DCG Commercial - Daikin Comfort

Transcription

DCG Commercial - Daikin Comfort
DCG Commercial
7½ - 12½ Ton Packaged Gas/ Electric
Up to 11.3 EER / 80% AFUE
Cooling Capacity: 88,000 — 144,000 BTU/h
Heating Capacity (Output): 168,000 BTU/h
■ Contents
Nomenclature......................................... 2
Product Specifications............................ 4
Expanded Cooling Data.......................... 8
Airflow Data.......................................... 16
Dimensions........................................... 20
Wiring Diagrams .................................. 24
– for Models with DDC Controls............... 36
Accessories........................................... 43
■ Standard Features
•
•
•
•
•
•
•
•
•
•
•
•
■ Cabinet Features
TuffTube™ tubular heat exchanger
• Heavy-gauge, galvanized-steel cabinet
with UV-resistant powder-paint finish
High-efficiency scroll compressors
• Full perimeter rail
Two-stage heating and cooling
• Sloped drain pan
Copper tube / aluminum fin coils
• Easy to service
Power block for field wiring
High-capacity, steel-cased filter drier
Single-point entry
24-volt terminal strip
Convertible airflow orientation
Built-in filter rack with standard 2" filters
Complies with California Low NOx emissions standards
Units meet the performance outlined in Table 6.8.1A of
ASHRAE Standard 90.1-2010
• AHRI Certified; ETL Listed
*Complete warranty details available from your local dealer or at www.daikincomfort.com.
SS-DCG7
www.daikincomfort.com
6/16
Supersedes 3/16
Nomenclature
D
1
C
2
G
3
090
4,5,6
210
7,8,9
3
10
B
11
*
12
*
13
*
14
A *
15 16
Revision Levels
Major & Minor
Brand
D Daikin
Configuration
C Commercial
T High Efficiency (3-5 Tons)
Application
C Cooling3
G Gas Heat
H Heat Pump3
Nominal Cooling Capacity
036 3 Tons
102
048 4 Tons
120
060 5 Tons
150
072 6 Tons
180
090 7½ Tons
240
8½ Tons
10 Tons
12½ tons
15 Tons
20 Tons
300 25 Tons
Nominal Heating Capacity
Gas/Electric
A/C H/P Factory-Installed Electric Heat
045 45,000 BTU/h
XXX No Heat
090 90,000 BTU/h
010 10 kW
030 30 kW
115 115,000 BTU/h
015 15 kW
031 30 kW
140 140,000 BTU/h
016 15 kW
045 45 kW
210 210,000 BTU/h
018 18 kW
046 45 kW
350 350,000 BTU/h
020 20 kW
060 60 kW
400 400,000 BTU/h
025 25 kW
See product specifications for heat size(s) available for each capacity.
Voltage
1 208-230/1/60
3 208-230/3/60
4
7
460/3/60
575/3/60
Supply Fan/Drive Type/Motor
B Belt Drive (single speed) V Two-Speed Belt Drive (also designates 6-Ton
D Direct Drive (3-5 Tons)
with two-stage compressor)
Factory-Installed Options
A Ultra Low-Leak Downflow Economizer1
B DDC-BACnet protocol
F Ultra Low-Leak Downflow Economizer1;
DDC-BACnet protocol
H Disconnect Switch (non-fused)
J Ultra Low-Leak Downflow Economizer1;
Disconnect Switch (non-fused)
M Disconnect Switch (non-fused); DDC-BACnet protocol
R Ultra Low-Leak Downflow Economizer1;
DDC-BACnet protocol;
Disconnect Switch (non-fused)
V Low-Leak Downflow Economizer2
W Low-Leak Downflow Economizer2
Disconnect Switch (non-fused)
X No Options
Note: Not all options available for all products.
2
Factory-Installed Options
No Options
Non-powered convenience outlet
Powered convenience outlet
Low-ambient kit
Return air smoke detector
Supply air smoke detector
Non-powered convenience outlet;
Low-ambient kit
G Non-powered convenience outlet;
Return air smoke detector
H Non-powered convenience outlet;
Supply air smoke detector
J Non-powered convenience outlet;
Return & Supply air smoke detectors
K Non-powered convenience outlet;
Low-ambient kit; Supply air smoke detector
L Non-powered convenience outlet;
Low-ambient kit
Return & Supply air smoke detectors
M Powered convenience outlet;
Low-ambient kit
N Powered convenience outlet;
Return air smoke detector
O Powered convenience outlet;
Return & Supply air smoke detectors
P Powered convenience outlet;
Supply air smoke detector
Q Powered convenience outlet; Low-ambient
kit; Return air smoke detector
R Powered convenience outlet; Low-ambient
kit; Supply air smoke detector
T Powered convenience outlet; Low-ambient
kit; Return & Supply air smoke detectors
U Non-powered convenience outlet;
Low-ambient kit; Return air smoke detector
V Low-ambient kit; Return air smoke detector
W Low-ambient kit; Supply air smoke detector
Y Low-ambient kit; Return & Supply
air smoke detectors
Z Return & Supply air smoke detectors
X
A
B
C
D
E
F
1
Please contact RRS Rooftop Systems directly if Power Exhaust is required. Ultra Low-Leak economizer for DDC controls.
2
Please use part number DPE901502 / DPE901504 / DPE901507 if Power Exhaust is required.
3
X= No Options in character 13th
www.daikincomfort.com
Factory-Installed Options
Standard Aluminized Heat Exchanger
Stainless-Steel Heat Exchanger
Hinged Panels (3-12½ Tons)
Stainless-Steel Heat Exchanger; Hinged
Panels (3-12½ tons)
B Phase Monitor
J Stainless Steel Heat Exchanger; Phase Monitor
M Hinged Panel (3-12½ tons); Phase Monitor
L Stainless-Steel Heat Exchanger;
Hinged Panels (3-12½ tons); Phase Monitor
X
S
D
K
SS-DCG7
Nomenclature
Factory-Installed Options
• Stainless-Steel Heat Exchanger (DCG units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.
• Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended
from 60°F ambient temperature to 35°F outside air temperature. On 7½ -20 ton units, cooling operation is extended from 35°F
ambient temperature to 0°F outside air temperature. For 25 ton units, cooling operation is extended from 24°F ambient temperature
to 0°F outside air temperature.
• Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.
• Electric Heat Kits (DCC and DCH units only): Available in all voltage options.
• Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs
power to the outlet.
• Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered
convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase
by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.
• Disconnect Switch (non-fused; 3-phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from
the switch to the unit. Please note that for air conditioning (DCC units) and heat pump models (DCH units), the appropriate electric heat
kit must be ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models
with a powered convenience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet
will be shut off when the disconnect switch (non-fused) is in the off position.
• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.
• Two-speed indoor fan blower models are available on 6, 7½, 8½, 10, 12½, 15, 20 & 25 ton units. Section 6.4.3.10.b of ASHRAE Standard
90.1-2010 and Section 6.5.3.2.1.a of ASHRAE Standard 90.1-2013 require a minimum of two fan speeds. Section 140.4(m)1 of California
Energy Commission Title 24 2013 contains a similar provision. When the units with the two-speed indoor fan blowers operate on a call
for the first stage of cooling, the fan operates at low speed, which is 66% of full speed. When the units operate on a call for the second
stage of cooling, the fan operates at full speed. In heating operation, the fan operates at full speed. During ventilation operation, the fan
operates at low speed.
• Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor,
filters and blower motor. Available on 3-12½ Tons units.
SS-DCG7
www.daikincomfort.com
3
Product Specifications — 7½ Tons
DCG090
2103B*** A*
DCG090
2103V*** A*
DCG090
2104B***A*
DCG090
2104V*** A*
Cooling Capacity
Total BTU/h
88,000
88,000
88,000
88,000
88,000
88,000
Sensible BTU/h
65,100
65,100
65,100
65,100
65,100
65,100
11.3 / 11.5
11.3 / 13.0
11.3 / 11.5
11.3 / 13.0
11.3 / 11.5
11.3 / 13.0
82
82
82
82
82
82
7041908
7041911
7041908
7041911
7041908
7041911
EER / IEER
Decibels
AHRI Reference #s
DCG090
2107B*** A*
DCG090
2107V*** A*
Heating Capacity
High Input / Output MBTU/h
210 / 168
210 / 168
210 / 168
210 / 168
210 / 168
210 / 168
Low Input / Output MBTU/h
157.5 / 126
157.5 / 126
157.5 / 126
157.5 / 126
157.5 / 126
157.5 / 126
Steady-State Efficiency (AFUE)
80
80
80
80
80
80
Temperature Rise Range (°F)
No. of Burners
35
6
35
6
35
6
35
6
35
6
35
6
Evaporator Motor / Coil
Motor Type
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
3,000
3,000
3,000
3,000
3,000
3,000
Indoor Nominal CFM
FLA (Cooling)
Horsepower / RPM
Piston Size (Cooling)
Filter Size (Qty)
Drain Size (NPT)
5.0
6.0
2.5
2.9
2.3
2.4
1½ / 1745
2/ 1740-1160
1½ / 1745
2/ 1740-1160
1½ / 1725
2 / 1745-1170
0.078
0.078
0.078
0.078
0.078
0.078
16" x 20" x 2"
16" x 20" x 2"
16" x 20" x 2"
16" x 20" x 2"
16" x 20" x 2"
16" x 20" x 2"
¾"
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge: Cir #1 / #2
100 oz.
100 oz.
100 oz.
100 oz.
100 oz.
100 oz.
Evaporator Coil Face Area (ft²)
Rows Deep / Fins per Inch
8.9
4 / 16
8.9
4 / 16
8.9
4 / 16
8.9
4 / 16
8.9
4 / 16
8.9
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
Motor / Blower Sheave
Belt
VL40 / AK74
AX51
VL40 / AK74
AX51
VL40 / AK74
AX51
VL40 / AK74
AX51
VL40 / AK74
AX51
VL40 / AK74
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
2
2
¼ - 1075
¼ - 1075
¼ - 1075
¼ - 1075
¼ - 1075
¼ - 1075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
7,200
7,200
7,200
7,200
7,200
7,200
Face Area (ft²)
Rows Deep / Fins per Inch
28.8
2 X2 / 27±1
28.8
2 X2 / 27±1
28.8
'2 X2 / 27±1
28.8
'2 X2 / 27±1
28.8
'2 X2 / 27±1
28.8
'2 X2 / 27±1
Compressor
Quantity / Type / Stage
Compressor RLA / LRA
2 / Scroll / 1
13.1 / 83.1
2 / Scroll / 1
13.1 / 83.1
2 / Scroll / 1
6.1 / 41.0
2 / Scroll / 1
6.1 / 41.0
2 / Scroll / 1
4.4 / 33.0
2 / Scroll / 1
4.4 / 33.0
Electrical Data
Voltage / Phase
208-230 / 3
208-230 / 3
460 / 3
460 / 3
575 / 3
575 / 3
1.5 / 5.0
2/6.0
1.5 / 2.5
2/2.9
1.5 / 2.3
2/2.4
1.0"
1.0"
1.0"
1.0"
1.0"
1.0"
(2) ¼ / 1.4
(2) ¼ / 1.4
(2) ¼ / 0.7
(2) ¼ / 0.7
(2) ¼ / 0.55
(2) ¼ / 0.55
Horsepower - RPM
Indoor Blower HP / FLA
Max External Static
Outdoor Fan HP / RLA
Total Unit Amps
34.0
35.0
16.1
16.5
12.2
12.3
Min. Circuit Ampacity¹
37
38.3
17.7
18
13.3
13.4
Max. Overcurrent Protection (amps)²
50
50
20
20
15
15
Entrance Power Supply
Entrance Control Voltage
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Operating Weight (lbs)
Ship Weight (lbs)
1100
1175
1100
1175
1100
1175
1100
1175
1100
1175
1100
1175
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
4
www.daikincomfort.com
SS-DCG7
Product Specifications — 8½ Tons
DCG102
2103B***A*
DCG102
2103V***A*
DCG102
2104B***A*
DCG102
2104V***A*
DCG102
2107B***A*
DCG102
2107V***A*
Total, BTU/h
102,000
102,000
102,000
102,000
102,000
102,000
Sensible BTU/h
70,380
70,380
70,380
70,380
70,380
70,380
11.3 / 11.2
11.3 / 13.4
11.3 / 11.2
11.3 / 13.4
11.3 / 11.2
11.3 / 13.4
Cooling Capacity
EER / IEER
Decibels
ARI Reference #s
83
83
83
83
83
83
7370921
7370924
7370921
7370924
7370921
7370924
Heating Capacity
High Input / Output BTU/h
210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000 210,000/ 168,000
Low Input / Output BTU/h
157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000 157,500/126,000
Steady State Efficciency
Temperature Rise Range (°F)
No. of Burners
80
80
80
80
80
80
35 - 65
35 - 65
35 - 65
35 - 65
35 - 65
35 - 65
6
6
6
6
6
6
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
3,200
3,200
3,200
3,200
3,200
3,200
7.8
6.0
3.9
2.9
2.3
2.4
2 / 1725
2/ 1740-1160
2 / 1725
2/ 1740-1160
2 / 1725
2 / 1745-1170
Evaporator Motor / Coil
Motor Type
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
0.080
0.080
0.080
0.080
0.080
0.080
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
Drain Size (NPT)
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
R-410A Refrigerant Charge Cir #1 #2 (oz.)
110.0
110.0
110.0
110.0
110.0
110.0
Evaporator Coil Face Area (ft2)
10.2
10.2
10.2
10.2
10.2
10.2
Rows Deep / Fins per Inch
4 / 14
4 / 14
4 / 14
4 / 14
4 / 14
4 / 14
# of Wheels (D x W)
1 (15" x 15")
1 (15" x 15")
1 (15" x 15")
1 (15" x 15")
1 (15" x 15")
1 (15" x 15")
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
AX51
AX51
AX51
AX51
AX51
AX51
Belt Drive Evap Fan Data
Belt
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
2
2
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
8,200
8,200
8,200
8,200
8,200
8,200
Face Area (ft²)
28.8
28.8
28.8
28.8
28.8
28.8
'2 X2 / 27±1
'2 X2 / 27±1
'2 X2 / 27±1
'2 X2 / 27±1
'2 X2 / 27±1
'2 X2 / 27±1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
14.5 / 98
14.5 / 98
6.3 / 55
6.3 / 55
6.0 / 41
6.0 / 41
575 / 3
Horsepower - RPM
Rows Deep / Fins per Inch
Compressor
Quantity / Type / Stage
Compressor RLA / LRA ea.
Electrical Data / Static
208-230 / 3
208-230 / 3
460 / 3
460 / 3
575 / 3
Outdoor Fan FLA ea.
Voltage / Phase (60 Hz)
1.40
1.40
0.70
0.70
0.55
0.55
Total Unit Amps
39.6
37.8
18.9
16.9
15.3
15.4
Min. Circuit Ampacity¹
43.2
41.4
20.5
18.5
16.9
17
50
50
25
20
20
20
Entrance Power Supply
Locating
Locating
Locating
Locating
Locating
Locating
Entrance Control Voltage
Dimple
Dimple
Dimple
Dimple
Dimple
Dimple
Operating Weight (lbs)
1140
1140
1140
1140
1140
1140
Ship Weight (lbs)
1215
1215
1215
1215
1215
1215
Max. Overcurrent Protection (amps)²
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
SS-DCG7
www.daikincomfort.com
5
Product Specifications — 10 Tons
DCG120
2103B***A*
DCG120
2103V***A*
DCG120
2104B***A*
DCG120
2104V***A*
DCG120
2107B***A*
DCG120
2107V***A*
Total BTU/h
116,000
116,000
116,000
116,000
116,000
116,000
Sensible BTU/h
84,700
84,700
84,700
84,700
84,700
84,700
11.3 / 11.5
11.3 / 12.8
11.3 / 11.5
11.3 / 12.8
11.3 / 11.5
11.3 / 12.8
Cooling Capacity
EER / IEER
Decibels
ARI Reference #s
83
83
83
83
83
83
6345698
6345699
6345698
6345699
6345698
6345699
210,000/
168,000
157,500/
126,000
210,000/
168,000
157,500/
126,000
210,000/
168,000
157,500/
126,000
210,000/
168,000
157,500/
126,000
210,000/
168,000
157,500/
126,000
210,000/
168,000
157,500/
126,000
Heating Capacity
High Input/Output (BTU/h)
Low Input/Output (BTU/h)
Steady State Efficiency
80
80
80
80
80
80
25-55
25-55
25-55
25-55
25-55
25-55
6
6
6
6
6
6
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
3,500
3,500
3,500
3,500
3,500
3,500
7.8
6.4
3.9
3.3
2.5
2.4
Horsepower - RPM
2.0 - 1,725
2.0/1750-1165
2.0 - 1,725
2.0/1750-1165
2.0 - 1,725
2.0/1750-1165
Piston Size (Cooling)
0.086
0.086
0.086
0.086
0.086
0.086
16”x24”x2”
16”x24”x2”
16”x24”x2”
16”x24”x2”
16”x24”x2”
16”x24”x2”
Temperature Rise Range (°F)
No. of Burners
Evaporator Motor / Coil
Motor Type
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Filter Size (#=4)
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & 2 (oz.)
¾"
¾"
¾"
¾"
¾"
¾"
144 / 123
144 / 123
144 / 123
144 / 123
144 / 123
144 / 123
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
10.2
10.2
10.2
Rows Deep/ Fins per Inch
4 / 14
4 / 14
4 / 14
4 / 14
4 / 14
4 / 14
# of Wheels (D x W)
(1) 15” x 15”
(1) 15” x 15”
(1) 15” x 15”
(1) 15” x 15”
(1) 15” x 15”
(1) 15” x 15”
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
AX51
AX50
AX51
AX50
AX51
AX50
Belt Drive Evap Fan Data
Belt
Condenser Fan / Coil
Quantity of Condenser Fan Motors
Horsepower - RPM
2
2
2
2
2
2
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
8,200
8,200
8,200
8,200
8,200
8,200
Face Area (ft²)
35.2
35.2
35.2
35.2
35.2
35.2
2 X2 / 27±1
2 X2 / 27±1
2 X2 / 27±1
2 X2 / 27±1
2 X2 / 27±1
2 X2 / 27±1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
16 / 110.0
16 / 110.0
7.8 / 52.0
7.8 / 52.0
5.7 / 38.9
5.7 / 38.9
208-230/ 3/ 60
208-230/ 3/ 60
460/ 3/ 60
460/ 3/ 60
575/ 3/ 60
575/ 3/ 60
2.00
2.00
0.85
0.85
0.67
0.67
Total Unit Amps
45
43
22
21
16
16
Min. Circuit Ampacity¹
49
47
24
23
17
17
Max. Overcurrent Protection (amps)²
60
60
30
30
20
20
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
# Coils / Rows Deep - Fins per Inch
Compressor
Quantity / Type / Stage
Compressor RLA / LRA ea.
Electrical Data
Voltage/Phase/ Frequency
Outdoor Fan RLA ea.
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
1140
1140
1140
1140
1140
1140
Ship Weight (lbs)
1215
1215
1215
1215
1215
1215
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
6
www.daikincomfort.com
SS-DCG7
Product Specifications — 12½ Tons
DCG150
2103B***A*
DCG150
2103V***A*
DCG150
2104B***A*
DCG150
2104V***A*
DCG150
2107B***A*
DCG150
2107V***A*
144,000
144,000
144,000
144,000
144,000
144,000
Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s
100,000
100,000
100,000
100,000
100,000
100,000
10.8 / 11.0
10.8 / 12.0
10.8 / 11.0
10.8 / 12.0
10.8 / 11.0
10.8 / 12.0
83
83
83
83
83
83
6885862
6885865
6885862
6885865
6885862
6885865
Heating Capacity
High Input / Output BTU/h
210,000 / 168,000
210,000 / 168,000
Low Input / Output BTU/h
157,500 / 126,000
157,500 / 126,000
Steady State Efficiency
Temperature Rise Range (°F)
No. of Burners
210,000 / 168,000
157,500 / 126,000
80
80
80
80
80
80
15 - 45
15 - 45
15 - 45
15 - 45
15 - 45
15 - 45
6
6
6
6
6
6
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
Belt Drive
2-speed Belt Drive
3,900
3,900
3,900
3,900
3,900
3,900
9.4
9.1
4.7
4.3
4.2
3.5
3.0 - 1,725
3.0/1760-1165
3.0 - 1,725
3.0/1760-1165
3.0 - 1,725
3.0/1760-1165
0.092
0.092
0.092
0.092
Evapoartor Motor / Coil
Motor Type (Belt Drive)
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
0.092
0.092
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
(4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2"
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1/ #2 (oz.)
175
175
175
175
175
175
Evaporator Coil Face Area (ft2)
14.7
14.7
14.7
14.7
14.7
14.7
Rows Deep / Fins per Inch
4 / 15
4 / 15
4 / 15
4 / 15
4 / 15
4 / 15
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK66
VP44 / AK71
VL40 / AK66
VP44 / AK71
VL40 / AK66
VP44 / AK71
AX49
AX48
AX49
AX48
AX49
AX48
Belt Drive Evap Fan Data
Belt
Condenser Fan / Coil
Quantity of condenser Fan Motors
Horsepower - RPM
2
2
2
2
2
2
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22/3
22/3
22/3
22/3
22/3
22/3
Outdoor Nominal CFM
8,400
8,400
8,400
8,400
8,400
8,400
Face Area (ft2)
# Coils / Rows Deep - Fins per Inch
39.0
39.0
39.0
39.0
39.0
39.0
2/2 rows 27 fpi
2/2 rows 27 fpi
2/2 rows 27 fpi
2/2 rows 27 fpi
2/2 rows 27 fpi
2/2 rows 27 fpi
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
22.4 / 149
22.4 / 149
10.6 / 75
10.6 / 75
7.7 / 54
7.7 / 54
575/3/60
Compressor
Quantity / Type / Stage
Compressor RLA / LRA ea.
Electrical Data / Static
Voltage / Phase / Frequency
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
Standard Max Static
1.4"
1.4"
1.4"
1.4"
1.4"
1.4"
Outdoor Fan FLA ea.
2.00
2.00
0.85
0.85
0.67
0.67
Total Unit Amps
59
57.9
28
26.9
21.4
20.7
Min. Circuit Ampacity1
65
63.5
31
29.9
23
23
Max. Overcurrent Protection (amps)2
80
80
40
40
30
30
Entrance Control Voltage
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Operating Weight (lbs)
Ship Weight (lbs)
1315
1340
1315
1340
1315
1340
1315
1340
1315
1340
1315
1340
Entrance Power Supply
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
SS-DCG7
www.daikincomfort.com
7
8
www.daikincomfort.com
59
86
0.74
17.5
6.1
234
108
84
0.71
18.2
6.1
231
107
77
0.68
20.2
5.9
224
104
88
0.84
20.2
6.2
236
109
85
0.81
21.0
6.1
234
108
79
0.78
23.4
6.0
227
105
Airflow
MBh
S/T
∆T
3375
kW
Hi PR
Lo PR
MBh
S/T
∆T
3000
kW
Hi PR
Lo PR
MBh
S/T
∆T
2400
kW
Hi PR
Lo PR
MBh
S/T
∆T
3375
kW
Hi PR
Lo PR
MBh
S/T
∆T
3000
kW
Hi PR
Lo PR
MBh
S/T
∆T
2400
kW
Hi PR
Lo PR
81
0.69
21.5
6.1
244
112
88
0.72
19.4
6.2
252
115
90
0.76
18.6
6.3
254
116
80
0.57
17.5
6.1
242
111
87
0.59
15.7
6.2
249
114
89
0.62
15.1
6.2
252
115
63
88
0.53
17.6
6.3
258
122
95
0.55
15.9
6.4
266
126
98
0.57
15.2
6.5
268
127
88
0.40
13.3
6.2
255
121
95
0.41
11.9
6.4
263
124
98
0.43
11.5
6.4
266
126
67
94
0.3
12.2
6.5
269
130
102
0.4
11.0
6.6
277
134
105
0.4
10.5
6.7
280
135
-
-
-
71
77
0.81
23.7
6.4
254
111
83
0.84
21.3
6.6
262
114
86
0.88
20.4
6.6
265
116
75
0.71
20.5
6.4
252
110
82
0.73
18.4
6.5
260
113
84
0.77
17.7
6.6
262
114
59
79
0.72
21.8
6.5
274
118
86
0.75
19.6
6.7
282
122
88
0.78
18.8
6.7
285
123
78
0.59
17.7
6.5
271
117
85
0.61
15.9
6.6
279
120
87
0.64
15.3
6.7
282
122
63
75
86
0.55
17.9
6.7
289
129
93
0.57
16.1
6.9
298
133
95
0.59
15.4
6.9
301
134
86
0.41
13.5
6.7
286
128
93
0.43
12.1
6.8
295
132
96
0.45
11.6
6.9
298
133
67
92
0.4
12.3
6.9
302
137
99
0.4
11.1
7.1
311
141
102
0.4
10.6
7.2
314
143
-
-
-
71
75
0.83
23.7
6.8
289
115
81
0.86
21.3
6.9
298
119
84
0.90
20.5
7.0
301
120
74
0.73
20.5
6.7
286
114
80
0.75
18.4
6.9
295
118
82
0.79
17.7
6.9
298
119
59
77
0.74
21.8
6.9
311
123
84
0.77
19.6
7.1
321
126
86
0.80
18.8
7.1
324
128
76
0.61
17.7
6.9
308
121
83
0.63
16.0
7.0
318
125
85
0.66
15.3
7.1
321
126
63
84
0.56
17.9
7.1
329
134
90
0.58
16.1
7.3
339
138
93
0.61
15.4
7.4
342
139
84
0.42
13.5
7.1
326
133
91
0.44
12.1
7.2
336
137
93
0.46
11.6
7.3
339
138
67
90
0.4
12.3
7.4
343
143
97
0.4
11.1
7.5
354
147
100
0.4
10.7
7.6
357
149
-
-
-
71
73
0.85
23.9
7.1
330
121
79
0.88
21.5
7.3
340
125
82
0.93
20.6
7.3
343
126
72
0.75
20.6
7.1
326
120
78
0.78
18.6
7.2
336
124
80
0.82
17.8
7.3
340
125
59
81
0.58
18.0
7.5
375
141
88
0.60
16.2
7.7
386
145
82
0.79
19.8
7.4
366
133
75
0.76
22.0
7.3
355
129
91
0.63
15.5
7.7
390
146
82
0.43
13.6
7.4
371
139
88
0.45
12.2
7.6
382
144
91
0.47
11.7
7.7
386
145
67
84
0.83
19.0
7.5
369
134
75
0.63
17.9
7.2
351
128
81
0.65
16.1
7.4
362
132
83
0.68
15.4
7.4
366
133
63
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
87
0.4
12.4
7.7
391
150
95
0.4
11.2
7.9
403
154
98
0.4
10.7
8.0
407
156
-
-
-
71
69
0.88
23.5
7.4
371
127
75
0.92
21.2
7.6
382
131
77
0.96
20.3
7.6
386
132
68
0.78
20.4
7.3
367
126
74
0.81
18.3
7.5
378
130
76
0.85
17.6
7.6
382
131
59
72
0.79
21.7
7.5
399
135
77
0.82
19.5
7.7
411
139
80
0.86
18.7
7.8
415
141
71
0.65
17.6
7.5
395
134
77
0.67
15.8
7.7
407
138
79
0.71
15.2
7.7
411
139
63
67
77
0.60
17.8
7.8
421
147
84
0.62
16.0
8.0
434
152
86
0.65
15.3
8.0
439
154
78
0.45
13.4
7.7
417
146
84
0.47
12.0
7.9
430
150
87
0.49
11.5
8.0
434
152
105
83
0.4
12.3
8.0
439
157
90
0.4
11.0
8.2
453
162
93
0.4
10.6
8.3
458
163
-
-
-
71
64
0.89
22.0
7.6
410
131
70
0.93
19.8
7.8
422
135
72
0.97
19.0
7.9
427
137
63
0.78
19.0
7.6
406
130
69
0.81
17.1
7.8
418
134
71
0.85
16.4
7.8
422
135
59
66
0.80
20.2
7.8
441
140
72
0.83
18.2
8.0
454
144
74
0.87
17.5
8.1
459
145
66
0.66
16.5
7.7
436
138
71
0.68
14.8
7.9
450
143
73
0.71
14.2
8.0
454
144
63
67
72
0.60
16.6
8.0
466
153
78
0.63
14.9
8.2
480
157
80
0.66
14.3
8.3
485
159
72
0.45
12.5
8.0
461
151
78
0.47
11.2
8.2
475
156
80
0.49
10.8
8.2
480
157
115
77
0.4
11.5
8.3
486
162
83
0.4
10.3
8.5
501
167
86
0.4
9.9
8.6
506
169
-
-
-
71
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects ACCA (TVA) Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
75
70
IDB
65
Expanded Cooling Data — 7½ Tons
SS-DCG7
SS-DCG7
www.daikincomfort.com
59
89
0.93
22.5
6.2
238
110
87
0.88
23.5
6.2
236
109
80
0.85
26.1
6.0
229
106
91
0.97
24.0
6.3
241
112
88
0.93
25.0
6.2
238
110
81
0.89
27.8
6.1
231
107
Airflow
MBh
S/T
∆T
3375
kW
Hi PR
Lo PR
MBh
S/T
∆T
3000
kW
Hi PR
Lo PR
MBh
S/T
∆T
2400
kW
Hi PR
Lo PR
MBh
S/T
∆T
3375
kW
Hi PR
Lo PR
MBh
S/T
∆T
3000
kW
Hi PR
Lo PR
MBh
S/T
∆T
2400
kW
Hi PR
Lo PR
83
0.86
27.4
6.2
249
114
90
0.89
24.6
6.3
257
118
93
0.94
23.6
6.4
259
119
82
0.80
25.0
6.1
246
113
89
0.83
22.5
6.3
254
116
91
0.87
21.6
6.3
257
118
63
87
0.78
25.9
6.4
263
124
94
0.81
23.3
6.5
271
128
97
0.85
22.3
6.6
274
130
87
0.65
21.8
6.3
260
123
95
0.67
19.6
6.5
268
127
97
0.71
18.8
6.5
271
128
67
71
93
0.6
22.4
6.6
274
133
100
0.7
20.1
6.7
283
137
103
0.7
19.3
6.8
285
138
93
0.5
17.4
6.5
271
131
101
0.50
15.6
6.7
280
135
104
0.5
15.0
6.7
283
137
79
0.93
28.2
6.5
260
113
86
0.96
25.3
6.7
268
117
89
1.00
24.2
6.7
270
118
78
0.88
26.4
6.5
257
112
85
0.92
23.8
6.6
265
116
87
0.96
22.8
6.7
268
117
59
81
0.89
27.7
6.6
279
120
88
0.93
24.9
6.8
288
124
90
0.97
23.9
6.8
291
125
80
0.83
25.3
6.6
277
119
86
0.86
22.8
6.7
285
123
89
0.90
21.9
6.8
288
124
63
75
85
0.81
26.2
6.8
295
131
92
0.84
23.6
7.0
304
136
95
0.88
22.6
7.1
307
137
85
0.67
22.0
6.8
292
130
92
0.70
19.8
6.9
301
134
95
0.73
19.0
7.0
304
136
67
71
91
0.7
22.7
7.0
308
140
98
0.7
20.4
7.2
317
144
101
0.7
19.6
7.3
320
146
91
0.5
17.6
7.0
305
139
99
0.52
15.8
7.2
314
143
102
0.5
15.2
7.2
317
144
78
0.95
28.2
6.9
295
118
84
0.98
25.4
7.1
304
121
87
1.00
23.6
7.1
307
122
76
0.91
26.5
6.8
292
116
83
0.94
23.8
7.0
301
120
85
1.00
23.2
7.1
304
121
59
79
0.92
27.8
7.0
318
125
86
0.95
24.9
7.2
328
129
88
1.00
24.0
7.3
331
130
78
0.85
25.4
7.0
315
124
84
0.88
22.8
7.1
324
128
87
0.92
21.9
7.2
328
129
63
83
0.83
26.2
7.2
335
137
90
0.86
23.6
7.4
346
141
92
0.90
22.6
7.5
349
142
83
0.69
22.0
7.2
332
135
90
0.72
19.8
7.4
342
139
93
0.75
19.0
7.4
346
141
67
88
0.7
22.7
7.5
350
146
96
0.7
20.4
7.6
361
150
99
0.7
19.6
7.7
364
152
89
0.5
17.6
7.4
346
144
96
0.54
15.8
7.6
357
149
99
0.6
15.2
7.6
361
150
71
76
0.98
28.4
7.2
336
124
82
1.00
25.1
7.4
347
127
84
1.00
23.0
7.5
350
129
74
0.93
26.6
7.2
333
122
81
0.97
23.9
7.3
343
126
83
1.00
22.6
7.4
347
127
59
77
0.95
28.0
7.4
362
131
84
0.98
25.1
7.6
373
136
86
1.00
23.5
7.6
377
137
76
0.88
25.5
7.3
358
130
82
0.91
22.9
7.5
369
134
85
0.95
22.0
7.6
373
136
63
81
0.85
26.4
7.6
382
144
88
0.89
23.7
7.8
394
148
90
0.93
22.8
7.8
398
149
86
0.7
22.9
7.8
399
153
93
0.7
20.6
8.0
411
158
96
0.8
19.7
8.1
415
159
87
0.5
17.7
7.8
395
151
94
0.55
15.9
8.0
407
156
88
0.74
20.0
7.7
390
147
81
0.71
22.2
7.5
378
142
97
0.6
15.3
8.0
411
158
71
91
0.78
19.2
7.8
394
148
67
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
72
1.00
27.5
7.5
378
130
78
1.00
23.9
7.7
390
134
80
1.00
21.9
7.8
394
135
71
0.97
26.3
7.5
375
128
77
1.00
23.5
7.6
386
132
79
1.00
21.5
7.7
390
134
59
73
0.98
27.6
7.7
407
138
79
1.00
24.3
7.9
420
142
82
1.00
22.3
7.9
424
143
72
0.91
25.2
7.6
403
136
78
0.94
22.6
7.8
415
141
81
1.00
22.0
7.9
420
142
63
67
77
0.89
26.0
7.9
430
150
83
0.92
23.4
8.1
443
155
86
0.96
22.5
8.2
448
157
77
0.74
21.9
7.8
426
149
84
0.77
19.7
8.0
439
154
86
0.81
18.9
8.1
443
155
105
82
0.7
22.5
8.2
448
160
89
0.7
20.3
8.4
462
165
91
0.8
19.5
8.4
467
167
82
0.6
17.5
8.1
444
159
89
0.57
15.7
8.3
458
164
92
0.6
15.1
8.4
462
165
71
67
1.00
25.5
7.8
418
134
72
1.00
22.1
7.9
431
138
74
1.00
20.3
8.0
435
139
65
0.98
24.5
7.7
414
133
71
1.00
21.7
7.9
427
137
73
1.00
19.9
7.9
431
138
59
68
0.99
25.7
7.9
450
143
74
1.00
22.5
8.1
464
147
76
1.00
20.6
8.2
468
148
67
0.92
23.5
7.9
445
141
72
0.95
21.1
8.1
459
145
75
1.00
20.3
8.1
464
147
63
67
71
0.89
24.3
8.2
475
156
77
0.93
21.9
8.4
490
160
79
0.97
21.0
8.4
495
162
71
0.75
20.4
8.1
470
154
77
0.77
18.4
8.3
485
159
80
0.81
17.6
8.4
490
160
115
75.9
0.7
21.1
8.4
495
166
82
0.8
18.9
8.6
511
171
85
0.8
18.2
8.7
516
173
76.4
0.6
16.3
8.4
490
164
83
0.58
14.7
8.6
506
169
85
0.6
14.1
8.6
511
171
71
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects AHRI Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
85
80
IDB
65
Expanded Cooling Data — 7½ Tons (cont.)
9
10
www.daikincomfort.com
59
100
0.73
17.5
7.2
238
106
97
0.69
18.2
7.1
235
105
90
0.67
18.5
7.0
228
102
102
0.83
20.2
7.2
240
107
99
0.79
21.0
7.2
238
106
91
0.76
21.3
7.0
231
103
Airflow
MBh
S/T
∆T
3820
kW
Hi PR
Lo PR
MBh
S/T
∆T
3400
kW
Hi PR
Lo PR
MBh
S/T
∆T
2980
kW
Hi PR
Lo PR
MBh
S/T
∆T
3820
kW
Hi PR
Lo PR
MBh
S/T
∆T
3400
kW
Hi PR
Lo PR
MBh
S/T
∆T
2980
kW
Hi PR
Lo PR
63
94
0.68
19.7
7.2
248
109
102
0.70
19.4
7.3
256
113
105
0.74
18.6
7.4
258
114
93
0.56
16.0
7.1
246
108
101
0.58
15.7
7.3
253
112
104
0.61
15.1
7.3
256
113
67
102
0.51
16.1
7.4
262
119
110
0.53
15.9
7.5
270
123
113
0.56
15.2
7.6
273
124
102
0.39
12.1
7.3
259
118
110
0.40
11.9
7.5
267
122
114
0.42
11.5
7.5
270
123
109
0.3
11.1
7.6
273
127
118
0.3
11.0
7.8
282
131
122
0.4
10.5
7.8
284
132
-
-
-
71
89
0.79
21.6
7.5
259
109
96
0.82
21.3
7.7
267
112
99
0.86
20.5
7.7
269
113
87
0.69
18.7
7.5
256
108
95
0.72
18.4
7.6
264
111
98
0.75
17.7
7.7
267
112
59
63
92
0.70
19.9
7.7
278
116
99
0.73
19.6
7.8
287
119
102
0.77
18.8
7.9
290
120
91
0.58
16.2
7.6
276
114
98
0.60
15.9
7.8
284
118
101
0.63
15.3
7.8
287
119
75
67
99
0.53
16.3
7.9
294
126
107
0.55
16.1
8.1
303
130
111
0.58
15.4
8.1
306
131
99
0.40
12.3
7.8
291
125
108
0.42
12.1
8.0
300
129
111
0.44
11.6
8.1
303
130
106
0.3
11.3
8.1
307
134
115
0.4
11.1
8.3
316
139
119
0.4
10.7
8.4
319
140
-
-
-
71
87
0.81
21.6
7.9
294
113
94
0.84
21.3
8.1
303
116
97
0.88
20.5
8.2
306
118
85
0.71
18.7
7.9
291
112
93
0.74
18.4
8.1
300
115
95
0.77
17.7
8.1
303
116
59
89
0.72
19.9
8.1
317
120
97
0.75
19.6
8.3
326
124
100
0.79
18.9
8.4
330
125
89
0.59
16.2
8.0
313
119
96
0.62
16.0
8.2
323
123
99
0.64
15.3
8.3
326
124
63
97
0.55
16.3
8.3
334
131
105
0.57
16.1
8.5
345
135
108
0.59
15.4
8.6
348
137
97
0.41
12.3
8.3
331
130
105
0.43
12.1
8.5
341
134
108
0.45
11.6
8.5
345
135
67
104
0.4
11.3
8.6
349
140
113
0.4
11.1
8.8
359
144
116
0.4
10.7
8.9
363
145
-
-
-
71
85
0.83
21.8
8.3
335
119
92
0.86
21.4
8.5
345
122
95
0.91
20.6
8.6
349
123
83
0.73
18.8
8.3
332
117
90
0.76
18.6
8.5
342
121
93
0.80
17.8
8.5
345
122
59
67
94
0.56
16.4
8.7
381
138
102
0.58
16.2
9.0
393
142
95
0.77
19.8
8.7
372
130
87
0.75
20.1
8.5
361
126
105
0.61
15.6
9.0
396
143
95
0.42
12.4
8.7
377
136
103
0.44
12.2
8.9
389
141
106
0.46
11.7
9.0
392
142
97
0.81
19.0
8.8
375
131
86
0.61
16.3
8.4
357
125
94
0.63
16.1
8.6
368
129
96
0.67
15.4
8.7
372
130
63
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
101
0.4
11.3
9.0
397
147
110
0.4
11.2
9.2
409
151
113
0.4
10.7
9.3
414
153
-
-
-
71
80
0.86
21.5
8.6
377
124
87
0.90
21.1
8.9
389
128
90
0.94
20.3
8.9
392
129
79
0.76
18.6
8.6
373
123
86
0.79
18.3
8.8
385
127
88
0.83
17.6
8.9
389
128
59
83
0.77
19.8
8.8
406
132
90
0.80
19.5
9.0
418
136
92
0.84
18.7
9.1
422
138
82
0.64
16.1
8.8
402
131
89
0.66
15.8
9.0
414
135
92
0.69
15.2
9.0
418
136
63
67
90
0.59
16.2
9.1
428
144
97
0.61
16.0
9.3
442
149
100
0.64
15.3
9.4
446
150
90
0.44
12.2
9.0
424
143
97
0.46
12.0
9.2
437
147
100
0.48
11.6
9.3
442
149
105
96
0.4
11.2
9.4
447
154
104
0.4
11.0
9.6
461
159
107
0.4
10.6
9.7
465
160
-
-
-
71
75
0.87
20.1
8.9
416
129
81
0.90
19.8
9.1
429
133
83
0.95
19.0
9.2
434
134
73
0.77
17.4
8.9
412
127
79
0.80
17.1
9.1
425
131
82
0.83
16.4
9.1
429
133
59
77
0.78
18.5
9.1
448
137
83
0.81
18.2
9.3
462
141
86
0.85
17.5
9.4
467
142
76
0.64
15.0
9.0
444
135
82
0.66
14.8
9.3
457
140
85
0.70
14.2
9.3
462
141
63
67
83
0.59
15.1
9.4
473
149
90
0.61
14.9
9.6
488
154
93
0.64
14.3
9.7
493
155
83
0.44
11.4
9.3
469
148
90
0.46
11.2
9.5
483
152
93
0.48
10.8
9.6
488
154
115
89
0.4
10.4
9.7
494
159
97
0.4
10.3
9.9
509
164
100
0.4
9.9
10.0
514
166
-
-
-
71
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects ACCA (TVA) Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Subcooling, 10±2 °F @ liquid access fitting; AHRI 95 test conditions. Design Superheat 8±3°F @ compressor suction access fitting.
75
70
IDB
65
Expanded Cooling Data — 8½ Tons
SS-DCG7
SS-DCG7
www.daikincomfort.com
59
103
0.91
22.6
7.3
242
108
100
0.86
23.5
7.2
240
107
93
0.83
23.8
7.1
233
104
105
0.95
24.1
7.3
245
109
102
0.91
25.0
7.3
242
108
94
0.87
25.4
7.1
235
105
Airflow
MBh
S/T
∆T
3820
kW
Hi PR
Lo PR
MBh
S/T
∆T
3400
kW
Hi PR
Lo PR
MBh
S/T
∆T
2980
kW
Hi PR
Lo PR
MBh
S/T
∆T
3820
kW
Hi PR
Lo PR
MBh
S/T
∆T
3400
kW
Hi PR
Lo PR
MBh
S/T
∆T
2980
kW
Hi PR
Lo PR
63
96
0.84
25.0
7.3
253
112
104
0.87
24.6
7.4
261
115
107
0.92
23.7
7.5
264
116
95
0.78
22.8
7.2
251
111
103
0.81
22.5
7.4
258
114
106
0.85
21.6
7.4
261
115
67
101
0.76
23.6
7.5
267
122
109
0.79
23.3
7.6
276
126
112
0.83
22.4
7.7
278
127
101
0.64
19.9
7.4
265
121
110
0.66
19.6
7.6
273
124
113
0.69
18.8
7.6
276
126
71
107
0.6
20.5
7.7
279
130
116
0.64
20.1
7.9
287
134
120
0.7
19.4
7.9
290
135
108
0.5
15.9
7.6
276
128
117
0.49
15.6
7.8
285
132
121
0.5
15.0
7.9
287
134
59
92
0.91
25.7
7.6
264
111
100
0.94
25.3
7.8
272
114
103
0.98
24.4
7.9
275
115
91
0.86
24.1
7.6
261
110
98
0.90
23.8
7.7
269
113
101
0.94
22.8
7.8
272
114
63
94
0.87
25.3
7.8
284
118
102
0.91
24.9
8.0
293
122
105
0.95
24.0
8.0
296
123
93
0.81
23.1
7.7
281
117
100
0.84
22.8
7.9
290
120
103
0.88
21.9
8.0
293
122
IDB: Entering Indoor Dry Bulb Temperature
High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
75
67
98
0.79
23.9
8.0
300
129
107
0.82
23.6
8.2
309
133
110
0.86
22.6
8.3
312
134
99
0.66
20.1
7.9
297
127
107
0.68
19.8
8.1
306
131
110
0.72
19.0
8.2
309
133
71
105
0.6
20.7
8.2
313
137
114
0.66
20.4
8.4
322
141
117
0.7
19.6
8.5
326
143
106
0.5
16.1
8.2
310
136
114
0.51
15.8
8.4
319
140
118
0.5
15.2
8.4
322
141
63
92
0.90
25.3
8.2
323
123
99
0.93
24.9
8.4
333
126
102
0.97
24.0
8.5
336
128
90
0.83
23.1
8.2
320
121
98
0.86
22.8
8.4
330
125
101
0.90
21.9
8.4
333
126
67
96
0.81
23.9
8.5
341
134
104
0.84
23.6
8.7
352
138
107
0.88
22.7
8.7
355
139
96
0.68
20.1
8.4
338
132
105
0.70
19.8
8.6
348
137
108
0.73
19.0
8.7
352
138
71
102
0.7
20.7
8.7
356
142
111
0.68
20.4
8.9
367
147
114
0.7
19.6
9.0
370
148
103
0.5
16.1
8.7
352
141
112
0.52
15.8
8.9
363
145
115
0.5
15.2
8.9
367
147
88
0.96
25.9
8.5
342
121
95
0.99
25.5
8.7
352
125
98
1.00
23.6
8.7
356
126
86
0.91
24.3
8.4
338
120
93
0.95
23.9
8.6
349
124
96
1.00
23.2
8.7
352
125
59
89
0.92
25.5
8.6
368
129
97
0.96
25.1
8.8
379
133
100
1.00
24.0
8.9
383
134
88
0.86
23.3
8.6
364
127
95
0.89
22.9
8.8
375
131
98
0.93
22.1
8.8
379
133
63
94
0.83
24.1
8.9
388
141
101
0.87
23.7
9.1
400
145
105
0.91
22.8
9.2
404
146
94
0.70
20.3
8.8
385
139
100
0.7
20.9
9.2
405
150
108
0.70
20.6
9.4
418
154
112
0.7
19.8
9.5
422
156
101
0.5
16.2
9.1
401
148
109
0.54
15.9
9.3
414
153
102
0.72
20.0
9.0
397
143
71
112
0.6
15.3
9.4
418
154
67
105
0.76
19.2
9.1
400
145
83
0.99
25.6
8.8
385
127
90
1.00
24.4
9.0
396
131
93
1.00
22.4
9.1
400
132
82
0.95
24.0
8.7
381
126
89
0.98
23.6
8.9
393
129
91
1.00
22.0
9.0
396
131
59
85
0.96
25.2
9.0
414
135
92
1.00
24.8
9.2
427
139
95
1.00
22.8
9.2
431
140
84
0.89
23.0
8.9
410
134
91
0.92
22.6
9.1
422
138
93
0.97
21.7
9.2
427
139
63
67
89
0.87
23.8
9.2
437
147
96
0.90
23.4
9.5
451
152
99
0.94
22.5
9.5
455
153
89
0.72
20.0
9.2
433
146
97
0.75
19.7
9.4
446
150
100
0.79
18.9
9.5
451
152
105
71
95
0.7
20.6
9.5
456
157
103
0.73
20.3
9.8
470
162
106
0.8
19.5
9.8
475
163
96
0.5
16.0
9.5
451
155
104
0.56
15.7
9.7
465
160
107
0.6
15.1
9.8
470
162
77
1.00
23.8
9.1
425
131
84
1.00
22.6
9.3
438
135
86
1.00
20.7
9.4
442
137
76
0.96
22.4
9.0
421
130
82
0.99
22.1
9.2
434
134
85
1.00
20.4
9.3
438
135
59
79
0.97
23.5
9.3
457
140
85
1.00
23.1
9.5
471
144
88
1.00
21.1
9.6
476
145
78
0.90
21.5
9.2
453
138
84
0.93
21.1
9.4
467
142
87
1.00
20.8
9.5
471
144
63
67
82
0.87
22.2
9.5
483
152
89
0.91
21.9
9.8
498
157
92
0.95
21.0
9.8
503
159
83
0.73
18.7
9.5
478
151
90
0.76
18.4
9.7
493
155
92
0.79
17.7
9.8
498
157
115
88
0.7
19.2
9.8
504
162
95
0.7
18.9
10.1
519
167
98
0.8
18.2
10.2
524
169
89
0.5
14.9
9.8
499
161
96
0.6
14.7
10.0
514
166
99
0.6
14.1
10.1
519
167
71
Shaded areas reflect AHRI Rating Conditions
AMPS: Unit amps (comp.+ evaporator + condenser fan motors)
Design Subcooling, 10±2 °F @ liquid access fitting; AHRI 95 test conditions. Design Superheat 8±3°F @ compressor suction access fitting.
90
0.93
25.8
8.1
300
115
97
0.96
25.4
8.3
309
119
100
1.00
24.2
8.3
313
120
88
0.89
24.1
8.0
297
114
96
0.92
23.8
8.2
306
118
99
0.96
22.9
8.3
309
119
59
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
Expanded Cooling Data — 8½ Tons (cont.)
11
12
www.daikincomfort.com
110
0.70
20.3
8.2
245
104
102
0.67
22.6
8.0
237
101
116
0.83
22.5
8.3
250
106
112
0.79
23.4
8.2
247
105
104
0.77
26.1
8.1
240
102
MBh
S/T
∆T
2800
kW
Hi PR
Lo PR
MBh
S/T
∆T
kW
Hi PR
Lo PR
MBh
S/T
∆T
kW
Hi PR
Lo PR
MBh
S/T
∆T
2800
kW
Hi PR
Lo PR
3500
3938
3500
3938
MBh
S/T
∆T
kW
Hi PR
Lo PR
59
114
0.73
19.5
8.2
247
105
MBh
S/T
∆T
kW
Hi PR
Lo PR
Airflow
63
107
0.69
24.0
8.2
258
108
116
0.71
21.6
8.4
266
111
119
0.75
20.7
8.4
269
113
106
0.56
19.5
8.1
255
107
114
0.58
17.5
8.3
263
110
118
0.61
16.8
8.4
266
111
67
115
0.52
19.7
8.4
272
118
125
0.54
17.7
8.6
281
122
129
0.56
17.0
8.7
284
123
116
0.39
14.8
8.4
270
117
125
0.40
13.3
8.5
278
120
129
0.42
12.8
8.6
281
122
124
0.3
13.6
8.7
284
126
134
0.3
12.2
8.8
293
130
138
0.4
11.7
8.9
296
131
-
-
-
71
59
101
0.79
26.4
8.6
269
107
110
0.82
23.7
8.8
277
111
113
0.86
22.8
8.8
280
112
99
0.70
22.8
8.5
266
106
108
0.72
20.5
8.7
274
110
111
0.76
19.7
8.8
277
111
63
104
0.71
24.3
8.7
289
114
113
0.74
21.8
8.9
298
118
116
0.77
21.0
9.0
301
119
103
0.58
19.8
8.7
286
113
112
0.61
17.8
8.9
295
117
115
0.63
17.1
8.9
298
118
75
67
113
0.54
19.9
9.0
306
125
122
0.56
17.9
9.2
315
128
126
0.58
17.2
9.3
318
130
113
0.40
15.0
8.9
302
123
122
0.42
13.5
9.1
312
127
126
0.44
12.9
9.2
315
128
121
0.3
13.7
9.2
319
133
131
0.4
12.4
9.5
329
137
135
0.4
11.9
9.5
332
138
-
-
-
71
59
99
0.81
26.4
9.1
306
112
107
0.84
23.7
9.3
315
115
110
0.89
22.8
9.3
318
116
97
0.72
22.9
9.0
303
110
105
0.74
20.5
9.2
312
114
108
0.78
19.7
9.3
315
115
102
0.73
24.3
9.2
329
119
110
0.76
21.9
9.4
339
122
113
0.79
21.0
9.5
343
124
101
0.60
19.8
9.2
326
117
109
0.62
17.8
9.4
336
121
112
0.65
17.1
9.4
339
122
63
110
0.55
19.9
9.5
348
130
119
0.57
17.9
9.7
358
134
123
0.60
17.2
9.8
362
135
110
0.41
15.0
9.4
344
128
119
0.43
13.5
9.6
355
132
123
0.45
13.0
9.7
358
134
67
118
0.4
13.8
9.8
362
138
128
0.4
12.4
10.0
374
142
132
0.4
11.9
10.1
377
144
-
-
-
71
96
0.84
26.6
9.5
348
117
104
0.87
23.9
9.7
359
121
108
0.91
23.0
9.8
363
122
95
0.74
23.0
9.4
345
116
103
0.77
20.7
9.6
355
120
106
0.80
19.9
9.7
359
121
59
67
107
0.57
20.1
9.9
396
136
116
0.59
18.0
10.2
408
140
107
0.78
22.0
9.9
386
128
99
0.75
24.5
9.7
375
125
120
0.62
17.3
10.2
412
142
108
0.43
15.1
9.9
392
135
117
0.44
13.6
10.1
404
139
120
0.47
13.0
10.2
408
140
111
0.82
21.1
9.9
390
130
98
0.62
19.9
9.6
371
123
106
0.64
17.9
9.8
383
127
110
0.67
17.2
9.9
386
128
63
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
115
0.4
13.9
10.2
413
145
125
0.4
12.5
10.5
426
149
129
0.4
12.0
10.5
430
151
-
-
-
71
59
92
0.87
26.2
9.8
392
123
99
0.90
23.6
10.0
404
127
102
0.95
22.6
10.1
408
128
90
0.77
22.7
9.7
388
122
98
0.80
20.4
10.0
400
125
100
0.83
19.6
10.0
404
127
63
94
0.78
24.2
10.0
422
131
102
0.81
21.7
10.2
435
135
105
0.85
20.8
10.3
439
136
93
0.64
19.6
9.9
417
129
101
0.66
17.7
10.2
430
133
104
0.70
16.9
10.2
435
135
67
102
0.59
19.8
10.3
445
143
111
0.61
17.8
10.5
459
147
114
0.64
17.1
10.6
464
148
102
0.44
14.9
10.2
441
141
111
0.46
13.4
10.5
454
146
114
0.48
12.9
10.5
459
147
105
109
0.4
13.7
10.6
464
152
119
0.4
12.3
10.9
479
157
122
0.4
11.8
10.9
484
158
-
-
-
71
85
0.88
24.5
10.1
433
127
92
0.91
22.0
10.4
446
131
95
0.96
21.1
10.4
451
132
83
0.77
21.2
10.0
429
126
90
0.80
19.1
10.3
442
130
93
0.84
18.3
10.4
446
131
59
87
0.79
22.6
10.3
466
135
95
0.82
20.3
10.6
480
139
97
0.86
19.5
10.6
485
141
86
0.65
18.3
10.2
461
134
94
0.67
16.5
10.5
476
138
96
0.70
15.8
10.6
480
139
63
67
95
0.60
18.5
10.6
492
148
102
0.62
16.6
10.9
507
152
105
0.65
15.9
11.0
512
154
95
0.45
13.9
10.6
487
146
103
0.46
12.5
10.8
502
151
106
0.49
12.0
10.9
507
152
115
101
0.4
12.8
11.0
513
157
110
0.4
11.5
11.2
529
162
113
0.4
11.0
11.3
534
164
-
-
-
71
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects ACCA (TVA) Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
75
70
IDB
65
Expanded Cooling Data — 10 Tons
SS-DCG7
SS-DCG7
www.daikincomfort.com
114
0.87
26.2
8.3
250
106
105
0.84
29.1
8.1
242
103
120
0.96
26.8
8.4
255
108
116
0.91
27.9
8.3
252
107
107
0.88
31.0
8.2
244
104
MBh
S/T
∆T
2800
kW
Hi PR
Lo PR
MBh
S/T
∆T
kW
Hi PR
Lo PR
MBh
S/T
∆T
kW
Hi PR
Lo PR
MBh
S/T
∆T
2800
kW
Hi PR
Lo PR
3500
3938
3500
3938
MBh
S/T
∆T
kW
Hi PR
Lo PR
59
118
0.91
25.1
8.3
252
107
MBh
S/T
∆T
kW
Hi PR
Lo PR
Airflow
63
109
0.85
30.5
8.3
263
110
118
0.88
27.4
8.5
271
114
122
0.92
26.3
8.6
274
115
108
0.79
27.9
8.3
261
109
117
0.82
25.1
8.4
269
113
120
0.86
24.1
8.5
271
114
67
115
0.77
28.9
8.5
278
120
124
0.80
25.9
8.7
286
124
128
0.83
24.9
8.8
289
125
115
0.64
24.3
8.5
275
119
125
0.67
21.8
8.7
284
123
128
0.70
20.9
8.7
286
124
71
122
0.6
25.0
8.8
290
128
132
0.65
22.5
9.0
299
132
136
0.7
21.6
9.0
302
133
123
0.5
19.4
8.7
287
127
133
0.50
17.4
8.9
296
131
137
0.5
16.7
9.0
299
132
59
105
0.91
31.4
8.7
274
109
114
0.95
28.2
8.9
283
113
117
0.99
27.1
9.0
286
114
103
0.87
29.5
8.6
272
108
112
0.90
26.5
8.8
280
112
115
0.95
25.4
8.9
283
113
63
107
0.88
30.9
8.9
295
116
116
0.91
27.8
9.1
304
120
119
0.96
26.7
9.1
307
121
105
0.82
28.2
8.8
292
115
114
0.85
25.4
9.0
301
119
117
0.89
24.4
9.1
304
120
75
67
112
0.80
29.2
9.1
312
127
121
0.82
26.3
9.3
321
131
125
0.86
25.2
9.4
325
132
112
0.67
24.5
9.1
309
126
122
0.69
22.1
9.3
318
130
125
0.72
21.2
9.3
321
131
71
119
0.6
25.3
9.4
325
135
129
0.67
22.7
9.6
335
140
133
0.7
21.8
9.7
339
141
120
0.5
19.6
9.3
322
134
130
0.52
17.6
9.5
332
138
134
0.5
16.9
9.6
335
140
59
102
0.94
31.5
9.2
312
114
111
0.97
28.3
9.4
322
117
114
1.00
26.7
9.5
325
118
101
0.89
29.5
9.1
309
113
109
0.93
26.5
9.3
318
116
112
1.00
26.2
9.4
322
117
104
0.90
30.9
9.4
336
121
113
0.94
27.8
9.6
346
125
116
0.98
26.7
9.6
350
126
103
0.84
28.3
9.3
332
120
111
0.87
25.4
9.5
343
124
115
0.91
24.4
9.6
346
125
63
109
0.82
29.2
9.6
355
132
118
0.85
26.3
9.8
366
136
122
0.89
25.2
9.9
369
138
110
0.68
24.6
9.6
351
131
119
0.71
22.1
9.8
362
135
122
0.74
21.2
9.8
366
136
67
116
0.7
25.3
9.9
370
141
126
0.69
22.8
10.1
381
145
130
0.7
21.8
10.2
385
147
117
0.5
19.6
9.8
366
139
127
0.53
17.6
10.1
377
144
131
0.6
16.9
10.1
381
145
71
100
0.97
31.7
9.6
355
120
108
1.00
28.4
9.8
366
123
111
1.00
26.0
9.9
370
124
98
0.92
29.7
9.5
352
118
106
0.96
26.7
9.8
363
122
109
1.00
25.6
9.8
366
123
59
102
0.93
31.2
9.8
382
127
110
0.97
28.0
10.0
394
131
114
1.00
26.5
10.1
398
132
100
0.86
28.5
9.7
379
126
109
0.90
25.6
9.9
390
130
112
0.94
24.6
10.0
394
131
63
107
0.84
29.4
10.1
404
139
115
0.87
26.5
10.3
416
143
119
0.92
25.4
10.4
420
145
107
0.70
24.7
10.0
400
137
114
0.7
25.5
10.4
421
148
123
0.71
22.9
10.6
434
152
127
0.7
22.0
10.7
439
154
114
0.5
19.8
10.3
417
146
124
0.55
17.8
10.5
430
151
116
0.73
22.2
10.2
412
142
71
128
0.6
17.1
10.6
434
152
119
0.77
21.4
10.3
416
143
67
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
59
95
1.00
31.1
10.0
400
125
103
1.00
27.0
10.2
412
129
106
1.00
24.7
10.3
416
130
93
0.96
29.3
9.9
396
124
101
0.99
26.3
10.1
408
128
104
1.00
24.3
10.2
412
129
63
97
0.97
30.7
10.2
430
133
105
1.00
27.5
10.4
444
137
108
1.00
25.2
10.5
448
139
95
0.90
28.1
10.1
426
132
103
0.93
25.2
10.3
439
136
106
1.00
24.8
10.4
444
137
67
101
0.87
29.0
10.5
454
145
110
0.91
26.1
10.7
468
150
113
0.95
25.1
10.8
473
151
102
0.73
24.4
10.4
450
144
110
0.76
21.9
10.6
464
149
114
0.79
21.1
10.7
468
150
105
71
108
0.7
25.1
10.8
474
155
117
0.74
22.6
11.0
489
160
120
0.8
21.7
11.1
493
161
109
0.5
19.5
10.7
469
153
118
0.57
17.5
11.0
484
158
121
0.6
16.8
11.0
489
160
88
1.00
28.8
10.3
442
130
95
1.00
25.0
10.5
455
134
98
1.00
22.9
10.6
460
135
86
0.97
27.3
10.2
437
128
94
1.00
24.6
10.4
451
132
96
1.00
22.5
10.5
455
134
59
90
0.98
28.7
10.5
475
138
97
1.00
25.5
10.7
490
142
100
1.00
23.3
10.8
495
144
88
0.91
26.2
10.4
471
136
96
0.94
23.6
10.6
485
141
98
1.00
23.0
10.7
490
142
63
67
94
0.88
27.1
10.8
502
150
102
0.91
24.4
11.0
517
155
105
0.96
23.4
11.1
523
157
94
0.74
22.8
10.7
497
149
102
0.76
20.5
11.0
512
154
105
0.80
19.7
11.0
517
155
115
71
100
0.7
23.5
11.1
524
160
108
0.7
21.1
11.4
540
165
112
0.8
20.3
11.5
545
167
101
0.6
18.2
11.0
518
159
109
0.6
16.4
11.3
534
164
112
0.6
15.7
11.4
540
165
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects AHRI Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
85
80
IDB
65
Expanded Cooling Data — 10 Tons (cont.)
13
14
www.daikincomfort.com
59
141
0.69
20.4
10.4
252
103
137
0.66
21.3
10.3
249
102
126
0.64
21.8
10.0
242
99
143
0.79
23.6
10.4
254
104
139
0.75
24.7
10.4
252
103
129
0.72
25.2
10.1
244
100
Airflow
MBh
S/T
∆T
4725
kW
Hi PR
Lo PR
MBh
S/T
∆T
4200
kW
Hi PR
Lo PR
MBh
S/T
∆T
3360
kW
Hi PR
Lo PR
MBh
S/T
∆T
4725
kW
Hi PR
Lo PR
MBh
S/T
∆T
4200
kW
Hi PR
Lo PR
MBh
S/T
∆T
3360
kW
Hi PR
Lo PR
63
132
0.65
23.2
10.3
263
107
143
0.67
22.7
10.6
271
110
148
0.70
21.8
10.7
274
111
131
0.53
18.9
10.2
260
106
142
0.55
18.5
10.5
268
109
146
0.58
17.7
10.6
271
110
67
143
0.49
19.0
10.7
277
117
155
0.51
18.6
10.9
286
120
160
0.53
17.8
11.0
289
121
144
0.37
14.3
10.6
275
115
156
0.38
14.0
10.8
283
119
160
0.40
13.4
10.9
286
120
154
0.3
13.1
11.0
289
124
167
0.3
12.9
11.3
298
128
172
0.3
12.3
11.4
301
129
-
-
-
71
59
126
0.75
25.5
10.9
274
106
136
0.78
25.0
11.2
282
109
140
0.82
23.9
11.3
285
110
124
0.66
22.1
10.8
271
105
134
0.69
21.6
11.1
280
108
138
0.72
20.7
11.2
282
109
63
129
0.67
23.5
11.1
295
113
140
0.70
23.0
11.4
304
116
144
0.73
22.0
11.5
307
117
128
0.55
19.1
11.0
292
112
139
0.57
18.7
11.3
301
115
143
0.60
17.9
11.4
304
116
75
67
140
0.51
19.2
11.5
311
123
152
0.53
18.8
11.8
321
127
156
0.55
18.0
11.9
324
128
140
0.38
14.5
11.4
308
122
152
0.40
14.2
11.7
318
126
157
0.42
13.6
11.8
321
127
150
0.3
13.3
11.9
325
131
163
0.3
13.0
12.2
335
135
168
0.4
12.5
12.3
338
137
-
-
-
71
59
123
0.77
25.5
11.6
312
110
133
0.80
25.0
11.9
321
114
137
0.84
23.9
12.0
324
115
121
0.68
22.1
11.5
308
109
131
0.70
21.6
11.8
318
112
135
0.74
20.7
11.9
321
114
126
0.69
23.5
11.8
335
117
137
0.71
23.0
12.1
346
121
141
0.75
22.0
12.2
349
122
125
0.57
19.1
11.7
332
116
135
0.59
18.7
12.0
342
120
139
0.62
17.9
12.1
346
121
63
137
0.52
19.3
12.2
354
128
148
0.54
18.9
12.5
365
132
152
0.57
18.1
12.6
369
133
137
0.39
14.5
12.1
351
127
148
0.41
14.2
12.4
361
131
153
0.43
13.6
12.5
365
132
67
147
0.3
13.3
12.6
369
136
159
0.3
13.0
12.9
381
141
164
0.4
12.5
13.0
385
142
-
-
-
71
120
0.79
25.7
12.2
355
116
130
0.82
25.2
12.5
366
119
133
0.86
24.1
12.6
370
121
118
0.70
22.2
12.1
351
115
127
0.73
21.8
12.4
362
118
131
0.76
20.9
12.5
366
119
59
67
134
0.40
14.6
12.7
399
133
149
0.58
18.2
13.3
420
140
144
0.56
19.0
13.2
416
139
133
0.54
19.4
12.9
403
134
137
0.77
22.2
12.9
398
128
133
0.74
23.2
12.8
394
127
123
0.71
23.7
12.4
382
123
145
0.42
14.3
13.1
412
137
149
0.44
13.7
13.2
416
139
122
0.58
19.2
12.3
378
122
132
0.61
18.9
12.7
390
126
136
0.63
18.0
12.8
394
127
63
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
143
0.3
13.4
13.3
421
143
155
0.4
13.1
13.6
434
148
160
0.4
12.6
13.7
438
149
-
-
-
71
59
114
0.82
25.3
12.7
399
121
123
0.86
24.8
13.0
412
125
127
0.90
23.8
13.1
416
126
112
0.73
21.9
12.6
395
120
121
0.75
21.5
12.9
407
124
125
0.79
20.6
13.0
412
125
63
117
0.74
23.3
13.0
430
129
127
0.77
22.9
13.3
443
133
131
0.80
21.9
13.4
447
134
116
0.61
19.0
12.9
425
128
125
0.63
18.6
13.2
439
132
129
0.66
17.8
13.3
443
133
67
127
0.56
19.1
13.4
454
141
137
0.58
18.7
13.8
468
145
141
0.61
17.9
13.9
472
147
127
0.42
14.4
13.3
449
139
137
0.44
14.1
13.6
463
144
142
0.46
13.5
13.8
468
145
105
136
0.4
13.2
13.9
473
150
147
0.4
12.9
14.2
488
155
152
0.4
12.4
14.3
493
156
-
-
-
71
59
105
0.83
23.7
13.1
441
125
114
0.86
23.2
13.5
455
129
117
0.90
22.2
13.6
459
131
104
0.73
20.5
13.0
437
124
112
0.76
20.1
13.4
450
128
116
0.80
19.2
13.5
455
129
63
108
0.74
21.8
13.4
475
133
117
0.77
21.4
13.8
489
138
121
0.81
20.4
13.9
494
139
107
0.61
17.7
13.3
470
132
116
0.63
17.4
13.7
485
136
120
0.66
16.6
13.8
489
138
67
117
0.56
17.9
13.9
501
146
127
0.58
17.5
14.2
517
150
131
0.61
16.7
14.4
522
152
118
0.42
13.5
13.8
496
144
127
0.44
13.2
14.1
512
149
131
0.46
12.6
14.2
517
150
115
126
0.4
12.3
14.3
523
155
136
0.4
12.1
14.7
539
160
141
0.4
11.6
14.9
544
162
-
-
-
71
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects ACCA Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
75
70
IDB
65
Expanded Cooling Data — 12½ Tons
SS-DCG7
SS-DCG7
www.daikincomfort.com
MBh
S/T
∆T
3360 kW
Hi PR
Lo PR
MBh
S/T
∆T
4200 kW
Hi PR
Lo PR
MBh
S/T
∆T
4725 kW
Hi PR
Lo PR
MBh
S/T
∆T
3360 kW
Hi PR
Lo PR
MBh
S/T
∆T
4200 kW
Hi PR
Lo PR
MBh
S/T
∆T
4725 kW
Hi PR
Lo PR
Airflow
133
0.83
30.0
10.3
249
102
144
0.86
29.4
10.5
257
106
149
0.91
28.1
10.6
259
107
131
0.79
28.1
10.2
247
101
142
0.82
27.5
10.4
254
105
136
0.80
29.5
10.5
268
109
147
0.83
28.9
10.8
276
112
151
0.87
27.7
10.8
279
113
134
0.75
26.9
10.4
265
108
145
0.77
26.4
10.7
274
111
63
149
0.81
25.3
10.8
276
112
59
146
0.86
26.4
10.5
257
106
67
142
0.73
27.9
10.8
283
119
154
0.75
27.3
11.1
292
123
159
0.79
26.1
11.2
295
124
143
0.61
23.4
10.7
280
118
155
0.63
23.0
11.0
289
121
159
0.66
22.0
11.1
292
123
71
152
0.6
24.1
11.2
295
127
164
0.61
23.6
11.5
304
131
169
0.6
22.6
11.5
307
132
153
0.5
18.7
11.1
292
125
165
0.47
18.3
11.4
301
129
170
0.5
17.6
11.5
304
131
59
130
0.86
30.4
11.1
280
108
141
0.90
29.7
11.3
288
112
145
0.94
28.5
11.4
291
113
128
0.82
28.5
11.0
277
107
138
0.85
27.9
11.3
285
110
143
0.90
26.7
11.3
288
112
63
133
0.83
29.9
11.3
301
115
144
0.86
29.3
11.6
310
119
148
0.91
28.0
11.7
313
120
131
0.77
27.3
11.2
298
114
142
0.80
26.7
11.5
307
117
146
0.84
25.6
11.6
310
119
75
67
139
0.75
28.2
11.7
318
126
150
0.78
27.6
12.0
327
130
155
0.82
26.5
12.1
331
131
140
0.63
23.7
11.6
315
124
151
0.65
23.2
11.9
324
128
156
0.68
22.2
12.0
327
130
71
148
0.6
24.4
12.1
331
134
161
0.63
23.9
12.4
342
138
165
0.7
22.9
12.5
345
139
149
0.5
19.0
12.0
328
132
162
0.49
18.6
12.3
338
137
166
0.5
17.8
12.4
342
138
59
127
0.89
30.4
11.8
318
112
138
0.92
29.8
12.1
328
116
142
0.96
28.5
12.2
331
117
125
0.84
28.5
11.7
315
111
135
0.88
27.9
12.0
325
115
139
0.92
26.7
12.1
328
116
129
0.85
29.9
12.0
342
120
140
0.89
29.3
12.3
353
123
144
0.93
28.0
12.4
356
125
128
0.79
27.3
11.9
339
118
138
0.82
26.7
12.2
349
122
142
0.86
25.6
12.3
353
123
63
136
0.77
28.3
12.4
361
131
147
0.80
27.7
12.7
372
135
151
0.84
26.5
12.8
376
136
136
0.64
23.7
12.3
358
129
148
0.67
23.3
12.6
369
133
152
0.70
22.3
12.7
372
135
67
145
0.6
24.5
12.8
377
139
157
0.65
24.0
13.2
388
143
161
0.7
22.9
13.3
392
145
146
0.5
19.0
12.7
373
138
158
0.50
18.6
13.0
385
142
163
0.5
17.8
13.2
388
143
71
124
0.91
30.6
12.4
362
118
134
0.95
30.0
12.7
373
122
138
0.99
28.7
12.8
377
123
122
0.87
28.7
12.3
359
117
132
0.90
28.1
12.6
370
121
136
0.95
26.9
12.7
373
122
59
126
0.88
30.1
12.7
390
126
137
0.91
29.5
13.0
402
130
141
0.96
28.2
13.1
406
131
124
0.82
27.5
12.6
386
124
135
0.85
26.9
12.9
398
128
139
0.89
25.8
13.0
402
130
63
132
0.80
28.5
13.1
411
137
143
0.83
27.9
13.4
424
141
148
0.87
26.7
13.5
428
143
133
0.67
23.9
13.0
407
136
144
0.69
23.4
13.3
420
140
148
0.72
22.4
13.4
424
141
67
Outdoor Ambient Temperature
85
95
Entering Indoor Wet Bulb Temperature
71
141
0.6
24.6
13.5
429
146
153
0.67
24.1
13.9
442
151
157
0.7
23.1
14.0
447
152
142
0.5
19.1
13.4
425
145
154
0.52
18.7
13.7
438
149
159
0.5
17.9
13.9
442
151
59
118
0.95
30.2
12.9
407
124
127
0.98
29.6
13.2
420
128
131
1.00
27.4
13.4
424
129
116
0.90
28.3
12.8
403
123
125
0.94
27.7
13.1
416
126
129
1.00
27.0
13.2
420
128
63
120
0.92
29.7
13.2
438
132
130
0.95
29.1
13.5
452
136
134
1.00
27.8
13.7
456
137
118
0.85
27.1
13.1
434
130
128
0.88
26.6
13.4
447
134
132
0.92
25.4
13.5
452
136
67
126
0.83
28.1
13.6
463
144
136
0.86
27.5
14.0
477
148
140
0.90
26.3
14.1
482
150
126
0.69
23.6
13.5
458
142
137
0.72
23.1
13.9
473
147
141
0.75
22.1
14.0
477
148
105
71
134
0.7
24.3
14.1
483
153
145
0.69
23.8
14.5
498
158
150
0.7
22.8
14.6
503
159
135
0.5
18.8
14.0
478
152
146
0.54
18.5
14.3
493
156
151
0.6
17.7
14.5
498
158
59
109
0.96
28.2
13.4
450
128
118
0.99
27.6
13.7
464
132
122
1.00
25.4
13.8
469
133
107
0.91
26.4
13.2
446
127
116
0.95
25.9
13.6
459
131
120
1.00
25.0
13.7
464
132
63
111
0.92
27.7
13.7
484
136
120
0.96
27.2
14.0
499
140
124
1.00
25.9
14.1
504
142
109
0.86
25.3
13.5
480
135
119
0.89
24.8
13.9
494
139
122
0.93
23.7
14.0
499
140
67
116
0.83
26.2
14.1
511
149
126
0.86
25.7
14.5
527
153
130
0.91
24.6
14.6
533
155
117
0.70
22.0
14.0
506
147
127
0.72
21.6
14.4
522
152
131
0.76
20.7
14.5
527
153
115
71
124
0.7
22.7
14.6
533
158
135
0.7
22.2
15.0
550
163
139
0.7
21.3
15.1
555
165
125
0.5
17.6
14.5
528
157
135
0.5
17.2
14.9
545
162
140
0.6
16.5
15.0
550
163
IDB: Entering Indoor Dry Bulb Temperature
Shaded area reflects AHRI Rating Conditions
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
High and low pressures are measured at the liquid and suction access fittings.
Design Superheat 7±2 °F, Design Subcooling 12 ±2 °F pressures measured @ the suction and liquid service ports, AHRI 95 test conditions
85
80
IDB
65
Expanded Cooling Data — 12½ Tons (cont.)
15
Airflow Data — 7½ Tons
Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Down Shot
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
---
---
BHP
0.1
---
---
---
---
0.3
---
---
---
---
---
---
0.5
---
---
---
3387
844
1.32
0.7
3453
893
1.5
2903
850
1.12
0.9
2957
899
1.29
---
---
---
2
CFM RPM
---
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
3522
1.14
3228
706
0.94
2964
661
0.73
---
---
750
3337
800
1.19
3102
756
1
2800
706
0.76
2504
661
0.59
2834
806
0.99
2603
757
0.8
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive — Down Shot
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.7
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
3575
904
1.66
0.9
---
---
---
---
---
---
---
---
---
---
---
---
3258
925
1.56
3113
909
1.41
1.1
---
---
---
---
---
---
---
---
---
3580
1013
1.97
3001
948
1.42
2722
915
1.25
1.3
---
---
---
---
---
---
3616
1063
2.17
3247
1019
1.79
2646
959
1.3
---
---
---
1.5
---
---
---
---
---
---
3275
1069
2.05
2803
1025
1.68
---
---
---
---
---
---
1.7
---
---
---
3346
1118
2.24
2885
1074
1.97
---
---
---
---
---
---
---
---
---
1.9
---
---
---
3009
1125
2.05
---
---
---
---
---
---
---
---
---
---
---
---
2.1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.1
---
---
---
---
---
---
---
---
---
---
---
---
3381
703
0.99
3078
659
0.78
0.3
---
---
---
---
---
---
3560
796
1.26
3271
747
1.02
2946
703
0.82
2604
659
0.63
0.5
---
---
---
3492
841
1.36
3159
799
1.09
2819
752
0.86
---
---
---
---
---
---
0.7
3453
891
1.5
3094
846
1.18
---
---
---
---
---
---
---
---
---
---
---
---
0.9
2964
896
1.29
2524
852
0.96
---
---
---
---
---
---
---
---
---
---
---
---
1.1
2537
902
1.08
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive — Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.7
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
3567
903
1.58
0.9
---
---
---
---
---
---
---
---
---
---
---
---
3596
953
1.79
3145
906
1.39
1.1
---
---
---
---
---
---
---
---
---
3630
1007
1.97
3168
963
1.56
2675
909
1.18
1.3
---
---
---
---
---
---
3649
1063
2.19
3255
1021
1.8
2724
965
1.35
---
---
---
1.5
---
---
---
---
---
---
3316
1068
2.0
2823
1058
1.61
---
---
---
---
---
---
1.7
---
---
---
3287
1112
2.16
2869
1074
1.78
---
---
---
---
---
---
---
---
---
1.9
---
---
---
2970
1122
2.0
---
---
---
---
---
---
---
---
---
---
---
---
2.1
---
---
---
2644
1133
1.92
---
---
---
---
---
---
---
---
---
---
---
---
Notes
• Assume dry coil with filter in place; CFM correction for wet coil = 3%
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that
• exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
16
www.daikincomfort.com
SS-DCG7
Airflow Data — 8½ Tons
Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Down Shot
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
0.1
---
---
---
---
---
---
---
---
---
3372
747
1.11
3078
703
0.91
2814
658
0.3
---
---
---
---
---
---
3187
797
1.16
2952
753
0.97
2650
703
0.73
---
---
---
0.5
---
---
---
3237
841
1.29
2684
803
0.96
2453
754
0.77
---
---
---
---
---
---
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
0.70
0.7
3303
890
1.47
2753
847
1.09
---
---
---
---
---
---
---
---
---
---
---
---
0.9
2807
896
1.26
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive -- Down Shot
ESP
(“ W.C.)
0.7
Turns Open
0
CFM RPM
---
---
BHP
---
1
CFM RPM
---
---
BHP
---
2
CFM RPM
---
---
BHP
---
3
CFM RPM
---
---
BHP
---
4
CFM RPM
---
BHP
---
---
5
CFM RPM
BHP
3425
1.63
901
0.9
---
---
---
---
---
---
---
---
---
---
---
---
3108
922
1.53
2963
906
1.38
1.1
---
---
---
---
---
---
---
---
---
3430
1010
1.94
2851
945
1.39
2572
912
1.22
1.3
---
---
---
---
---
---
3466
1060
2.14
3097
1016
1.76
2496
956
1.27
---
---
---
1.5
---
---
---
---
---
---
3125
1066
2.02
2653
1022
1.65
---
---
---
---
---
---
1.7
---
---
---
3196
1115
2.21
2735
1071
1.94
---
---
---
---
---
---
---
---
---
1.9
3251
1160
2.36
2859
1122
2.02
---
---
---
---
---
---
---
---
---
---
---
---
2.1
2914
1167
2.17
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Standard Belt Drive & Two-Speed Standard Belt Drive at High Speed — Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.75
0.1
---
---
---
---
---
---
---
---
---
---
---
---
3231
700
0.96
2928
656
0.3
---
---
---
---
---
---
3410
793
1.23
3121
744
0.99
2796
700
0.79
---
---
---
0.5
---
---
---
3342
838
1.33
3009
796
1.06
2669
749
0.83
---
---
---
---
---
---
0.7
3303
888
1.47
2944
843
1.15
---
---
---
---
---
---
---
---
---
---
---
---
0.9
2814
893
1.26
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive -- Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.7
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
3417
900
1.55
0.9
---
---
---
---
---
---
---
---
---
---
---
---
3446
950
1.76
2995
903
1.36
1.1
---
---
---
---
---
---
---
---
---
3480
1004
1.94
3018
960
1.53
2525
906
1.15
1.3
---
---
---
---
---
---
3499
1060
2.16
3105
1018
1.77
2574
962
1.32
---
---
---
1.5
---
---
---
---
---
---
3166
1065
1.97
2673
1055
1.58
---
---
---
---
---
---
1.7
---
---
---
3137
1109
2.13
2719
1071
1.75
---
---
---
---
---
---
---
---
---
1.9
3107
1154
2.28
2820
1119
1.97
---
---
---
---
---
---
---
---
---
---
---
---
2.1
2790
1164
2.12
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Notes
• Assume dry coil with filter in place; CFM correction for wet coil = 3%
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that
• exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
SS-DCG7
www.daikincomfort.com
17
Airflow Data — 10 Tons
Standard & Two-Speed Belt-Drive at High Speed — Down Shot
ESP
(“ W.C.)
0.2
Turns Open
0
CFM RPM
---
---
BHP
---
1
CFM RPM
---
---
BHP
---
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
4316
1.57
4118
738
1.36
3771
1.08
3376
0.85
780
687
644
0.4
---
---
---
4282
830
1.76
3928
786
1.4
3595
740
1.13
---
---
---
---
---
---
0.6
4232
874
1.87
3872
830
1.52
3444
786
1.2
---
---
---
---
---
---
---
---
---
0.8
3839
880
1.64
3367
836
1.27
---
---
---
---
---
---
---
---
---
---
---
---
1
3326
885
1.4
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1.2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1.4
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt-Drive — Down Shot
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.8
---
---
---
---
---
---
---
---
---
---
---
---
4188
943
2.11
3793
889
1.67
1
---
---
---
---
---
---
---
---
---
4305
1002
2.39
3836
946
1.89
3416
893
1.45
1.2
---
---
---
---
---
---
4324
1053
2.63
3879
1003
2.11
3425
951
1.63
---
---
---
1.4
---
---
---
4428
1109
2.92
3973
1056
2.35
3434
1009
1.8
---
---
---
---
---
---
1.6
4465
1160
3.2
4088
1113
2.67
3506
1068
2.1
---
---
---
---
---
---
---
---
---
1.8
4129
1168
2.9
3625
1122
2.3
---
---
---
---
---
---
---
---
---
---
---
---
2
3694
1175
2.65
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Standard & Two-Speed Belt-Drive at High Speed — Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.2
---
---
---
---
---
---
---
---
---
4391
737
1.48
4054
693
1.22
3760
645
0.97
0.4
---
---
---
---
---
---
4314
781
1.61
3969
737
1.29
3534
693
1
---
---
---
0.6
---
---
---
4255
826
1.69
3894
781
1.38
3447
743
1.09
---
---
---
---
---
---
0.8
4234
876
1.85
3792
832
1.47
---
---
---
---
---
---
---
---
---
---
---
---
1
3724
877
1.59
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1.2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1.4
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt-Drive — Horizontal
ESP
(“ W.C.)
Turns Open
0
CFM RPM
BHP
1
CFM RPM
BHP
2
CFM RPM
BHP
3
CFM RPM
BHP
4
CFM RPM
BHP
5
CFM RPM
BHP
0.8
---
---
---
---
---
---
---
---
---
---
---
---
4408
885
2.02
1
---
---
---
---
---
---
---
---
---
4464
940
2.29
3929
891
1.76
1.46
1.2
1.4
1.6
DO NOT
OPERATE
---
---
---
---
---
---
4585
996
2.58
4026
946
2
3436
897
---
---
---
4697
1049
2.92
4141
1001
2.26
3509
951
1.7
---
---
---
---
---
---
4264
1056
2.58
3663
1007
1.96
---
---
---
---
---
---
1.8
4359
1105
2.85
3785
1061
2.22
---
---
---
---
---
---
---
---
---
2
3907
1114
2.49
---
---
---
---
---
---
---
---
---
---
---
---
Notes
• Assume dry coil with filter in place; CFM correction for wet coil = 3%
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that
• exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
18
www.daikincomfort.com
SS-DCG7
Airflow Data — 12½ Tons
Standard Belt Drive and 2 Speed Belt Drive at High Speed — Down Shot
ESP
(“ W.C.)
0.2
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
5514
2.92
5604
3.22
5064
2.16
4775
1.81
4514
1.49
4271
1.23
0.4
5279
2.74
5110
2.40
4696
1.94
4447
1.63
4123
1.31
---
---
0.6
5185
2.67
4813
2.20
4352
1.74
4039
1.43
---
---
---
---
0.8
4766
2.37
4526
2.02
---
---
---
---
---
---
---
---
1.0
4223
2.01
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive — Down Shot
ESP
(“ W.C.)
0.6
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
---
---
---
---
---
---
---
---
5515
3.21
5124
2.68
0.8
---
---
---
---
5840
4.06
5781
3.73
5344
3.07
4721
2.37
1.0
---
---
5908
4.49
5643
3.86
5369
3.36
4887
2.71
4365
2.13
1.2
5869
4.74
5542
4.11
5229
3.47
4853
2.92
4404
2.35
3986
1.88
1.4
5464
4.30
5180
3.75
4917
3.19
4584
2.71
4197
2.21
---
---
1.6
5229
4.05
4960
3.53
4397
2.75
4204
2.41
---
---
---
---
1.8
4961
3.78
4553
3.16
---
---
---
---
---
---
---
---
2.0
4790
3.61
4315
2.95
---
---
---
---
---
---
---
---
Standard Belt Drive and 2 Speed Belt Drive at High Speed — Horizontal
ESP
(“ W.C.)
0.2
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
5762
3.08
5485
2.63
5140
2.21
4855
1.84
4513
1.48
4197
1.20
0.4
5550
2.91
5207
2.44
4857
2.03
4489
1.64
4100
1.29
---
---
0.6
5202
2.65
4922
2.25
4487
1.81
4113
1.45
---
---
---
---
0.8
4898
2.43
4515
1.99
4074
1.58
---
---
---
---
---
---
1.0
4549
2.20
4135
1.76
---
---
---
---
---
---
---
---
1.2
4258
2.01
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive — Horizontal
ESP
(“ W.C.)
0.6
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
---
---
---
---
---
---
5967
3.92
5451
3.16
5275
2.77
0.8
---
---
---
---
---
---
5628
3.61
5223
2.97
4959
2.54
1.0
---
---
---
---
5840
4.10
5385
3.39
4999
2.80
4635
2.31
1.2
---
---
---
---
5643
3.90
5003
3.06
4803
2.65
4160
1.99
1.4
6007
4.93
5740
4.32
5229
3.51
4576
2.71
4440
2.38
---
---
1.6
5752
4.64
5401
3.97
4917
3.23
---
---
---
---
---
---
1.8
5380
4.24
5033
3.61
4397
2.79
---
---
---
---
---
---
2.0
5065
3.91
4573
3.18
---
---
---
---
---
---
---
---
Notes
• Assume dry coil with filter in place; CFM correction for wet coil = 3%
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application
• that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
Airflow Pressure Drop of Downflow Economizer for 7.5 to 12.5 Ton Rooftop Units (100% Return Air)
SCFM
2000
2500
3000
3500
4000
4500
5000
5500
in. WG
0.02
0.04
0.06
0.09
0.13
0.18
0.23
0.29
SS-DCG7
www.daikincomfort.com
19
20
www.daikincomfort.com
50.239
53.686
FRONT VIEW
99.980
COMBINATION
AIR INLET
(GAS UNIT)
DC*090-150***
4.475
23.286
7.5 THRU 12.5 TON COMMERCIAL
GAS LINE ENTRANCE
FLUE / VENT OUTLET
ALL DIMENSIONS GIVEN ARE IN INCHES
ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
6.192
TOP VIEW
6.150
13.875
"A"
7.251
19.688
DISCONNECT SWITCH
42.875
RIGHT END VIEW
23.930
12.625
28.312
61.730
"B"
20.055
20.055
20.055
18.055
"A"
53.339
53.339
53.339
58.839
"B"
38.884
LIFTING SHACKLE HOLES
BOTH SIDES AND ENDS
6.152
36.375
RETURN AIR SUPPLY
CONDENSATE DRAIN OUTLET
SUPPLY AIR DUCT
MODEL TONNAGE
7.5 TON COMMERCIAL
GAS, HT PUMP, AIR CONDITIONER
8.5 TON COMMERCIAL
GAS, HT PUMP, AIR CONDITIONER
10 TON COMMERCIAL
GAS, HT PUMP, AIR CONDITIONER
12.5 TON COMMERCIAL
GAS, HT PUMP, AIR CONDITIONER
Dimensions
SS-DCG7
Unit Clearances
Maintain an adequate clearance around the unit for safety, service,
maintenance, and proper unit operation. Leave a total clearance of 75”
on the main control panel side of the unit for possible removal
of fan shaft, coil, electric heat, and gas furnace. Leave a
clearance of 48” on all other sides of the unit for possible
compressor removal or service access, and to ensure
proper ventilation and condenser airflow. Do not
48”
install the unit beneath any obstruction.
Install the unit away from all building
exhausts to inhibit ingestion of exhaust air
into the unit’s fresh-air intake.
48”
36” Min.
75”
48”
Electrical Entrance Locations
3 7¾”
3/4”
Dimples Mark
Drill Locations
DIMPLES
MARK
DRILL LOCATIONS
High-Voltage
Entrance
HIGH
VOLTAGE
ENTRANCE
3
10103/16”
/16”
LOW
VOLTAGE
ENTRANCE
Low-Voltage
Entrance
26
½”
28½”
Power and Low-Voltage Block Locations
SS-DCG7
www.daikincomfort.com
21
Roof Curb Installation — Rigging
Provisions for forks have been included in the unit base frame. No other
fork locations are approved.
• Unit must be lifted by the four lifting holes located at the base frame corners.
• Lifting cables should be attached to the unit with shackles.
• The distance between the crane hook and the top of the unit must
not be less than 60”.
• Two spreader bars must span over the unit to prevent damage to the
cabinet by the lift cables. Spreader bars must be of sufficient length
so that cables do not come in contact with the unit during transport.
Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base
frame from fork lift damage. To remove the struts, extract the sheet
metal retainers and pull the struts through the base of the unit. Refer
to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work should be
attached to the curb prior to installing the unit. Duct-work dimensions
are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the National
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
A
While rigging the unit, the center of gravity
will cause the condenser end to be lower than
the supply air end.
Y
30”
Bring condenser end of unit into alignment
with the curb. With condenser end of the
unit resting on curb member and using curb
COMPRESSOR
Compressor 1 1
as a fulcrum, lower opposite end of the unit
until entire unit is seated on the curb. When a
COMPRESSOR
Compressor 2 2
rectangular cantilever curb is used, take care
to center the unit. Check for proper alignment
and orientation of supply and return openings
with duct.
B
C
RETURN
Return
Evaporator Coil
EVAPORATOR
COIL
CG
X
49”
Supply
SUPPLY
D
Corner & Center-of-Gravity Locations
Rigging Weights
7½-Ton
Weights (lbs)
8½-Ton & 10-Ton
Weights (lbs)
12½-Ton
Weights (lbs)
Weight A
Weight B
Weight C
Weight D
269
297
254
280
255
321
250
314
315
370
290
340
Shipping Weight
Operating Weight
1175
1100
1215
1140
1390
1365
Weight Types
To assist in determining rigging requirements, unit weights are shown to the right.
Note: These weights are calculated without accessories installed.
22
www.daikincomfort.com
SS-DCG7
Roof Curb Installation
3-D View
92¼
15⅜ x 31⅛
Supply Opening
14⅝ x 38⅜
Return Opening
Curb installations must comply with local codes and should follow the
established guidelines of the National Roofing Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently
attached to the roof structure. Check for adequate fastening method prior to
setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped
unassembled. The installing contractor is responsible for field assembly,
squaring, leveling, and mounting on the roof structure. All required hardware
necessary for the assembly of the sheet metal curb is included in the curb
accessory package.
• Determine sufficient structural support before locating and mounting the
curb and package unit.
• Duct-work must be constructed using industry guidelines. The duct-work
must be placed into the roof curb before mounting the package unit. Our
full perimeter curbs include duct connection frames to be assembled with
the curb. Cantilevered-type curbs are not available from the factory.
• Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.
• Support curbs on parallel sides with roof members.
To prevent damage to the unit, the roof members
cannot penetrate supply and return duct openings.
53¼
Note: The unit and curb accessories are designed to allow
vertical duct installation before unit placement. Duct
installation after unit placement is not recommended.
See the manual shipped with the roof curb for assembly
14
and installation instructions.
¾
1⅝
14
1⅜
Top View
SS-DCG7
www.daikincomfort.com
23
CM1
CM2
www.daikincomfort.com
GR
L1
OR
BK
RD
RD
BK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
BC
C
L2
L1
L2
L3
C
YL
LPS 2
LPS1
⚠ Warning
GR
BK
RD
OR
YL
TR
BL
BL
BL
YL
1
4
1
2 3
22
S1
YL
RD
S2
RD
PK
PU
BL
PK
RD
CCR 2
4
2 3
22
CCR1
POWER SUPPLY
208-240/3/60
SEE NOTE 4
PK
BL
C
BL
PK
GR
G
GR
GR
W1
WH
WH
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
RD
BR RD BL
RD
BL
YL YL
W2
BR
Y1
Y2
BL
BR
BL
O
PU
YL
YL
⚡
YL
1
2
3
PU
BL
WH WH
4
5
7
6
9
YL
ECON
RS
ALS
PU
PLF 8
RD
GR
BL
RD
RD
BL
PU
RD
SEE NOTE 2
PU
BL
BL
RD
BL
BL
GR
WH
RD
YL
RD
SEE NOTE 5
YL
BL
RD
RD
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
GR
HPS 2
HPS1
GND
208
240
GR
PB
BL
WH
PS
RD
UNUSED HEAT COOL
T1
T2
T3
T1
T2
OR
YL
BK
BK
BK
RD
RD
OR
OR
BL
PK
WH
LS
RD
PU
PU
GR
RD
YL
BR
YL
YL
BK
0140L03028-A
GV
YL
IGN OR
FS
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
12
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
BL
L3
CC2
L1
RD
OR
OR
SEE NOTE 6
RD
VMR
BL
L2
RD
BK
BK
RD
T3
BL
BL
T1
RD
OR
RD
RD
1
3
L1
CC1
L2
BL
OR
OR
WH
DI
YL
RD
C
L3
BK
FC2
PU
BK
FS
T2
T3
C
F
PU
FC1
6
OR
RD
RD
BL
BK
BR
C
F
3
BK
YL
BK
BK
RD
BR
VM
2
EM
BK
BR
PU
BK
BR
RD
9
1
COMP1
8
5
COMP 2
11
7
4
T1 T2 T3
10
T1 T2 T3
24V
24
C
PU
Wiring Diagram — DCG 7½ – 12½ Tons (230V, Three-Phase Belt Drive)
SS-DCG7
Wiring Diagram — DCG 7½ – 12½ Tons (230V, Three-Phase Belt Drive)
T3
CC1
T3
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
T1
COMP2
CC2
T2
T2
T1
T3
T3
CC2
BC
BC
BC
EM
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLACK
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
⚡
T1
L3
L2
CC1
T2
COMP1 T2
CC1
YL /PK YELLOW WITH
PINK STRIP
4
VM
2
BL /PK BLUE WITH
PINK STRIP
VMR
SEE NOTE 6
C
TR
L1
NOTE 3
1
F
NOTE 3
24V
HC
IGN
FS
FS
H C
L2
NOTES
BC
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
4
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
LS
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
CC2
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
CCR2
6
9
PS
ECON
2
8
7
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
SUPPLY VOLTAGE
208-240/3/60
L1
NOTE 2
S1
S2
TO THERMOSTAT
O
R
++
W2 W1
Y2
Y1
G
C
PLF
9
6
3
8
5
2
7
4
1
TB1
NOTE 5
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
NORMAL OPERATION
------
OFF
NO POWER OR
INTERNAL CONTROL
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
C
W2
STAT
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
EQUIPMENT STATUS
ON
IGNITION FAILURE
W1
GR
CHECK
STATUS LIGHT
OPEN ROLLOUT
SWITCH
WH
G
TB1
INSTALLER/SERVICEMAN
1 BLINK
W1
⚠ Warning
2 STAGE COOLING
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
208-240/3/60 0140L02572-A
SS-DCG7
www.daikincomfort.com
25
CM1
CM2
BK
www.daikincomfort.com
T1
BK
GR
L1
BK
RD
OR
BK
RD
BK
RD
OR
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
C
L2
L1
L2
L3
C
OR
⚠ Warning
GR
YL
LPS 2
LPS1
YL
46O OR
APPROPRIATE
INPUT
GR
VOLTAGE
GR
BL
BL
BL
YL
1
4
1
2 3
22
S1
YL
S2
RD
PK
PU
RD
BL
PK
RD
CCR 2
4
2 3
22
CCR1
BL
C
G
GR
GR
PK
W1
WH
WH
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
BL
BR RD BL
RD
BL
W2
BR
Y1
Y2
O
⚡
YL
7
1
2
3
PU
BL
WH WH
4
5
YL
ECON
RS
ALS
PU
6
PLF
GR
YL
9
RD
BL
BL
BL
BL
RD
RD
BL
PU
RD
SEE NOTE 2 8
PU
BL
RD
GR
PU
YL
SEE NOTE 5
YL
BL
BR
WH
RD
YL
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
HPS 2
HPS1
GND
BK
BK
POWER SUPPLY
460-575/3/60
SEE NOTE 4
PK
YL YL
RD
UNUSED HEAT COOL
BC
T2
T3
T1
T2
RD
BL
L3
CC2
BK
YL
BK
RD
C
RD
RD
OR
OR
PB
BL
WH
PS
RD
RD
L2
OR
BK
RD
T3
BL
BL
CC1
L1
L2
BL
OR
PK
SEE NOTE 6
RD
L1
YL
RD
C
OR
OR
OR
BK
WH
LS
DI
T1
L3
RD
460
OR APPROPRIATE
INPUT VOLTAGE
240
RD
1
BL
FS
T2
BL
FC2
BK
RD
3
BK
RD
PU
PU
GR
FS
BR
YL
YL
BK
0140L03029-A
GV
YL
IGN OR
RD
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
12
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
RD
T3
BK
C
F
PU
BK
WH
VMR
6
RD
BL
BK
BR
C
FC1
3
BK
YL
BK
BK
RD
F
2
EM
PU
BR
BK
BR
VM
9
1
COMP1
8
5
COMP 2
11
7
4
T1 T2 T3
10
T1 T2 T3
RD
TR
26
24V
PU
Wiring Diagram — DCG 7½ – 12½ Tons (460V/ 575V, Three-Phase Belt Drive)
SS-DCG7
Wiring Diagram — DCG 7½ – 12½ Tons (460V/ 575V, Three-Phase Belt Drive)
T3
CC1
T3
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
T1
COMP2
CC2
T2
T2
T1
T3
T3
CC2
BC
BC
BC
EM
4
VM
2
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLACK
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
BL /PK BLUE WITH
PINK STRIP
460V OR
APPROPRIATE
INPUTVOLTAGE
SEE NOTE 6
LINE VOLTAGE
LOW VOLTAGE
YL /PK YELLOW WITH
PINK STRIP
VMR
C
FACTORY WIRING
⚡
T1
L3
L2
CC1
T2
COMP1 T2
CC1
C
TR
L1
NOTE 3
HC
1
F
NOTE 3
24V
IGN
FS
FS
H C
L2
NOTES
BC
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
4
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
LS
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
CC2
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
CCR2
6
9
PS
ECON
2
8
7
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
SUPPLY VOLTAGE
460-575/3/60
L1
NOTE 2
O
S2
TO THERMOSTAT
++
R
W2 W1
Y2
Y1
G
C
PLF
6
3
8
5
2
7
4
1
TB1
NOTE 5
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
EQUIPMENT STATUS
ON
NORMAL OPERATION
OFF
NO POWER OR
INTERNAL CONTROL
------
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
IGNITION FAILURE
OPEN ROLLOUT
SWITCH
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
400V/50Hz
SS-DCG7
W1
GR
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
C
W2
STAT
CHECK
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
1 BLINK
WH
G
TB1
INSTALLER/SERVICEMAN
STATUS LIGHT
W1
www.daikincomfort.com
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
S1
9
⚠ Warning
2 STAGE COOLING
0140L02570-A
27
28
BK
BK
CM2
T3 T2 T1
T3 T2 T1
COMP1
COMP 2
www.daikincomfort.com
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
YL
BL
GY
BC 2
T1
T2
T3
L1
L2
L3
GR
L1
C
C
L1
OR
OR
GR
BK
RD
BK
RD
RD
BK
BK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
YL
BL
GY
BL
BC 1
T1
L2
L3
C
L2
BL
YL
3
1
3
1
NC
NO
5
2
4
BR2
4
BR1
NC
NO
5
2
LPS1
GR
GR
LPS 2
YL
⚠ Warning
YL
GR
BK
RD
YL
GR
208
240
BL
BL
BL
YL
YL
4
1
22
2 3
S1
PK
BL
RD
S2
RD
PK
PU
BL
C
BL
BL
G
GR
GR
W1
WH
WH WH
PK
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
RD
BR RD
BL
W2
BR
Y1
Y2
PU
O
PU
SEE NOTE 5
YL
YL
BL
YL
PU
BL
BL
GR
YL
8
⚡
YL
3
1
2
BL
WH WH
4
5
6
PU
RS
ALS
PU
9
GR
BL
RD
PLF 7
WH
RD
BL
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
PU
WH
HPS1
HPS 2
BL
1
RD
CCR 2
4
YL
BL
BL
YL
RD
PU
PU
GR
RD
YL
BR
YL
YL
BK
0140L03758-A
SEE NOTE 2
GV
YL
GR
IGN OR
FS
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
12
OR
WH
BL
HIGH
EM
LOW
BK
T2
T3
T1
T2
OR
OR
TR
GND
2 3
22
BL
BR
WH
ECON
UNUSED HEAT COOL
BK
RD
OR
BL
BL
L3
CC2
YL
BK
CCR1
WH
RD
YL
RD
BL
PU
L2
RD
BK
RD
BK
T3
BL
BL
CC1
BK
BK
RD
BL
RD
RD
DI
YL
RD
RD
POWER SUPPLY
208-240/3/60
SEE NOTE 4
PK
YL YL
RD
L1
L1
RD
PB
BL
BL
WH
RD
RD
FS
L2
RD
RD
OR
OR
BL
PK
PS
RD
6
T1
C
OR
OR
OR
SEE NOTE 6
RD
VMR
WH
LS
3
L3
BL
RD
RD
BL
2
T2
T3
BK
FC2
OR
1
3
9
1
OR
RD
RD
C
F
PU
OR
WH
BK
8
5
BL
BK
BR
C
FC1
11
7
4
BK
YL
BK
BK
RD
F
VM
10
BK
BR
PU
BK
BR
RD
24V
CM1
C
PU
Wiring Diagram — DCG 7½-8½ Tons (230V, Two-Speed, Three-Phase Belt Drive)
SS-DCG7
Wiring Diagram — DCG 7½-8½ Tons (230V, Two-Speed, Three-Phase Belt Drive)
CC1
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
BC2
T1
COMP2
CC2
T2
T2
T1
T3
T3
LOW SPEED
CC2
BC2
BC1
BC2
EM
HIGH SPEED
BC1
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK BLACK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YL /PK YELLOW WITH
PINK STRIP
BC1
4
VM
FACTORY WIRING
⚡
T3
T3
2
BL /PK BLUE WITH
PINK STRIP
VMR
SEE NOTE 6
C
TR
L1
HC
1
F
NOTE 3
24V
NOTE 3
IGN
FS
FS
H C
BR1
4
2
BC1
5
BC2
BR1
4
BR2
LS
5
IIC
L2
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
2
4
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
N OTES
CC2
CCR2
6
9
PS
ECON
8
7
2
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
2 STAGE COOLING
S1
S2
TO THERMOSTAT
O
++
R
W2 W1
Y2
Y1
G
C
PLF
9
6
3
8
5
2
7
4
1
NOTE 2
TB1
NOTE 5
W1
WH
W1
G
GR
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
TB1
INSTALLER/SERVICEMAN
C
W2
STAT
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
T1
L3
L2
CC1
T2
COMP1 T2
CC1
⚠ Warning
SUPPLY VOLTAGE
208-240/3/60
L1
CHECK
STATUS LIGHT
EQUIPMENT STATUS
ON
NORMAL OPERATION
------
OFF
NO POWER OR
INTERNAL CONTROL
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
IGNITION FAILURE
1 BLINK
OPEN ROLLOUT
SWITCH
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
208-240/3/60 0140L03759-A
SS-DCG7
www.daikincomfort.com
29
BK
BK
CM2
T3 T2 T1
T3 T2 T1
COMP1
COMP 2
www.daikincomfort.com
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
YL
BL
GY
BC 2
T1
T2
T3
C
L1
L2
L3
GR
L1
OR
OR
GR
BK
RD
BK
RD
RD
BK
BK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
YL
BL
GY
BL
BC 1
T1
C
L2
L3
L1
OR
BL
YL
3
1
3
1
NC
NO
5
2
4
BR2
4
BR1
NC
NO
5
2
GR
GR
LPS 2
LPS1
⚠ Warning
YL
GR
BK
RD
OR
VOLTAGE
BL
BL
BL
YL
YL
4
1
2 3
22
S1
PK
BL
RD
S2
RD
PK
PU
BL
C
BL
BL
G
GR
GR
WH
W1
WH
WH
PK
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
RD
BR
RD
BL
W2
BR
Y1
Y2
PU
O
PU
SEE NOTE 5
YL
YL
BL
YL
PU
BL
BL
GR
BL
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
YL
PU
WH
GR
HPS 2
HPS1
BL
1
RD
CCR 2
4
YL
BL
BR
WH
YL
9
8
⚡
YL
3
1
2
BL
WH WH
4
5
6
PU
RS
ALS
PU
GR
BL
RD
PLF 7
WH
RD
BL
BL
YL
RD
PU
FS
GV
YL
GR
IGN OR
RD
YL
BR
YL
YL
BK
0140L03760-A
SEE NOTE 2
PU
GR
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
12
OR
WH
BL
HIGH
EM
LOW
BK
T2
T3
T1
C
L2
L3
YL
46O OR
APPROPRIATE
INPUT
GND
22
2 3
CCR1
WH
ECON
UNUSED HEAT COOL
BK
RD
OR
BL
BL
T3
T2
CC2
YL
BK
BK
RD
RD
YL
RD
BL
PU
L2
RD
BK
BK
RD
BL
BL
RD
POWER SUPPLY
460-575/3/60
SEE NOTE 4
BL
RD
RD
DI
CC1
BK
C
RD
RD
OR
OR
PB
BL
PK
YL YL
RD
L1
L1
L2
BL
BL
WH
PS
RD
RD
FS
YL
RD
C
OR
PK
SEE NOTE 6
RD
9
T1
RD
OR
OR
BK
WH
LS
3
L3
BL
RD
OR
RD
1
BL
2
T2
T3
BK
FC2
RD
RD
3
BK
6
1
OR
RD
RD
C
F
PU
BK
WH
VMR
8
5
BL
BK
BR
C
FC1
11
7
4
BK
YL
BK
BK
RD
F
VM
10
BK
BR
PU
BK
BR
RD
460
OR APPROPRIATE
INPUT VOLTAGE
240
30
TR
CM1
24V
PU
Wiring Diagram — DCG 7½-8½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt Drive)
SS-DCG7
Wiring Diagram — DCG 7½-8½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt Drive)
T3
CC1
T3
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
BC2
T1
COMP2
CC2
T2
T2
T1
T3
T3
LOW SPEED
CC2
BC2
BC1
BC2
EM
HIGH SPEED
BC1
BC1
4
VM
2
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK BLACK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
BL /PK BLUE WITH
PINK STRIP
460V OR
APPROPRIATE
INPUTVOLTAGE
SEE NOTE 6
LINE VOLTAGE
LOW VOLTAGE
YL /PK YELLOW WITH
PINK STRIP
VMR
C
FACTORY WIRING
⚡
T1
L3
L2
CC1
T2
COMP1 T2
CC1
C
TR
HC
1
F
NOTE 3
24V
L1 NOTE 3
IGN
FS
FS
H C
BR1
4
2
BC1
5
BC2
IIC
4
BR2
LS
2
4
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
BR1
5
L2
CC2
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
CCR2
6
9
PS
ECON
2
8
7
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
SUPPLY VOLTAGE
460-575/3/60
L1
NOTE 2
TO THERMOSTAT
O
++
R
W2 W1
Y2
Y1
G
C
PLF
6
3
8
5
2
7
4
1
TB1
NOTE 5
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
EQUIPMENT STATUS
ON
NORMAL OPERATION
------
OFF
NO POWER OR
INTERNAL CONTROL
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
IGNITION FAILURE
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
W1
GR
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
C
W2
STAT
CHECK
STATUS LIGHT
OPEN ROLLOUT
SWITCH
WH
G
TB1
INSTALLER/SERVICEMAN
1 BLINK
W1
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
S1
S2
9
⚠ Warning
2 STAGE COOLING
460-575/3/60 0140L03761-A
SS-DCG7
www.daikincomfort.com
31
YL
BK
COMP 2
www.daikincomfort.com
GY
BL
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
YL
BK
BK
BK
HIGH
EM
LOW
YL
RD
BK
OR
COMP1
YL
PU
BR
BK
T3 T2 T1
RD
RD
CB1
HIGH
SPEED
BK
YL
BK
YL
T2
T3 T2 T1
L3
CB2
LOW
SPEED
BK
C
BC 2
T1
T2
C
L1
L2
L3
GR
L1
L2
L3
OR
OR
GR
BK
RD
BK
RD
RD
YL
BK
OR
BL
RD
OR
BK
BK
RD
OR
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
YL
BL
T3
BL
BC 1
T1
BK
T3
L1
L2
C
T2
T1
L3
T2
GY
L1
L2
CC2
C
L3
BK
FC2
PU
FC1
T3
BL
BL
C
F
C
CC1
T1
T2
T3
RD
OR
BL
BL
RD
RD
BL
BK
BR
BK
RD
F
BL
YL
3
1
3
1
OR
NC
NO
5
2
4
BR2
4
BR1
NC
NO
5
2
GR
GR
LPS 2
LPS1
YL
YL
WH
OR
SEE NOTE 6
RD
⚠ Warning
YL
GR
BK
RD
OR
RD
RD
OR
VM
VMR
HPS1
208
240
PB
BL
BL
BL
BL
BL
BL
1
YL
4
1
2 3
22
S1
YL
RD
S2
RD
BL
PK
PK
PU
BL
PK
RD
CCR 2
4
2 3
22
CCR1
POWER SUPPLY
208-240/3/60
SEE NOTE 4
YL
BL
PK
WH
C
PK
GR
G
GR
GR
BL
BL
BL
BL
W1
WH
WH
WH
YL YL
PS
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
RD
BR RD
RD
WH
LS
W2
BR
RD
Y1
Y2
PU
BL
BR
BL
O
PU
YL
GR
YL
⚡
YL
PLF
RD
BL
RD
RD
BL
PU
RD
YL
9
7
ECON
3
1
2
BL
WH WH
4
5
6
PU
RS
ALS
PU
SEE NOTE 2 8
PU
BL
BL
RD
BL
BL
GR
WH
RD
YL
RD
SEE NOTE 5
YL
YL
BL
RD
RD
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
GR
HPS 2
PU
WH
TR
GND
BK
BK
RD
RD
OR
OR
BL
1
3
BK
L2
T3
BR
RD
UNUSED HEAT COOL
T1
L1
T3
DI
T2
RD
PU
PU
GR
RD
YL
BR
YL
YL
BK
0140L02575-A
GV
YL
IGN OR
FS
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
3
FS
T1
1
6
L2
9
2
L1
12
8
5
L3
11
7
4
L2
CM2
10
L1
32
24V
CM1
C
PU
Wiring Diagram — DCG 10 – 12½ Tons (230V, Two-Speed, Three-Phase Belt Drive)
SS-DCG7
Wiring Diagram — DCG 10 – 12½ Tons (230V, Two-Speed, Three-Phase Belt Drive)
T3
CC1
T3
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
BC2
CB2
BC1
T1
COMP2
CC2
T2
T2
T1
T3
T3
LOW SPEED
CB1
CB2
BC2
CB2
BC2
CC2
EM
HIGH SPEED
CB1
BC1
CB1
BC1
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLACK
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
YL /PK YELLOW WITH
PINK STRIP
4
VM
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
⚡
T1
L3
L2
CC1
T2
COMP1 T2
CC1
2
BL /PK BLUE WITH
PINK STRIP
VMR
SEE NOTE 6
C
TR
L1
HC
1
F
NOTE 3
24V
NOTE 3
IGN
FS
FS
H C
BR1
4
2
BC1
5
BC2
BR1
4
BR2
LS
5
IIC
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
2
4
L2
CC2
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
CCR2
6
9
PS
ECON
8
7
2
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
SUPPLY VOLTAGE
208-240/3/60
L1
NOTE 2
S1
S2
TO THERMOSTAT
O
++
R
W2 W1
Y2
Y1
G
C
PLF
9
6
3
8
5
2
7
4
1
TB1
NOTE 5
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
NORMAL OPERATION
------
OFF
NO POWER OR
INTERNAL CONTROL
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
C
W2
STAT
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
EQUIPMENT STATUS
ON
IGNITION FAILURE
W1
GR
CHECK
STATUS LIGHT
OPEN ROLLOUT
SWITCH
WH
G
TB1
INSTALLER/SERVICEMAN
1 BLINK
W1
⚠ Warning
2 STAGE COOLING
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
208-240/3/60 0140L02576-A
SS-DCG7
www.daikincomfort.com
33
YL
BK
T3 T2 T1
COMP1
COMP 2
www.daikincomfort.com
GY
BL
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN
OR --------------- ORANGE
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
PK --------------- PINK
GR---------------- GREEN
GY---------------- GREY
YL
BK
BK
BK
HIGH
EM
LOW
RD
RD
CB1
HIGH
SPEED
BK
YL
BK
YL
CB2
LOW
SPEED
BK
C
BC 2
T1
T2
C
L1
L2
L3
GR
L1
L2
L3
OR
OR
GR
BK
RD
BK
RD
RD
YL
BK
OR
BL
RD
BK
BK
RD
RD
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
YL
BL
T3
BL
BC 1
T1
BK
T3
L1
L2
C
T2
T1
L3
T2
GY
L1
L2
CC2
C
L3
BK
FC2
PU
FC1
T3
BL
BL
C
F
C
CC1
T1
T2
T3
RD
OR
BL
BL
RD
RD
BL
BK
BR
BK
RD
F
OR
BL
YL
3
1
3
1
OR
NC
NO
5
2
4
BR2
4
GR
1
3
46O OR
APPROPRIATE
INPUT
GR
HPS 2
HPS1
GND
BK
BK
PU
WH
C
RD
RD
OR
OR
VMR
VOLTAGE
PB
BL
BL
BL
BL
PK
WH
BL
YL
1
YL
4
1
2 3
22
YL
RD
S2
RD
BL
PK
PK
PU
BL
PK
S1
RD
CCR 2
4
2 3
22
CCR1
POWER SUPPLY
460-575/3/60
SEE NOTE 4
BL
BL
SEE NOTE 6
RD
RD
C
BL
G
PS
W1
WH
WH
WH
YL YL
PK
GR
GR
GR
BL
BL
BL
WH
LS
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR WH
R
RD
BR
BK
W2
BR
RD
Y1
Y2
PU
BL
BR
BL
O
PU
YL
GR
⚡
YL
YL
PLF
RD
BL
RD
RD
BL
PU
RD
YL
9
7
ECON
3
1
2
BL
WH WH
4
5
6
PU
RS
ALS
PU
SEE NOTE 2 8
PU
BL
BL
RD
BL
BL
GR
WH
RD
YL
RD
SEE NOTE 5
YL
YL
BL
RD
RD
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
YL
WH
BL
GR
LPS 2
LPS1
BR1
NC
NO
5
2
OR
YL
OR
RD
BK
RD
⚠ Warning
YL
GR
BK
RD
OR
RD
BK
VM
UNUSED HEAT COOL
YL
RD
BK
OR
T3 T2 T1
YL
PU
BR
BK
BR
RD
L2
T3
L1
T2
DI
T1
FS
T3
6
T2
RD
PU
PU
GR
RD
YL
BR
YL
YL
BK
0140L02567-A
GV
YL
IGN OR
FS
YL
YL
IIC
OR
SEE
NOTE 3
BK
WH
GR
WH
12
T1
3
L3
2
L2
9
1
L1
8
5
L3
11
7
4
L2
CM2
10
L1
460
OR APPROPRIATE
INPUT VOLTAGE
240
34
TR
CM1
24V
PU
Wiring Diagram — DCG 10 – 12½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt)
SS-DCG7
Wiring Diagram — DCG 10 – 12½ Tons (460V/ 575V, Two-Speed, Three-Phase Belt)
T3
CC1
T3
ALS
BC
BR
CB
CC
CCR
CM
COMP
EM
F
FC
FS
GND
GV
HPS
IBR
IIC
IGN
LPS
LS
PLF
PS
RS
TB1
TR
VM
VMR
C
FC1
F
CM1
C
FC2
F
CM2
CC2
BC2
CB2
BC1
CB1
T1
COMP2
CC2
T2
T2
T1
T3
T3
LOW SPEED
CB2
BC2
CB2
BC2
CC2
EM
HIGH SPEED
CB1
BC1
CB1
BC1
4
VM
2
COMPONENT LEGEND
AUXILLARY LIMIT SWITCH
BLOWER CONTACTOR
BLOWER RELAY
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
COMPRESSOR CONTACTOR RELAY
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
FUSE
FAN CAPACITOR
FLAME SENSOR
EQUIPMENT GROUND
GAS VALVE
HIGH PRESSURE SWITCH
INDOOR BLOWER RELAY
INTEGRATED IGNITION CONTROL
IGNITOR
LOW PRESSURE SWITCH
LIMIT SWITCH
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLLOUT SWITCH
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
WIRE CODE
BK
BL
BR
GR
OR
PK
PU
RD
WH
YL
BLACK
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
BL /PK BLUE WITH
PINK STRIP
460V OR
APPROPRIATE
INPUTVOLTAGE
SEE NOTE 6
LINE VOLTAGE
LOW VOLTAGE
YL /PK YELLOW WITH
PINK STRIP
VMR
C
FACTORY WIRING
⚡
T1
L3
L2
CC1
T2
COMP1 T2
CC1
C
TR
L1 NOTE 3
1
F
NOTE 3
24V
HC
IGN
FS
FS
H C
BR1
4
2
BC1
5
BC2
BR1
4
BR2
LS
5
IIC
5
IIC
BR2
VMR
D1
CCR1
4
CCR2
ALS
3
4
HPS1
LPS1
2
CC1
2
RS
LPS2
HPS2
GV
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
2
4
L2
CC2
2. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO THE ECONOMIZER
ACCESSORY.
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
4. USE COPPER CONDUCTORS ONLY.
++ USE NEC CLASS 2 WIRE.
5. FOR TWO STAGE OPERATION REMOVE
W1 TO W2 JUMPER WIRE
6. MOVE WIRE(S) TO APPROPRIATE INPUT
VOLTAGE TERMINAL ON TRANSFORMER.
CCR2
6
9
PS
ECON
8
7
2
CCR1
12
10
11
THERMOSTAT
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
SUPPLY VOLTAGE
460-575/3/60
L1
NOTE 2
TO THERMOSTAT
O
++
R
W2 W1
Y2
Y1
G
C
PLF
6
3
8
5
2
7
4
1
TB1
NOTE 5
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
EQUIPMENT STATUS
ON
NORMAL OPERATION
------
OFF
NO POWER OR
INTERNAL CONTROL
CHECK INPUT POWER
CHECK FUSE ON CONTROL
REPLACE CONTROL
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
STICKING GAS VALVE
6 BLINKS
COMPRESSOR
OUTPUT DELAY
3 MIN. COMP.
ANTI-CYCLE TIMER
IGNITION FAILURE
OPEN AUX. LIMIT
SWITCH
2 BLINKS
3 BLINKS
PRESSURE SWITCH
OPEN
PRESSURE SWITCH CLOSED
WITHOUT INDUCER ON
W1
GR
G
R
RD
R
Y1
YL
Y1
Y2
PK
Y2
C
BL
W2
BR
C
W2
STAT
CHECK
STATUS LIGHT
OPEN ROLLOUT
SWITCH
WH
G
TB1
INSTALLER/SERVICEMAN
1 BLINK
W1
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
S1
S2
9
⚠ Warning
2 STAGE COOLING
460-575/3/60 0140L02566-A
SS-DCG7
www.daikincomfort.com
35
WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS
For complete information and installation instructions for models
with DDC controls, see manual DK-DDC-TGD-XXX
36
www.daikincomfort.com
SS-DCG7
SS-DCG7
www.daikincomfort.com
3A
IGNITOR
F1
F1
WH
PK
PK
WH
BR
WH
IAH
BL
PU
RD
RD
YL
YL
WH
BR
PK
PK
BL
BL
BL
BL
GY
BK
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
HEAT
PK
BR
RD
BK
RD
BL
WH
PK
BL
GY
2
PU
RD
RD
BL
RD
GR
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
GY
RD
GR
GR
RD
RS
GR
GR
YL
YL
RD
LS
PU
RD
RD
RD
GR
BL
BL
1 GND
BL
(OAH)
(OAT)
(ECON FB)
(SUPPLY AIR TMP)
BL
BL
PS
BL
BK
WH
BL
WH
BL
BL
WH
BR
BK
BR
WH
1 WH
2
3
4
5
6
BK
BR
BR
BR
BR
BR
BR
WH
WH
BR
BK
BK
BK
WH
-
BL
BL
BL
BL
BL
BK
BL
BR
WH
+ ALRM -
+ EXF
+ HGRH -
WH
BAC NET
WH
BR
BR
HTR PLF1
11
22
RD
WH
BR
BR
BR
BR
BR
BR
WH
WH
WH
PU
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
BK
BK
BK
BK
BL
GR
5
RD
UNUSED
IIC
OR
RD
1
6
6
VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY
POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2
TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2
TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE
FROM IIC-UNUSED AND CONNECT TO CC1-L1.
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE
CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V
SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE
208V TAP.
IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
4
5
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
TB1-XS TO TB1-ES.
VMR
3
2
6
RD
OR
BK
BK
RD
OR
PU
VM
L1
BK
T2
BK
T1
BK
PB
ALS
BK BK
RD
RD
RD
RD
RD
RD
RD
L3
L2
L1
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
⚡
BR
BR
BK
PU
BK
BR
PU
BK
BR
BK
L3
COMP1
T1
CF2
CF1
BM
COMP2
T3
T1
T3
COMPONENT LEGEND
FC2
FC1
PU
T2
T2
BK
PU
RD
OR
BL
BK
RD
YL
BL
BL
BK
RD
YL
BL
GND
L1
L2
BL
BL
LINE
VOLTAGE
0140L05764-A
AUXILIARY LIMIT SWITCH
ALARM
BLOWER CONTACTOR
BLOWER CURRENT SWITCH
BLOWER MOTOR
CIRCUIT BREAKER
CB
COMPRESSOR CONTACTOR
CC
CF
CONDENSER FAN
CFS
CLOGGED FILTER SWITCH
COMP COMPRESSOR
CO2
CARBON DIOXIDE SENSOR
DAT
DISCHARGE AIR TEMPERATURE SENSOR
DDC
DIRECT DIGITAL CONTROL
ECON ECONOMIZER
EXF
EXHAUST FAN
FAN CAPACITOR
FC
FLAME SENSE
FS
EQUIPMENT GROUND
GND
GV
GAS VALVE
HGRH HOT GAS REHEAT
HPS
HIGH PRESSURE SWITCH
IAH
INDOOR AIR HUMIDITY SENSOR
IIC
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LS
LOAD SHEDDING
LDS
LPS
LOW PRESSURE SWITCH
OAT
OUTDOOR AIR TEMPERATURE SENSOR
OAH
OUTDOOR AIR HUMIDITY SENSOR
PB
POWER DISTRIBUTION BLOCK
PLF
FEMALE PLUG/CONNECTOR
PLM
MALE PLUG/CONNECTOR
PS
PRESSURE SWITCH
RS
ROLL-OUT SWITCH
RSS
REMOTE START/STOP
SMOKE DETECTOR
SMK
SPC
TEMP SPACE TEMPERATURE SENSOR
TB
TERMINAL BLOCK (24V SIGNAL)
TR
TRANSFORMER
VENT MOTOR
VM
VENT MOTOR RELAY
VMR
FACTORY WIRING
ALRM
BC
HIGH VOLTAGE
BCS
LOW VOLTAGE
BM
OPTIONAL LOW VOLTAGE
BK
WH
RD
L2
RD
T3
T1
T2
T3
T1
T2
T3
CC1
OR
BC
CC2
BL
OPTIONAL ACCESSORIES
OR FIELD SUPPLIED
COMPONENTS
BK
WH
RD
L3
L1
L2
L3
L1
L2
L3
OR
BK
BK
OR
OR
OR
RD
RD
RD
BK
BK
YL
BK
OR
RD
BK
BK
RD
OR
BK
BK
BK
RD
RD
OR
BK
3
OR
RD
BK
BK
RD
RD
OR
RD
OR
RD
OR
OR
OR
RD
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
NOTES:
BR WH
BL
4
BK
YL
PU
24V CNTL
VOLTAGE
HTR PLM1
ECON
PLF 6 5 4 3 2 1
RD
YL PU PK
LINE
VOLTAGE
POWER & CONTROL WIRING DIAGRAM
DCG(090-150) ***(3)B
DDC
BK
BR
BL
AO1
AO2
AO3
AO4
GND
GND
R+ 1
SH 2
T- 3
PK
WH
BR
YL
PU
PU
BK
YL
RD
TR1
OR
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
BL
BL
1ST STG COM 2ND STG
GV
2 24VAC
(BAC
NET)
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
(EMER)
(FAN PROV)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
(24V IN)
(ECON PWR)
(HEAT 1)
(HEAT 2)
(CO2)
(SPC TMP)
5 AI6
(SPC SLIDE ADJ)
4 AI7
(SPC HUM)
3 AI8
2 AGND
(ISOL GND)
1 AGND
8 AI3
7 AI4
6 AI5
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
RD
(BLOWER STAGE 1)
RD
GR
GR
BK
BR
9 AI2
8
7
6
5
4
3
2
1
PU 10 AI1
PK
BK
YL
PU
BK
BR
VMR
GY
PK
SPCTEMP
TEMP
STPT OFFSET
GND
PU
YL
BK
BK
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
PU
YL
XS DA
PU BK PK PU YL
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BK
BR
RD
BK
RD
PK
T T TTT C
PS
1 2 345 S
BL/PK
24VAC
TB2
(CLASS2)
GR
GR BR
VOUT (DC)
GND
24 VAC
1
2
3
4
TMP LMT IN
5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
IIC
3
-t°
DAT
GR
BR
BR
-t°
OAT
HPS2
HPS1
SMK/EMG
OAH
VOUT (DC)
GND
24 VAC
CFS
LDS
WH
RD
GY
GY
TB1
(CLASS2)
RSS
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
PK
RD
RD
PK
Wiring Diagram with DDC — DCG 090*/ 102*/ 120*/ 150* 208-230 / 3 / 60 1SP
37
38
www.daikincomfort.com
3A
IGNITOR
F1
F1
WH
PK
PK
WH
HPS1
BR
PK
PK
BL
BL
BL
BL
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
GY
BK
BL
PU
RD
RD
YL
YL
WH
PK
GR
BR
RD
BK
RD
WH
PK
BL
BL
GY
2
PU
RD
RD
BL
RD
GY
GY
VMR
RD
GR
GR
BK
BR
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
YL
BK
BK
PK
PU BK PK PU YL
RD
RS
YL
YL
RD
LS
PU
RD
BL
RD
BL
RD
GR
GR
SPCTEMP
TEMP
STPT OFFSET
GND
PU
PU
YL
XS DA
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BK
BR
RD
BK
RD
T T TTT C
PS
1 2 345 S
BL/PK
24VAC
TB2
(CLASS2)
VOUT (DC)
GND
24 VAC
IAH
OAH
VOUT (DC)
GND
24 VAC
WH
HPS2
BR
-t°
OAT
GR BR
HEAT
GY
SMK/EMG
1
2
3
4
TMP LMT IN
5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
IIC
3
-t°
DAT
GR
BR
BR
CFS
LDS
WH
RD
GY
TB1
(CLASS2)
RSS
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
PK
RD
RD
PK
8
7
6
5
4
3
2
1
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
9 AI2
1 GND
BL
BL
PS
BL
BK
WH
BL
WH
BL
WH
BR
BK
BR
WH
1 WH
2
3
4
5
6
PK
BR
BR
BR
BR
BR
BR
BK
WH
BR
11
22
WH
BR
WH
WH
BR
BK
BK
WH
-
BL
BL
BK
BL
BR
WH
+ ALRM -
+ EXF
+ HGRH -
WH
BAC NET
RD
BR
BR
BR
BL
BK
BK
BK
BK
BL
GR
5
BL
BL
BL
BL
BL
BL
BL
PU
BL
BL
BL
BL
RD
BK
BK
IIC
UNUSED
OR
RD
OR
1
OR
BK
OR
RD
RD
OR
OR
OR
BK
OR
RD
BK
VMR
BK
RD
OR
5
4
3
2
RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH
VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY
SIDE OF TR1.
IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
TB1-XS TO TB1-ES.
3
460V
OR
575V
230V
COM
RD
VM
L1
BK
T2
BK
T1
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
⚡
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
PB
BK BK
RD
PU
BR
PU
BR
BK
BK
BR
PU
BK
BR
BK
L3
COMP1
T1
CF2
CF1
BM
COMP2
T3
T1
T3
COMPONENT LEGEND
FC2
FC1
T2
T2
PU
BK
RD
OR
BL
BK
RD
YL
BL
BL
BK
RD
YL
BL
GND
L1
L2
BL
BL
LINE
VOLTAGE
0140L05758-A
SPACE TEMPERATURE SENSOR
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
AUXILIARY LIMIT SWITCH
ALARM
BLOWER CONTACTOR
BLOWER CURRENT SWITCH
BLOWER MOTOR
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
CONDENSER FAN
CLOGGED FILTER SWITCH
COMPRESSOR
CARBON DIOXIDE SENSOR
DISCHARGE AIR TEMPERATURE SENSOR
DIRECT DIGITAL CONTROL
ECONOMIZER
EXHAUST FAN
FAN CAPACITOR
FLAME SENSE
EQUIPMENT GROUND
GAS VALVE
HOT GAS REHEAT
HIGH PRESSURE SWITCH
INDOOR AIR HUMIDITY SENSOR
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LOAD SHEDDING
LOW PRESSURE SWITCH
OUTDOOR AIR TEMPERATURE SENSOR
OUTDOOR AIR HUMIDITY SENSOR
POWER DISTRIBUTION BLOCK
FEMALE PLUG/CONNECTOR
MALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLL-OUT SWITCH
REMOTE START/STOP
SMOKE DETECTOR
RD
RD
RD
RD
RD
RD
L3
L2
L1
ALS
ALRM
BC
BCS
BM
CB
CC
CF
CFS
COMP
CO2
DAT
DDC
ECON
EXF
FC
FS
GND
GV
HGRH
HPS
IAH
IIC
LS
LDS
LPS
OAT
OAH
PB
PLF
PLM
PS
RS
RSS
SMK
SPC
TEMP
TB
TR
VM
VMR
BK
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL LOW VOLTAGE
BK
WH
L2
RD
OPTIONAL ACCESSORIES
OR FIELD SUPPLIED
COMPONENTS
BK
WH
RD
L3
OR
T3
T1
RD
L1
T3
BK
BK
BC
CC2
T2
L3
T1
T2
T3
CC1
L2
OR
L1
L2
L3
BL
OR
RD
OR
PU
RD
RD
BK
BK
OR
BK
BK
OR
OR
YL
BK
OR
RD
BK
TR3
BK
RD
OR
BK
BK
BK
RD
RD
OR
BK
BK
OR
RD
BK
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
WH
WH
WH
BR
BR
NOTES:
BR WH
BL
4
BK
YL
PU
24V CNTL
VOLTAGE
HTR PLM1
ECON
PLF 6 5 4 3 2 1
HTR PLF1
RD
OR
POWER & CONTROL WIRING DIAGRAM
DCG(090-150) ***(4,7)B
DDC
BK
BR
BL
AO1
AO2
AO3
AO4
GND
GND
R+ 1
SH 2
T- 3
YL
YL
PU
PU
BK
YL PU PK
LINE
VOLTAGE
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
BL
BL
BL
(ISOL GND)
(CO2)
(SPC TMP)
(SPC SLIDE ADJ)
(SPC HUM)
(OAH)
(OAT)
(ECON FB)
(SUPPLY AIR TMP)
1ST STG COM 2ND STG
GV
2 24VAC
AGND
AGND
AI6
AI7
AI8
(BAC
NET)
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
BL
5
4
3
2
1
8 AI3
7 AI4
6 AI5
(24V IN)
(ECON PWR)
(EMER)
(FAN PROV)
RD
GR
GR
BK
BR
PU 10 AI1
PK
BK
YL
PU
(HEAT 1)
(HEAT 2)
(BLOWER STAGE 1)
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
TR1
OR
Wiring Diagram with DDC — DCG 090*/ 102*/ 120*/ 150* 460, 575 / 3 / 60 1SP
SS-DCG7
SS-DCG7
www.daikincomfort.com
F1
3A
IGNITOR
F1
IIC
WH
PK
PK
WH
BR
PK
PK
BL
BL
BL
BL
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
GY
BK
BL
PU
RD
RD
YL
YL
WH
PK
GR
BR
WH
PK
BL
BL
GY
2
PU
RD
RD
BL
RD
GY
RD
GR
GR
VMR
GY
8
7
6
5
4
3
2
1
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RD
RS
YL
YL
RD
LS
1 GND
BL
BL
PS
BL
BL
BK
WH
BL
BL
WH
BL
BK
BR
BL
(ISOL GND)
BL
(CO2)
(SPC TMP)
(SPC SLIDE ADJ)
(SPC HUM)
(OAH)
(OAT)
(ECON FB)
(SUPPLY AIR TMP)
1ST STG COM 2ND STG
GV
2 24VAC
BL
AGND
AGND
AI6
AI7
AI8
RD
GR
5
4
3
2
1
8 AI3
7 AI4
6 AI5
(BAC
NET)
WH
PK
WH
BK
BR
BR
BR
BR
BR
BR
HTR PLF1
BR
WH
BK
BK
BL
BL
BL
BL
BL
BR
BR
BK
BR
BK
RD
BL
RD
PU
RD
VM
OR
BK
BK
BK
BL
BL
ALS
ALRM
BC
BCS
BM
CB
CC
CF
CFS
COMP
CO2
DAT
DDC
ECON
EXF
FC
FS
GND
GV
HGRH
HPS
IAH
IIC
LS
LDS
LPS
OAT
OAH
PB
PLF
PLM
PS
RS
RSS
SMK
SPC
TEMP
TB
TR
VM
VMR
BL
BL
BL
BL
BL
UNUSED
IIC
OR
1
OR
6
VMR
3
BK
WH
SPACE TEMPERATURE SENSOR
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
AUXILIARY LIMIT SWITCH
ALARM
BLOWER CONTACTOR
BLOWER CURRENT SWITCH
BLOWER MOTOR
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
CONDENSER FAN
CLOGGED FILTER SWITCH
COMPRESSOR
CARBON DIOXIDE SENSOR
DISCHARGE AIR TEMPERATURE SENSOR
DIRECT DIGITAL CONTROL
ECONOMIZER
EXHAUST FAN
FAN CAPACITOR
FLAME SENSE
EQUIPMENT GROUND
GAS VALVE
HOT GAS REHEAT
HIGH PRESSURE SWITCH
INDOOR AIR HUMIDITY SENSOR
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LOAD SHEDDING
LOW PRESSURE SWITCH
OUTDOOR AIR TEMPERATURE SENSOR
OUTDOOR AIR HUMIDITY SENSOR
POWER DISTRIBUTION BLOCK
FEMALE PLUG/CONNECTOR
MALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLL-OUT SWITCH
REMOTE START/STOP
SMOKE DETECTOR
COMPONENT LEGEND
BK
WH
BK
BK
RD
OR
BR
OPTIONAL ACCESSORIES
OR FIELD SUPPLIED
COMPONENTS
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
BC2
T2
⚡
L1
L2
L3
PB
BK
RD
BK
BL
BL
RD
RD
RD
RD
RD
RD
L3
L2
L1
FC2
FC1
BR
BK
PU
BK
BR
PU
YL
BL
GY
BK
RD
OR
BL
BK
RD
YL
BL
BL
BK
RD
YL
BL
BK
BR
PU
BK
BR
PU
T2
T2
T1
L3
COMP1
BM
CF2
CF1
BK
BK
BK
YL
YL
YL
COMP2
T3
T1
T3
GND
L1
L2
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
TB1-XS TO TB1-ES.
6
5
0140L05773-A
VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY
POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2
TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2
TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE
FROM IIC-UNUSED AND CONNECT TO CC1-L1.
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE
CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V
SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE
208V TAP.
4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
3
2
BL
BL
LINE
VOLTAGE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
NOTES:
T1
T2
T3
T1
L2
L1
T3
L3
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL LOW VOLTAGE
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
BK
WH
RD
RD
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
BL
BR
WH
+ ALRM -
-
BC1
T1
L1
RD
BK
BK
T3
T2
CC2
T1
T2
T3
CC1
L2
L3
L1
L2
L3
BL
OR
RD
OR
OR
BK
BK
OR
OR
RD
BK
RD
OR
PU
BK
RD
OR
OR
YL
BK
RD
RD
OR
RD
OR
BK
BK
BK
RD
RD
OR
BK
6
BK
OR
RD
BK
OR
RD
BK
OR
RD
OR
BK
BK
BR
BR
BR
BR
WH
BK
BL
GR
RD
RD
BR WH
BL
4
BR
RD
5
+ HGRH -
BR
WH
WH
BR
HTR PLM1
YL
PU
24V CNTL
VOLTAGE
LINE
VOLTAGE
+ EXF
WH
BAC NET
WH
11
22
RD
TR1
OR
ECON
PLF 6 5 4 3 2 1
RD
PK
YL PU PK
WH
BR
YL
PU
PU
BR
BK
YL
1 WH
2
3
4
5
6
BR
BK
BR
AO1
AO2
AO3
AO4
GND
GND
R+ 1
SH 2
T- 3
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
(EMER)
(FAN PROV)
(24V IN)
(ECON PWR)
(BLOWER STAGE 1)
(BLOWER STAGE 2)
(HEAT 1)
(HEAT 2)
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
POWER & CONTROL WIRING DIAGRAM
DCG(090-102) ***(3)V
DDC
PU
RD
BL
RD
BL
RD
GR
GR
GR
BK
BR
9 AI2
PK
BK
YL
PU
PU 10 AI1
YL
YL
PU
BK
BR
SPCTEMP
TEMP
STPT OFFSET
GND
PU
YL
BK
PK
PU
PU
YL
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
PU
YL
PU BK PK
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
XS DA
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BL/PK
BK
BR
RD
BK
RD
T T TTT C
PS
1 2 345 S
RD
BK
RD
24VAC
TB2
(CLASS2)
VOUT DC
GND
24 VAC
IAH
OAH
VOUT (DC)
GND
24 VAC
GR BR
HEAT
WH
BR
-t°
OAT
HPS2
HPS1
SMK/EMG
1
2
3
4
TMP LMT IN
5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
3
-t°
DAT
GR
BR
BR
LDS
CFS
WH
RD
GY
GY
TB1
(CLASS2)
RSS
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
PK
RD
RD
PK
Wiring Diagram with DDC — DCG 090* / 102* 208-230 / 3 / 60 2SP
39
40
www.daikincomfort.com
3A
WH
PK
PK
WH
GY
WH
BL
PU
RD
RD
YL
YL
WH
BR
PK
PK
BL
BL
BL
BL
GY
BK
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
HEAT
PK
GR
GR BR
BR
BL
WH
PK
BL
GY
2
PU
RD
RD
BL
RD
8
7
6
5
4
3
2
1
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
GY
RD
GR
GR
RD
RS
YL
YL
RD
LS
PU
RD
BL
RD
BL
RD
GR
GR
1 GND
BL
BL
BL
BL
BK
WH
BL
BL
WH
BL
BK
BR
BL
(ISOL GND)
BL
(CO2)
(SPC TMP)
(SPC SLIDE ADJ)
(SPC HUM)
(OAH)
(OAT)
(ECON FB)
WH
PK
WH
BR
BR
BR
BR
BR
BR
BK
WH
BR
1 WH
2
3
4
5
6
BR
BK
BR
AO1
AO2
AO3
AO4
GND
GND
YL
YL
PU
PU
BR
BK
HTR PLF1
11
22
RD
BR
BR
WH
WH
BK
BK
WH
-
BL
BL
BK
BL
BR
WH
+ ALRM -
+ EXF
+ HGRH -
WH
BAC NET
BR
BL
BL
BL
BL
BL
BL
WH
BK
BK
BR
BK
BL
IIC
UNUSED
BL
BK
BR
1
VMR
BK
OR
OR
OR
BK
COMPONENT LEGEND
BR
WH
WH
BR
BR
BL
PU
BL
BK
3
RD
RD
OR
BK
RD
BK
WH
BR
BK
OR
BK
BK
BK
RD
OR
BR
BK
BK
RD
RD
L1
L2
L3
L1
L2
L3
OPTIONAL ACCESSORIES
OR FIELD SUPPLIED
COMPONENTS
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL LOW VOLTAGE
VM
RD
OR
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
BK
WH
RD
460V
OR
575V
230V
COM
OR
T1
T2
T3
T1
PB
RD
BK BK
BL
BL
RD
RD
RD
L3
L2
L1
YL
BL
GY
PU
FC2
BR
BK
PU
BK
BR
BK
BR
PU
BK
BR
PU
YL
BL
GY
BK
RD
BK
OR
RD
T2
T2
OR
FC1
BL
BK
RD
YL
BL
BL
BK
RD
YL
BL
T1
L3
COMP1
BM
CF2
CF1
BL
OR
WH
BK
BK
BK
COMP2
T3
T1
T3
GND
L1
L2
BL
BL
LINE
VOLTAGE
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
TB1-XS TO TB1-ES.
5
0140L05771-A
RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH
VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY
SIDE OF TR1.
4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
3
2
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
NOTES:
BC2
T3
T2
BC1
T1
RD
L1
T3
BK
BK
CC2
T2
L3
T1
T2
T3
CC1
L2
OR
L1
L2
L3
BL
OR
RD
OR
PU
RD
RD
BK
BK
OR
BK
OR
OR
YL
BK
OR
RD
BK
TR3
BK
RD
OR
BK
BK
BK
RD
RD
OR
BK
BR
BK
OR
RD
BK
OR
RD
OR
BK
OR
OR
RD
AUXILIARY LIMIT SWITCH
ALS
ALRM ALARM
BC
BLOWER CONTACTOR
BCS
BLOWER CURRENT SWITCH
BM
BLOWER MOTOR
CIRCUIT BREAKER
CB
COMPRESSOR CONTACTOR
CC
CF
CONDENSER FAN
CFS
CLOGGED FILTER SWITCH
COMP COMPRESSOR
CO2
CARBON DIOXIDE SENSOR
DAT
DISCHARGE AIR TEMPERATURE SENSOR
DDC
DIRECT DIGITAL CONTROL
ECON ECONOMIZER
EXF
EXHAUST FAN
FAN CAPACITOR
FC
FLAME SENSE
FS
EQUIPMENT GROUND
GND
GV
GAS VALVE
HGRH HOT GAS REHEAT
HPS
HIGH PRESSURE SWITCH
IAH
INDOOR AIR HUMIDITY SENSOR
IIC
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LS
LOAD SHEDDING
LDS
LPS
LOW PRESSURE SWITCH
OAT
OUTDOOR AIR TEMPERATURE SENSOR
OAH
OUTDOOR AIR HUMIDITY SENSOR
PB
POWER DISTRIBUTION BLOCK
PLF
FEMALE PLUG/CONNECTOR
PLM
MALE PLUG/CONNECTOR
PS
PRESSURE SWITCH
RS
ROLL-OUT SWITCH
RSS
REMOTE START/STOP
SMOKE DETECTOR
SMK
SPC
TEMP SPACE TEMPERATURE SENSOR
TB
TERMINAL BLOCK (24V SIGNAL)
TR
TRANSFORMER
VENT MOTOR
VM
VENT MOTOR RELAY
VMR
BR
BR WH
BL
4
BR
BK
5
RD
BK
GR
BL
OR
YL
PU
24V CNTL
VOLTAGE
LINE
VOLTAGE
HTR PLM1
TR1
OR
ECON
PLF 6 5 4 3 2 1
RD
YL PU PK
POWER & CONTROL WIRING DIAGRAM
DCG(090-102) ***(4,7)V
DDC
PS
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
R+ 1
SH 2
T- 3
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(BAC
NET)
(SUPPLY AIR TMP)
1ST STG COM 2ND STG
GV
2 24VAC
AGND
AGND
AI6
AI7
AI8
(24V IN)
(ECON PWR)
(EMER)
(FAN PROV)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
BL
5
4
3
2
1
8 AI3
7 AI4
6 AI5
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
(BLOWER STAGE 1)
(BLOWER STAGE 2)
(HEAT 1)
(HEAT 2)
RD
GR
GR
BK
BR
9 AI2
PK
BK
YL
PU
PU 10 AI1
YL
PU
BK
BR
VMR
GY
PK
PU
SPCTEMP
TEMP
STPT OFFSET
GND
PU
YL
BK
BK
PU BK PK
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
PU
YL
XS DA
YL
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BL/PK
BK
BR
RD
BK
RD
T T TTT C
PS
1 2 345 S
RD
BK
RD
24VAC
TB2
(CLASS2)
VOUT (DC)
GND
24 VAC
IAH
OAH
VOUT (DC)
GND
24 VAC
BR
-t°
OAT
HPS2
HPS1
SMK/EMG
1
2
3
4
TMP LMT IN 5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
IIC
3
-t°
DAT
GR
BR
BR
LDS
CFS
WH
RD
GY
TB1
(CLASS2)
RSS
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
IGNITOR
F1
F1
RD
RD
PK
Wiring Diagram with DDC — DCG 090*/ 102* 460, 575 / 3 / 60 2SP
SS-DCG7
SS-DCG7
www.daikincomfort.com
3A
IIC
IGNITOR
F1
F1
WH
PK
PK
WH
GY
WH
BL
PU
RD
RD
YL
YL
WH
BR
PK
PK
BL
BL
BL
BL
GY
BK
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
HEAT
PK
GR
GR BR
BR
BK
RD
WH
PK
BL
BL
GY
2
PU
RD
RD
BL
RD
GY
RD
GR
GR
VMR
GY
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RD
RS
YL
YL
RD
LS
1 GND
BL
BL
BL
PS
BL
BL
BK
WH
BL
BL
WH
BL
BK
BR
BL
(ISOL GND)
BL
(CO2)
(SPC TMP)
(SPC SLIDE ADJ)
(SPC HUM)
(OAH)
(OAT)
(ECON FB)
(SUPPLY AIR TMP)
1ST STG COM 2ND STG
GV
2 24VAC
AGND
AGND
AI6
AI7
AI8
RD
5
4
3
2
1
8 AI3
7 AI4
6 AI5
(BAC
NET)
WH
PK
WH
BK
BR
BR
BR
BR
BR
BR
HTR PLF1
11
22
RD
BR
BK
BL
BL
BL
OR
RD
1
RD
RD
VM
OR
BK
6
RD
OR
BK
BK
BK
RD
OR
PU
BK
RD
OR
BK
OR
OR
RD
BK
OR
OR
RD
YL
BK
BK
RD
OR
RD
OR
RD
BK
BK
OR
BK
BL
BL
BK
ALS
ALRM
BC
BCS
BM
CB
CC
CF
CFS
COMP
CO2
DAT
DDC
ECON
EXF
FC
FS
GND
GV
HGRH
HPS
IAH
IIC
LS
LDS
LPS
OAT
OAH
PB
PLF
PLM
PS
RS
RSS
SMK
SPC
TEMP
TB
TR
VM
VMR
BL
BL
UNUSED
IIC
OR
6
VMR
3
BK
WH
SPACE TEMPERATURE SENSOR
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
VENT MOTOR
VENT MOTOR RELAY
AUXILIARY LIMIT SWITCH
ALARM
BLOWER CONTACTOR
BLOWER CURRENT SWITCH
BLOWER MOTOR
CIRCUIT BREAKER
COMPRESSOR CONTACTOR
CONDENSER FAN
CLOGGED FILTER SWITCH
COMPRESSOR
CARBON DIOXIDE SENSOR
DISCHARGE AIR TEMPERATURE SENSOR
DIRECT DIGITAL CONTROL
ECONOMIZER
EXHAUST FAN
FAN CAPACITOR
FLAME SENSE
EQUIPMENT GROUND
GAS VALVE
HOT GAS REHEAT
HIGH PRESSURE SWITCH
INDOOR AIR HUMIDITY SENSOR
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LOAD SHEDDING
LOW PRESSURE SWITCH
OUTDOOR AIR TEMPERATURE SENSOR
OUTDOOR AIR HUMIDITY SENSOR
POWER DISTRIBUTION BLOCK
FEMALE PLUG/CONNECTOR
MALE PLUG/CONNECTOR
PRESSURE SWITCH
ROLL-OUT SWITCH
REMOTE START/STOP
SMOKE DETECTOR
COMPONENT LEGEND
BL
WH
BK
BK
RD
OR
BR
OPTIONAL ACCESSORIES
OR FIELD SUPPLIED
COMPONENTS
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
T1
⚡
L1
L2
L3
L1
PB
BK
RD
BK
BL
BL
RD
RD
RD
RD
RD
RD
L3
L2
L1
L3
L1
FC2
FC1
YL
BR
BK
PU
BK
BR
PU
BK
BR
PU
BK
BR
PU
T1 YL
T2 BL
T3 GY
BK
RD
T1
OR
T3
T2
T2
T2
CB2
(LO SPD)
L1
L2
BL L2
GY
BK
BK
RD
YL
BL
BL
BK
BL
CB1
(HI SPD)
OR L3
RD
YL
BL
RD
T1
L3
COMP1
BM
CF2
CF1
BK
BK
BK
YL
YL
YL
COMP2
T3
T1
T3
GND
L1
L2
2
IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
TB1-XS TO TB1-ES.
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
6
5
0140L05774-A
VM WIRED FOR 230V SUPPLY POWER. FOR 208V SUPPLY
POWER, DISCONNECT THE RED VM WIRE FROM CC1-L2
TERMINAL. CONNECT THE RED WIRE REMOVED FROM CC1-L2
TO IIC UNUSED TERMINAL, THEN DISCONNECT BLACK WIRE
FROM IIC-UNUSED AND CONNECT TO CC1-L1.
TR1 PRIMARY (HIGH VOLTAGE) CONNECTIONS: RED WIRE
CONNECTED TO 240V TAP AT THE FACTORY.FOR 208V
SUPPLY POWER, MOVE RED WIRE FROM 240V TAP TO THE
208V TAP.
4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
3
BL
BL
LINE
VOLTAGE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
NOTES:
T1
T2
T3
T1
T3
T2
L2
BC2
T2
T3
T1
T2
T3
CC1
BC1
CC2
BL
OR
L3
L1
L2
L3
L1
L2
L3
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL LOW VOLTAGE
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
BK
WH
RD
RD
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
BL
BR
WH
+ ALRM -
BK
WH
WH
BK
BR
RD
OR
RD
BK
BK
BK
RD
RD
OR
BK
BK
BR
WH
BK
BR
BR
PU
OR
+ EXF -
BR
WH
BK
BK
BL
BL
BL
BL
BL
RD
RD
BR
BR
BR
BR
WH
BK
BL
GR
5
RD
+ HGRH -
WH
BAC NET
BR WH
BL
4
BR
YL
PU
24V CNTL
VOLTAGE
LINE
VOLTAGE
HTR PLM1
TR1
OR
ECON
PLF 6 5 4 3 2 1
RD
YL PU PK
WH
BR
YL
PU
PU
BR
BK
YL
1 WH
2
3
4
5
6
BR
BK
BR
AO1
AO2
AO3
AO4
GND
GND
R+ 1
SH 2
T- 3
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
(EMER)
(FAN PROV)
(24V IN)
(ECON PWR)
(BLOWER STAGE 1)
(BLOWER STAGE 2)
(HEAT 1)
(HEAT 2)
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
POWER & CONTROL WIRING DIAGRAM
DCG(120-150) ***(3)V
DDC
PU
RD
BL
RD
BL
RD
GR
GR
GR
GR
BK
BR
9 AI2
8
7
6
5
4
3
2
1
PU 10 AI1
PK
BK
YL
PU
BK
BR
SPCTEMP
TEMP
STPT OFFSET
GND
PU
YL
BK
PK
PU BK PK PU YL
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
PU
YL
XS DA
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BK
BR
RD
BK
RD
T T TTT C
PS
1 2 345 S
BL/PK
24VAC
TB2
(CLASS2)
VOUT DC
GND
24 VAC
IAH
OAH
VOUT (DC)
GND
24 VAC
BR
-t°
OAT
HPS2
HPS1
SMK/EMG
1
2
3
4
TMP LMT IN
5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
3
-t°
DAT
GR
BR
BR
CFS
LDS
RSS
WH
RD
GY
TB1
(CLASS2)
PK
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
PK
RD
RD
PK
Wiring Diagram with DDC — DCG 120* / 150* 208-230 / 3 / 60 2SP
41
42
www.daikincomfort.com
3A
WH
PK
PK
WH
GY
WH
BL
PU
RD
RD
YL
YL
WH
BR
PK
PK
BL
BL
BL
BL
GY
BK
FLAME SENSE
24 VAC L1
PWR
L1
L2
24 VAC L2
COM L2
L2
VENT MTR D1
HEAT
PK
GR
GR BR
BR
BK
RD
BL
WH
PK
BL
GY
2
PU
RD
RD
BL
RD
GY
RD
GR
GR
VMR
GY
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RD
RS
YL
YL
RD
LS
PU
RD
BL
RD
BL
RD
GR
GR
1 GND
BL
BL
BL
BL
BK
WH
BL
WH
BL
BK
BR
BL
(ISOL GND)
BL
(CO2)
(SPC TMP)
(SPC SLIDE ADJ)
(SPC HUM)
(OAH)
(OAT)
(ECON FB)
WH
WH
1 WH
2
3
4
5
6
BR
BK
BR
AO1
AO2
AO3
AO4
GND
GND
PK
BR
BR
BR
BR
BR
BR
BK
WH
BR
YL
PU
PU
BR
BK
YL
HTR PLF1
11
22
RD
BR
WH
WH
BK
BK
WH
BR
BL
BL
BK
BL
BR
WH
+ ALRM -
+ EXF -
+ HGRH -
WH
BAC NET
BR
BL
4
BK
BK
BL
BL
BL
BL
BL
WH
WH
BR
BK
BL
IIC
UNUSED
BL
BK
BR
BK
1
VMR
BK
OR
OR
OR
COMPONENT LEGEND
BR
BR
WH
BL
PU
BL
BK
3
RD
RD
OR
BK
RD
BK
WH
BR
BK
OR
OR
OR
RD
RD
BK
BK
RD
BK
RD
OR
BR
BK
BK
BC2
T3
T2
L1
L2
L3
T1
T2
T3
T1
L2
L1
L3
PB
RD
BK BK
BL
BL
RD
RD
RD
L3
L2
L1
YL
BL
YL
T1
L3
FC2
FC1
L1
PU
BR
BK
PU
BK
BR
T1
T2
T3
CB2
(LO SPD)
L1
BL L2
GY
BK
T3
T2
L2
OR L3
RD
BL
CB1
(HI SPD)
BK
RD
YL
BL
BL
BK
RD
BK
BR
PU
BK
BR
PU
YL
BL
GY
BK
RD
OR
T2
T2
L3
COMP1
T1
BM
CF2
CF1
BK
BK
BK
YL
YL
YL
COMP2
T3
T1
T3
GND
L1
L2
BL
BL
LINE
VOLTAGE
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
5
0140L05772-A
RED/BLACK WIRES CONNECTED TO APPROPRIATE HIGH
VOLTAGE (460V OR 575 V) INPUT TERMINAL ON PRIMARY
SIDE OF TR1.
4 IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT
ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED
IN THE RETURN AIR COMPARTMENT.
FACTORY WIRING
NOTES:
HIGH VOLTAGE
LOW VOLTAGE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE
OPTIONAL LOW VOLTAGE
OF INSULATION AS ORIGINAL (AT LEAST 105° C).
USE COPPER CONDUCTORS ONLY.
FIELD WIRING
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE
FIELD CONNECTIONS.
HIGH VOLTAGE
LOW VOLTAGE
2 IF OPTIONAL SMOKE DETECTOR IS INSTALLED,
REMOVE RED JUMPER WIRE CONNECTIONS
OPTIONAL ACCESSORIES
TB1-XS TO TB1-ES.
OR FIELD SUPPLIED
COMPONENTS
3 DISCHARGE AIR TEMPERATURE SENSOR SHIPPED
WITH UNIT IN CONTROL BOX. INSTALL AND CONNECT
PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
VM
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIPE
BL/PK BLUE WITH
PINK STRIPE
BK
WH
RD
460V
OR
575V
230V
COM
BC1
T1
L1
RD
BK
BK
T3
T2
L3
CC2
T1
T2
T3
CC1
L2
OR
L1
L2
L3
BL
OR
RD
OR
PU
RD
RD
BK
BK
OR
BK
OR
OR
YL
BK
OR
RD
BK
TR3
BK
RD
OR
BK
BK
BK
RD
RD
OR
BK
BR
BK
OR
RD
BK
OR
RD
OR
BK
OR
OR
RD
AUXILIARY LIMIT SWITCH
ALS
ALRM ALARM
BC
BLOWER CONTACTOR
BCS
BLOWER CURRENT SWITCH
BM
BLOWER MOTOR
CIRCUIT BREAKER
CB
COMPRESSOR CONTACTOR
CC
CF
CONDENSER FAN
CFS
CLOGGED FILTER SWITCH
COMP COMPRESSOR
CO2
CARBON DIOXIDE SENSOR
DAT
DISCHARGE AIR TEMPERATURE SENSOR
DDC
DIRECT DIGITAL CONTROL
ECON ECONOMIZER
EXF
EXHAUST FAN
FAN CAPACITOR
FC
FLAME SENSE
FS
EQUIPMENT GROUND
GND
GV
GAS VALVE
HGRH HOT GAS REHEAT
HPS
HIGH PRESSURE SWITCH
IAH
INDOOR AIR HUMIDITY SENSOR
IIC
INTIGRATED IGNITION CONTROL
LIMIT SWITCH
LS
LOAD SHEDDING
LDS
LPS
LOW PRESSURE SWITCH
OAT
OUTDOOR AIR TEMPERATURE SENSOR
OAH
OUTDOOR AIR HUMIDITY SENSOR
PB
POWER DISTRIBUTION BLOCK
PLF
FEMALE PLUG/CONNECTOR
PLM
MALE PLUG/CONNECTOR
PS
PRESSURE SWITCH
RS
ROLL-OUT SWITCH
RSS
REMOTE START/STOP
SMOKE DETECTOR
SMK
SPC
TEMP SPACE TEMPERATURE SENSOR
TB
TERMINAL BLOCK (24V SIGNAL)
TR
TRANSFORMER
VENT MOTOR
VM
VENT MOTOR RELAY
VMR
BR
BR WH
BL
BR
BR
BK
5
RD
BK
GR
BL
OR
YL
PU
24V CNTL
VOLTAGE
LINE
VOLTAGE
HTR PLM1
ECON
PLF 6 5 4 3 2 1
RD
YL PU PK
OR
TR1
POWER & CONTROL WIRING DIAGRAM
DCG(120-150) ***(4,7)V
DDC
PS
BL
(ECON DMPR)
(MOD HGRH)
(EXF)
(ALRM)
R+ 1
SH 2
T- 3
COM1 1
RLY1 2
RLY2 3
COM2 4
RLY3 5
RLY4 6
RLY5 7
RLY6 8
RLY7 9
RLY8 10
COM3-8 11
COM3-8 12
(BAC
NET)
(SUPPLY AIR TMP)
1ST STG COM 2ND STG
GV
2 24VAC
AGND
AGND
AI6
AI7
AI8
(EMER)
(FAN PROV)
(24V IN)
(ECON PWR)
(COMP PRESS 1)
(COMP PRESS 2)
(RMT STRT/STP)
(SHED)
(CFS)
BL
5
4
3
2
1
8 AI3
7 AI4
6 AI5
(COMP2 OUT)
(COMP2 IN)
(COMP1 IN)
(COMP1 OUT)
DDC (CLASS2)
PK
PU
YL
(BLOWER STAGE 1)
(BLOWER STAGE 2)
(HEAT 1)
(HEAT 2)
RD
GR
GR
BK
BR
9 AI2
8
7
6
5
4
3
2
1
PU 10 AI1
PK
BK
YL
PU
BK
BR
SPCTEMP
TEMP
STPT OFFSET
GND
PU
YL
BK
PK
PU BK PK PU YL
PU
YL/PK
YL/PK
PU
LPS2
LPS1
BK
BK
PU
PU
YL
XS DA
⚠ Warning
BL
FS
ALS
GR
AG
VOUT (DC)
GND
24VAC (COM)
24 VAC
CO2
YL/PK
ES
PK RD PU
PK
BCS
PK
YL/PK
PU YL BK
BL
PK
BL
C
BL/PK
BK
BR
RD
BK
RD
T T TTT C
PS
1 2 345 S
BL/PK
24VAC
TB2
(CLASS2)
VOUT DC
GND
24 VAC
IAH
OAH
VOUT (DC)
GND
24 VAC
BR
-t°
OAT
HPS2
HPS1
SMK/EMG
1
2
3
4
TMP LMT IN
5
PRESS SW IN 6
PRESS SW OUT 8
HEAT IN 10
24 VAC PWR
24 VAC COM
GV OUT
TMP LMT OUT
IIC
3
-t°
DAT
GR
BR
BR
CFS
LDS
WH
RD
GY
TB1
(CLASS2)
RSS
BL/PK
BL/PK
PU
GR
PU
PU
BL/PK
BL/PK
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
IGNITOR
F1
F1
RD
RD
PK
Wiring Diagram with DDC — DCG 120*/ 150* 460, 575 / 3 / 60 2SP
SS-DCG7
Accessories
Filed-Installed
Item #
Fits
Model Sizes
Description
FieldInstalled
FactoryOperating
Installed Weight (lbs)
14CURB90150
14" Roof Curb
7½-12½ tons
√
143
D25FD90150
25% Manual Fresh Air Damper
7½-12½ tons
√
15
D25MFD90150
25% Motorized Fresh Air Damper
7½-12½ tons
√
21
DBRD3672
Barometric Relief Damper (2 required)
7½-12½ tons
√
30
DDNBBS90150
Burglar Bar Sleeves: includes Supply & Return
7½-12½ tons
√
45
CDK120
Concentric Duct Kit
10 tons
√
104
CDK150
Concentric Duct Kit
12½ tons
√
151
CDK90102
Concentric Duct Kit
7½-8½ tons
√
42
HailGD02D
Condenser Coil Hail Guard
7½-10 tons
√
34
HailGD05D
Condenser Coil Hail Guard
12½ tons
√
37
Convenience Outlet: Powered
All Models
√
42
Convenience Outlet: Non Powered
All Models
√
2
All Models
√
5
√
137
√
130
Disconnect Switch (non-fused)
Ultra Low-Leak Downflow Economizer
7½-12½ tons
Low-Leak Downflow Economizer3
7½-12½ tons
√
2
DDNECNJ90150B
DDNSQRD9020
HAKT36300
7½ tons
√
Electric Heat Kits
Downflow Square-to-Round Adapter 20" Round
All Models
√
High-Altitude Kit
All Models
√
55
√
21
1
HSKT090G¹
High-Static Kit (230/460v)
7½ tons
√
10
HSKT102¹
High-Static Kit (230/460v)
8½ tons
√
10
HSKT090G-7¹
High-Static Kit (575v)
7½ tons
√
10
HSKT102-7¹
High-Static Kit (575v)
8½ tons
√
10
HSKT120¹
High-Static Kit (230/460v)
10 tons
√
48
HSKT120-7¹
High-Static Kit (575v)
HSKT150¹
High-Static Kit (230/460v)
HSKT150-7¹
High-Static Kit (575v)
DHZECNJ90150
Horizontal Economizer
GHRC-1
Hurricane Restraint Clips
10 tons
√
48
12½ tons
√
80
12½ tons
√
80
7½-12½ tons
√
90
All Models
√
2
LAKT03
Low-Ambient Kit
7½-12½ tons
√
DPE901502
Downflow Power Exhaust (208/230v)
7½-12½ tons
√
√
65
2
DPE901504
Downflow Power Exhaust (460v)
7½-12½ tons
√
65
DPE901507
Downflow Power Exhaust (575v)
7½-12½ tons
√
65
3PMNDK01
Phase Monitor - Non DDC
3-20 tons
√
√
2
Smoke Detector (supply and/or return air)
All Models
√
11
Hinged Panels
3-12½ tons
√
34
√
2
√
2
DDC communicating controller (built-in BACnet® MS/TP)
DLAKT03
Low-Ambient*
LONKT01
LonWorks®*
3PMK01
Phase Monitor*
DFSKT01
Dirty Filter Switch*
3-20 tons
7½-20 tons
√
3-20 tons
√
3-20 tons
√
3-12½ tons
√
1
√
2
1
HSKT High-Static Kits are for use with standard single-speed belt-drive units only.
2
Please contact RRS Rooftop Systems directly if Power Exhaust is required. Ultra Low-Leak economizer for DDC controls.
3
Please use part number DPE901502 / DPE901504 / DPE901507 if Power Exhaust is required.
1
Note: Where multiple variations are available, the heaviest combination is listed.
*Indicates accessories for use with DDC models only.
SS-DCG7
www.daikincomfort.com
43
Notes
Our continuing commitment to quality products may mean a change in specifications without notice.
© 2016
• Houston, Texas • Printed in the USA.
44
www.daikincomfort.com
SS-DCG7

Similar documents

TECHNICAL GUIDE R-410A ZF SERIES 6-1/2 - 12

TECHNICAL GUIDE R-410A ZF SERIES 6-1/2 - 12 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1...

More information

Specs - Climate Solutions, Inc.

Specs - Climate Solutions, Inc. Drain Size (NPT) R-410A Refrigerant Charge (oz.) Evaporator Coil Face Area (ft²) Rows Deep/ Fins per Inch Tube Diameter/ Material Evaporator Fan Standard Direct Drive (D x W) HP Standard Belt Drive...

More information