y Low-ambient kit; Return & Supply air smoke detectors Z Return & Supply air smoke detectors X A B C D E F 1 Please contact RRS Rooftop Systems directly if Power Exhaust is required. Ultra Low-Leak economizer for DDC controls. 2 Please use part number DPE901502 / DPE901504 / DPE901507 if Power Exhaust is required. 3 X= No Options in character 13th www.daikincomfort.com Factory-Installed Options Standard Aluminized Heat Exchanger Stainless-Steel Heat Exchanger Hinged Panels (3-12½ Tons) Stainless-Steel Heat Exchanger; Hinged Panels (3-12½ tons) B Phase Monitor J Stainless Steel Heat Exchanger; Phase Monitor M Hinged Panel (3-12½ tons); Phase Monitor L Stainless-Steel Heat Exchanger; Hinged Panels (3-12½ tons); Phase Monitor X S D K SS-DCG7 Nomenclature Factory-Installed Options • Stainless-Steel Heat Exchanger (DCG units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit. • Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended from 60°F ambient temperature to 35°F outside air temperature. On 7½ -20 ton units, cooling operation is extended from 35°F ambient temperature to 0°F outside air temperature. For 25 ton units, cooling operation is extended from 24°F ambient temperature to 0°F outside air temperature. • Economizers (Downflow): Based on air conditions, can provide outside air to cool the space. • Electric Heat Kits (DCC and DCH units only): Available in all voltage options. • Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs power to the outlet. • Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly. • Disconnect Switch (non-fused; 3-phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit. Please note that for air conditioning (DCC units) and heat pump models (DCH units), the appropriate electric heat kit must be ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models with a powered convenience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position. • Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit. • Two-speed indoor fan blower models are available on 6, 7½, 8½, 10, 12½, 15, 20 & 25 ton units. Section 6.4.3.10.b of ASHRAE Standard 90.1-2010 and Section 6.5.3.2.1.a of ASHRAE Standard 90.1-2013 require a minimum of two fan speeds. Section 140.4(m)1 of California Energy Commission Title 24 2013 contains a similar provision. When the units with the two-speed indoor fan blowers operate on a call for the first stage of cooling, the fan operates at low speed, which is 66% of full speed. When the units operate on a call for the second stage of cooling, the fan operates at full speed. In heating operation, the fan operates at full speed. During ventilation operation, the fan operates at low speed. • Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor, filters and blower motor. Available on 3-12½ Tons units. SS-DCG7 www.daikincomfort.com 3 Product Specifications — 7½ Tons DCG090 2103B*** A* DCG090 2103V*** A* DCG090 2104B***A* DCG090 2104V*** A* Cooling Capacity Total BTU/h 88,000 88,000 88,000 88,000 88,000 88,000 Sensible BTU/h 65,100 65,100 65,100 65,100 65,100 65,100 11.3 / 11.5 11.3 / 13.0 11.3 / 11.5 11.3 / 13.0 11.3 / 11.5 11.3 / 13.0 82 82 82 82 82 82 7041908 7041911 7041908 7041911 7041908 7041911 EER / IEER Decibels AHRI Reference #s DCG090 2107B*** A* DCG090 2107V*** A* Heating Capacity High Input / Output MBTU/h 210 / 168 210 / 168 210 / 168 210 / 168 210 / 168 210 / 168 Low Input / Output MBTU/h 157.5 / 126 157.5 / 126 157.5 / 126 157.5 / 126 157.5 / 126 157.5 / 126 Steady-State Efficiency (AFUE) 80 80 80 80 80 80 Temperature Rise Range (°F) No. of Burners 35 6 35 6 35 6 35 6 35 6 35 6 Evaporator Motor / Coil Motor Type Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive 3,000 3,000 3,000 3,000 3,000 3,000 Indoor Nominal CFM FLA (Cooling) Horsepower / RPM Piston Size (Cooling) Filter Size (Qty) Drain Size (NPT) 5.0 6.0 2.5 2.9 2.3 2.4 1½ / 1745 2/ 1740-1160 1½ / 1745 2/ 1740-1160 1½ / 1725 2 / 1745-1170 0.078 0.078 0.078 0.078 0.078 0.078 16" x 20" x 2" 16" x 20" x 2" 16" x 20" x 2" 16" x 20" x 2" 16" x 20" x 2" 16" x 20" x 2" ¾" ¾" ¾" ¾" ¾" ¾" R-410A Refrigerant Charge: Cir #1 / #2 100 oz. 100 oz. 100 oz. 100 oz. 100 oz. 100 oz. Evaporator Coil Face Area (ft²) Rows Deep / Fins per Inch 8.9 4 / 16 8.9 4 / 16 8.9 4 / 16 8.9 4 / 16 8.9 4 / 16 8.9 4 / 16 Belt Drive Evap Fan Data # of Wheels (D x W) 1 (15" x 12") 1 (15" x 12") 1 (15" x 12") 1 (15" x 12") 1 (15" x 12") 1 (15" x 12") Motor / Blower Sheave Belt VL40 / AK74 AX51 VL40 / AK74 AX51 VL40 / AK74 AX51 VL40 / AK74 AX51 VL40 / AK74 AX51 VL40 / AK74 AX51 Condenser Fan / Coil Quantity of Condenser Fan Motors 2 2 2 2 2 2 ¼ - 1075 ¼ - 1075 ¼ - 1075 ¼ - 1075 ¼ - 1075 ¼ - 1075 Fan Diameter / # Fan Blades 22 / 4 22 / 4 22 / 4 22 / 4 22 / 4 22 / 4 Outdoor Nominal CFM 7,200 7,200 7,200 7,200 7,200 7,200 Face Area (ft²) Rows Deep / Fins per Inch 28.8 2 X2 / 27±1 28.8 2 X2 / 27±1 28.8 '2 X2 / 27±1 28.8 '2 X2 / 27±1 28.8 '2 X2 / 27±1 28.8 '2 X2 / 27±1 Compressor Quantity / Type / Stage Compressor RLA / LRA 2 / Scroll / 1 13.1 / 83.1 2 / Scroll / 1 13.1 / 83.1 2 / Scroll / 1 6.1 / 41.0 2 / Scroll / 1 6.1 / 41.0 2 / Scroll / 1 4.4 / 33.0 2 / Scroll / 1 4.4 / 33.0 Electrical Data Voltage / Phase 208-230 / 3 208-230 / 3 460 / 3 460 / 3 575 / 3 575 / 3 1.5 / 5.0 2/6.0 1.5 / 2.5 2/2.9 1.5 / 2.3 2/2.4 1.0" 1.0" 1.0" 1.0" 1.0" 1.0" (2) ¼ / 1.4 (2) ¼ / 1.4 (2) ¼ / 0.7 (2) ¼ / 0.7 (2) ¼ / 0.55 (2) ¼ / 0.55 Horsepower - RPM Indoor Blower HP / FLA Max External Static Outdoor Fan HP / RLA Total Unit Amps 34.0 35.0 16.1 16.5 12.2 12.3 Min. Circuit Ampacity¹ 37 38.3 17.7 18 13.3 13.4 Max. Overcurrent Protection (amps)² 50 50 20 20 15 15 Entrance Power Supply Entrance Control Voltage Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple Operating Weight (lbs) Ship Weight (lbs) 1100 1175 1100 1175 1100 1175 1100 1175 1100 1175 1100 1175 ¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed. 4 www.daikincomfort.com SS-DCG7 Product Specifications — 8½ Tons DCG102 2103B***A* DCG102 2103V***A* DCG102 2104B***A* DCG102 2104V***A* DCG102 2107B***A* DCG102 2107V***A* Total, BTU/h 102,000 102,000 102,000 102,000 102,000 102,000 Sensible BTU/h 70,380 70,380 70,380 70,380 70,380 70,380 11.3 / 11.2 11.3 / 13.4 11.3 / 11.2 11.3 / 13.4 11.3 / 11.2 11.3 / 13.4 Cooling Capacity EER / IEER Decibels ARI Reference #s 83 83 83 83 83 83 7370921 7370924 7370921 7370924 7370921 7370924 Heating Capacity High Input / Output BTU/h 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 Low Input / Output BTU/h 157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000 Steady State Efficciency Temperature Rise Range (°F) No. of Burners 80 80 80 80 80 80 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65 6 6 6 6 6 6 Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive 3,200 3,200 3,200 3,200 3,200 3,200 7.8 6.0 3.9 2.9 2.3 2.4 2 / 1725 2/ 1740-1160 2 / 1725 2/ 1740-1160 2 / 1725 2 / 1745-1170 Evaporator Motor / Coil Motor Type Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM Piston Size (Cooling) Filter Size (Qty) 0.080 0.080 0.080 0.080 0.080 0.080 (4) 16 x 24 x 2 (4) 16 x 24 x 2 (4) 16 x 24 x 2 (4) 16 x 24 x 2 (4) 16 x 24 x 2 (4) 16 x 24 x 2 Drain Size (NPT) 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" R-410A Refrigerant Charge Cir #1 #2 (oz.) 110.0 110.0 110.0 110.0 110.0 110.0 Evaporator Coil Face Area (ft2) 10.2 10.2 10.2 10.2 10.2 10.2 Rows Deep / Fins per Inch 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14 # of Wheels (D x W) 1 (15" x 15") 1 (15" x 15") 1 (15" x 15") 1 (15" x 15") 1 (15" x 15") 1 (15" x 15") Motor Sheave / Blower Sheave VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 AX51 AX51 AX51 AX51 AX51 AX51 Belt Drive Evap Fan Data Belt Condenser Fan / Coil Quantity of Condenser Fan Motors 2 2 2 2 2 2 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 Outdoor Nominal CFM 8,200 8,200 8,200 8,200 8,200 8,200 Face Area (ft²) 28.8 28.8 28.8 28.8 28.8 28.8 '2 X2 / 27±1 '2 X2 / 27±1 '2 X2 / 27±1 '2 X2 / 27±1 '2 X2 / 27±1 '2 X2 / 27±1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 14.5 / 98 14.5 / 98 6.3 / 55 6.3 / 55 6.0 / 41 6.0 / 41 575 / 3 Horsepower - RPM Rows Deep / Fins per Inch Compressor Quantity / Type / Stage Compressor RLA / LRA ea. Electrical Data / Static 208-230 / 3 208-230 / 3 460 / 3 460 / 3 575 / 3 Outdoor Fan FLA ea. Voltage / Phase (60 Hz) 1.40 1.40 0.70 0.70 0.55 0.55 Total Unit Amps 39.6 37.8 18.9 16.9 15.3 15.4 Min. Circuit Ampacity¹ 43.2 41.4 20.5 18.5 16.9 17 50 50 25 20 20 20 Entrance Power Supply Locating Locating Locating Locating Locating Locating Entrance Control Voltage Dimple Dimple Dimple Dimple Dimple Dimple Operating Weight (lbs) 1140 1140 1140 1140 1140 1140 Ship Weight (lbs) 1215 1215 1215 1215 1215 1215 Max. Overcurrent Protection (amps)² ¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed. SS-DCG7 www.daikincomfort.com 5 Product Specifications — 10 Tons DCG120 2103B***A* DCG120 2103V***A* DCG120 2104B***A* DCG120 2104V***A* DCG120 2107B***A* DCG120 2107V***A* Total BTU/h 116,000 116,000 116,000 116,000 116,000 116,000 Sensible BTU/h 84,700 84,700 84,700 84,700 84,700 84,700 11.3 / 11.5 11.3 / 12.8 11.3 / 11.5 11.3 / 12.8 11.3 / 11.5 11.3 / 12.8 Cooling Capacity EER / IEER Decibels ARI Reference #s 83 83 83 83 83 83 6345698 6345699 6345698 6345699 6345698 6345699 210,000/ 168,000 157,500/ 126,000 210,000/ 168,000 157,500/ 126,000 210,000/ 168,000 157,500/ 126,000 210,000/ 168,000 157,500/ 126,000 210,000/ 168,000 157,500/ 126,000 210,000/ 168,000 157,500/ 126,000 Heating Capacity High Input/Output (BTU/h) Low Input/Output (BTU/h) Steady State Efficiency 80 80 80 80 80 80 25-55 25-55 25-55 25-55 25-55 25-55 6 6 6 6 6 6 Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive 3,500 3,500 3,500 3,500 3,500 3,500 7.8 6.4 3.9 3.3 2.5 2.4 Horsepower - RPM 2.0 - 1,725 2.0/1750-1165 2.0 - 1,725 2.0/1750-1165 2.0 - 1,725 2.0/1750-1165 Piston Size (Cooling) 0.086 0.086 0.086 0.086 0.086 0.086 16”x24”x2” 16”x24”x2” 16”x24”x2” 16”x24”x2” 16”x24”x2” 16”x24”x2” Temperature Rise Range (°F) No. of Burners Evaporator Motor / Coil Motor Type Indoor Nominal CFM Indoor Motor FLA (Cooling) Filter Size (#=4) Drain Size (NPT) R-410A Refrigerant Charge Cir #1 & 2 (oz.) ¾" ¾" ¾" ¾" ¾" ¾" 144 / 123 144 / 123 144 / 123 144 / 123 144 / 123 144 / 123 Evaporator Coil Face Area (ft²) 10.2 10.2 10.2 10.2 10.2 10.2 Rows Deep/ Fins per Inch 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14 # of Wheels (D x W) (1) 15” x 15” (1) 15” x 15” (1) 15” x 15” (1) 15” x 15” (1) 15” x 15” (1) 15” x 15” Motor Sheave / Blower Sheave VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 AX51 AX50 AX51 AX50 AX51 AX50 Belt Drive Evap Fan Data Belt Condenser Fan / Coil Quantity of Condenser Fan Motors Horsepower - RPM 2 2 2 2 2 2 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 Outdoor Nominal CFM 8,200 8,200 8,200 8,200 8,200 8,200 Face Area (ft²) 35.2 35.2 35.2 35.2 35.2 35.2 2 X2 / 27±1 2 X2 / 27±1 2 X2 / 27±1 2 X2 / 27±1 2 X2 / 27±1 2 X2 / 27±1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 16 / 110.0 16 / 110.0 7.8 / 52.0 7.8 / 52.0 5.7 / 38.9 5.7 / 38.9 208-230/ 3/ 60 208-230/ 3/ 60 460/ 3/ 60 460/ 3/ 60 575/ 3/ 60 575/ 3/ 60 2.00 2.00 0.85 0.85 0.67 0.67 Total Unit Amps 45 43 22 21 16 16 Min. Circuit Ampacity¹ 49 47 24 23 17 17 Max. Overcurrent Protection (amps)² 60 60 30 30 20 20 Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple # Coils / Rows Deep - Fins per Inch Compressor Quantity / Type / Stage Compressor RLA / LRA ea. Electrical Data Voltage/Phase/ Frequency Outdoor Fan RLA ea. Entrance Power Supply Entrance Control Voltage Operating Weight (lbs) 1140 1140 1140 1140 1140 1140 Ship Weight (lbs) 1215 1215 1215 1215 1215 1215 ¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed. 6 www.daikincomfort.com SS-DCG7 Product Specifications — 12½ Tons DCG150 2103B***A* DCG150 2103V***A* DCG150 2104B***A* DCG150 2104V***A* DCG150 2107B***A* DCG150 2107V***A* 144,000 144,000 144,000 144,000 144,000 144,000 Cooling Capacity Total, BTU/h Sensible BTU/h EER / IEER Decibels ARI Reference #s 100,000 100,000 100,000 100,000 100,000 100,000 10.8 / 11.0 10.8 / 12.0 10.8 / 11.0 10.8 / 12.0 10.8 / 11.0 10.8 / 12.0 83 83 83 83 83 83 6885862 6885865 6885862 6885865 6885862 6885865 Heating Capacity High Input / Output BTU/h 210,000 / 168,000 210,000 / 168,000 Low Input / Output BTU/h 157,500 / 126,000 157,500 / 126,000 Steady State Efficiency Temperature Rise Range (°F) No. of Burners 210,000 / 168,000 157,500 / 126,000 80 80 80 80 80 80 15 - 45 15 - 45 15 - 45 15 - 45 15 - 45 15 - 45 6 6 6 6 6 6 Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive 3,900 3,900 3,900 3,900 3,900 3,900 9.4 9.1 4.7 4.3 4.2 3.5 3.0 - 1,725 3.0/1760-1165 3.0 - 1,725 3.0/1760-1165 3.0 - 1,725 3.0/1760-1165 0.092 0.092 0.092 0.092 Evapoartor Motor / Coil Motor Type (Belt Drive) Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM Piston Size (Cooling) Filter Size (Qty) 0.092 0.092 (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2" Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾" R-410A Refrigerant Charge Cir #1/ #2 (oz.) 175 175 175 175 175 175 Evaporator Coil Face Area (ft2) 14.7 14.7 14.7 14.7 14.7 14.7 Rows Deep / Fins per Inch 4 / 15 4 / 15 4 / 15 4 / 15 4 / 15 4 / 15 # of Wheels (D x W) (1) 15" x 15" (1) 15" x 15" (1) 15" x 15" (1) 15" x 15" (1) 15" x 15" (1) 15" x 15" Motor Sheave / Blower Sheave VL40 / AK66 VP44 / AK71 VL40 / AK66 VP44 / AK71 VL40 / AK66 VP44 / AK71 AX49 AX48 AX49 AX48 AX49 AX48 Belt Drive Evap Fan Data Belt Condenser Fan / Coil Quantity of condenser Fan Motors Horsepower - RPM 2 2 2 2 2 2 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 Fan Diameter / # Fan Blades 22/3 22/3 22/3 22/3 22/3 22/3 Outdoor Nominal CFM 8,400 8,400 8,400 8,400 8,400 8,400 Face Area (ft2) # Coils / Rows Deep - Fins per Inch 39.0 39.0 39.0 39.0 39.0 39.0 2/2 rows 27 fpi 2/2 rows 27 fpi 2/2 rows 27 fpi 2/2 rows 27 fpi 2/2 rows 27 fpi 2/2 rows 27 fpi 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 2 / Scroll / 1 22.4 / 149 22.4 / 149 10.6 / 75 10.6 / 75 7.7 / 54 7.7 / 54 575/3/60 Compressor Quantity / Type / Stage Compressor RLA / LRA ea. Electrical Data / Static Voltage / Phase / Frequency 208-230/3/60 208-230/3/60 460/3/60 460/3/60 575/3/60 Standard Max Static 1.4" 1.4" 1.4" 1.4" 1.4" 1.4" Outdoor Fan FLA ea. 2.00 2.00 0.85 0.85 0.67 0.67 Total Unit Amps 59 57.9 28 26.9 21.4 20.7 Min. Circuit Ampacity1 65 63.5 31 29.9 23 23 Max. Overcurrent Protection (amps)2 80 80 40 40 30 30 Entrance Control Voltage Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple Locating Dimple Operating Weight (lbs) Ship Weight (lbs) 1315 1340 1315 1340 1315 1340 1315 1340 1315 1340 1315 1340 Entrance Power Supply ¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed. SS-DCG7 www.daikincomfort.com 7 8 www.daikincomfort.com 59 86 0.74 17.5 6.1 234 108 84 0.71 18.2 6.1 231 107 77 0.68 20.2 5.9 224 104 88 0.84 20.2 6.2 236 109 85 0.81 21.0 6.1 234 108 79 0.78 23.4 6.0 227 105 Airflow MBh S/T ∆T 3375 kW Hi PR Lo PR MBh S/T ∆T 3000 kW Hi PR Lo PR MBh S/T ∆T 2400 kW Hi PR Lo PR MBh S/T ∆T 3375 kW Hi PR Lo PR MBh S/T ∆T 3000 kW Hi PR Lo PR MBh S/T ∆T 2400 kW Hi PR Lo PR 81 0.69 21.5 6.1 244 112 88 0.72 19.4 6.2 252 115 90 0.76 18.6 6.3 254 116 80 0.57 17.5 6.1 242 111 87 0.59 15.7 6.2 249 114 89 0.62 15.1 6.2 252 115 63 88 0.53 17.6 6.3 258 122 95 0.55 15.9 6.4 266 126 98 0.57 15.2 6.5 268 127 88 0.40 13.3 6.2 255 121 95 0.41 11.9 6.4 263 124 98 0.43 11.5 6.4 266 126 67 94 0.3 12.2 6.5 269 130 102 0.4 11.0 6.6 277 134 105 0.4 10.5 6.7 280 135 - - - 71 77 0.81 23.7 6.4 254 111 83 0.84 21.3 6.6 262 114 86 0.88 20.4 6.6 265 116 75 0.71 20.5 6.4 252 110 82 0.73 18.4 6.5 260 113 84 0.77 17.7 6.6 262 114 59 79 0.72 21.8 6.5 274 118 86 0.75 19.6 6.7 282 122 88 0.78 18.8 6.7 285 123 78 0.59 17.7 6.5 271 117 85 0.61 15.9 6.6 279 120 87 0.64 15.3 6.7 282 122 63 75 86 0.55 17.9 6.7 289 129 93 0.57 16.1 6.9 298 133 95 0.59 15.4 6.9 301 134 86 0.41 13.5 6.7 286 128 93 0.43 12.1 6.8 295 132 96 0.45 11.6 6.9 298 133 67 92 0.4 12.3 6.9 302 137 99 0.4 11.1 7.1 311 141 102 0.4 10.6 7.2 314 143 - - - 71 75 0.83 23.7 6.8 289 115 81 0.86 21.3 6.9 298 119 84 0.90 20.5 7.0 301 120 74 0.73 20.5 6.7 286 114 80 0.75 18.4 6.9 295 118 82 0.79 17.7 6.9 298 119 59 77 0.74 21.8 6.9 311 123 84 0.77 19.6 7.1 321 126 86 0.80 18.8 7.1 324 128 76 0.61 17.7 6.9 308 121 83 0.63 16.0 7.0 318 125 85 0.66 15.3 7.1 321 126 63 84 0.56 17.9 7.1 329 134 90 0.58 16.1 7.3 339 138 93 0.61 15.4 7.4 342 139 84 0.42 13.5 7.1 326 133 91 0.44 12.1 7.2 336 137 93 0.46 11.6 7.3 339 138 67 90 0.4 12.3 7.4 343 143 97 0.4 11.1 7.5 354 147 100 0.4 10.7 7.6 357 149 - - - 71 73 0.85 23.9 7.1 330 121 79 0.88 21.5 7.3 340 125 82 0.93 20.6 7.3 343 126 72 0.75 20.6 7.1 326 120 78 0.78 18.6 7.2 336 124 80 0.82 17.8 7.3 340 125 59 81 0.58 18.0 7.5 375 141 88 0.60 16.2 7.7 386 145 82 0.79 19.8 7.4 366 133 75 0.76 22.0 7.3 355 129 91 0.63 15.5 7.7 390 146 82 0.43 13.6 7.4 371 139 88 0.45 12.2 7.6 382 144 91 0.47 11.7 7.7 386 145 67 84 0.83 19.0 7.5 369 134 75 0.63 17.9 7.2 351 128 81 0.65 16.1 7.4 362 132 83 0.68 15.4 7.4 366 133 63 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 87 0.4 12.4 7.7 391 150 95 0.4 11.2 7.9 403 154 98 0.4 10.7 8.0 407 156 - - - 71 69 0.88 23.5 7.4 371 127 75 0.92 21.2 7.6 382 131 77 0.96 20.3 7.6 386 132 68 0.78 20.4 7.3 367 126 74 0.81 18.3 7.5 378 130 76 0.85 17.6 7.6 382 131 59 72 0.79 21.7 7.5 399 135 77 0.82 19.5 7.7 411 139 80 0.86 18.7 7.8 415 141 71 0.65 17.6 7.5 395 134 77 0.67 15.8 7.7 407 138 79 0.71 15.2 7.7 411 139 63 67 77 0.60 17.8 7.8 421 147 84 0.62 16.0 8.0 434 152 86 0.65 15.3 8.0 439 154 78 0.45 13.4 7.7 417 146 84 0.47 12.0 7.9 430 150 87 0.49 11.5 8.0 434 152 105 83 0.4 12.3 8.0 439 157 90 0.4 11.0 8.2 453 162 93 0.4 10.6 8.3 458 163 - - - 71 64 0.89 22.0 7.6 410 131 70 0.93 19.8 7.8 422 135 72 0.97 19.0 7.9 427 137 63 0.78 19.0 7.6 406 130 69 0.81 17.1 7.8 418 134 71 0.85 16.4 7.8 422 135 59 66 0.80 20.2 7.8 441 140 72 0.83 18.2 8.0 454 144 74 0.87 17.5 8.1 459 145 66 0.66 16.5 7.7 436 138 71 0.68 14.8 7.9 450 143 73 0.71 14.2 8.0 454 144 63 67 72 0.60 16.6 8.0 466 153 78 0.63 14.9 8.2 480 157 80 0.66 14.3 8.3 485 159 72 0.45 12.5 8.0 461 151 78 0.47 11.2 8.2 475 156 80 0.49 10.8 8.2 480 157 115 77 0.4 11.5 8.3 486 162 83 0.4 10.3 8.5 501 167 86 0.4 9.9 8.6 506 169 - - - 71 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects ACCA (TVA) Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 75 70 IDB 65 Expanded Cooling Data — 7½ Tons SS-DCG7 SS-DCG7 www.daikincomfort.com 59 89 0.93 22.5 6.2 238 110 87 0.88 23.5 6.2 236 109 80 0.85 26.1 6.0 229 106 91 0.97 24.0 6.3 241 112 88 0.93 25.0 6.2 238 110 81 0.89 27.8 6.1 231 107 Airflow MBh S/T ∆T 3375 kW Hi PR Lo PR MBh S/T ∆T 3000 kW Hi PR Lo PR MBh S/T ∆T 2400 kW Hi PR Lo PR MBh S/T ∆T 3375 kW Hi PR Lo PR MBh S/T ∆T 3000 kW Hi PR Lo PR MBh S/T ∆T 2400 kW Hi PR Lo PR 83 0.86 27.4 6.2 249 114 90 0.89 24.6 6.3 257 118 93 0.94 23.6 6.4 259 119 82 0.80 25.0 6.1 246 113 89 0.83 22.5 6.3 254 116 91 0.87 21.6 6.3 257 118 63 87 0.78 25.9 6.4 263 124 94 0.81 23.3 6.5 271 128 97 0.85 22.3 6.6 274 130 87 0.65 21.8 6.3 260 123 95 0.67 19.6 6.5 268 127 97 0.71 18.8 6.5 271 128 67 71 93 0.6 22.4 6.6 274 133 100 0.7 20.1 6.7 283 137 103 0.7 19.3 6.8 285 138 93 0.5 17.4 6.5 271 131 101 0.50 15.6 6.7 280 135 104 0.5 15.0 6.7 283 137 79 0.93 28.2 6.5 260 113 86 0.96 25.3 6.7 268 117 89 1.00 24.2 6.7 270 118 78 0.88 26.4 6.5 257 112 85 0.92 23.8 6.6 265 116 87 0.96 22.8 6.7 268 117 59 81 0.89 27.7 6.6 279 120 88 0.93 24.9 6.8 288 124 90 0.97 23.9 6.8 291 125 80 0.83 25.3 6.6 277 119 86 0.86 22.8 6.7 285 123 89 0.90 21.9 6.8 288 124 63 75 85 0.81 26.2 6.8 295 131 92 0.84 23.6 7.0 304 136 95 0.88 22.6 7.1 307 137 85 0.67 22.0 6.8 292 130 92 0.70 19.8 6.9 301 134 95 0.73 19.0 7.0 304 136 67 71 91 0.7 22.7 7.0 308 140 98 0.7 20.4 7.2 317 144 101 0.7 19.6 7.3 320 146 91 0.5 17.6 7.0 305 139 99 0.52 15.8 7.2 314 143 102 0.5 15.2 7.2 317 144 78 0.95 28.2 6.9 295 118 84 0.98 25.4 7.1 304 121 87 1.00 23.6 7.1 307 122 76 0.91 26.5 6.8 292 116 83 0.94 23.8 7.0 301 120 85 1.00 23.2 7.1 304 121 59 79 0.92 27.8 7.0 318 125 86 0.95 24.9 7.2 328 129 88 1.00 24.0 7.3 331 130 78 0.85 25.4 7.0 315 124 84 0.88 22.8 7.1 324 128 87 0.92 21.9 7.2 328 129 63 83 0.83 26.2 7.2 335 137 90 0.86 23.6 7.4 346 141 92 0.90 22.6 7.5 349 142 83 0.69 22.0 7.2 332 135 90 0.72 19.8 7.4 342 139 93 0.75 19.0 7.4 346 141 67 88 0.7 22.7 7.5 350 146 96 0.7 20.4 7.6 361 150 99 0.7 19.6 7.7 364 152 89 0.5 17.6 7.4 346 144 96 0.54 15.8 7.6 357 149 99 0.6 15.2 7.6 361 150 71 76 0.98 28.4 7.2 336 124 82 1.00 25.1 7.4 347 127 84 1.00 23.0 7.5 350 129 74 0.93 26.6 7.2 333 122 81 0.97 23.9 7.3 343 126 83 1.00 22.6 7.4 347 127 59 77 0.95 28.0 7.4 362 131 84 0.98 25.1 7.6 373 136 86 1.00 23.5 7.6 377 137 76 0.88 25.5 7.3 358 130 82 0.91 22.9 7.5 369 134 85 0.95 22.0 7.6 373 136 63 81 0.85 26.4 7.6 382 144 88 0.89 23.7 7.8 394 148 90 0.93 22.8 7.8 398 149 86 0.7 22.9 7.8 399 153 93 0.7 20.6 8.0 411 158 96 0.8 19.7 8.1 415 159 87 0.5 17.7 7.8 395 151 94 0.55 15.9 8.0 407 156 88 0.74 20.0 7.7 390 147 81 0.71 22.2 7.5 378 142 97 0.6 15.3 8.0 411 158 71 91 0.78 19.2 7.8 394 148 67 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 72 1.00 27.5 7.5 378 130 78 1.00 23.9 7.7 390 134 80 1.00 21.9 7.8 394 135 71 0.97 26.3 7.5 375 128 77 1.00 23.5 7.6 386 132 79 1.00 21.5 7.7 390 134 59 73 0.98 27.6 7.7 407 138 79 1.00 24.3 7.9 420 142 82 1.00 22.3 7.9 424 143 72 0.91 25.2 7.6 403 136 78 0.94 22.6 7.8 415 141 81 1.00 22.0 7.9 420 142 63 67 77 0.89 26.0 7.9 430 150 83 0.92 23.4 8.1 443 155 86 0.96 22.5 8.2 448 157 77 0.74 21.9 7.8 426 149 84 0.77 19.7 8.0 439 154 86 0.81 18.9 8.1 443 155 105 82 0.7 22.5 8.2 448 160 89 0.7 20.3 8.4 462 165 91 0.8 19.5 8.4 467 167 82 0.6 17.5 8.1 444 159 89 0.57 15.7 8.3 458 164 92 0.6 15.1 8.4 462 165 71 67 1.00 25.5 7.8 418 134 72 1.00 22.1 7.9 431 138 74 1.00 20.3 8.0 435 139 65 0.98 24.5 7.7 414 133 71 1.00 21.7 7.9 427 137 73 1.00 19.9 7.9 431 138 59 68 0.99 25.7 7.9 450 143 74 1.00 22.5 8.1 464 147 76 1.00 20.6 8.2 468 148 67 0.92 23.5 7.9 445 141 72 0.95 21.1 8.1 459 145 75 1.00 20.3 8.1 464 147 63 67 71 0.89 24.3 8.2 475 156 77 0.93 21.9 8.4 490 160 79 0.97 21.0 8.4 495 162 71 0.75 20.4 8.1 470 154 77 0.77 18.4 8.3 485 159 80 0.81 17.6 8.4 490 160 115 75.9 0.7 21.1 8.4 495 166 82 0.8 18.9 8.6 511 171 85 0.8 18.2 8.7 516 173 76.4 0.6 16.3 8.4 490 164 83 0.58 14.7 8.6 506 169 85 0.6 14.1 8.6 511 171 71 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects AHRI Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 85 80 IDB 65 Expanded Cooling Data — 7½ Tons (cont.) 9 10 www.daikincomfort.com 59 100 0.73 17.5 7.2 238 106 97 0.69 18.2 7.1 235 105 90 0.67 18.5 7.0 228 102 102 0.83 20.2 7.2 240 107 99 0.79 21.0 7.2 238 106 91 0.76 21.3 7.0 231 103 Airflow MBh S/T ∆T 3820 kW Hi PR Lo PR MBh S/T ∆T 3400 kW Hi PR Lo PR MBh S/T ∆T 2980 kW Hi PR Lo PR MBh S/T ∆T 3820 kW Hi PR Lo PR MBh S/T ∆T 3400 kW Hi PR Lo PR MBh S/T ∆T 2980 kW Hi PR Lo PR 63 94 0.68 19.7 7.2 248 109 102 0.70 19.4 7.3 256 113 105 0.74 18.6 7.4 258 114 93 0.56 16.0 7.1 246 108 101 0.58 15.7 7.3 253 112 104 0.61 15.1 7.3 256 113 67 102 0.51 16.1 7.4 262 119 110 0.53 15.9 7.5 270 123 113 0.56 15.2 7.6 273 124 102 0.39 12.1 7.3 259 118 110 0.40 11.9 7.5 267 122 114 0.42 11.5 7.5 270 123 109 0.3 11.1 7.6 273 127 118 0.3 11.0 7.8 282 131 122 0.4 10.5 7.8 284 132 - - - 71 89 0.79 21.6 7.5 259 109 96 0.82 21.3 7.7 267 112 99 0.86 20.5 7.7 269 113 87 0.69 18.7 7.5 256 108 95 0.72 18.4 7.6 264 111 98 0.75 17.7 7.7 267 112 59 63 92 0.70 19.9 7.7 278 116 99 0.73 19.6 7.8 287 119 102 0.77 18.8 7.9 290 120 91 0.58 16.2 7.6 276 114 98 0.60 15.9 7.8 284 118 101 0.63 15.3 7.8 287 119 75 67 99 0.53 16.3 7.9 294 126 107 0.55 16.1 8.1 303 130 111 0.58 15.4 8.1 306 131 99 0.40 12.3 7.8 291 125 108 0.42 12.1 8.0 300 129 111 0.44 11.6 8.1 303 130 106 0.3 11.3 8.1 307 134 115 0.4 11.1 8.3 316 139 119 0.4 10.7 8.4 319 140 - - - 71 87 0.81 21.6 7.9 294 113 94 0.84 21.3 8.1 303 116 97 0.88 20.5 8.2 306 118 85 0.71 18.7 7.9 291 112 93 0.74 18.4 8.1 300 115 95 0.77 17.7 8.1 303 116 59 89 0.72 19.9 8.1 317 120 97 0.75 19.6 8.3 326 124 100 0.79 18.9 8.4 330 125 89 0.59 16.2 8.0 313 119 96 0.62 16.0 8.2 323 123 99 0.64 15.3 8.3 326 124 63 97 0.55 16.3 8.3 334 131 105 0.57 16.1 8.5 345 135 108 0.59 15.4 8.6 348 137 97 0.41 12.3 8.3 331 130 105 0.43 12.1 8.5 341 134 108 0.45 11.6 8.5 345 135 67 104 0.4 11.3 8.6 349 140 113 0.4 11.1 8.8 359 144 116 0.4 10.7 8.9 363 145 - - - 71 85 0.83 21.8 8.3 335 119 92 0.86 21.4 8.5 345 122 95 0.91 20.6 8.6 349 123 83 0.73 18.8 8.3 332 117 90 0.76 18.6 8.5 342 121 93 0.80 17.8 8.5 345 122 59 67 94 0.56 16.4 8.7 381 138 102 0.58 16.2 9.0 393 142 95 0.77 19.8 8.7 372 130 87 0.75 20.1 8.5 361 126 105 0.61 15.6 9.0 396 143 95 0.42 12.4 8.7 377 136 103 0.44 12.2 8.9 389 141 106 0.46 11.7 9.0 392 142 97 0.81 19.0 8.8 375 131 86 0.61 16.3 8.4 357 125 94 0.63 16.1 8.6 368 129 96 0.67 15.4 8.7 372 130 63 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 101 0.4 11.3 9.0 397 147 110 0.4 11.2 9.2 409 151 113 0.4 10.7 9.3 414 153 - - - 71 80 0.86 21.5 8.6 377 124 87 0.90 21.1 8.9 389 128 90 0.94 20.3 8.9 392 129 79 0.76 18.6 8.6 373 123 86 0.79 18.3 8.8 385 127 88 0.83 17.6 8.9 389 128 59 83 0.77 19.8 8.8 406 132 90 0.80 19.5 9.0 418 136 92 0.84 18.7 9.1 422 138 82 0.64 16.1 8.8 402 131 89 0.66 15.8 9.0 414 135 92 0.69 15.2 9.0 418 136 63 67 90 0.59 16.2 9.1 428 144 97 0.61 16.0 9.3 442 149 100 0.64 15.3 9.4 446 150 90 0.44 12.2 9.0 424 143 97 0.46 12.0 9.2 437 147 100 0.48 11.6 9.3 442 149 105 96 0.4 11.2 9.4 447 154 104 0.4 11.0 9.6 461 159 107 0.4 10.6 9.7 465 160 - - - 71 75 0.87 20.1 8.9 416 129 81 0.90 19.8 9.1 429 133 83 0.95 19.0 9.2 434 134 73 0.77 17.4 8.9 412 127 79 0.80 17.1 9.1 425 131 82 0.83 16.4 9.1 429 133 59 77 0.78 18.5 9.1 448 137 83 0.81 18.2 9.3 462 141 86 0.85 17.5 9.4 467 142 76 0.64 15.0 9.0 444 135 82 0.66 14.8 9.3 457 140 85 0.70 14.2 9.3 462 141 63 67 83 0.59 15.1 9.4 473 149 90 0.61 14.9 9.6 488 154 93 0.64 14.3 9.7 493 155 83 0.44 11.4 9.3 469 148 90 0.46 11.2 9.5 483 152 93 0.48 10.8 9.6 488 154 115 89 0.4 10.4 9.7 494 159 97 0.4 10.3 9.9 509 164 100 0.4 9.9 10.0 514 166 - - - 71 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects ACCA (TVA) Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Subcooling, 10±2 °F @ liquid access fitting; AHRI 95 test conditions. Design Superheat 8±3°F @ compressor suction access fitting. 75 70 IDB 65 Expanded Cooling Data — 8½ Tons SS-DCG7 SS-DCG7 www.daikincomfort.com 59 103 0.91 22.6 7.3 242 108 100 0.86 23.5 7.2 240 107 93 0.83 23.8 7.1 233 104 105 0.95 24.1 7.3 245 109 102 0.91 25.0 7.3 242 108 94 0.87 25.4 7.1 235 105 Airflow MBh S/T ∆T 3820 kW Hi PR Lo PR MBh S/T ∆T 3400 kW Hi PR Lo PR MBh S/T ∆T 2980 kW Hi PR Lo PR MBh S/T ∆T 3820 kW Hi PR Lo PR MBh S/T ∆T 3400 kW Hi PR Lo PR MBh S/T ∆T 2980 kW Hi PR Lo PR 63 96 0.84 25.0 7.3 253 112 104 0.87 24.6 7.4 261 115 107 0.92 23.7 7.5 264 116 95 0.78 22.8 7.2 251 111 103 0.81 22.5 7.4 258 114 106 0.85 21.6 7.4 261 115 67 101 0.76 23.6 7.5 267 122 109 0.79 23.3 7.6 276 126 112 0.83 22.4 7.7 278 127 101 0.64 19.9 7.4 265 121 110 0.66 19.6 7.6 273 124 113 0.69 18.8 7.6 276 126 71 107 0.6 20.5 7.7 279 130 116 0.64 20.1 7.9 287 134 120 0.7 19.4 7.9 290 135 108 0.5 15.9 7.6 276 128 117 0.49 15.6 7.8 285 132 121 0.5 15.0 7.9 287 134 59 92 0.91 25.7 7.6 264 111 100 0.94 25.3 7.8 272 114 103 0.98 24.4 7.9 275 115 91 0.86 24.1 7.6 261 110 98 0.90 23.8 7.7 269 113 101 0.94 22.8 7.8 272 114 63 94 0.87 25.3 7.8 284 118 102 0.91 24.9 8.0 293 122 105 0.95 24.0 8.0 296 123 93 0.81 23.1 7.7 281 117 100 0.84 22.8 7.9 290 120 103 0.88 21.9 8.0 293 122 IDB: Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings. 85 80 IDB 65 75 67 98 0.79 23.9 8.0 300 129 107 0.82 23.6 8.2 309 133 110 0.86 22.6 8.3 312 134 99 0.66 20.1 7.9 297 127 107 0.68 19.8 8.1 306 131 110 0.72 19.0 8.2 309 133 71 105 0.6 20.7 8.2 313 137 114 0.66 20.4 8.4 322 141 117 0.7 19.6 8.5 326 143 106 0.5 16.1 8.2 310 136 114 0.51 15.8 8.4 319 140 118 0.5 15.2 8.4 322 141 63 92 0.90 25.3 8.2 323 123 99 0.93 24.9 8.4 333 126 102 0.97 24.0 8.5 336 128 90 0.83 23.1 8.2 320 121 98 0.86 22.8 8.4 330 125 101 0.90 21.9 8.4 333 126 67 96 0.81 23.9 8.5 341 134 104 0.84 23.6 8.7 352 138 107 0.88 22.7 8.7 355 139 96 0.68 20.1 8.4 338 132 105 0.70 19.8 8.6 348 137 108 0.73 19.0 8.7 352 138 71 102 0.7 20.7 8.7 356 142 111 0.68 20.4 8.9 367 147 114 0.7 19.6 9.0 370 148 103 0.5 16.1 8.7 352 141 112 0.52 15.8 8.9 363 145 115 0.5 15.2 8.9 367 147 88 0.96 25.9 8.5 342 121 95 0.99 25.5 8.7 352 125 98 1.00 23.6 8.7 356 126 86 0.91 24.3 8.4 338 120 93 0.95 23.9 8.6 349 124 96 1.00 23.2 8.7 352 125 59 89 0.92 25.5 8.6 368 129 97 0.96 25.1 8.8 379 133 100 1.00 24.0 8.9 383 134 88 0.86 23.3 8.6 364 127 95 0.89 22.9 8.8 375 131 98 0.93 22.1 8.8 379 133 63 94 0.83 24.1 8.9 388 141 101 0.87 23.7 9.1 400 145 105 0.91 22.8 9.2 404 146 94 0.70 20.3 8.8 385 139 100 0.7 20.9 9.2 405 150 108 0.70 20.6 9.4 418 154 112 0.7 19.8 9.5 422 156 101 0.5 16.2 9.1 401 148 109 0.54 15.9 9.3 414 153 102 0.72 20.0 9.0 397 143 71 112 0.6 15.3 9.4 418 154 67 105 0.76 19.2 9.1 400 145 83 0.99 25.6 8.8 385 127 90 1.00 24.4 9.0 396 131 93 1.00 22.4 9.1 400 132 82 0.95 24.0 8.7 381 126 89 0.98 23.6 8.9 393 129 91 1.00 22.0 9.0 396 131 59 85 0.96 25.2 9.0 414 135 92 1.00 24.8 9.2 427 139 95 1.00 22.8 9.2 431 140 84 0.89 23.0 8.9 410 134 91 0.92 22.6 9.1 422 138 93 0.97 21.7 9.2 427 139 63 67 89 0.87 23.8 9.2 437 147 96 0.90 23.4 9.5 451 152 99 0.94 22.5 9.5 455 153 89 0.72 20.0 9.2 433 146 97 0.75 19.7 9.4 446 150 100 0.79 18.9 9.5 451 152 105 71 95 0.7 20.6 9.5 456 157 103 0.73 20.3 9.8 470 162 106 0.8 19.5 9.8 475 163 96 0.5 16.0 9.5 451 155 104 0.56 15.7 9.7 465 160 107 0.6 15.1 9.8 470 162 77 1.00 23.8 9.1 425 131 84 1.00 22.6 9.3 438 135 86 1.00 20.7 9.4 442 137 76 0.96 22.4 9.0 421 130 82 0.99 22.1 9.2 434 134 85 1.00 20.4 9.3 438 135 59 79 0.97 23.5 9.3 457 140 85 1.00 23.1 9.5 471 144 88 1.00 21.1 9.6 476 145 78 0.90 21.5 9.2 453 138 84 0.93 21.1 9.4 467 142 87 1.00 20.8 9.5 471 144 63 67 82 0.87 22.2 9.5 483 152 89 0.91 21.9 9.8 498 157 92 0.95 21.0 9.8 503 159 83 0.73 18.7 9.5 478 151 90 0.76 18.4 9.7 493 155 92 0.79 17.7 9.8 498 157 115 88 0.7 19.2 9.8 504 162 95 0.7 18.9 10.1 519 167 98 0.8 18.2 10.2 524 169 89 0.5 14.9 9.8 499 161 96 0.6 14.7 10.0 514 166 99 0.6 14.1 10.1 519 167 71 Shaded areas reflect AHRI Rating Conditions AMPS: Unit amps (comp.+ evaporator + condenser fan motors) Design Subcooling, 10±2 °F @ liquid access fitting; AHRI 95 test conditions. Design Superheat 8±3°F @ compressor suction access fitting. 90 0.93 25.8 8.1 300 115 97 0.96 25.4 8.3 309 119 100 1.00 24.2 8.3 313 120 88 0.89 24.1 8.0 297 114 96 0.92 23.8 8.2 306 118 99 0.96 22.9 8.3 309 119 59 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature Expanded Cooling Data — 8½ Tons (cont.) 11 12 www.daikincomfort.com 110 0.70 20.3 8.2 245 104 102 0.67 22.6 8.0 237 101 116 0.83 22.5 8.3 250 106 112 0.79 23.4 8.2 247 105 104 0.77 26.1 8.1 240 102 MBh S/T ∆T 2800 kW Hi PR Lo PR MBh S/T ∆T kW Hi PR Lo PR MBh S/T ∆T kW Hi PR Lo PR MBh S/T ∆T 2800 kW Hi PR Lo PR 3500 3938 3500 3938 MBh S/T ∆T kW Hi PR Lo PR 59 114 0.73 19.5 8.2 247 105 MBh S/T ∆T kW Hi PR Lo PR Airflow 63 107 0.69 24.0 8.2 258 108 116 0.71 21.6 8.4 266 111 119 0.75 20.7 8.4 269 113 106 0.56 19.5 8.1 255 107 114 0.58 17.5 8.3 263 110 118 0.61 16.8 8.4 266 111 67 115 0.52 19.7 8.4 272 118 125 0.54 17.7 8.6 281 122 129 0.56 17.0 8.7 284 123 116 0.39 14.8 8.4 270 117 125 0.40 13.3 8.5 278 120 129 0.42 12.8 8.6 281 122 124 0.3 13.6 8.7 284 126 134 0.3 12.2 8.8 293 130 138 0.4 11.7 8.9 296 131 - - - 71 59 101 0.79 26.4 8.6 269 107 110 0.82 23.7 8.8 277 111 113 0.86 22.8 8.8 280 112 99 0.70 22.8 8.5 266 106 108 0.72 20.5 8.7 274 110 111 0.76 19.7 8.8 277 111 63 104 0.71 24.3 8.7 289 114 113 0.74 21.8 8.9 298 118 116 0.77 21.0 9.0 301 119 103 0.58 19.8 8.7 286 113 112 0.61 17.8 8.9 295 117 115 0.63 17.1 8.9 298 118 75 67 113 0.54 19.9 9.0 306 125 122 0.56 17.9 9.2 315 128 126 0.58 17.2 9.3 318 130 113 0.40 15.0 8.9 302 123 122 0.42 13.5 9.1 312 127 126 0.44 12.9 9.2 315 128 121 0.3 13.7 9.2 319 133 131 0.4 12.4 9.5 329 137 135 0.4 11.9 9.5 332 138 - - - 71 59 99 0.81 26.4 9.1 306 112 107 0.84 23.7 9.3 315 115 110 0.89 22.8 9.3 318 116 97 0.72 22.9 9.0 303 110 105 0.74 20.5 9.2 312 114 108 0.78 19.7 9.3 315 115 102 0.73 24.3 9.2 329 119 110 0.76 21.9 9.4 339 122 113 0.79 21.0 9.5 343 124 101 0.60 19.8 9.2 326 117 109 0.62 17.8 9.4 336 121 112 0.65 17.1 9.4 339 122 63 110 0.55 19.9 9.5 348 130 119 0.57 17.9 9.7 358 134 123 0.60 17.2 9.8 362 135 110 0.41 15.0 9.4 344 128 119 0.43 13.5 9.6 355 132 123 0.45 13.0 9.7 358 134 67 118 0.4 13.8 9.8 362 138 128 0.4 12.4 10.0 374 142 132 0.4 11.9 10.1 377 144 - - - 71 96 0.84 26.6 9.5 348 117 104 0.87 23.9 9.7 359 121 108 0.91 23.0 9.8 363 122 95 0.74 23.0 9.4 345 116 103 0.77 20.7 9.6 355 120 106 0.80 19.9 9.7 359 121 59 67 107 0.57 20.1 9.9 396 136 116 0.59 18.0 10.2 408 140 107 0.78 22.0 9.9 386 128 99 0.75 24.5 9.7 375 125 120 0.62 17.3 10.2 412 142 108 0.43 15.1 9.9 392 135 117 0.44 13.6 10.1 404 139 120 0.47 13.0 10.2 408 140 111 0.82 21.1 9.9 390 130 98 0.62 19.9 9.6 371 123 106 0.64 17.9 9.8 383 127 110 0.67 17.2 9.9 386 128 63 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 115 0.4 13.9 10.2 413 145 125 0.4 12.5 10.5 426 149 129 0.4 12.0 10.5 430 151 - - - 71 59 92 0.87 26.2 9.8 392 123 99 0.90 23.6 10.0 404 127 102 0.95 22.6 10.1 408 128 90 0.77 22.7 9.7 388 122 98 0.80 20.4 10.0 400 125 100 0.83 19.6 10.0 404 127 63 94 0.78 24.2 10.0 422 131 102 0.81 21.7 10.2 435 135 105 0.85 20.8 10.3 439 136 93 0.64 19.6 9.9 417 129 101 0.66 17.7 10.2 430 133 104 0.70 16.9 10.2 435 135 67 102 0.59 19.8 10.3 445 143 111 0.61 17.8 10.5 459 147 114 0.64 17.1 10.6 464 148 102 0.44 14.9 10.2 441 141 111 0.46 13.4 10.5 454 146 114 0.48 12.9 10.5 459 147 105 109 0.4 13.7 10.6 464 152 119 0.4 12.3 10.9 479 157 122 0.4 11.8 10.9 484 158 - - - 71 85 0.88 24.5 10.1 433 127 92 0.91 22.0 10.4 446 131 95 0.96 21.1 10.4 451 132 83 0.77 21.2 10.0 429 126 90 0.80 19.1 10.3 442 130 93 0.84 18.3 10.4 446 131 59 87 0.79 22.6 10.3 466 135 95 0.82 20.3 10.6 480 139 97 0.86 19.5 10.6 485 141 86 0.65 18.3 10.2 461 134 94 0.67 16.5 10.5 476 138 96 0.70 15.8 10.6 480 139 63 67 95 0.60 18.5 10.6 492 148 102 0.62 16.6 10.9 507 152 105 0.65 15.9 11.0 512 154 95 0.45 13.9 10.6 487 146 103 0.46 12.5 10.8 502 151 106 0.49 12.0 10.9 507 152 115 101 0.4 12.8 11.0 513 157 110 0.4 11.5 11.2 529 162 113 0.4 11.0 11.3 534 164 - - - 71 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects ACCA (TVA) Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 75 70 IDB 65 Expanded Cooling Data — 10 Tons SS-DCG7 SS-DCG7 www.daikincomfort.com 114 0.87 26.2 8.3 250 106 105 0.84 29.1 8.1 242 103 120 0.96 26.8 8.4 255 108 116 0.91 27.9 8.3 252 107 107 0.88 31.0 8.2 244 104 MBh S/T ∆T 2800 kW Hi PR Lo PR MBh S/T ∆T kW Hi PR Lo PR MBh S/T ∆T kW Hi PR Lo PR MBh S/T ∆T 2800 kW Hi PR Lo PR 3500 3938 3500 3938 MBh S/T ∆T kW Hi PR Lo PR 59 118 0.91 25.1 8.3 252 107 MBh S/T ∆T kW Hi PR Lo PR Airflow 63 109 0.85 30.5 8.3 263 110 118 0.88 27.4 8.5 271 114 122 0.92 26.3 8.6 274 115 108 0.79 27.9 8.3 261 109 117 0.82 25.1 8.4 269 113 120 0.86 24.1 8.5 271 114 67 115 0.77 28.9 8.5 278 120 124 0.80 25.9 8.7 286 124 128 0.83 24.9 8.8 289 125 115 0.64 24.3 8.5 275 119 125 0.67 21.8 8.7 284 123 128 0.70 20.9 8.7 286 124 71 122 0.6 25.0 8.8 290 128 132 0.65 22.5 9.0 299 132 136 0.7 21.6 9.0 302 133 123 0.5 19.4 8.7 287 127 133 0.50 17.4 8.9 296 131 137 0.5 16.7 9.0 299 132 59 105 0.91 31.4 8.7 274 109 114 0.95 28.2 8.9 283 113 117 0.99 27.1 9.0 286 114 103 0.87 29.5 8.6 272 108 112 0.90 26.5 8.8 280 112 115 0.95 25.4 8.9 283 113 63 107 0.88 30.9 8.9 295 116 116 0.91 27.8 9.1 304 120 119 0.96 26.7 9.1 307 121 105 0.82 28.2 8.8 292 115 114 0.85 25.4 9.0 301 119 117 0.89 24.4 9.1 304 120 75 67 112 0.80 29.2 9.1 312 127 121 0.82 26.3 9.3 321 131 125 0.86 25.2 9.4 325 132 112 0.67 24.5 9.1 309 126 122 0.69 22.1 9.3 318 130 125 0.72 21.2 9.3 321 131 71 119 0.6 25.3 9.4 325 135 129 0.67 22.7 9.6 335 140 133 0.7 21.8 9.7 339 141 120 0.5 19.6 9.3 322 134 130 0.52 17.6 9.5 332 138 134 0.5 16.9 9.6 335 140 59 102 0.94 31.5 9.2 312 114 111 0.97 28.3 9.4 322 117 114 1.00 26.7 9.5 325 118 101 0.89 29.5 9.1 309 113 109 0.93 26.5 9.3 318 116 112 1.00 26.2 9.4 322 117 104 0.90 30.9 9.4 336 121 113 0.94 27.8 9.6 346 125 116 0.98 26.7 9.6 350 126 103 0.84 28.3 9.3 332 120 111 0.87 25.4 9.5 343 124 115 0.91 24.4 9.6 346 125 63 109 0.82 29.2 9.6 355 132 118 0.85 26.3 9.8 366 136 122 0.89 25.2 9.9 369 138 110 0.68 24.6 9.6 351 131 119 0.71 22.1 9.8 362 135 122 0.74 21.2 9.8 366 136 67 116 0.7 25.3 9.9 370 141 126 0.69 22.8 10.1 381 145 130 0.7 21.8 10.2 385 147 117 0.5 19.6 9.8 366 139 127 0.53 17.6 10.1 377 144 131 0.6 16.9 10.1 381 145 71 100 0.97 31.7 9.6 355 120 108 1.00 28.4 9.8 366 123 111 1.00 26.0 9.9 370 124 98 0.92 29.7 9.5 352 118 106 0.96 26.7 9.8 363 122 109 1.00 25.6 9.8 366 123 59 102 0.93 31.2 9.8 382 127 110 0.97 28.0 10.0 394 131 114 1.00 26.5 10.1 398 132 100 0.86 28.5 9.7 379 126 109 0.90 25.6 9.9 390 130 112 0.94 24.6 10.0 394 131 63 107 0.84 29.4 10.1 404 139 115 0.87 26.5 10.3 416 143 119 0.92 25.4 10.4 420 145 107 0.70 24.7 10.0 400 137 114 0.7 25.5 10.4 421 148 123 0.71 22.9 10.6 434 152 127 0.7 22.0 10.7 439 154 114 0.5 19.8 10.3 417 146 124 0.55 17.8 10.5 430 151 116 0.73 22.2 10.2 412 142 71 128 0.6 17.1 10.6 434 152 119 0.77 21.4 10.3 416 143 67 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 59 95 1.00 31.1 10.0 400 125 103 1.00 27.0 10.2 412 129 106 1.00 24.7 10.3 416 130 93 0.96 29.3 9.9 396 124 101 0.99 26.3 10.1 408 128 104 1.00 24.3 10.2 412 129 63 97 0.97 30.7 10.2 430 133 105 1.00 27.5 10.4 444 137 108 1.00 25.2 10.5 448 139 95 0.90 28.1 10.1 426 132 103 0.93 25.2 10.3 439 136 106 1.00 24.8 10.4 444 137 67 101 0.87 29.0 10.5 454 145 110 0.91 26.1 10.7 468 150 113 0.95 25.1 10.8 473 151 102 0.73 24.4 10.4 450 144 110 0.76 21.9 10.6 464 149 114 0.79 21.1 10.7 468 150 105 71 108 0.7 25.1 10.8 474 155 117 0.74 22.6 11.0 489 160 120 0.8 21.7 11.1 493 161 109 0.5 19.5 10.7 469 153 118 0.57 17.5 11.0 484 158 121 0.6 16.8 11.0 489 160 88 1.00 28.8 10.3 442 130 95 1.00 25.0 10.5 455 134 98 1.00 22.9 10.6 460 135 86 0.97 27.3 10.2 437 128 94 1.00 24.6 10.4 451 132 96 1.00 22.5 10.5 455 134 59 90 0.98 28.7 10.5 475 138 97 1.00 25.5 10.7 490 142 100 1.00 23.3 10.8 495 144 88 0.91 26.2 10.4 471 136 96 0.94 23.6 10.6 485 141 98 1.00 23.0 10.7 490 142 63 67 94 0.88 27.1 10.8 502 150 102 0.91 24.4 11.0 517 155 105 0.96 23.4 11.1 523 157 94 0.74 22.8 10.7 497 149 102 0.76 20.5 11.0 512 154 105 0.80 19.7 11.0 517 155 115 71 100 0.7 23.5 11.1 524 160 108 0.7 21.1 11.4 540 165 112 0.8 20.3 11.5 545 167 101 0.6 18.2 11.0 518 159 109 0.6 16.4 11.3 534 164 112 0.6 15.7 11.4 540 165 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects AHRI Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 85 80 IDB 65 Expanded Cooling Data — 10 Tons (cont.) 13 14 www.daikincomfort.com 59 141 0.69 20.4 10.4 252 103 137 0.66 21.3 10.3 249 102 126 0.64 21.8 10.0 242 99 143 0.79 23.6 10.4 254 104 139 0.75 24.7 10.4 252 103 129 0.72 25.2 10.1 244 100 Airflow MBh S/T ∆T 4725 kW Hi PR Lo PR MBh S/T ∆T 4200 kW Hi PR Lo PR MBh S/T ∆T 3360 kW Hi PR Lo PR MBh S/T ∆T 4725 kW Hi PR Lo PR MBh S/T ∆T 4200 kW Hi PR Lo PR MBh S/T ∆T 3360 kW Hi PR Lo PR 63 132 0.65 23.2 10.3 263 107 143 0.67 22.7 10.6 271 110 148 0.70 21.8 10.7 274 111 131 0.53 18.9 10.2 260 106 142 0.55 18.5 10.5 268 109 146 0.58 17.7 10.6 271 110 67 143 0.49 19.0 10.7 277 117 155 0.51 18.6 10.9 286 120 160 0.53 17.8 11.0 289 121 144 0.37 14.3 10.6 275 115 156 0.38 14.0 10.8 283 119 160 0.40 13.4 10.9 286 120 154 0.3 13.1 11.0 289 124 167 0.3 12.9 11.3 298 128 172 0.3 12.3 11.4 301 129 - - - 71 59 126 0.75 25.5 10.9 274 106 136 0.78 25.0 11.2 282 109 140 0.82 23.9 11.3 285 110 124 0.66 22.1 10.8 271 105 134 0.69 21.6 11.1 280 108 138 0.72 20.7 11.2 282 109 63 129 0.67 23.5 11.1 295 113 140 0.70 23.0 11.4 304 116 144 0.73 22.0 11.5 307 117 128 0.55 19.1 11.0 292 112 139 0.57 18.7 11.3 301 115 143 0.60 17.9 11.4 304 116 75 67 140 0.51 19.2 11.5 311 123 152 0.53 18.8 11.8 321 127 156 0.55 18.0 11.9 324 128 140 0.38 14.5 11.4 308 122 152 0.40 14.2 11.7 318 126 157 0.42 13.6 11.8 321 127 150 0.3 13.3 11.9 325 131 163 0.3 13.0 12.2 335 135 168 0.4 12.5 12.3 338 137 - - - 71 59 123 0.77 25.5 11.6 312 110 133 0.80 25.0 11.9 321 114 137 0.84 23.9 12.0 324 115 121 0.68 22.1 11.5 308 109 131 0.70 21.6 11.8 318 112 135 0.74 20.7 11.9 321 114 126 0.69 23.5 11.8 335 117 137 0.71 23.0 12.1 346 121 141 0.75 22.0 12.2 349 122 125 0.57 19.1 11.7 332 116 135 0.59 18.7 12.0 342 120 139 0.62 17.9 12.1 346 121 63 137 0.52 19.3 12.2 354 128 148 0.54 18.9 12.5 365 132 152 0.57 18.1 12.6 369 133 137 0.39 14.5 12.1 351 127 148 0.41 14.2 12.4 361 131 153 0.43 13.6 12.5 365 132 67 147 0.3 13.3 12.6 369 136 159 0.3 13.0 12.9 381 141 164 0.4 12.5 13.0 385 142 - - - 71 120 0.79 25.7 12.2 355 116 130 0.82 25.2 12.5 366 119 133 0.86 24.1 12.6 370 121 118 0.70 22.2 12.1 351 115 127 0.73 21.8 12.4 362 118 131 0.76 20.9 12.5 366 119 59 67 134 0.40 14.6 12.7 399 133 149 0.58 18.2 13.3 420 140 144 0.56 19.0 13.2 416 139 133 0.54 19.4 12.9 403 134 137 0.77 22.2 12.9 398 128 133 0.74 23.2 12.8 394 127 123 0.71 23.7 12.4 382 123 145 0.42 14.3 13.1 412 137 149 0.44 13.7 13.2 416 139 122 0.58 19.2 12.3 378 122 132 0.61 18.9 12.7 390 126 136 0.63 18.0 12.8 394 127 63 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 143 0.3 13.4 13.3 421 143 155 0.4 13.1 13.6 434 148 160 0.4 12.6 13.7 438 149 - - - 71 59 114 0.82 25.3 12.7 399 121 123 0.86 24.8 13.0 412 125 127 0.90 23.8 13.1 416 126 112 0.73 21.9 12.6 395 120 121 0.75 21.5 12.9 407 124 125 0.79 20.6 13.0 412 125 63 117 0.74 23.3 13.0 430 129 127 0.77 22.9 13.3 443 133 131 0.80 21.9 13.4 447 134 116 0.61 19.0 12.9 425 128 125 0.63 18.6 13.2 439 132 129 0.66 17.8 13.3 443 133 67 127 0.56 19.1 13.4 454 141 137 0.58 18.7 13.8 468 145 141 0.61 17.9 13.9 472 147 127 0.42 14.4 13.3 449 139 137 0.44 14.1 13.6 463 144 142 0.46 13.5 13.8 468 145 105 136 0.4 13.2 13.9 473 150 147 0.4 12.9 14.2 488 155 152 0.4 12.4 14.3 493 156 - - - 71 59 105 0.83 23.7 13.1 441 125 114 0.86 23.2 13.5 455 129 117 0.90 22.2 13.6 459 131 104 0.73 20.5 13.0 437 124 112 0.76 20.1 13.4 450 128 116 0.80 19.2 13.5 455 129 63 108 0.74 21.8 13.4 475 133 117 0.77 21.4 13.8 489 138 121 0.81 20.4 13.9 494 139 107 0.61 17.7 13.3 470 132 116 0.63 17.4 13.7 485 136 120 0.66 16.6 13.8 489 138 67 117 0.56 17.9 13.9 501 146 127 0.58 17.5 14.2 517 150 131 0.61 16.7 14.4 522 152 118 0.42 13.5 13.8 496 144 127 0.44 13.2 14.1 512 149 131 0.46 12.6 14.2 517 150 115 126 0.4 12.3 14.3 523 155 136 0.4 12.1 14.7 539 160 141 0.4 11.6 14.9 544 162 - - - 71 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects ACCA Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 75 70 IDB 65 Expanded Cooling Data — 12½ Tons SS-DCG7 SS-DCG7 www.daikincomfort.com MBh S/T ∆T 3360 kW Hi PR Lo PR MBh S/T ∆T 4200 kW Hi PR Lo PR MBh S/T ∆T 4725 kW Hi PR Lo PR MBh S/T ∆T 3360 kW Hi PR Lo PR MBh S/T ∆T 4200 kW Hi PR Lo PR MBh S/T ∆T 4725 kW Hi PR Lo PR Airflow 133 0.83 30.0 10.3 249 102 144 0.86 29.4 10.5 257 106 149 0.91 28.1 10.6 259 107 131 0.79 28.1 10.2 247 101 142 0.82 27.5 10.4 254 105 136 0.80 29.5 10.5 268 109 147 0.83 28.9 10.8 276 112 151 0.87 27.7 10.8 279 113 134 0.75 26.9 10.4 265 108 145 0.77 26.4 10.7 274 111 63 149 0.81 25.3 10.8 276 112 59 146 0.86 26.4 10.5 257 106 67 142 0.73 27.9 10.8 283 119 154 0.75 27.3 11.1 292 123 159 0.79 26.1 11.2 295 124 143 0.61 23.4 10.7 280 118 155 0.63 23.0 11.0 289 121 159 0.66 22.0 11.1 292 123 71 152 0.6 24.1 11.2 295 127 164 0.61 23.6 11.5 304 131 169 0.6 22.6 11.5 307 132 153 0.5 18.7 11.1 292 125 165 0.47 18.3 11.4 301 129 170 0.5 17.6 11.5 304 131 59 130 0.86 30.4 11.1 280 108 141 0.90 29.7 11.3 288 112 145 0.94 28.5 11.4 291 113 128 0.82 28.5 11.0 277 107 138 0.85 27.9 11.3 285 110 143 0.90 26.7 11.3 288 112 63 133 0.83 29.9 11.3 301 115 144 0.86 29.3 11.6 310 119 148 0.91 28.0 11.7 313 120 131 0.77 27.3 11.2 298 114 142 0.80 26.7 11.5 307 117 146 0.84 25.6 11.6 310 119 75 67 139 0.75 28.2 11.7 318 126 150 0.78 27.6 12.0 327 130 155 0.82 26.5 12.1 331 131 140 0.63 23.7 11.6 315 124 151 0.65 23.2 11.9 324 128 156 0.68 22.2 12.0 327 130 71 148 0.6 24.4 12.1 331 134 161 0.63 23.9 12.4 342 138 165 0.7 22.9 12.5 345 139 149 0.5 19.0 12.0 328 132 162 0.49 18.6 12.3 338 137 166 0.5 17.8 12.4 342 138 59 127 0.89 30.4 11.8 318 112 138 0.92 29.8 12.1 328 116 142 0.96 28.5 12.2 331 117 125 0.84 28.5 11.7 315 111 135 0.88 27.9 12.0 325 115 139 0.92 26.7 12.1 328 116 129 0.85 29.9 12.0 342 120 140 0.89 29.3 12.3 353 123 144 0.93 28.0 12.4 356 125 128 0.79 27.3 11.9 339 118 138 0.82 26.7 12.2 349 122 142 0.86 25.6 12.3 353 123 63 136 0.77 28.3 12.4 361 131 147 0.80 27.7 12.7 372 135 151 0.84 26.5 12.8 376 136 136 0.64 23.7 12.3 358 129 148 0.67 23.3 12.6 369 133 152 0.70 22.3 12.7 372 135 67 145 0.6 24.5 12.8 377 139 157 0.65 24.0 13.2 388 143 161 0.7 22.9 13.3 392 145 146 0.5 19.0 12.7 373 138 158 0.50 18.6 13.0 385 142 163 0.5 17.8 13.2 388 143 71 124 0.91 30.6 12.4 362 118 134 0.95 30.0 12.7 373 122 138 0.99 28.7 12.8 377 123 122 0.87 28.7 12.3 359 117 132 0.90 28.1 12.6 370 121 136 0.95 26.9 12.7 373 122 59 126 0.88 30.1 12.7 390 126 137 0.91 29.5 13.0 402 130 141 0.96 28.2 13.1 406 131 124 0.82 27.5 12.6 386 124 135 0.85 26.9 12.9 398 128 139 0.89 25.8 13.0 402 130 63 132 0.80 28.5 13.1 411 137 143 0.83 27.9 13.4 424 141 148 0.87 26.7 13.5 428 143 133 0.67 23.9 13.0 407 136 144 0.69 23.4 13.3 420 140 148 0.72 22.4 13.4 424 141 67 Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 71 141 0.6 24.6 13.5 429 146 153 0.67 24.1 13.9 442 151 157 0.7 23.1 14.0 447 152 142 0.5 19.1 13.4 425 145 154 0.52 18.7 13.7 438 149 159 0.5 17.9 13.9 442 151 59 118 0.95 30.2 12.9 407 124 127 0.98 29.6 13.2 420 128 131 1.00 27.4 13.4 424 129 116 0.90 28.3 12.8 403 123 125 0.94 27.7 13.1 416 126 129 1.00 27.0 13.2 420 128 63 120 0.92 29.7 13.2 438 132 130 0.95 29.1 13.5 452 136 134 1.00 27.8 13.7 456 137 118 0.85 27.1 13.1 434 130 128 0.88 26.6 13.4 447 134 132 0.92 25.4 13.5 452 136 67 126 0.83 28.1 13.6 463 144 136 0.86 27.5 14.0 477 148 140 0.90 26.3 14.1 482 150 126 0.69 23.6 13.5 458 142 137 0.72 23.1 13.9 473 147 141 0.75 22.1 14.0 477 148 105 71 134 0.7 24.3 14.1 483 153 145 0.69 23.8 14.5 498 158 150 0.7 22.8 14.6 503 159 135 0.5 18.8 14.0 478 152 146 0.54 18.5 14.3 493 156 151 0.6 17.7 14.5 498 158 59 109 0.96 28.2 13.4 450 128 118 0.99 27.6 13.7 464 132 122 1.00 25.4 13.8 469 133 107 0.91 26.4 13.2 446 127 116 0.95 25.9 13.6 459 131 120 1.00 25.0 13.7 464 132 63 111 0.92 27.7 13.7 484 136 120 0.96 27.2 14.0 499 140 124 1.00 25.9 14.1 504 142 109 0.86 25.3 13.5 480 135 119 0.89 24.8 13.9 494 139 122 0.93 23.7 14.0 499 140 67 116 0.83 26.2 14.1 511 149 126 0.86 25.7 14.5 527 153 130 0.91 24.6 14.6 533 155 117 0.70 22.0 14.0 506 147 127 0.72 21.6 14.4 522 152 131 0.76 20.7 14.5 527 153 115 71 124 0.7 22.7 14.6 533 158 135 0.7 22.2 15.0 550 163 139 0.7 21.3 15.1 555 165 125 0.5 17.6 14.5 528 157 135 0.5 17.2 14.9 545 162 140 0.6 16.5 15.0 550 163 IDB: Entering Indoor Dry Bulb Temperature Shaded area reflects AHRI Rating Conditions Amps: Unit amps (comp.+ evaporator + condenser fan motors) High and low pressures are measured at the liquid and suction access fittings. Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions 85 80 IDB 65 Expanded Cooling Data — 12½ Tons (cont.) 15 Airflow Data — 7½ Tons Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM --- --- BHP 0.1 --- --- --- --- 0.3 --- --- --- --- --- --- 0.5 --- --- --- 3387 844 1.32 0.7 3453 893 1.5 2903 850 1.12 0.9 2957 899 1.29 --- --- --- 2 CFM RPM --- BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 3522 1.14 3228 706 0.94 2964 661 0.73 --- --- 750 3337 800 1.19 3102 756 1 2800 706 0.76 2504 661 0.59 2834 806 0.99 2603 757 0.8 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.7 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 3575 904 1.66 0.9 --- --- --- --- --- --- --- --- --- --- --- --- 3258 925 1.56 3113 909 1.41 1.1 --- --- --- --- --- --- --- --- --- 3580 1013 1.97 3001 948 1.42 2722 915 1.25 1.3 --- --- --- --- --- --- 3616 1063 2.17 3247 1019 1.79 2646 959 1.3 --- --- --- 1.5 --- --- --- --- --- --- 3275 1069 2.05 2803 1025 1.68 --- --- --- --- --- --- 1.7 --- --- --- 3346 1118 2.24 2885 1074 1.97 --- --- --- --- --- --- --- --- --- 1.9 --- --- --- 3009 1125 2.05 --- --- --- --- --- --- --- --- --- --- --- --- 2.1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.1 --- --- --- --- --- --- --- --- --- --- --- --- 3381 703 0.99 3078 659 0.78 0.3 --- --- --- --- --- --- 3560 796 1.26 3271 747 1.02 2946 703 0.82 2604 659 0.63 0.5 --- --- --- 3492 841 1.36 3159 799 1.09 2819 752 0.86 --- --- --- --- --- --- 0.7 3453 891 1.5 3094 846 1.18 --- --- --- --- --- --- --- --- --- --- --- --- 0.9 2964 896 1.29 2524 852 0.96 --- --- --- --- --- --- --- --- --- --- --- --- 1.1 2537 902 1.08 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive — Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.7 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 3567 903 1.58 0.9 --- --- --- --- --- --- --- --- --- --- --- --- 3596 953 1.79 3145 906 1.39 1.1 --- --- --- --- --- --- --- --- --- 3630 1007 1.97 3168 963 1.56 2675 909 1.18 1.3 --- --- --- --- --- --- 3649 1063 2.19 3255 1021 1.8 2724 965 1.35 --- --- --- 1.5 --- --- --- --- --- --- 3316 1068 2.0 2823 1058 1.61 --- --- --- --- --- --- 1.7 --- --- --- 3287 1112 2.16 2869 1074 1.78 --- --- --- --- --- --- --- --- --- 1.9 --- --- --- 2970 1122 2.0 --- --- --- --- --- --- --- --- --- --- --- --- 2.1 --- --- --- 2644 1133 1.92 --- --- --- --- --- --- --- --- --- --- --- --- Notes • Assume dry coil with filter in place; CFM correction for wet coil = 3% • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that • exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton. 16 www.daikincomfort.com SS-DCG7 Airflow Data — 8½ Tons Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM 0.1 --- --- --- --- --- --- --- --- --- 3372 747 1.11 3078 703 0.91 2814 658 0.3 --- --- --- --- --- --- 3187 797 1.16 2952 753 0.97 2650 703 0.73 --- --- --- 0.5 --- --- --- 3237 841 1.29 2684 803 0.96 2453 754 0.77 --- --- --- --- --- --- BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 0.70 0.7 3303 890 1.47 2753 847 1.09 --- --- --- --- --- --- --- --- --- --- --- --- 0.9 2807 896 1.26 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive -- Down Shot ESP (“ W.C.) 0.7 Turns Open 0 CFM RPM --- --- BHP --- 1 CFM RPM --- --- BHP --- 2 CFM RPM --- --- BHP --- 3 CFM RPM --- --- BHP --- 4 CFM RPM --- BHP --- --- 5 CFM RPM BHP 3425 1.63 901 0.9 --- --- --- --- --- --- --- --- --- --- --- --- 3108 922 1.53 2963 906 1.38 1.1 --- --- --- --- --- --- --- --- --- 3430 1010 1.94 2851 945 1.39 2572 912 1.22 1.3 --- --- --- --- --- --- 3466 1060 2.14 3097 1016 1.76 2496 956 1.27 --- --- --- 1.5 --- --- --- --- --- --- 3125 1066 2.02 2653 1022 1.65 --- --- --- --- --- --- 1.7 --- --- --- 3196 1115 2.21 2735 1071 1.94 --- --- --- --- --- --- --- --- --- 1.9 3251 1160 2.36 2859 1122 2.02 --- --- --- --- --- --- --- --- --- --- --- --- 2.1 2914 1167 2.17 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.75 0.1 --- --- --- --- --- --- --- --- --- --- --- --- 3231 700 0.96 2928 656 0.3 --- --- --- --- --- --- 3410 793 1.23 3121 744 0.99 2796 700 0.79 --- --- --- 0.5 --- --- --- 3342 838 1.33 3009 796 1.06 2669 749 0.83 --- --- --- --- --- --- 0.7 3303 888 1.47 2944 843 1.15 --- --- --- --- --- --- --- --- --- --- --- --- 0.9 2814 893 1.26 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive -- Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.7 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 3417 900 1.55 0.9 --- --- --- --- --- --- --- --- --- --- --- --- 3446 950 1.76 2995 903 1.36 1.1 --- --- --- --- --- --- --- --- --- 3480 1004 1.94 3018 960 1.53 2525 906 1.15 1.3 --- --- --- --- --- --- 3499 1060 2.16 3105 1018 1.77 2574 962 1.32 --- --- --- 1.5 --- --- --- --- --- --- 3166 1065 1.97 2673 1055 1.58 --- --- --- --- --- --- 1.7 --- --- --- 3137 1109 2.13 2719 1071 1.75 --- --- --- --- --- --- --- --- --- 1.9 3107 1154 2.28 2820 1119 1.97 --- --- --- --- --- --- --- --- --- --- --- --- 2.1 2790 1164 2.12 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- Notes • Assume dry coil with filter in place; CFM correction for wet coil = 3% • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that • exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton. SS-DCG7 www.daikincomfort.com 17 Airflow Data — 10 Tons Standard & Two-Speed Belt-Drive at High Speed — Down Shot ESP (“ W.C.) 0.2 Turns Open 0 CFM RPM --- --- BHP --- 1 CFM RPM --- --- BHP --- 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 4316 1.57 4118 738 1.36 3771 1.08 3376 0.85 780 687 644 0.4 --- --- --- 4282 830 1.76 3928 786 1.4 3595 740 1.13 --- --- --- --- --- --- 0.6 4232 874 1.87 3872 830 1.52 3444 786 1.2 --- --- --- --- --- --- --- --- --- 0.8 3839 880 1.64 3367 836 1.27 --- --- --- --- --- --- --- --- --- --- --- --- 1 3326 885 1.4 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1.2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1.4 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt-Drive — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.8 --- --- --- --- --- --- --- --- --- --- --- --- 4188 943 2.11 3793 889 1.67 1 --- --- --- --- --- --- --- --- --- 4305 1002 2.39 3836 946 1.89 3416 893 1.45 1.2 --- --- --- --- --- --- 4324 1053 2.63 3879 1003 2.11 3425 951 1.63 --- --- --- 1.4 --- --- --- 4428 1109 2.92 3973 1056 2.35 3434 1009 1.8 --- --- --- --- --- --- 1.6 4465 1160 3.2 4088 1113 2.67 3506 1068 2.1 --- --- --- --- --- --- --- --- --- 1.8 4129 1168 2.9 3625 1122 2.3 --- --- --- --- --- --- --- --- --- --- --- --- 2 3694 1175 2.65 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- Standard & Two-Speed Belt-Drive at High Speed — Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.2 --- --- --- --- --- --- --- --- --- 4391 737 1.48 4054 693 1.22 3760 645 0.97 0.4 --- --- --- --- --- --- 4314 781 1.61 3969 737 1.29 3534 693 1 --- --- --- 0.6 --- --- --- 4255 826 1.69 3894 781 1.38 3447 743 1.09 --- --- --- --- --- --- 0.8 4234 876 1.85 3792 832 1.47 --- --- --- --- --- --- --- --- --- --- --- --- 1 3724 877 1.59 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1.2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1.4 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- High-Static Belt-Drive — Horizontal ESP (“ W.C.) Turns Open 0 CFM RPM BHP 1 CFM RPM BHP 2 CFM RPM BHP 3 CFM RPM BHP 4 CFM RPM BHP 5 CFM RPM BHP 0.8 --- --- --- --- --- --- --- --- --- --- --- --- 4408 885 2.02 1 --- --- --- --- --- --- --- --- --- 4464 940 2.29 3929 891 1.76 1.46 1.2 1.4 1.6 DO NOT OPERATE --- --- --- --- --- --- 4585 996 2.58 4026 946 2 3436 897 --- --- --- 4697 1049 2.92 4141 1001 2.26 3509 951 1.7 --- --- --- --- --- --- 4264 1056 2.58 3663 1007 1.96 --- --- --- --- --- --- 1.8 4359 1105 2.85 3785 1061 2.22 --- --- --- --- --- --- --- --- --- 2 3907 1114 2.49 --- --- --- --- --- --- --- --- --- --- --- --- Notes • Assume dry coil with filter in place; CFM correction for wet coil = 3% • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that • exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton. 18 www.daikincomfort.com SS-DCG7 Airflow Data — 12½ Tons Standard Belt Drive and 2 Speed Belt Drive at High Speed — Down Shot ESP (“ W.C.) 0.2 Turns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 5514 2.92 5604 3.22 5064 2.16 4775 1.81 4514 1.49 4271 1.23 0.4 5279 2.74 5110 2.40 4696 1.94 4447 1.63 4123 1.31 --- --- 0.6 5185 2.67 4813 2.20 4352 1.74 4039 1.43 --- --- --- --- 0.8 4766 2.37 4526 2.02 --- --- --- --- --- --- --- --- 1.0 4223 2.01 --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive — Down Shot ESP (“ W.C.) 0.6 Turns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP --- --- --- --- --- --- --- --- 5515 3.21 5124 2.68 0.8 --- --- --- --- 5840 4.06 5781 3.73 5344 3.07 4721 2.37 1.0 --- --- 5908 4.49 5643 3.86 5369 3.36 4887 2.71 4365 2.13 1.2 5869 4.74 5542 4.11 5229 3.47 4853 2.92 4404 2.35 3986 1.88 1.4 5464 4.30 5180 3.75 4917 3.19 4584 2.71 4197 2.21 --- --- 1.6 5229 4.05 4960 3.53 4397 2.75 4204 2.41 --- --- --- --- 1.8 4961 3.78 4553 3.16 --- --- --- --- --- --- --- --- 2.0 4790 3.61 4315 2.95 --- --- --- --- --- --- --- --- Standard Belt Drive and 2 Speed Belt Drive at High Speed — Horizontal ESP (“ W.C.) 0.2 Turns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 5762 3.08 5485 2.63 5140 2.21 4855 1.84 4513 1.48 4197 1.20 0.4 5550 2.91 5207 2.44 4857 2.03 4489 1.64 4100 1.29 --- --- 0.6 5202 2.65 4922 2.25 4487 1.81 4113 1.45 --- --- --- --- 0.8 4898 2.43 4515 1.99 4074 1.58 --- --- --- --- --- --- 1.0 4549 2.20 4135 1.76 --- --- --- --- --- --- --- --- 1.2 4258 2.01 --- --- --- --- --- --- --- --- --- --- High-Static Belt Drive — Horizontal ESP (“ W.C.) 0.6 Turns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP --- --- --- --- --- --- 5967 3.92 5451 3.16 5275 2.77 0.8 --- --- --- --- --- --- 5628 3.61 5223 2.97 4959 2.54 1.0 --- --- --- --- 5840 4.10 5385 3.39 4999 2.80 4635 2.31 1.2 --- --- --- --- 5643 3.90 5003 3.06 4803 2.65 4160 1.99 1.4 6007 4.93 5740 4.32 5229 3.51 4576 2.71 4440 2.38 --- --- 1.6 5752 4.64 5401 3.97 4917 3.23 --- --- --- --- --- --- 1.8 5380 4.24 5033 3.61 4397 2.79 --- --- --- --- --- --- 2.0 5065 3.91 4573 3.18 --- --- --- --- --- --- --- --- Notes • Assume dry coil with filter in place; CFM correction for wet coil = 3% • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application • that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton. Airflow Pressure Drop of Downflow Economizer for 7.5 to 12.5 Ton Rooftop Units (100% Return Air) SCFM 2000 2500 3000 3500 4000 4500 5000 5500 in. WG 0.02 0.04 0.06 0.09 0.13 0.18 0.23 0.29 SS-DCG7 www.daikincomfort.com 19 20 www.daikincomfort.com 50.239 53.686 FRONT VIEW 99.980 COMBINATION AIR INLET (GAS UNIT) DC*090-150*** 4.475 23.286 7.5 THRU 12.5 TON COMMERCIAL GAS LINE ENTRANCE FLUE / VENT OUTLET ALL DIMENSIONS GIVEN ARE IN INCHES ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE 6.192 TOP VIEW 6.150 13.875 "A" 7.251 19.688 DISCONNECT SWITCH 42.875 RIGHT END VIEW 23.930 12.625 28.312 61.730 "B" 20.055 20.055 20.055 18.055 "A" 53.339 53.339 53.339 58.839 "B" 38.884 LIFTING SHACKLE HOLES BOTH SIDES AND ENDS 6.152 36.375 RETURN AIR SUPPLY CONDENSATE DRAIN OUTLET SUPPLY AIR DUCT MODEL TONNAGE 7.5 TON COMMERCIAL GAS, HT PUMP, AIR CONDITIONER 8.5 TON COMMERCIAL GAS, HT PUMP, AIR CONDITIONER 10 TON COMMERCIAL GAS, HT PUMP, AIR CONDITIONER 12.5 TON COMMERCIAL GAS, HT PUMP, AIR CONDITIONER Dimensions SS-DCG7 Unit Clearances Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and condenser airflow. Do not 48” install the unit beneath any obstruction. Install the unit away from all building exhausts to inhibit ingestion of exhaust air into the unit’s fresh-air intake. 48” 36” Min. 75” 48” Electrical Entrance Locations 3 7¾” 3/4” Dimples Mark Drill Locations DIMPLES MARK DRILL LOCATIONS High-Voltage Entrance HIGH VOLTAGE ENTRANCE 3 10103/16” /16” LOW VOLTAGE ENTRANCE Low-Voltage Entrance 26 ½” 28½” Power and Low-Voltage Block Locations SS-DCG7 www.daikincomfort.com 21 Roof Curb Installation — Rigging Provisions for forks have been included in the unit base frame. No other fork locations are approved. • Unit must be lifted by the four lifting holes located at the base frame corners. • Lifting cables should be attached to the unit with shackles. • The distance between the crane hook and the top of the unit must not be less than 60”. • Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. To remove the struts, extract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit. Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Duct-work dimensions are shown in Roof Curb Installation Instructions Manual. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Lower unit carefully onto roof mounting curb. A While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end. Y 30” Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb COMPRESSOR Compressor 1 1 as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a COMPRESSOR Compressor 2 2 rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct. B C RETURN Return Evaporator Coil EVAPORATOR COIL CG X 49” Supply SUPPLY D Corner & Center-of-Gravity Locations Rigging Weights 7½-Ton Weights (lbs) 8½-Ton & 10-Ton Weights (lbs) 12½-Ton Weights (lbs) Weight A Weight B Weight C Weight D 269 297 254 280 255 321 250 314 315 370 290 340 Shipping Weight Operating Weight 1175 1100 1215 1140 1390 1365 Weight Types To assist in determining rigging requirements, unit weights are shown to the right. Note: These weights are calculated without accessories installed. 22 www.daikincomfort.com SS-DCG7 Roof Curb Installation 3-D View 92¼ 15⅜ x 31⅛ Supply Opening 14⅝ x 38⅜ Return Opening Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb. Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory package. • Determine sufficient structural support before locating and mounting the curb and package unit. • Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs are not available from the factory. • Contractor furnishes curb insulation, cant strips, flashing, and general roofing material. • Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply and return duct openings. 53¼ Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation after unit placement is not recommended. See the manual shipped with the roof curb for assembly 14 and installation instructions. ¾ 1⅝ 14 1⅜ Top View SS-DCG7 www.daikincomfort.com 23 CM1 CM2 www.daikincomfort.com GR L1 OR BK RD RD BK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE BC C L2 L1 L2 L3 C YL LPS 2 LPS1 ⚠ Warning GR BK RD OR YL TR BL BL BL YL 1 4 1 2 3 22 S1 YL RD S2 RD PK PU BL PK RD CCR 2 4 2 3 22 CCR1 POWER SUPPLY 208-240/3/60 SEE NOTE 4 PK BL C BL PK GR G GR GR W1 WH WH REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R RD BR RD BL RD BL YL YL W2 BR Y1 Y2 BL BR BL O PU YL YL ⚡ YL 1 2 3 PU BL WH WH 4 5 7 6 9 YL ECON RS ALS PU PLF 8 RD GR BL RD RD BL PU RD SEE NOTE 2 PU BL BL RD BL BL GR WH RD YL RD SEE NOTE 5 YL BL RD RD High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. GR HPS 2 HPS1 GND 208 240 GR PB BL WH PS RD UNUSED HEAT COOL T1 T2 T3 T1 T2 OR YL BK BK BK RD RD OR OR BL PK WH LS RD PU PU GR RD YL BR YL YL BK 0140L03028-A GV YL IGN OR FS YL YL IIC OR SEE NOTE 3 BK WH GR WH 12 COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY BL L3 CC2 L1 RD OR OR SEE NOTE 6 RD VMR BL L2 RD BK BK RD T3 BL BL T1 RD OR RD RD 1 3 L1 CC1 L2 BL OR OR WH DI YL RD C L3 BK FC2 PU BK FS T2 T3 C F PU FC1 6 OR RD RD BL BK BR C F 3 BK YL BK BK RD BR VM 2 EM BK BR PU BK BR RD 9 1 COMP1 8 5 COMP 2 11 7 4 T1 T2 T3 10 T1 T2 T3 24V 24 C PU Wiring Diagram — DCG 7½ – 12½ Tons (230V, Three-Phase Belt Drive) SS-DCG7 Wiring Diagram — DCG 7½ – 12½ Tons (230V, Three-Phase Belt Drive) T3 CC1 T3 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 T1 COMP2 CC2 T2 T2 T1 T3 T3 CC2 BC BC BC EM COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY FACTORY WIRING LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BL BR GR OR PK PU RD WH YL BLACK BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW ⚡ T1 L3 L2 CC1 T2 COMP1 T2 CC1 YL /PK YELLOW WITH PINK STRIP 4 VM 2 BL /PK BLUE WITH PINK STRIP VMR SEE NOTE 6 C TR L1 NOTE 3 1 F NOTE 3 24V HC IGN FS FS H C L2 NOTES BC 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). 4 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. LS 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV CC2 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. CCR2 6 9 PS ECON 2 8 7 CCR1 12 10 11 THERMOSTAT FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. SUPPLY VOLTAGE 208-240/3/60 L1 NOTE 2 S1 S2 TO THERMOSTAT O R ++ W2 W1 Y2 Y1 G C PLF 9 6 3 8 5 2 7 4 1 TB1 NOTE 5 THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: NORMAL OPERATION ------ OFF NO POWER OR INTERNAL CONTROL CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR C W2 STAT Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. EQUIPMENT STATUS ON IGNITION FAILURE W1 GR CHECK STATUS LIGHT OPEN ROLLOUT SWITCH WH G TB1 INSTALLER/SERVICEMAN 1 BLINK W1 ⚠ Warning 2 STAGE COOLING SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION 208-240/3/60 0140L02572-A SS-DCG7 www.daikincomfort.com 25 CM1 CM2 BK www.daikincomfort.com T1 BK GR L1 BK RD OR BK RD BK RD OR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE C L2 L1 L2 L3 C OR ⚠ Warning GR YL LPS 2 LPS1 YL 46O OR APPROPRIATE INPUT GR VOLTAGE GR BL BL BL YL 1 4 1 2 3 22 S1 YL S2 RD PK PU RD BL PK RD CCR 2 4 2 3 22 CCR1 BL C G GR GR PK W1 WH WH REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R BL BR RD BL RD BL W2 BR Y1 Y2 O ⚡ YL 7 1 2 3 PU BL WH WH 4 5 YL ECON RS ALS PU 6 PLF GR YL 9 RD BL BL BL BL RD RD BL PU RD SEE NOTE 2 8 PU BL RD GR PU YL SEE NOTE 5 YL BL BR WH RD YL High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. HPS 2 HPS1 GND BK BK POWER SUPPLY 460-575/3/60 SEE NOTE 4 PK YL YL RD UNUSED HEAT COOL BC T2 T3 T1 T2 RD BL L3 CC2 BK YL BK RD C RD RD OR OR PB BL WH PS RD RD L2 OR BK RD T3 BL BL CC1 L1 L2 BL OR PK SEE NOTE 6 RD L1 YL RD C OR OR OR BK WH LS DI T1 L3 RD 460 OR APPROPRIATE INPUT VOLTAGE 240 RD 1 BL FS T2 BL FC2 BK RD 3 BK RD PU PU GR FS BR YL YL BK 0140L03029-A GV YL IGN OR RD YL YL IIC OR SEE NOTE 3 BK WH GR WH 12 COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY RD T3 BK C F PU BK WH VMR 6 RD BL BK BR C FC1 3 BK YL BK BK RD F 2 EM PU BR BK BR VM 9 1 COMP1 8 5 COMP 2 11 7 4 T1 T2 T3 10 T1 T2 T3 RD TR 26 24V PU Wiring Diagram — DCG 7½ – 12½ Tons (460V/ 575V, Three-Phase Belt Drive) SS-DCG7 Wiring Diagram — DCG 7½ – 12½ Tons (460V/ 575V, Three-Phase Belt Drive) T3 CC1 T3 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 T1 COMP2 CC2 T2 T2 T1 T3 T3 CC2 BC BC BC EM 4 VM 2 COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BL BR GR OR PK PU RD WH YL BLACK BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW BL /PK BLUE WITH PINK STRIP 460V OR APPROPRIATE INPUTVOLTAGE SEE NOTE 6 LINE VOLTAGE LOW VOLTAGE YL /PK YELLOW WITH PINK STRIP VMR C FACTORY WIRING ⚡ T1 L3 L2 CC1 T2 COMP1 T2 CC1 C TR L1 NOTE 3 HC 1 F NOTE 3 24V IGN FS FS H C L2 NOTES BC 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). 4 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. LS 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV CC2 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. CCR2 6 9 PS ECON 2 8 7 CCR1 12 10 11 THERMOSTAT FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. SUPPLY VOLTAGE 460-575/3/60 L1 NOTE 2 O S2 TO THERMOSTAT ++ R W2 W1 Y2 Y1 G C PLF 6 3 8 5 2 7 4 1 TB1 NOTE 5 THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: EQUIPMENT STATUS ON NORMAL OPERATION OFF NO POWER OR INTERNAL CONTROL ------ 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER IGNITION FAILURE OPEN ROLLOUT SWITCH OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION 400V/50Hz SS-DCG7 W1 GR G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR C W2 STAT CHECK CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 1 BLINK WH G TB1 INSTALLER/SERVICEMAN STATUS LIGHT W1 www.daikincomfort.com Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. S1 9 ⚠ Warning 2 STAGE COOLING 0140L02570-A 27 28 BK BK CM2 T3 T2 T1 T3 T2 T1 COMP1 COMP 2 www.daikincomfort.com COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY YL BL GY BC 2 T1 T2 T3 L1 L2 L3 GR L1 C C L1 OR OR GR BK RD BK RD RD BK BK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE YL BL GY BL BC 1 T1 L2 L3 C L2 BL YL 3 1 3 1 NC NO 5 2 4 BR2 4 BR1 NC NO 5 2 LPS1 GR GR LPS 2 YL ⚠ Warning YL GR BK RD YL GR 208 240 BL BL BL YL YL 4 1 22 2 3 S1 PK BL RD S2 RD PK PU BL C BL BL G GR GR W1 WH WH WH PK REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R RD BR RD BL W2 BR Y1 Y2 PU O PU SEE NOTE 5 YL YL BL YL PU BL BL GR YL 8 ⚡ YL 3 1 2 BL WH WH 4 5 6 PU RS ALS PU 9 GR BL RD PLF 7 WH RD BL High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. PU WH HPS1 HPS 2 BL 1 RD CCR 2 4 YL BL BL YL RD PU PU GR RD YL BR YL YL BK 0140L03758-A SEE NOTE 2 GV YL GR IGN OR FS YL YL IIC OR SEE NOTE 3 BK WH GR WH 12 OR WH BL HIGH EM LOW BK T2 T3 T1 T2 OR OR TR GND 2 3 22 BL BR WH ECON UNUSED HEAT COOL BK RD OR BL BL L3 CC2 YL BK CCR1 WH RD YL RD BL PU L2 RD BK RD BK T3 BL BL CC1 BK BK RD BL RD RD DI YL RD RD POWER SUPPLY 208-240/3/60 SEE NOTE 4 PK YL YL RD L1 L1 RD PB BL BL WH RD RD FS L2 RD RD OR OR BL PK PS RD 6 T1 C OR OR OR SEE NOTE 6 RD VMR WH LS 3 L3 BL RD RD BL 2 T2 T3 BK FC2 OR 1 3 9 1 OR RD RD C F PU OR WH BK 8 5 BL BK BR C FC1 11 7 4 BK YL BK BK RD F VM 10 BK BR PU BK BR RD 24V CM1 C PU Wiring Diagram — DCG 7½-8½ Tons (230V, Two-Speed, Three-Phase Belt Drive) SS-DCG7 Wiring Diagram — DCG 7½-8½ Tons (230V, Two-Speed, Three-Phase Belt Drive) CC1 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 BC2 T1 COMP2 CC2 T2 T2 T1 T3 T3 LOW SPEED CC2 BC2 BC1 BC2 EM HIGH SPEED BC1 COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BLACK BL BR GR OR PK PU RD WH YL BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW YL /PK YELLOW WITH PINK STRIP BC1 4 VM FACTORY WIRING ⚡ T3 T3 2 BL /PK BLUE WITH PINK STRIP VMR SEE NOTE 6 C TR L1 HC 1 F NOTE 3 24V NOTE 3 IGN FS FS H C BR1 4 2 BC1 5 BC2 BR1 4 BR2 LS 5 IIC L2 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. 2 4 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV N OTES CC2 CCR2 6 9 PS ECON 8 7 2 CCR1 12 10 11 THERMOSTAT FIELD WIRING 2 STAGE COOLING S1 S2 TO THERMOSTAT O ++ R W2 W1 Y2 Y1 G C PLF 9 6 3 8 5 2 7 4 1 NOTE 2 TB1 NOTE 5 W1 WH W1 G GR G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR TB1 INSTALLER/SERVICEMAN C W2 STAT High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. T1 L3 L2 CC1 T2 COMP1 T2 CC1 ⚠ Warning SUPPLY VOLTAGE 208-240/3/60 L1 CHECK STATUS LIGHT EQUIPMENT STATUS ON NORMAL OPERATION ------ OFF NO POWER OR INTERNAL CONTROL CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER IGNITION FAILURE 1 BLINK OPEN ROLLOUT SWITCH OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION 208-240/3/60 0140L03759-A SS-DCG7 www.daikincomfort.com 29 BK BK CM2 T3 T2 T1 T3 T2 T1 COMP1 COMP 2 www.daikincomfort.com COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY YL BL GY BC 2 T1 T2 T3 C L1 L2 L3 GR L1 OR OR GR BK RD BK RD RD BK BK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE YL BL GY BL BC 1 T1 C L2 L3 L1 OR BL YL 3 1 3 1 NC NO 5 2 4 BR2 4 BR1 NC NO 5 2 GR GR LPS 2 LPS1 ⚠ Warning YL GR BK RD OR VOLTAGE BL BL BL YL YL 4 1 2 3 22 S1 PK BL RD S2 RD PK PU BL C BL BL G GR GR WH W1 WH WH PK REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R RD BR RD BL W2 BR Y1 Y2 PU O PU SEE NOTE 5 YL YL BL YL PU BL BL GR BL High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. YL PU WH GR HPS 2 HPS1 BL 1 RD CCR 2 4 YL BL BR WH YL 9 8 ⚡ YL 3 1 2 BL WH WH 4 5 6 PU RS ALS PU GR BL RD PLF 7 WH RD BL BL YL RD PU FS GV YL GR IGN OR RD YL BR YL YL BK 0140L03760-A SEE NOTE 2 PU GR YL YL IIC OR SEE NOTE 3 BK WH GR WH 12 OR WH BL HIGH EM LOW BK T2 T3 T1 C L2 L3 YL 46O OR APPROPRIATE INPUT GND 22 2 3 CCR1 WH ECON UNUSED HEAT COOL BK RD OR BL BL T3 T2 CC2 YL BK BK RD RD YL RD BL PU L2 RD BK BK RD BL BL RD POWER SUPPLY 460-575/3/60 SEE NOTE 4 BL RD RD DI CC1 BK C RD RD OR OR PB BL PK YL YL RD L1 L1 L2 BL BL WH PS RD RD FS YL RD C OR PK SEE NOTE 6 RD 9 T1 RD OR OR BK WH LS 3 L3 BL RD OR RD 1 BL 2 T2 T3 BK FC2 RD RD 3 BK 6 1 OR RD RD C F PU BK WH VMR 8 5 BL BK BR C FC1 11 7 4 BK YL BK BK RD F VM 10 BK BR PU BK BR RD 460 OR APPROPRIATE INPUT VOLTAGE 240 30 TR CM1 24V PU Wiring Diagram — DCG 7½-8½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt Drive) SS-DCG7 Wiring Diagram — DCG 7½-8½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt Drive) T3 CC1 T3 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 BC2 T1 COMP2 CC2 T2 T2 T1 T3 T3 LOW SPEED CC2 BC2 BC1 BC2 EM HIGH SPEED BC1 BC1 4 VM 2 COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BLACK BL BR GR OR PK PU RD WH YL BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW BL /PK BLUE WITH PINK STRIP 460V OR APPROPRIATE INPUTVOLTAGE SEE NOTE 6 LINE VOLTAGE LOW VOLTAGE YL /PK YELLOW WITH PINK STRIP VMR C FACTORY WIRING ⚡ T1 L3 L2 CC1 T2 COMP1 T2 CC1 C TR HC 1 F NOTE 3 24V L1 NOTE 3 IGN FS FS H C BR1 4 2 BC1 5 BC2 IIC 4 BR2 LS 2 4 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV NOTES 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). BR1 5 L2 CC2 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. CCR2 6 9 PS ECON 2 8 7 CCR1 12 10 11 THERMOSTAT FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. SUPPLY VOLTAGE 460-575/3/60 L1 NOTE 2 TO THERMOSTAT O ++ R W2 W1 Y2 Y1 G C PLF 6 3 8 5 2 7 4 1 TB1 NOTE 5 THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: EQUIPMENT STATUS ON NORMAL OPERATION ------ OFF NO POWER OR INTERNAL CONTROL CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER IGNITION FAILURE OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON W1 GR G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR C W2 STAT CHECK STATUS LIGHT OPEN ROLLOUT SWITCH WH G TB1 INSTALLER/SERVICEMAN 1 BLINK W1 SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. S1 S2 9 ⚠ Warning 2 STAGE COOLING 460-575/3/60 0140L03761-A SS-DCG7 www.daikincomfort.com 31 YL BK COMP 2 www.daikincomfort.com GY BL COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY YL BK BK BK HIGH EM LOW YL RD BK OR COMP1 YL PU BR BK T3 T2 T1 RD RD CB1 HIGH SPEED BK YL BK YL T2 T3 T2 T1 L3 CB2 LOW SPEED BK C BC 2 T1 T2 C L1 L2 L3 GR L1 L2 L3 OR OR GR BK RD BK RD RD YL BK OR BL RD OR BK BK RD OR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE YL BL T3 BL BC 1 T1 BK T3 L1 L2 C T2 T1 L3 T2 GY L1 L2 CC2 C L3 BK FC2 PU FC1 T3 BL BL C F C CC1 T1 T2 T3 RD OR BL BL RD RD BL BK BR BK RD F BL YL 3 1 3 1 OR NC NO 5 2 4 BR2 4 BR1 NC NO 5 2 GR GR LPS 2 LPS1 YL YL WH OR SEE NOTE 6 RD ⚠ Warning YL GR BK RD OR RD RD OR VM VMR HPS1 208 240 PB BL BL BL BL BL BL 1 YL 4 1 2 3 22 S1 YL RD S2 RD BL PK PK PU BL PK RD CCR 2 4 2 3 22 CCR1 POWER SUPPLY 208-240/3/60 SEE NOTE 4 YL BL PK WH C PK GR G GR GR BL BL BL BL W1 WH WH WH YL YL PS REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R RD BR RD RD WH LS W2 BR RD Y1 Y2 PU BL BR BL O PU YL GR YL ⚡ YL PLF RD BL RD RD BL PU RD YL 9 7 ECON 3 1 2 BL WH WH 4 5 6 PU RS ALS PU SEE NOTE 2 8 PU BL BL RD BL BL GR WH RD YL RD SEE NOTE 5 YL YL BL RD RD High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. GR HPS 2 PU WH TR GND BK BK RD RD OR OR BL 1 3 BK L2 T3 BR RD UNUSED HEAT COOL T1 L1 T3 DI T2 RD PU PU GR RD YL BR YL YL BK 0140L02575-A GV YL IGN OR FS YL YL IIC OR SEE NOTE 3 BK WH GR WH 3 FS T1 1 6 L2 9 2 L1 12 8 5 L3 11 7 4 L2 CM2 10 L1 32 24V CM1 C PU Wiring Diagram — DCG 10 – 12½ Tons (230V, Two-Speed, Three-Phase Belt Drive) SS-DCG7 Wiring Diagram — DCG 10 – 12½ Tons (230V, Two-Speed, Three-Phase Belt Drive) T3 CC1 T3 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 BC2 CB2 BC1 T1 COMP2 CC2 T2 T2 T1 T3 T3 LOW SPEED CB1 CB2 BC2 CB2 BC2 CC2 EM HIGH SPEED CB1 BC1 CB1 BC1 FACTORY WIRING LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BL BR GR OR PK PU RD WH YL BLACK BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW YL /PK YELLOW WITH PINK STRIP 4 VM COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY ⚡ T1 L3 L2 CC1 T2 COMP1 T2 CC1 2 BL /PK BLUE WITH PINK STRIP VMR SEE NOTE 6 C TR L1 HC 1 F NOTE 3 24V NOTE 3 IGN FS FS H C BR1 4 2 BC1 5 BC2 BR1 4 BR2 LS 5 IIC 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV NOTES 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). 2 4 L2 CC2 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. CCR2 6 9 PS ECON 8 7 2 CCR1 12 10 11 THERMOSTAT FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. SUPPLY VOLTAGE 208-240/3/60 L1 NOTE 2 S1 S2 TO THERMOSTAT O ++ R W2 W1 Y2 Y1 G C PLF 9 6 3 8 5 2 7 4 1 TB1 NOTE 5 THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: NORMAL OPERATION ------ OFF NO POWER OR INTERNAL CONTROL CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR C W2 STAT Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. EQUIPMENT STATUS ON IGNITION FAILURE W1 GR CHECK STATUS LIGHT OPEN ROLLOUT SWITCH WH G TB1 INSTALLER/SERVICEMAN 1 BLINK W1 ⚠ Warning 2 STAGE COOLING SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION 208-240/3/60 0140L02576-A SS-DCG7 www.daikincomfort.com 33 YL BK T3 T2 T1 COMP1 COMP 2 www.daikincomfort.com GY BL COLOR CODE BK --------------- BLACK BL --------------- BLUE BR --------------- BROWN OR --------------- ORANGE PU --------------- PURPLE RD --------------- RED WH -------------- WHITE YL --------------- YELLOW PK --------------- PINK GR---------------- GREEN GY---------------- GREY YL BK BK BK HIGH EM LOW RD RD CB1 HIGH SPEED BK YL BK YL CB2 LOW SPEED BK C BC 2 T1 T2 C L1 L2 L3 GR L1 L2 L3 OR OR GR BK RD BK RD RD YL BK OR BL RD BK BK RD RD Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE YL BL T3 BL BC 1 T1 BK T3 L1 L2 C T2 T1 L3 T2 GY L1 L2 CC2 C L3 BK FC2 PU FC1 T3 BL BL C F C CC1 T1 T2 T3 RD OR BL BL RD RD BL BK BR BK RD F OR BL YL 3 1 3 1 OR NC NO 5 2 4 BR2 4 GR 1 3 46O OR APPROPRIATE INPUT GR HPS 2 HPS1 GND BK BK PU WH C RD RD OR OR VMR VOLTAGE PB BL BL BL BL PK WH BL YL 1 YL 4 1 2 3 22 YL RD S2 RD BL PK PK PU BL PK S1 RD CCR 2 4 2 3 22 CCR1 POWER SUPPLY 460-575/3/60 SEE NOTE 4 BL BL SEE NOTE 6 RD RD C BL G PS W1 WH WH WH YL YL PK GR GR GR BL BL BL WH LS REPLACE JUMPER WITH SMOKE/FIRE DETECTOR WH R RD BR BK W2 BR RD Y1 Y2 PU BL BR BL O PU YL GR ⚡ YL YL PLF RD BL RD RD BL PU RD YL 9 7 ECON 3 1 2 BL WH WH 4 5 6 PU RS ALS PU SEE NOTE 2 8 PU BL BL RD BL BL GR WH RD YL RD SEE NOTE 5 YL YL BL RD RD High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. YL WH BL GR LPS 2 LPS1 BR1 NC NO 5 2 OR YL OR RD BK RD ⚠ Warning YL GR BK RD OR RD BK VM UNUSED HEAT COOL YL RD BK OR T3 T2 T1 YL PU BR BK BR RD L2 T3 L1 T2 DI T1 FS T3 6 T2 RD PU PU GR RD YL BR YL YL BK 0140L02567-A GV YL IGN OR FS YL YL IIC OR SEE NOTE 3 BK WH GR WH 12 T1 3 L3 2 L2 9 1 L1 8 5 L3 11 7 4 L2 CM2 10 L1 460 OR APPROPRIATE INPUT VOLTAGE 240 34 TR CM1 24V PU Wiring Diagram — DCG 10 – 12½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt) SS-DCG7 Wiring Diagram — DCG 10 – 12½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt) T3 CC1 T3 ALS BC BR CB CC CCR CM COMP EM F FC FS GND GV HPS IBR IIC IGN LPS LS PLF PS RS TB1 TR VM VMR C FC1 F CM1 C FC2 F CM2 CC2 BC2 CB2 BC1 CB1 T1 COMP2 CC2 T2 T2 T1 T3 T3 LOW SPEED CB2 BC2 CB2 BC2 CC2 EM HIGH SPEED CB1 BC1 CB1 BC1 4 VM 2 COMPONENT LEGEND AUXILLARY LIMIT SWITCH BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR FUSE FAN CAPACITOR FLAME SENSOR EQUIPMENT GROUND GAS VALVE HIGH PRESSURE SWITCH INDOOR BLOWER RELAY INTEGRATED IGNITION CONTROL IGNITOR LOW PRESSURE SWITCH LIMIT SWITCH FEMALE PLUG/CONNECTOR PRESSURE SWITCH ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE WIRE CODE BK BL BR GR OR PK PU RD WH YL BLACK BLUE BROWN GREEN ORANGE PINK PURPLE RED WHITE YELLOW BL /PK BLUE WITH PINK STRIP 460V OR APPROPRIATE INPUTVOLTAGE SEE NOTE 6 LINE VOLTAGE LOW VOLTAGE YL /PK YELLOW WITH PINK STRIP VMR C FACTORY WIRING ⚡ T1 L3 L2 CC1 T2 COMP1 T2 CC1 C TR L1 NOTE 3 1 F NOTE 3 24V HC IGN FS FS H C BR1 4 2 BC1 5 BC2 BR1 4 BR2 LS 5 IIC 5 IIC BR2 VMR D1 CCR1 4 CCR2 ALS 3 4 HPS1 LPS1 2 CC1 2 RS LPS2 HPS2 GV NOTES 1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY). 2 4 L2 CC2 2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 3. L1 AND L2 ON IIC CONTROL IS 24V INPUT. 4. USE COPPER CONDUCTORS ONLY. ++ USE NEC CLASS 2 WIRE. 5. FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE 6. MOVE WIRE(S) TO APPROPRIATE INPUT VOLTAGE TERMINAL ON TRANSFORMER. CCR2 6 9 PS ECON 8 7 2 CCR1 12 10 11 THERMOSTAT FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. SUPPLY VOLTAGE 460-575/3/60 L1 NOTE 2 TO THERMOSTAT O ++ R W2 W1 Y2 Y1 G C PLF 6 3 8 5 2 7 4 1 TB1 NOTE 5 THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS: EQUIPMENT STATUS ON NORMAL OPERATION ------ OFF NO POWER OR INTERNAL CONTROL CHECK INPUT POWER CHECK FUSE ON CONTROL REPLACE CONTROL 4 BLINKS OPEN LIMIT SWITCH 5 BLINKS FALSE FLAME SENSED GAS FLOW GAS PRESSURE GAS VALVE FLAME SENSOR FLAME ROLLOUT BAD SWITCH AUX. LIMIT OPEN CHECK PRESSURE SWITCH CHECK PRESSURE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 6 BLINKS COMPRESSOR OUTPUT DELAY 3 MIN. COMP. ANTI-CYCLE TIMER IGNITION FAILURE OPEN AUX. LIMIT SWITCH 2 BLINKS 3 BLINKS PRESSURE SWITCH OPEN PRESSURE SWITCH CLOSED WITHOUT INDUCER ON W1 GR G R RD R Y1 YL Y1 Y2 PK Y2 C BL W2 BR C W2 STAT CHECK STATUS LIGHT OPEN ROLLOUT SWITCH WH G TB1 INSTALLER/SERVICEMAN 1 BLINK W1 SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. S1 S2 9 ⚠ Warning 2 STAGE COOLING 460-575/3/60 0140L02566-A SS-DCG7 www.daikincomfort.com 35 WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS For complete information and installation instructions for models with DDC controls, see manual DK-DDC-TGD-XXX 36 www.daikincomfort.com SS-DCG7 SS-DCG7 www.daikincomfort.com 3A IGNITOR F1 F1 WH PK PK WH BR WH IAH BL PU RD RD YL YL WH BR PK PK BL BL BL BL GY BK FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 HEAT PK BR RD BK RD BL WH PK BL GY 2 PU RD RD BL RD GR BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 GY RD GR GR RD RS GR GR YL YL RD LS PU RD RD RD GR BL BL 1 GND BL (OAH) (OAT) (ECON FB) (SUPPLY AIR TMP) BL BL PS BL BK WH BL WH BL BL WH BR BK BR WH 1 WH 2 3 4 5 6 BK BR BR BR BR BR BR WH WH BR BK BK BK WH - BL BL BL BL BL BK BL BR WH + ALRM - + EXF + HGRH - WH BAC NET WH BR BR HTR PLF1 11 22 RD WH BR BR BR BR BR BR WH WH WH PU BL BL BL BL BL BL BL BL BL BL BL BL BK BK BK BK BL GR 5 RD UNUSED IIC OR RD 1 6 6 VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2 TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2 TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE FROM IIC-UNUSED AND CONNECT TO CC1-L1. TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE 208V TAP. IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. 4 5 DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES. VMR 3 2 6 RD OR BK BK RD OR PU VM L1 BK T2 BK T1 BK PB ALS BK BK RD RD RD RD RD RD RD L3 L2 L1 HIGH VOLTAGE LOW VOLTAGE FIELD WIRING WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE ⚡ BR BR BK PU BK BR PU BK BR BK L3 COMP1 T1 CF2 CF1 BM COMP2 T3 T1 T3 COMPONENT LEGEND FC2 FC1 PU T2 T2 BK PU RD OR BL BK RD YL BL BL BK RD YL BL GND L1 L2 BL BL LINE VOLTAGE 0140L05764-A AUXILIARY LIMIT SWITCH ALARM BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER CB COMPRESSOR CONTACTOR CC CF CONDENSER FAN CFS CLOGGED FILTER SWITCH COMP COMPRESSOR CO2 CARBON DIOXIDE SENSOR DAT DISCHARGE AIR TEMPERATURE SENSOR DDC DIRECT DIGITAL CONTROL ECON ECONOMIZER EXF EXHAUST FAN FAN CAPACITOR FC FLAME SENSE FS EQUIPMENT GROUND GND GV GAS VALVE HGRH HOT GAS REHEAT HPS HIGH PRESSURE SWITCH IAH INDOOR AIR HUMIDITY SENSOR IIC INTIGRATED IGNITION CONTROL LIMIT SWITCH LS LOAD SHEDDING LDS LPS LOW PRESSURE SWITCH OAT OUTDOOR AIR TEMPERATURE SENSOR OAH OUTDOOR AIR HUMIDITY SENSOR PB POWER DISTRIBUTION BLOCK PLF FEMALE PLUG/CONNECTOR PLM MALE PLUG/CONNECTOR PS PRESSURE SWITCH RS ROLL-OUT SWITCH RSS REMOTE START/STOP SMOKE DETECTOR SMK SPC TEMP SPACE TEMPERATURE SENSOR TB TERMINAL BLOCK (24V SIGNAL) TR TRANSFORMER VENT MOTOR VM VENT MOTOR RELAY VMR FACTORY WIRING ALRM BC HIGH VOLTAGE BCS LOW VOLTAGE BM OPTIONAL LOW VOLTAGE BK WH RD L2 RD T3 T1 T2 T3 T1 T2 T3 CC1 OR BC CC2 BL OPTIONAL ACCESSORIES OR FIELD SUPPLIED COMPONENTS BK WH RD L3 L1 L2 L3 L1 L2 L3 OR BK BK OR OR OR RD RD RD BK BK YL BK OR RD BK BK RD OR BK BK BK RD RD OR BK 3 OR RD BK BK RD RD OR RD OR RD OR OR OR RD 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. NOTES: BR WH BL 4 BK YL PU 24V CNTL VOLTAGE HTR PLM1 ECON PLF 6 5 4 3 2 1 RD YL PU PK LINE VOLTAGE POWER & CONTROL WIRING DIAGRAM DCG(090-150) ***(3)B DDC BK BR BL AO1 AO2 AO3 AO4 GND GND R+ 1 SH 2 T- 3 PK WH BR YL PU PU BK YL RD TR1 OR High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. BL BL 1ST STG COM 2ND STG GV 2 24VAC (BAC NET) COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (ECON DMPR) (MOD HGRH) (EXF) (ALRM) (EMER) (FAN PROV) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) (24V IN) (ECON PWR) (HEAT 1) (HEAT 2) (CO2) (SPC TMP) 5 AI6 (SPC SLIDE ADJ) 4 AI7 (SPC HUM) 3 AI8 2 AGND (ISOL GND) 1 AGND 8 AI3 7 AI4 6 AI5 (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL RD (BLOWER STAGE 1) RD GR GR BK BR 9 AI2 8 7 6 5 4 3 2 1 PU 10 AI1 PK BK YL PU BK BR VMR GY PK SPCTEMP TEMP STPT OFFSET GND PU YL BK BK PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU PU YL XS DA PU BK PK PU YL ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BK BR RD BK RD PK T T TTT C PS 1 2 345 S BL/PK 24VAC TB2 (CLASS2) GR GR BR VOUT (DC) GND 24 VAC 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT IIC 3 -t° DAT GR BR BR -t° OAT HPS2 HPS1 SMK/EMG OAH VOUT (DC) GND 24 VAC CFS LDS WH RD GY GY TB1 (CLASS2) RSS BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. PK RD RD PK Wiring Diagram with DDC — DCG 090*/ 102*/ 120*/ 150* 208-230 / 3 / 60 1SP 37 38 www.daikincomfort.com 3A IGNITOR F1 F1 WH PK PK WH HPS1 BR PK PK BL BL BL BL FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 GY BK BL PU RD RD YL YL WH PK GR BR RD BK RD WH PK BL BL GY 2 PU RD RD BL RD GY GY VMR RD GR GR BK BR PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU YL BK BK PK PU BK PK PU YL RD RS YL YL RD LS PU RD BL RD BL RD GR GR SPCTEMP TEMP STPT OFFSET GND PU PU YL XS DA ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BK BR RD BK RD T T TTT C PS 1 2 345 S BL/PK 24VAC TB2 (CLASS2) VOUT (DC) GND 24 VAC IAH OAH VOUT (DC) GND 24 VAC WH HPS2 BR -t° OAT GR BR HEAT GY SMK/EMG 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT IIC 3 -t° DAT GR BR BR CFS LDS WH RD GY TB1 (CLASS2) RSS BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. PK RD RD PK 8 7 6 5 4 3 2 1 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 9 AI2 1 GND BL BL PS BL BK WH BL WH BL WH BR BK BR WH 1 WH 2 3 4 5 6 PK BR BR BR BR BR BR BK WH BR 11 22 WH BR WH WH BR BK BK WH - BL BL BK BL BR WH + ALRM - + EXF + HGRH - WH BAC NET RD BR BR BR BL BK BK BK BK BL GR 5 BL BL BL BL BL BL BL PU BL BL BL BL RD BK BK IIC UNUSED OR RD OR 1 OR BK OR RD RD OR OR OR BK OR RD BK VMR BK RD OR 5 4 3 2 RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY SIDE OF TR1. IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES. 3 460V OR 575V 230V COM RD VM L1 BK T2 BK T1 HIGH VOLTAGE LOW VOLTAGE FIELD WIRING ⚡ WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE PB BK BK RD PU BR PU BR BK BK BR PU BK BR BK L3 COMP1 T1 CF2 CF1 BM COMP2 T3 T1 T3 COMPONENT LEGEND FC2 FC1 T2 T2 PU BK RD OR BL BK RD YL BL BL BK RD YL BL GND L1 L2 BL BL LINE VOLTAGE 0140L05758-A SPACE TEMPERATURE SENSOR TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY AUXILIARY LIMIT SWITCH ALARM BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR CONDENSER FAN CLOGGED FILTER SWITCH COMPRESSOR CARBON DIOXIDE SENSOR DISCHARGE AIR TEMPERATURE SENSOR DIRECT DIGITAL CONTROL ECONOMIZER EXHAUST FAN FAN CAPACITOR FLAME SENSE EQUIPMENT GROUND GAS VALVE HOT GAS REHEAT HIGH PRESSURE SWITCH INDOOR AIR HUMIDITY SENSOR INTIGRATED IGNITION CONTROL LIMIT SWITCH LOAD SHEDDING LOW PRESSURE SWITCH OUTDOOR AIR TEMPERATURE SENSOR OUTDOOR AIR HUMIDITY SENSOR POWER DISTRIBUTION BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR PRESSURE SWITCH ROLL-OUT SWITCH REMOTE START/STOP SMOKE DETECTOR RD RD RD RD RD RD L3 L2 L1 ALS ALRM BC BCS BM CB CC CF CFS COMP CO2 DAT DDC ECON EXF FC FS GND GV HGRH HPS IAH IIC LS LDS LPS OAT OAH PB PLF PLM PS RS RSS SMK SPC TEMP TB TR VM VMR BK FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE BK WH L2 RD OPTIONAL ACCESSORIES OR FIELD SUPPLIED COMPONENTS BK WH RD L3 OR T3 T1 RD L1 T3 BK BK BC CC2 T2 L3 T1 T2 T3 CC1 L2 OR L1 L2 L3 BL OR RD OR PU RD RD BK BK OR BK BK OR OR YL BK OR RD BK TR3 BK RD OR BK BK BK RD RD OR BK BK OR RD BK 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. WH WH WH BR BR NOTES: BR WH BL 4 BK YL PU 24V CNTL VOLTAGE HTR PLM1 ECON PLF 6 5 4 3 2 1 HTR PLF1 RD OR POWER & CONTROL WIRING DIAGRAM DCG(090-150) ***(4,7)B DDC BK BR BL AO1 AO2 AO3 AO4 GND GND R+ 1 SH 2 T- 3 YL YL PU PU BK YL PU PK LINE VOLTAGE High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. BL BL BL (ISOL GND) (CO2) (SPC TMP) (SPC SLIDE ADJ) (SPC HUM) (OAH) (OAT) (ECON FB) (SUPPLY AIR TMP) 1ST STG COM 2ND STG GV 2 24VAC AGND AGND AI6 AI7 AI8 (BAC NET) COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (ECON DMPR) (MOD HGRH) (EXF) (ALRM) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) BL 5 4 3 2 1 8 AI3 7 AI4 6 AI5 (24V IN) (ECON PWR) (EMER) (FAN PROV) RD GR GR BK BR PU 10 AI1 PK BK YL PU (HEAT 1) (HEAT 2) (BLOWER STAGE 1) (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL TR1 OR Wiring Diagram with DDC — DCG 090*/ 102*/ 120*/ 150* 460, 575 / 3 / 60 1SP SS-DCG7 SS-DCG7 www.daikincomfort.com F1 3A IGNITOR F1 IIC WH PK PK WH BR PK PK BL BL BL BL FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 GY BK BL PU RD RD YL YL WH PK GR BR WH PK BL BL GY 2 PU RD RD BL RD GY RD GR GR VMR GY 8 7 6 5 4 3 2 1 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 RD RS YL YL RD LS 1 GND BL BL PS BL BL BK WH BL BL WH BL BK BR BL (ISOL GND) BL (CO2) (SPC TMP) (SPC SLIDE ADJ) (SPC HUM) (OAH) (OAT) (ECON FB) (SUPPLY AIR TMP) 1ST STG COM 2ND STG GV 2 24VAC BL AGND AGND AI6 AI7 AI8 RD GR 5 4 3 2 1 8 AI3 7 AI4 6 AI5 (BAC NET) WH PK WH BK BR BR BR BR BR BR HTR PLF1 BR WH BK BK BL BL BL BL BL BR BR BK BR BK RD BL RD PU RD VM OR BK BK BK BL BL ALS ALRM BC BCS BM CB CC CF CFS COMP CO2 DAT DDC ECON EXF FC FS GND GV HGRH HPS IAH IIC LS LDS LPS OAT OAH PB PLF PLM PS RS RSS SMK SPC TEMP TB TR VM VMR BL BL BL BL BL UNUSED IIC OR 1 OR 6 VMR 3 BK WH SPACE TEMPERATURE SENSOR TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY AUXILIARY LIMIT SWITCH ALARM BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR CONDENSER FAN CLOGGED FILTER SWITCH COMPRESSOR CARBON DIOXIDE SENSOR DISCHARGE AIR TEMPERATURE SENSOR DIRECT DIGITAL CONTROL ECONOMIZER EXHAUST FAN FAN CAPACITOR FLAME SENSE EQUIPMENT GROUND GAS VALVE HOT GAS REHEAT HIGH PRESSURE SWITCH INDOOR AIR HUMIDITY SENSOR INTIGRATED IGNITION CONTROL LIMIT SWITCH LOAD SHEDDING LOW PRESSURE SWITCH OUTDOOR AIR TEMPERATURE SENSOR OUTDOOR AIR HUMIDITY SENSOR POWER DISTRIBUTION BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR PRESSURE SWITCH ROLL-OUT SWITCH REMOTE START/STOP SMOKE DETECTOR COMPONENT LEGEND BK WH BK BK RD OR BR OPTIONAL ACCESSORIES OR FIELD SUPPLIED COMPONENTS HIGH VOLTAGE LOW VOLTAGE FIELD WIRING BC2 T2 ⚡ L1 L2 L3 PB BK RD BK BL BL RD RD RD RD RD RD L3 L2 L1 FC2 FC1 BR BK PU BK BR PU YL BL GY BK RD OR BL BK RD YL BL BL BK RD YL BL BK BR PU BK BR PU T2 T2 T1 L3 COMP1 BM CF2 CF1 BK BK BK YL YL YL COMP2 T3 T1 T3 GND L1 L2 DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES. 6 5 0140L05773-A VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2 TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2 TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE FROM IIC-UNUSED AND CONNECT TO CC1-L1. TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE 208V TAP. 4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. 3 2 BL BL LINE VOLTAGE 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. NOTES: T1 T2 T3 T1 L2 L1 T3 L3 FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE BK WH RD RD High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. BL BR WH + ALRM - - BC1 T1 L1 RD BK BK T3 T2 CC2 T1 T2 T3 CC1 L2 L3 L1 L2 L3 BL OR RD OR OR BK BK OR OR RD BK RD OR PU BK RD OR OR YL BK RD RD OR RD OR BK BK BK RD RD OR BK 6 BK OR RD BK OR RD BK OR RD OR BK BK BR BR BR BR WH BK BL GR RD RD BR WH BL 4 BR RD 5 + HGRH - BR WH WH BR HTR PLM1 YL PU 24V CNTL VOLTAGE LINE VOLTAGE + EXF WH BAC NET WH 11 22 RD TR1 OR ECON PLF 6 5 4 3 2 1 RD PK YL PU PK WH BR YL PU PU BR BK YL 1 WH 2 3 4 5 6 BR BK BR AO1 AO2 AO3 AO4 GND GND R+ 1 SH 2 T- 3 COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (ECON DMPR) (MOD HGRH) (EXF) (ALRM) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) (EMER) (FAN PROV) (24V IN) (ECON PWR) (BLOWER STAGE 1) (BLOWER STAGE 2) (HEAT 1) (HEAT 2) (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL POWER & CONTROL WIRING DIAGRAM DCG(090-102) ***(3)V DDC PU RD BL RD BL RD GR GR GR BK BR 9 AI2 PK BK YL PU PU 10 AI1 YL YL PU BK BR SPCTEMP TEMP STPT OFFSET GND PU YL BK PK PU PU YL PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU PU YL PU BK PK ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES XS DA PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BL/PK BK BR RD BK RD T T TTT C PS 1 2 345 S RD BK RD 24VAC TB2 (CLASS2) VOUT DC GND 24 VAC IAH OAH VOUT (DC) GND 24 VAC GR BR HEAT WH BR -t° OAT HPS2 HPS1 SMK/EMG 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT 3 -t° DAT GR BR BR LDS CFS WH RD GY GY TB1 (CLASS2) RSS BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. PK RD RD PK Wiring Diagram with DDC — DCG 090* / 102* 208-230 / 3 / 60 2SP 39 40 www.daikincomfort.com 3A WH PK PK WH GY WH BL PU RD RD YL YL WH BR PK PK BL BL BL BL GY BK FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 HEAT PK GR GR BR BR BL WH PK BL GY 2 PU RD RD BL RD 8 7 6 5 4 3 2 1 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 GY RD GR GR RD RS YL YL RD LS PU RD BL RD BL RD GR GR 1 GND BL BL BL BL BK WH BL BL WH BL BK BR BL (ISOL GND) BL (CO2) (SPC TMP) (SPC SLIDE ADJ) (SPC HUM) (OAH) (OAT) (ECON FB) WH PK WH BR BR BR BR BR BR BK WH BR 1 WH 2 3 4 5 6 BR BK BR AO1 AO2 AO3 AO4 GND GND YL YL PU PU BR BK HTR PLF1 11 22 RD BR BR WH WH BK BK WH - BL BL BK BL BR WH + ALRM - + EXF + HGRH - WH BAC NET BR BL BL BL BL BL BL WH BK BK BR BK BL IIC UNUSED BL BK BR 1 VMR BK OR OR OR BK COMPONENT LEGEND BR WH WH BR BR BL PU BL BK 3 RD RD OR BK RD BK WH BR BK OR BK BK BK RD OR BR BK BK RD RD L1 L2 L3 L1 L2 L3 OPTIONAL ACCESSORIES OR FIELD SUPPLIED COMPONENTS HIGH VOLTAGE LOW VOLTAGE FIELD WIRING High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡ FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE VM RD OR WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE BK WH RD 460V OR 575V 230V COM OR T1 T2 T3 T1 PB RD BK BK BL BL RD RD RD L3 L2 L1 YL BL GY PU FC2 BR BK PU BK BR BK BR PU BK BR PU YL BL GY BK RD BK OR RD T2 T2 OR FC1 BL BK RD YL BL BL BK RD YL BL T1 L3 COMP1 BM CF2 CF1 BL OR WH BK BK BK COMP2 T3 T1 T3 GND L1 L2 BL BL LINE VOLTAGE DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES. 5 0140L05771-A RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY SIDE OF TR1. 4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. 3 2 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. NOTES: BC2 T3 T2 BC1 T1 RD L1 T3 BK BK CC2 T2 L3 T1 T2 T3 CC1 L2 OR L1 L2 L3 BL OR RD OR PU RD RD BK BK OR BK OR OR YL BK OR RD BK TR3 BK RD OR BK BK BK RD RD OR BK BR BK OR RD BK OR RD OR BK OR OR RD AUXILIARY LIMIT SWITCH ALS ALRM ALARM BC BLOWER CONTACTOR BCS BLOWER CURRENT SWITCH BM BLOWER MOTOR CIRCUIT BREAKER CB COMPRESSOR CONTACTOR CC CF CONDENSER FAN CFS CLOGGED FILTER SWITCH COMP COMPRESSOR CO2 CARBON DIOXIDE SENSOR DAT DISCHARGE AIR TEMPERATURE SENSOR DDC DIRECT DIGITAL CONTROL ECON ECONOMIZER EXF EXHAUST FAN FAN CAPACITOR FC FLAME SENSE FS EQUIPMENT GROUND GND GV GAS VALVE HGRH HOT GAS REHEAT HPS HIGH PRESSURE SWITCH IAH INDOOR AIR HUMIDITY SENSOR IIC INTIGRATED IGNITION CONTROL LIMIT SWITCH LS LOAD SHEDDING LDS LPS LOW PRESSURE SWITCH OAT OUTDOOR AIR TEMPERATURE SENSOR OAH OUTDOOR AIR HUMIDITY SENSOR PB POWER DISTRIBUTION BLOCK PLF FEMALE PLUG/CONNECTOR PLM MALE PLUG/CONNECTOR PS PRESSURE SWITCH RS ROLL-OUT SWITCH RSS REMOTE START/STOP SMOKE DETECTOR SMK SPC TEMP SPACE TEMPERATURE SENSOR TB TERMINAL BLOCK (24V SIGNAL) TR TRANSFORMER VENT MOTOR VM VENT MOTOR RELAY VMR BR BR WH BL 4 BR BK 5 RD BK GR BL OR YL PU 24V CNTL VOLTAGE LINE VOLTAGE HTR PLM1 TR1 OR ECON PLF 6 5 4 3 2 1 RD YL PU PK POWER & CONTROL WIRING DIAGRAM DCG(090-102) ***(4,7)V DDC PS (ECON DMPR) (MOD HGRH) (EXF) (ALRM) R+ 1 SH 2 T- 3 COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (BAC NET) (SUPPLY AIR TMP) 1ST STG COM 2ND STG GV 2 24VAC AGND AGND AI6 AI7 AI8 (24V IN) (ECON PWR) (EMER) (FAN PROV) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) BL 5 4 3 2 1 8 AI3 7 AI4 6 AI5 (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL (BLOWER STAGE 1) (BLOWER STAGE 2) (HEAT 1) (HEAT 2) RD GR GR BK BR 9 AI2 PK BK YL PU PU 10 AI1 YL PU BK BR VMR GY PK PU SPCTEMP TEMP STPT OFFSET GND PU YL BK BK PU BK PK PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU PU YL XS DA YL ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BL/PK BK BR RD BK RD T T TTT C PS 1 2 345 S RD BK RD 24VAC TB2 (CLASS2) VOUT (DC) GND 24 VAC IAH OAH VOUT (DC) GND 24 VAC BR -t° OAT HPS2 HPS1 SMK/EMG 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT IIC 3 -t° DAT GR BR BR LDS CFS WH RD GY TB1 (CLASS2) RSS BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. IGNITOR F1 F1 RD RD PK Wiring Diagram with DDC — DCG 090*/ 102* 460, 575 / 3 / 60 2SP SS-DCG7 SS-DCG7 www.daikincomfort.com 3A IIC IGNITOR F1 F1 WH PK PK WH GY WH BL PU RD RD YL YL WH BR PK PK BL BL BL BL GY BK FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 HEAT PK GR GR BR BR BK RD WH PK BL BL GY 2 PU RD RD BL RD GY RD GR GR VMR GY BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 RD RS YL YL RD LS 1 GND BL BL BL PS BL BL BK WH BL BL WH BL BK BR BL (ISOL GND) BL (CO2) (SPC TMP) (SPC SLIDE ADJ) (SPC HUM) (OAH) (OAT) (ECON FB) (SUPPLY AIR TMP) 1ST STG COM 2ND STG GV 2 24VAC AGND AGND AI6 AI7 AI8 RD 5 4 3 2 1 8 AI3 7 AI4 6 AI5 (BAC NET) WH PK WH BK BR BR BR BR BR BR HTR PLF1 11 22 RD BR BK BL BL BL OR RD 1 RD RD VM OR BK 6 RD OR BK BK BK RD OR PU BK RD OR BK OR OR RD BK OR OR RD YL BK BK RD OR RD OR RD BK BK OR BK BL BL BK ALS ALRM BC BCS BM CB CC CF CFS COMP CO2 DAT DDC ECON EXF FC FS GND GV HGRH HPS IAH IIC LS LDS LPS OAT OAH PB PLF PLM PS RS RSS SMK SPC TEMP TB TR VM VMR BL BL UNUSED IIC OR 6 VMR 3 BK WH SPACE TEMPERATURE SENSOR TERMINAL BLOCK (24V SIGNAL) TRANSFORMER VENT MOTOR VENT MOTOR RELAY AUXILIARY LIMIT SWITCH ALARM BLOWER CONTACTOR BLOWER CURRENT SWITCH BLOWER MOTOR CIRCUIT BREAKER COMPRESSOR CONTACTOR CONDENSER FAN CLOGGED FILTER SWITCH COMPRESSOR CARBON DIOXIDE SENSOR DISCHARGE AIR TEMPERATURE SENSOR DIRECT DIGITAL CONTROL ECONOMIZER EXHAUST FAN FAN CAPACITOR FLAME SENSE EQUIPMENT GROUND GAS VALVE HOT GAS REHEAT HIGH PRESSURE SWITCH INDOOR AIR HUMIDITY SENSOR INTIGRATED IGNITION CONTROL LIMIT SWITCH LOAD SHEDDING LOW PRESSURE SWITCH OUTDOOR AIR TEMPERATURE SENSOR OUTDOOR AIR HUMIDITY SENSOR POWER DISTRIBUTION BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR PRESSURE SWITCH ROLL-OUT SWITCH REMOTE START/STOP SMOKE DETECTOR COMPONENT LEGEND BL WH BK BK RD OR BR OPTIONAL ACCESSORIES OR FIELD SUPPLIED COMPONENTS HIGH VOLTAGE LOW VOLTAGE FIELD WIRING T1 ⚡ L1 L2 L3 L1 PB BK RD BK BL BL RD RD RD RD RD RD L3 L2 L1 L3 L1 FC2 FC1 YL BR BK PU BK BR PU BK BR PU BK BR PU T1 YL T2 BL T3 GY BK RD T1 OR T3 T2 T2 T2 CB2 (LO SPD) L1 L2 BL L2 GY BK BK RD YL BL BL BK BL CB1 (HI SPD) OR L3 RD YL BL RD T1 L3 COMP1 BM CF2 CF1 BK BK BK YL YL YL COMP2 T3 T1 T3 GND L1 L2 2 IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES. DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. 6 5 0140L05774-A VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2 TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2 TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE FROM IIC-UNUSED AND CONNECT TO CC1-L1. TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE 208V TAP. 4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. 3 BL BL LINE VOLTAGE 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. NOTES: T1 T2 T3 T1 T3 T2 L2 BC2 T2 T3 T1 T2 T3 CC1 BC1 CC2 BL OR L3 L1 L2 L3 L1 L2 L3 FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL LOW VOLTAGE WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE BK WH RD RD High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. BL BR WH + ALRM - BK WH WH BK BR RD OR RD BK BK BK RD RD OR BK BK BR WH BK BR BR PU OR + EXF - BR WH BK BK BL BL BL BL BL RD RD BR BR BR BR WH BK BL GR 5 RD + HGRH - WH BAC NET BR WH BL 4 BR YL PU 24V CNTL VOLTAGE LINE VOLTAGE HTR PLM1 TR1 OR ECON PLF 6 5 4 3 2 1 RD YL PU PK WH BR YL PU PU BR BK YL 1 WH 2 3 4 5 6 BR BK BR AO1 AO2 AO3 AO4 GND GND R+ 1 SH 2 T- 3 COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (ECON DMPR) (MOD HGRH) (EXF) (ALRM) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) (EMER) (FAN PROV) (24V IN) (ECON PWR) (BLOWER STAGE 1) (BLOWER STAGE 2) (HEAT 1) (HEAT 2) (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL POWER & CONTROL WIRING DIAGRAM DCG(120-150) ***(3)V DDC PU RD BL RD BL RD GR GR GR GR BK BR 9 AI2 8 7 6 5 4 3 2 1 PU 10 AI1 PK BK YL PU BK BR SPCTEMP TEMP STPT OFFSET GND PU YL BK PK PU BK PK PU YL PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU PU YL XS DA ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BK BR RD BK RD T T TTT C PS 1 2 345 S BL/PK 24VAC TB2 (CLASS2) VOUT DC GND 24 VAC IAH OAH VOUT (DC) GND 24 VAC BR -t° OAT HPS2 HPS1 SMK/EMG 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT 3 -t° DAT GR BR BR CFS LDS RSS WH RD GY TB1 (CLASS2) PK BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. PK RD RD PK Wiring Diagram with DDC — DCG 120* / 150* 208-230 / 3 / 60 2SP 41 42 www.daikincomfort.com 3A WH PK PK WH GY WH BL PU RD RD YL YL WH BR PK PK BL BL BL BL GY BK FLAME SENSE 24 VAC L1 PWR L1 L2 24 VAC L2 COM L2 L2 VENT MTR D1 HEAT PK GR GR BR BR BK RD BL WH PK BL GY 2 PU RD RD BL RD GY RD GR GR VMR GY BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 RD RS YL YL RD LS PU RD BL RD BL RD GR GR 1 GND BL BL BL BL BK WH BL WH BL BK BR BL (ISOL GND) BL (CO2) (SPC TMP) (SPC SLIDE ADJ) (SPC HUM) (OAH) (OAT) (ECON FB) WH WH 1 WH 2 3 4 5 6 BR BK BR AO1 AO2 AO3 AO4 GND GND PK BR BR BR BR BR BR BK WH BR YL PU PU BR BK YL HTR PLF1 11 22 RD BR WH WH BK BK WH BR BL BL BK BL BR WH + ALRM - + EXF - + HGRH - WH BAC NET BR BL 4 BK BK BL BL BL BL BL WH WH BR BK BL IIC UNUSED BL BK BR BK 1 VMR BK OR OR OR COMPONENT LEGEND BR BR WH BL PU BL BK 3 RD RD OR BK RD BK WH BR BK OR OR OR RD RD BK BK RD BK RD OR BR BK BK BC2 T3 T2 L1 L2 L3 T1 T2 T3 T1 L2 L1 L3 PB RD BK BK BL BL RD RD RD L3 L2 L1 YL BL YL T1 L3 FC2 FC1 L1 PU BR BK PU BK BR T1 T2 T3 CB2 (LO SPD) L1 BL L2 GY BK T3 T2 L2 OR L3 RD BL CB1 (HI SPD) BK RD YL BL BL BK RD BK BR PU BK BR PU YL BL GY BK RD OR T2 T2 L3 COMP1 T1 BM CF2 CF1 BK BK BK YL YL YL COMP2 T3 T1 T3 GND L1 L2 BL BL LINE VOLTAGE High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡ 5 0140L05772-A RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY SIDE OF TR1. 4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT. FACTORY WIRING NOTES: HIGH VOLTAGE LOW VOLTAGE 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OPTIONAL LOW VOLTAGE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY. FIELD WIRING USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. HIGH VOLTAGE LOW VOLTAGE 2 IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS OPTIONAL ACCESSORIES TB1-XS TO TB1-ES. OR FIELD SUPPLIED COMPONENTS 3 DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM. VM WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW WITH PINK STRIPE BL/PK BLUE WITH PINK STRIPE BK WH RD 460V OR 575V 230V COM BC1 T1 L1 RD BK BK T3 T2 L3 CC2 T1 T2 T3 CC1 L2 OR L1 L2 L3 BL OR RD OR PU RD RD BK BK OR BK OR OR YL BK OR RD BK TR3 BK RD OR BK BK BK RD RD OR BK BR BK OR RD BK OR RD OR BK OR OR RD AUXILIARY LIMIT SWITCH ALS ALRM ALARM BC BLOWER CONTACTOR BCS BLOWER CURRENT SWITCH BM BLOWER MOTOR CIRCUIT BREAKER CB COMPRESSOR CONTACTOR CC CF CONDENSER FAN CFS CLOGGED FILTER SWITCH COMP COMPRESSOR CO2 CARBON DIOXIDE SENSOR DAT DISCHARGE AIR TEMPERATURE SENSOR DDC DIRECT DIGITAL CONTROL ECON ECONOMIZER EXF EXHAUST FAN FAN CAPACITOR FC FLAME SENSE FS EQUIPMENT GROUND GND GV GAS VALVE HGRH HOT GAS REHEAT HPS HIGH PRESSURE SWITCH IAH INDOOR AIR HUMIDITY SENSOR IIC INTIGRATED IGNITION CONTROL LIMIT SWITCH LS LOAD SHEDDING LDS LPS LOW PRESSURE SWITCH OAT OUTDOOR AIR TEMPERATURE SENSOR OAH OUTDOOR AIR HUMIDITY SENSOR PB POWER DISTRIBUTION BLOCK PLF FEMALE PLUG/CONNECTOR PLM MALE PLUG/CONNECTOR PS PRESSURE SWITCH RS ROLL-OUT SWITCH RSS REMOTE START/STOP SMOKE DETECTOR SMK SPC TEMP SPACE TEMPERATURE SENSOR TB TERMINAL BLOCK (24V SIGNAL) TR TRANSFORMER VENT MOTOR VM VENT MOTOR RELAY VMR BR BR WH BL BR BR BK 5 RD BK GR BL OR YL PU 24V CNTL VOLTAGE LINE VOLTAGE HTR PLM1 ECON PLF 6 5 4 3 2 1 RD YL PU PK OR TR1 POWER & CONTROL WIRING DIAGRAM DCG(120-150) ***(4,7)V DDC PS BL (ECON DMPR) (MOD HGRH) (EXF) (ALRM) R+ 1 SH 2 T- 3 COM1 1 RLY1 2 RLY2 3 COM2 4 RLY3 5 RLY4 6 RLY5 7 RLY6 8 RLY7 9 RLY8 10 COM3-8 11 COM3-8 12 (BAC NET) (SUPPLY AIR TMP) 1ST STG COM 2ND STG GV 2 24VAC AGND AGND AI6 AI7 AI8 (EMER) (FAN PROV) (24V IN) (ECON PWR) (COMP PRESS 1) (COMP PRESS 2) (RMT STRT/STP) (SHED) (CFS) BL 5 4 3 2 1 8 AI3 7 AI4 6 AI5 (COMP2 OUT) (COMP2 IN) (COMP1 IN) (COMP1 OUT) DDC (CLASS2) PK PU YL (BLOWER STAGE 1) (BLOWER STAGE 2) (HEAT 1) (HEAT 2) RD GR GR BK BR 9 AI2 8 7 6 5 4 3 2 1 PU 10 AI1 PK BK YL PU BK BR SPCTEMP TEMP STPT OFFSET GND PU YL BK PK PU BK PK PU YL PU YL/PK YL/PK PU LPS2 LPS1 BK BK PU PU YL XS DA ⚠ Warning BL FS ALS GR AG VOUT (DC) GND 24VAC (COM) 24 VAC CO2 YL/PK ES PK RD PU PK BCS PK YL/PK PU YL BK BL PK BL C BL/PK BK BR RD BK RD T T TTT C PS 1 2 345 S BL/PK 24VAC TB2 (CLASS2) VOUT DC GND 24 VAC IAH OAH VOUT (DC) GND 24 VAC BR -t° OAT HPS2 HPS1 SMK/EMG 1 2 3 4 TMP LMT IN 5 PRESS SW IN 6 PRESS SW OUT 8 HEAT IN 10 24 VAC PWR 24 VAC COM GV OUT TMP LMT OUT IIC 3 -t° DAT GR BR BR CFS LDS WH RD GY TB1 (CLASS2) RSS BL/PK BL/PK PU GR PU PU BL/PK BL/PK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. IGNITOR F1 F1 RD RD PK Wiring Diagram with DDC — DCG 120*/ 150* 460, 575 / 3 / 60 2SP SS-DCG7 Accessories Filed-Installed Item # Fits Model Sizes Description FieldInstalled FactoryOperating Installed Weight (lbs) 14CURB90150 14" Roof Curb 7½-12½ tons √ 143 D25FD90150 25% Manual Fresh Air Damper 7½-12½ tons √ 15 D25MFD90150 25% Motorized Fresh Air Damper 7½-12½ tons √ 21 DBRD3672 Barometric Relief Damper (2 required) 7½-12½ tons √ 30 DDNBBS90150 Burglar Bar Sleeves: includes Supply & Return 7½-12½ tons √ 45 CDK120 Concentric Duct Kit 10 tons √ 104 CDK150 Concentric Duct Kit 12½ tons √ 151 CDK90102 Concentric Duct Kit 7½-8½ tons √ 42 HailGD02D Condenser Coil Hail Guard 7½-10 tons √ 34 HailGD05D Condenser Coil Hail Guard 12½ tons √ 37 Convenience Outlet: Powered All Models √ 42 Convenience Outlet: Non Powered All Models √ 2 All Models √ 5 √ 137 √ 130 Disconnect Switch (non-fused) Ultra Low-Leak Downflow Economizer 7½-12½ tons Low-Leak Downflow Economizer3 7½-12½ tons √ 2 DDNECNJ90150B DDNSQRD9020 HAKT36300 7½ tons √ Electric Heat Kits Downflow Square-to-Round Adapter 20" Round All Models √ High-Altitude Kit All Models √ 55 √ 21 1 HSKT090G¹ High-Static Kit (230/460v) 7½ tons √ 10 HSKT102¹ High-Static Kit (230/460v) 8½ tons √ 10 HSKT090G-7¹ High-Static Kit (575v) 7½ tons √ 10 HSKT102-7¹ High-Static Kit (575v) 8½ tons √ 10 HSKT120¹ High-Static Kit (230/460v) 10 tons √ 48 HSKT120-7¹ High-Static Kit (575v) HSKT150¹ High-Static Kit (230/460v) HSKT150-7¹ High-Static Kit (575v) DHZECNJ90150 Horizontal Economizer GHRC-1 Hurricane Restraint Clips 10 tons √ 48 12½ tons √ 80 12½ tons √ 80 7½-12½ tons √ 90 All Models √ 2 LAKT03 Low-Ambient Kit 7½-12½ tons √ DPE901502 Downflow Power Exhaust (208/230v) 7½-12½ tons √ √ 65 2 DPE901504 Downflow Power Exhaust (460v) 7½-12½ tons √ 65 DPE901507 Downflow Power Exhaust (575v) 7½-12½ tons √ 65 3PMNDK01 Phase Monitor - Non DDC 3-20 tons √ √ 2 Smoke Detector (supply and/or return air) All Models √ 11 Hinged Panels 3-12½ tons √ 34 √ 2 √ 2 DDC communicating controller (built-in BACnet® MS/TP) DLAKT03 Low-Ambient* LONKT01 LonWorks®* 3PMK01 Phase Monitor* DFSKT01 Dirty Filter Switch* 3-20 tons 7½-20 tons √ 3-20 tons √ 3-20 tons √ 3-12½ tons √ 1 √ 2 1 HSKT High-Static Kits are for use with standard single-speed belt-drive units only. 2 Please contact RRS Rooftop Systems directly if Power Exhaust is required. Ultra Low-Leak economizer for DDC controls. 3 Please use part number DPE901502 / DPE901504 / DPE901507 if Power Exhaust is required. 1 Note: Where multiple variations are available, the heaviest combination is listed. *Indicates accessories for use with DDC models only. SS-DCG7 www.daikincomfort.com 43 Notes Our continuing commitment to quality products may mean a change in specifications without notice. © 2016 • Houston, Texas • Printed in the USA. 44 www.daikincomfort.com SS-DCG7
Similar documents
TECHNICAL GUIDE R-410A ZF SERIES 6-1/2 - 12
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1...
More informationSpecs - Climate Solutions, Inc.
Drain Size (NPT) R-410A Refrigerant Charge (oz.) Evaporator Coil Face Area (ft²) Rows Deep/ Fins per Inch Tube Diameter/ Material Evaporator Fan Standard Direct Drive (D x W) HP Standard Belt Drive...
More information