fan powered terminals
Transcription
fan powered terminals
fan powered terminals open ceiling N Redefine your comfort zone. ™ | www.titus-hvac.com energy solutions Redefine your comfort zone™ | www.titus-hvac.com Table of Contents FAN POWERED TERMINALS N N2 N2 fan powered terminals fan powered terminals Fan Powered Terminal Products............................................................................................................................................................N4 overview Design Features.....................................................................................................................................................................................N6 Application Guidelines..........................................................................................................................................................................N7 Application Icons Key..........................................................................................................................................................................N10 series fan powered terminals TFS.......................................................................................................................................................................................................N11 Dimensions..................................................................................................................................................................................N12 Hot Water Coil Section................................................................................................................................................................N13 Electric Coil Section....................................................................................................................................................................N13 Additional Accessories (Optional)...............................................................................................................................................N13 TFS-A...................................................................................................................................................................................................N14 Dimensions..................................................................................................................................................................................N15 Hot Water Coil Section................................................................................................................................................................N16 Electric Coil Section....................................................................................................................................................................N16 Additional Accessories (Optional)...............................................................................................................................................N16 TFS-G...................................................................................................................................................................................................N17 Dimensions..................................................................................................................................................................................N18 Hot Water Coil Section................................................................................................................................................................N19 Electric Coil Section....................................................................................................................................................................N19 Additional Accessories (Optional)...............................................................................................................................................N19 TFS Performance Data.................................................................................................................................................................N20 TFS with ECM Motor Performance Data.....................................................................................................................................N26 TFS-F Fantom IQTM...............................................................................................................................................................................N30 Dimensions..................................................................................................................................................................................N31 Hot Water Coil Section................................................................................................................................................................N32 Electric Coil Section....................................................................................................................................................................N32 Additional Accessories (Optional)...............................................................................................................................................N32 TFS-F Performance Data..............................................................................................................................................................N33 TFS-F with ECM Motor Performance Data..................................................................................................................................N38 AHRI Directory of Certified Performance....................................................................................................................................N41 TQS with UltraLocTM Liner, TQS with UltraLocTM Liner and ECM Motor.............................................................................................N42 Dimensions..................................................................................................................................................................................N43 Hot Water Coil Section................................................................................................................................................................N44 Electric Coil Section....................................................................................................................................................................N44 Additional Accessories (Optional)...............................................................................................................................................N44 TQS with UltraLocTM Features.....................................................................................................................................................N45 TQS with UltraLocTM Liner Performance Data.............................................................................................................................N46 TQS with UltraLocTM Liner and ECM Motor Performance Data..................................................................................................N50 TQS with IAQ.......................................................................................................................................................................................N52 Dimensions..................................................................................................................................................................................N53 Hot Water Coil Section................................................................................................................................................................N54 Electric Coil Section....................................................................................................................................................................N54 Additional Accessories (Optional)...............................................................................................................................................N54 TQS with Indoor Air Quality (IAQ) Inlet Features........................................................................................................................N55 TQS with IAQ Performance Data.................................................................................................................................................N56 Table of Contents (continued) fan powered terminals FLS...................................................................................................................................................................................N57 Dimensions..................................................................................................................................................................................N58 Hot Water Coil Section................................................................................................................................................................N59 Electric Coil Section....................................................................................................................................................................N59 Additional Accessories (Optional)...............................................................................................................................................N59 Performance Data........................................................................................................................................................................N60 AHRI Directory of Certified Performance....................................................................................................................................N63 DLSC....................................................................................................................................................................................................N64 Dimensions..................................................................................................................................................................................N65 Hot Water Coil Section................................................................................................................................................................N66 Electric Coil Section....................................................................................................................................................................N67 Additional Accessories (Optional)...............................................................................................................................................N68 Performance Data........................................................................................................................................................................N69 parallel fan powered terminal TQP......................................................................................................................................................................................................N72 Dimensions..................................................................................................................................................................................N73 Hot Water Coil Section................................................................................................................................................................N74 Electric Coil Section....................................................................................................................................................................N74 Additional Accessories (Optional)...............................................................................................................................................N74 Performance Data........................................................................................................................................................................N75 low profile parallel terminal Redefine your comfort zone™ | www.titus-hvac.com low profile series terminals N FLP.......................................................................................................................................................................................................N82 Dimensions..................................................................................................................................................................................N83 Hot Water Coil Section................................................................................................................................................................N84 Electric Coil Section....................................................................................................................................................................N84 Additional Accessories (Optional)...............................................................................................................................................N84 Performance Data........................................................................................................................................................................N85 AHRI Directory of Certified Performance....................................................................................................................................N89 electric coils Features...............................................................................................................................................................................................N91 FAN POWERED TERMINALS N3 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com Fan Powered Terminals Products N series fan powered terminals pages: N11-N56 TFS TFS-F Fantom CONSTANT VOLUME TERMINAL CONSTANT VOLUME TERMINAL CONSTANT VOLUME TERMINAL • Quiet, efficient operation • Pressure independent airflow control • 150-3800 cfm flow range • Ultra quiet FAST™ attentuator system • Pressure independent airflow control • 350-2400 cfm flow range • Available with UltraLoc™ or with IAQ inlet • Pressure independent airflow control • 300-3200 cfm flow range low profile series terminals FAN POWERED TERMINALS pages: N57-N71 N4 N4 TQS FLS DLSC CONSTANT VOLUME TERMINAL INDUCTION TERMINAL • 10 1/2” overall unit height • Pressure independent airflow control • 300-1700 cfm flow range • Under 12” high on all sizes for application on shallow ceiling plenums • Pressure independent airflow control • ETL Listed fan powered terminals Fan Powered Terminal Products (continued) TQP VARIABLE VOLUME TERMINAL Redefine your comfort zone™ | www.titus-hvac.com parallel fan powered terminals pages: N72-N81 • Quiet, efficient operation • Pressure independent airflow control • 300-2000 cfm fan flow range N low profile parallel terminals pages: N82-N90 VARIABLE VOLUME TERMINAL • 10 1/2” overall unit height • Pressure independent airflow control • 200-900 cfm flow range FAN POWERED TERMINALS FLP N5 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com Design Features N LEADING THE INDUSTRY: TITUS FAN POWERED TERMINALS Titus continues to lead the industry with the broadest line of fan powered terminals available today. Whether your application requires series or parallel flow, Titus fan powered terminals outperform and outlast other industry offerings. Titus’ line of fan powered terminals include the series flow TFS for quiet applications and the parallel flow TQP for standard plenum height designs. Titus fan terminals are available from 150 to 3800 cfm, providing the utmost in flexibility for the system designer. All Titus fan terminals are designed for maximum performance with matched motor/blower combinations, rugged construction, and energy-efficient fan motors produced to our specifications for reliable operation. Additionally, all Titus fan powered terminals are agency listed, providing the assurance that Titus units meet today’s safety standards. For high performance, quality and dependability, specify the Titus fan powered terminal! In those applications with exceptionally limited plenum space, the Titus FLS and FLP low profile units provide the widest airflow range available in the industry. Energy efficient motor: State of the art, permanent split capacitor motors produced to Titus specifications run quietly, reliably, and maintenance-free for years. Solid construction: Rugged galvanized steel casing with dual density insulation results in quiet operation and long life. Titus terminals meet NFPA 90A (25/50) and UL 181 requirements. Optional ultra high efficiency ECM motor available on the TFS provide constant CFM independent of changes in downstream static pressure. Reassurance of agency listings: The entire fan section and all electrical components have been qualified and are ETL listed. In addition, all fan powered terminals are rated in accordance with AHRI Standard 880. Certification performance data rating points are reported to and check tested by AHRI for accuracy. Modular Design: Converts quickly between different inlet and/or fan unit sizes. Allows for stocking of parts for warehousing. AeroCrossTM multi-point, center averaging flow sensor. Provides accurate low flow sensing, regardless of inlet duct configuration. Two Casing Footprints: Simplifies the design layout. Precise solid state fan speed control: Titus SCR fan speed controls assure primary airflow matches design requirements, minimizing the need for fan balancing dampers. Easy accessibility: Full width bottom access panels permit quick, easy maintenance of all internal components. Panels are insulated for added sound attenuation. DESIGN FEATURES Additionally, all Titus fan powered terminals are complete with these time/cost saving, field-friendly features: N6 N6 • Titus reduces field balancing and start-up labor by taking extra steps to assure consistent quality and superior performance • Maximum and minimum primary air quantities are factory set when controls are supplied by Titus • Factory set pneumatic electric switches • Fan motors and heaters are energized and checked for amperage • Dielectric tests are performed on each terminal unit after assembly • • • • • • • Quality audits are completed on each component Each terminal is run tested at the factory before shipment Select Titus fan powered terminals for improved system design Provide perimeter heating and cooling without reheat Lower operating costs as well as lower first cost All-metal control enclosure to protect controls in field and shipping Retrofit tight spaces with ease, using low-profile configurations fan powered terminals APPLICATION GUIDELINES Select from two basic types of fan powered terminals: • Parallel Flow (Variable Volume) • Series Flow (Constant Volume) GENERAL Fan powered variable air volume (VAV) terminals are a popular choice for heating and cooling perimeter zones. In addition to the inherent VAV economies, fan powered terminals make use of the “free” heat that collects in the ceiling plenum after being emitted by lighting, people, and other equipment. Reasonable first cost, capacity for improved air motion, and low operating costs are additional reasons for the popularity of fan powered VAV terminals. The table, “Summary of Fan Powered Terminal Characteristics” highlights both parallel and series fan terminals. SUMMARY OF FAN POWERED TERMINAL CHARACTERISTICS FUNCTION The basic difference in configuration of these terminals is shown in the figures, “Parallel Flow, Fan Powered Terminal” and “Series Flow, Fan Powered Terminal.” In a parallel flow terminal, the fan is outside the primary airstream and runs intermittently, that is, when the primary air is off. In a series flow terminal, the fan is in the primary airstream and runs constantly when the zone is occupied. SERIES FAN POWERED TERMINALS Variable Volume Fan Powered VAV System Constant Volume Fan Powered VAV System Fan Operation Intermittent. Runs only during heating and low cooling loads, or on night cycle. Continuous. Runs during heating and cooling and on night cycle. cfm delivery to the occupied space Variable during mid to high cooling loads, or night cycle. Constant during heating and low cooling periods. Constant. From fan and air handler. Discharge air temperature Constant during mid to high cooling loads. All air is from central fan. Variable during heating and low cooling loads. Supplemental heat raises temperature in stages. Variable. Primary and plenum air mix in varying proportions during cooling. Supplemental heat raises temperature in stages. Fan sizing For design heating load (typically 60% of cooling) at reduced downstream static pressure due to reduced airflow. For design cooling cfm (typically 100% of cooling) at medium downstream static pressure. Minimum primary air inlet static pressure Higher (0.4 to 0.7 inch wg) to overcome damper, downstream duct, and diffuser losses. Lower (0.1 to 0.4 inch wg) to overcome damper pressure loss only. Fan control From thermostat signal. No central fan interlock required. Interlock with central system fan to prevent over pressurizing. Terminal fan Cycles while in occupied and unoccupied heating modes. Runs continuously during occupied mode, cycles during unoccupied. Central fan Static pressure to overcome damper, duct, and diffuser losses. Requires higher horsepower. Static pressure to overcome damper pressure loss only. Requires lower horsepower. Acoustics Fan off during mid to high cooling. Similar to non-fan terminal. During heating and low cooling, fan cycling may be audible. Fan operation and discharge sound are continuous during both heating and cooling. APPLICATION Either parallel or series flow fan powered terminals can be installed in the ceiling plenum. Each type takes its return air from the ceiling plenum or else has its induction port connected to a duct from the occupied space. Each contains a VAV damper to modulate primary air, plus a fan-and-motor assembly. PARALLEL FAN POWERED TERMINALS Parallel Flow, Fan Powered Terminal Unit Discharge Backdraft Damper Fan/Motor N APPLICATION GUIDELINES While both types of fan powered terminals provide VAV energy savings at the central fan, they differ from each other in their inlet static pressure requirements. Redefine your comfort zone™ | www.titus-hvac.com CHARACTERISTICS OF PARALLEL AND SERIES FLOW FAN POWERED TERMINALS Induced Air Inlet Primary Air Valve N7 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com APPLICATION GUIDELINES Parallel flow terminals, like non-fan terminals, require enough inlet static pressure to force the air through the primary air damper, casing, downstream ductwork, and diffusers. Typically, the resistance is 0.2 inch wg. for the damper and 0.3 inch wg. for ductwork and diffusers, or a total of 0.5 inch wg. In series flow terminals the fan boosts the air through the discharge duct and diffusers, so the inlet static pressure must only overcome losses through the primary air damper. As a result, the central fan and duct system can be designed for less inlet static pressure, typically 0.1 to 0.2 inch wg. PARALLEL FLOW TERMINALS Parallel flow or variable volume fan powered terminals operate in two distinct modes: 1.variable volume, constant temperature when handling high cooling loads; 2.constant volume, variable temperature when heating or handling light cooling loads The figure, “Parallel Flow Operation” illustrates the operating sequence of the parallel flow terminal. N During full cooling, the controls open the primary air damper for full airflow while the fan is off. As the cooling load decreases, less primary air is delivered to the zone. During this phase the primary air section acts like a nonfan terminal. As cooling demand decreases still further, the fan starts. This boosts air delivery to the zone by inducing warm plenum air into the colder primary air. The total air volume delivered to the zone is now the constant volume provided by the fan plus the primary inlet. The primary air damper may be set to some minimum position or else fully closed. The delivered air temperature approaches that of the plenum, taking advantage of heat captured in the plenum from lights, occupants, and equipment. Series flow or constant volume terminals are often selected for their acoustical qualities. The sound level is nearly constant as the fan runs continuously (with parallel flow terminals, on-off fan operation can cause noticeable changes in sound levels in the occupied space). Low temperature and ice storage applications capitalize on the temperature blending characteristic of series flow terminals. Models with low temperature liner mix cold supply air with warm plenum air to deliver the required air temperature to the zone. The low supply air temperature permits downsizing the central air handling system, branch ducts, and primary air valve. Series flow terminals are also selected where it is desirable to maintain a constant cfm, regardless of load. Such areas include lobbies, hallways, restrooms, atriums, and conference rooms. The figure, “Series Flow Operation” shows the operating sequence of the series flow terminal. The terminal fan starts whenever the zone is occupied. It delivers design cfm at all times. Pressure independent controls modulate the primary air damper to maintain the volume called for by the thermostat, regardless of changes in inlet static pressure. As the cooling load decreases, the controls throttle the primary air. The terminal fan makes up the difference by taking more return air from the plenum. This causes the air temperature to vary with the load. At low cooling loads, the primary air damper may close or go to a minimum ventilation setting. As the zone temperature decreases, the zone thermostat energizes stages of optional supplemental heat. The sequence reverses when the load is increased. CAUTION: The series flow fan must be adjusted to handle the maximum primary air volume. If the primary air exceeds the fan cfm, it will spill into the return air plenum and waste energy. The SCR fan speed control provides this adjustment. The minimum voltage stop should be set at 50 percent of rated voltage. As the zone temperature drops further, the thermostat automatically energizes supplemental electric or hot water heating coils (optional equipment on the terminal). The discharge air temperature increases as heat is added. A call for cooling reverses the sequence. Designers choose series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. Series Flow, Fan Powered Terminal Parallel Flow Operation Fan/Motor Percent Design CFM Unit Discharge Induced Air Inlet N8 N8 100 75 Primary Air Valve Total Air 50 Plenum Air 25 0 Delivered Air Temp. (F) APPLICATION GUIDELINES SERIES FLOW TERMINALS 110 100 Primary Air Cold Room Fan + Heat Fan Only Hot Room Cooling 90 80 70 60 50 Cold Room Hot Room fan powered terminals APPLICATION GUIDELINES Percent Design CFM Delivered Air Temp. (F) Total Air 100 Plenum Air 75 50 25 110 100 90 80 70 60 50 0 Primary Air Cold Room Fan + Heat Fan Only Cold Room Hot Room Cooling Series flow terminals may produce a slightly higher overall sound level in the occupied space than do parallel flow terminals. Both the primary air damper and the terminal fan act as sound sources; each generates both discharge (airborne) and radiated sound. Usually, it is the radiated sound that predominates in a room. Hot Room Radiated fan sound differs between types of terminals because of different air volume requirements. Series flow terminal fans must be sized to deliver design cooling volume, while parallel flow terminal fans can be downsized to deliver a smaller volume, generally 50 to 65 percent of design cooling cfm. As a result, parallel flow terminals normally can have smaller fans with lower sound levels. Room noise arising from parallel flow terminals may change with airflow. The intermittent fan operation causes a change in radiated sound as the fan motor starts and stops. This change may be more discernible than a constant sound, even if the constant sound is at a higher level. SYSTEM CONSIDERATIONS Series terminal fans should be interlocked to be energized ahead of the central fan to prevent backflow of primary air into the ceiling plenum and to prevent backward rotation of the terminal fan. The interlock can be electrical, by means of an auxiliary contact in the central fan starter for line voltage or a 24 VAC loop for analog electronic controls; pneumatic, using a PE switch; or direct digital, with coordinated start times of terminals and central fans on a communicating digital network. ENERGY CONSUMPTION Series flow terminal fans run during all occupied, and some unoccupied periods, ranging from 3,000 to 4,000 hours annually. Parallel flow terminal fans run during periods of heating and low-load cooling with operating times ranging from 500 to 2,000 hours annually, depending upon the climate and other factors. Series flow terminal fans are selected to deliver design cooling cfm, while parallel flow fans are selected to deliver design heating cfm. Typically, this ranges from 50 to 65 percent of cooling design cfm. For example, a series flow terminal might be selected for 1,000 cfm. A parallel flow terminal fan selected for the same duct system might be selected for 60 percent of this airflow or 600 cfm. Note that the lower airflow requirements will also result in reduced downstream static pressure, falling in this case from 0.55 inch down to 0.20 inch wg. A comparison between the two types of fan powered VAV systems, the energy savings at the central fan must be credited to the series flow fan terminal. The table, Fan Powered Terminal Operating Costs is a comparison of a series flow and parallel flow system. This comparison is typical of the “standard” terminals on the market. By using quieter, more efficient series flow terminals such as the Titus DTFS, the system could be designed with larger zones and the same NC. This would lower first costs and narrow (or possibly eliminate) the cost differential between the two systems. AVAILABLE CONTROLS TYPES Titus offers three types of available controls, they are as follows. • Pneumatic, Pressure Independent Models: PTFS, PTQS, PFLS, PTQP, and PFLP • Analog Electronic, Pressure Independent Models: ATFS, ATQS, AFLS, ATQP, and AFLP Fan Powered Terminal Operating Costs • Digital Electronic, Central Fan Series Flow Parallel Flow Pressure Independent Fan cfm 30,000 30,000 Models: DTFS, DTQS, Annual operating 4,000 4,000 DFLS, DTQP, and DFLP hours A schematic for each type of control appears on the next page. Static Pressure (wg.) kW demand 2.6 3.0 10.7 12.5 42,900 50,000 $0.07 $0.07 $12.00 $12.00 Elec. consump. cost $2,996.00 $3,500.00 Demand charge $1,540.80 $1,800.00 Total fan operating cost $4,536.80 $5,300.00 kWh consumption Elec. cost/kWh Monthly demand chg/kW Terminals Number of zones Fan cfm/zone Annual operating hours Watts demand/ terminal Total kW demand Series Flow Parallel Flow 30 30 1,000 2,000 4,000 2,000 424 245 12.72 7.35 Total kWh comsunption 50,880 14,770 Elec. cost/kW $0.07 $0.07 $12.00 $12.00 Elec. consump. cost $3,561.60 $1,029.00 Demand charge $1,831.68 $1,058.40 Total terminal operating cost $5,393.28 $2,087.40 Total system operating cost $9,930.00 $7,387.40 Monthly demand chg/kW N APPLICATION GUIDELINES An energy consumption analysis should include terminals as well as the central equipment. The energy used by the terminal fan is a function of the operating hours and fan loading. These will vary by terminal type — parallel flow (variable volume) or series flow (constant volume). With fewer hours of operation and lower airflow requirements, a parallel flow terminal consumes less energy than a series flow terminal. Series flow fan powered terminals, however, reduce the pressure a central air handler must operate under. With parallel flow fan terminals, the central fan must overcome the terminal damper, downstream duct work, and the diffuser. With series flow fan terminals, the central fan only needs to overcome the terminal damper. The terminal fan addresses the downstream duct work and diffuser. Redefine your comfort zone™ | www.titus-hvac.com ACOUSTICS Series Flow Operation N9 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com APPLICATION GUIDELINES ECM MOTOR TECHNOLOGY - THE ULTIMATE IN ENERGY SAVINGS! A substantial energy savings can be realized when using an ECM motor in a series flow fan terminal compared to using conventional induction motors. The ECM motor is an ultra-high efficiency, brushless DC motor with a unique microprocessor based motor controller. Motor efficiencies of 70 percent or better across the entire operating range of the motor saves considerable electrical energy when compared to conventional induction motors. The motor controller, tuned to a Titus fan powered terminal, provides a large turn down ratio and constant volume airflow regardless of changes in downstream static pressure operating against the fan. Features and related benefits of the ECM motor in a Titus fan powered terminal are: • 70 percent motor efficiency across the entire operating range of the motor yields substantial electrical savings/payback in less than two years • Microprocessor based internal motor control maintains constant airflow regardless of changes in downstream static pressure N APPLICATION ICONS KEY contributes toward energy savings by reducing operating costs of air distribution devices APPLICATION GUIDELINES energy solutions N10 N10 can be used in open ceiling environments open ceiling • Motor operates efficiently down to 300 rpm providing a wide operating range covering most applications • Simplify design layout with fewer models to choose from due to increased fan range • Increased application flexibility due to larger operating range • Unique fan speed control provides simple manual or remote adjustment through the unit direct digital controls (DDC) • Factory preset fan airflows minimize fan terminal balancing efforts • Ball bearing design and low heat rise characteristics substantially increase motor life See the section, Engineering Guidelines and the topic ‘ECM Motors - Fan Powered Terminals’ for additional information. See specific models for ECM performance data. Series Fan Powered Terminals fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com TFS • Two casings for easy design layout • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional TITAN™ programmed ECM motor provides ultra-high efficiency, pressure independent operation • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • 20-gauge galvanized steel casing • Centered, rectangular discharge opening is designed for flanged duct connections TFS • Top and bottom access panels can be removed for service energy solutions AVAILABLE MODELS: open ceiling See website for Specifications N PTFS / Pneumatic Control ATFS / Analog Control DTFS / Digital Control OVERVIEW Quiet Operation Designers choose Series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. ADDITIONAL FEATURES • Rectangular discharge opening is designed for flanged duct connections • Dual density insulation, coated to prevent air erosion, meet requirements of NFPA 90A and UL 181 TFS terminal unit installed in an open ceiling environment TFS N11 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS TFS UNIT DIMENSIONS TFS / Sizes B-E 3 B 3 /8 20 N 12 6¼ A Primary Air Inlet with AeroCross Multipoint Center Averaging Sensor C W F G Induced Air Inlet K L E N Size B C D A 6 6 7 8 6 6 7 8 7 8 10 11 8 10 11 B C 8 12½ 10 12 D 57/8 77/8 97/8 117/8 57/8 77/8 97/8 117/8 97/8 117/8 137/8 157/8 117/8 137/8 157/8 H TFS Series Unit F G E H J K L 14¼ 141/8 11½ 16 111/8 2¼ 43 18¼ 16½ 11¼ 20 145/8 2 47½ DIMENSIONS E Unit 6 8 10 12 6 8 10 12 10 12 14 16 12 14 16 N12 N12 J All dimensions are in inches N 27/8 27/8 47/8 47/8 27/8 27/8 47/8 47/8 47/8 47/8 67/8 67/8 47/8 67/8 67/8 W Filter Size 37 16 x 14 39 14 x 18 fan powered terminals DIMENSIONS STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins • Connections: Male solder 5 /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit R 1" COIL ROWS • 1-Row • 2-Row 9 • 120V, 1 ph, 60 Hz. • 208/240V, 1 ph, 60 Hz. • 277V, 1 ph, 60 Hz. STANDARD FEATURES • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals S Hot Water Coil Section (Discharge Mounted) Unit Size M (1-Row) M (2-Row) R B, C 1 1 20½ D, E 1 1¼ 25 SUPPLY VOLTAGE ELECTRIC COIL SECTION M S 12½ 17½ Redefine your comfort zone™ | www.titus-hvac.com HOT WATER COIL SECTION Note: R and S are inside dimensions • Magnetic contactor per step on terminals with DDC or analog electronic controls • • • • • OPTIONS • • • • • • N SUPPLY VOLTAGE Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction Optional Lynergy Comfort Controlled SSR Electric Heat available 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 12 31 6¼ Heater Rack Access Cover 1" Typ. R Electric Coil Section (Discharge Mounted) Unit Size U R S T B, C 14½ 11½ 113/8 23/8 D, E 11 17 15 31/8 U Note: R and S are inside dimensions See Electric Heat Coils in Section O for more information • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • 1” Liner • Fibre-Free Liner • SteriLoc Liner • EcoShield liner • Fan unit fusing • Hanger brackets • Camlocks on fan access door Unit Size B C D E Motor HP /6 /4 1 /3 3 /4 1 1 Electrical Data 120V FLA 2.3 4.0 8.5 8.6 208/240V FLA 0.9 1.8 3.6 4.2 T 277V FLA 0.8 1.4 3.0 4.5 All motors are single phase, 60(Hz). FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye) For ECM electrical data see page N27 DIMENSIONS ADDITIONAL ACCESSORIES (OPTIONAL) S 9¾ N13 Redefine your comfort zone™ | www.titus-hvac.com Series Fan Powered Terminals (continued) fan powered terminals TFS-A • Two casings for easy design layout • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional TITAN™ programmed ECM motor provides ultra-high efficiency, pressure independent operation • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • 20-gauge galvanized steel casing • Centered, rectangular discharge opening is designed for flanged duct connections TFS-A • Bottom access panels can be removed for service N AVAILABLE MODELS: PTFS-A / Pneumatic Control ATFS-A / Analog Control DTFS-A / Digital Control OVERVIEW Quiet Operation TFS-A Designers choose Series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. N14 N14 See website for Specifications fan powered terminals DIMENSIONS TFS / Size A 1 92 1 2 28 A Primary Air Inlet with AeroCross™ Multipoint Center Averaging Flow Sensor Control Enclosure 1 64 F D W 7 1 34 7 68 G 3 38 L Redefine your comfort zone™ | www.titus-hvac.com TFS-A UNIT DIMENSIONS H 2 N Induced Air Inlet B E C Unit Size Inlet Size A B C D E F G H L W Filter Size A 6” Diameter 6 14 8 57/8 3 55/8 51/4 101/2 48 21 10 x 16 DIMENSIONS All dimensions are in inches N15 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS HOT WATER COIL SECTION STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins, 10 per inch • Connections: Male solder 5 /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit Slip & Drive Connection 18 1/2 COIL ROWS • 1-Row • 2-Row 3.00 SUPPLY VOLTAGE 2 1/4 ELECTRIC COIL SECTION STANDARD FEATURES • Auto reset thermal cutouts (one per element) • Single point electrical connection for entire unit • Positive pressure flow switch • Transformer OPTIONS • Fuse Block • Disconnect switch, door interlock type • Manual reset cutout SUPPLY VOLTAGE DIMENSIONS • • • • • N16 N16 181 10 • 120V, 1 ph, 60 Hz. • 208/240V, 1 ph, 60 Hz. • 277V, 1 ph, 60 Hz. N 921 1 1/8 Typ. 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 921 HEATER COVER 941 3 44 1021 1" TYP. 11 916 7 816 ADDITIONAL ACCESSORIES (OPTIONAL) • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • Fibre-Free Liner • Fan unit fusing • Hanger brackets • Camlocks on fan access door • EcoShield Liner Unit Size A Motor HP ⁄10 1 Electrical Data 120V 208/240/1/60V FLA FLA 1.3 0.6 277/1/60V FLA 0.5 All motors are single phase, 60(Hz). FLA = Full Load Amperage, as tested in accordance with UL 1995. All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye). For ECM electrical data see page N27 Series Fan Powered Terminals (continued) fan powered terminals • Two casings for easy design layout • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional TITAN™ programmed ECM motor provides ultra-high efficiency, pressure independent operation • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • 20-gauge galvanized steel casing • Centered, rectangular discharge opening is designed for flanged duct connections TFS-G Redefine your comfort zone™ | www.titus-hvac.com TFS-G • Bottom access panels can be removed for service AVAILABLE MODELS: See website for Specifications N PTFS-G / Pneumatic Control ATFS-G / Analog Control DTFS-G / Digital Control OVERVIEW Quiet Operation Designers choose Series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. ADDITIONAL FEATURES • Rectangular discharge opening is designed for flanged duct connections • Dual density insulation, coated to prevent air erosion, meet requirements of NFPA 90A and UL 181 TFS-G N17 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS TFS-G UNIT DIMENSIONS TFS / Size G 15 81 Induced Air Inlet 11 Primary Air Inlet with AeroCross Multipoint Center Avg. Sensor 15 81 52 26 15 81 15 1 8 Induced Air Inlet Left hand unit, top view shown Inlet Size Filter Size G 16 17 x 17 DIMENSIONS Unit Size N18 N18 1 41 10 15 78 N 18 39 81 All dimensions are in inches 32 fan powered terminals DIMENSIONS STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins, 10 per inch • Connections: Male solder. ⅝” for both 1-row and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit SUPPLY VOLTAGE • 120V, 1 ph, 60 Hz. • 208/240V, 1 ph, 60 Hz. • 277V, 1 ph, 60 Hz. 34.00 COIL ROWS • 1-Row • 2-Row 1.00 1 2 8 15 Redefine your comfort zone™ | www.titus-hvac.com HOT WATER COIL SECTION ELECTRIC COIL SECTION STANDARD FEATURES • Single side access to low and high voltage and electric heater controls • Auto reset thermal cutouts (one per element) • Single point electrical connection for entire unit • Positive pressure flow switch • Flanged duct connection • Coil is installed at discharge of unit • Transformer N 31 12 6 1/4 Heater Rack Access Cover 9 OPTIONS • • • • • 34 Fuse Block Disconnect switch, door interlock type Manual reset cutout Dust tight construction Mercury contactors 1" Typ. 12 SUPPLY VOLTAGE • • • • • 15 2 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) (OPTIONAL) • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • 1” Liner • Fibre-Free Liner • SteriLoc Liner • EcoShield liner • Fan unit fusing • Hanger brackets • Camlocks on fan access door Unit Size G Electrical Data 208/240/1/60V Motor HP FLA (2) 3/4 13.2 277/1/60V FLA 9.9 FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye) For ECM electrical data see page N27 DIMENSIONS ADDITIONAL ACCESSORIES N19 fan powered terminals PTFS, ATFS, DTFS / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE TFS Size B TFS Size A 500 700 650 450 600 400 550 350 500 CFM CFM 300 350 200 300 150 250 100 50 N 200 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 150 0.6 TFS Size C 0.1 0.2 0.3 0.4 0.5 Downstream Static Pressure (Inches of Water) 0.6 TFS Size D 1900 1200 1800 1100 1700 CFM 1000 1600 900 800 1400 1200 1100 1000 500 900 400 300 1500 1300 600 800 0 0.1 0.2 0.3 0.4 0.5 Downstream Static Pressure (Inches of Water) 700 0.6 TFS Size E 0 2700 4000 2600 3800 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 TFS Size G 2500 3600 2400 2300 3400 2200 3200 CFM 2100 CFM PERFORMANCE DATA 0 2000 1300 700 2000 1900 3000 2800 1800 2600 1700 2400 1600 1500 2200 1400 1300 N20 N20 450 400 250 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil 2000 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 fan powered terminals PERFORMANCE DATA Redefine your comfort zone™ | www.titus-hvac.com PTFS, ATFS, DTFS / PRIMARY AIR INLET PRESSURE PRIMARY AIR INLET PRESSURE / PTFS, ATFS, DTFS 3000 2000 1000 . 900 . . . n. 6 in 0 in 4 in 2 in 12 i 800 -E 1 . -C 1 -E 1 -C 1 D-E B D B 8 in Airflow, 700 Size D e e e e z z z i S Si Si Siz B-C cfm 600 Size 500 400 300 200 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. Note: For selection procedure, see the Engineering Guidelines and the topic, ‘Sizing Basic Terminals from Capacity Tables’. N PERFORMANCE DATA N21 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTFS, ATFS, DTFS / WATER COIL HEATING CAPACITY (MBH) Unit Size Rows One Row A Two Row Unit Size Rows One Row N B Two Row Unit Size Rows One Row C Two Row PERFORMANCE DATA Unit Size Rows One Row D Two Row Unit Size Rows One Row E N22 N22 Two Row gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 Head Loss 0.83 3.15 12.03 26.37 Airside DPs 0.22 0.82 3.14 6.87 Airside DPs Head Loss 0.14 0.52 1.99 4.36 Airside DPs 0.14 0.54 2.10 4.66 Airside DPs Head Loss 0.14 0.52 2.00 4.37 Airside DPs 0.14 0.54 2.10 4.66 Airside DPs Head Loss 0.23 0.86 3.28 7.16 Airside DPs 0.48 1.80 6.80 14.85 Airside DPs Head Loss 0.23 0.86 3.28 7.16 Airside DPs 0.48 1.80 6.80 14.85 Airside DPs 200 9.8 10.7 11.2 11.3 0.01 14.0 15.7 16.6 17.0 0.02 250 11.0 12.1 12.7 12.9 0.02 15.9 18.1 19.4 19.9 0.04 300 12.0 13.3 14.0 14.3 0.02 17.5 20.2 21.9 22.5 0.05 200 10.7 11.7 12.4 12.6 0.01 14.9 16.7 17.8 18.2 0.01 250 11.9 13.3 14.1 14.5 0.01 16.9 19.4 20.9 21.5 0.02 300 13.0 14.7 15.7 16.1 0.01 18.7 21.7 23.7 24.4 0.03 400 14.7 16.9 18.3 18.9 0.02 21.5 25.7 28.6 29.7 0.05 490 16.0 18.6 20.4 21.0 0.03 23.4 28.7 32.3 33.8 0.06 580 17.0 20.1 22.1 22.9 0.04 25.0 31.2 35.6 37.4 0.08 800 24.0 29.3 32.9 34.3 0.03 34.3 44.5 51.8 54.7 0.06 925 25.2 31.1 35.3 36.9 0.03 36.1 47.7 56.3 59.8 0.08 1050 26.2 32.8 37.4 39.3 0.04 37.5 50.4 60.3 64.3 0.09 1400 28.5 36.5 42.4 44.9 0.07 40.5 56.7 69.7 75.3 0.15 1525 29.1 37.6 43.9 46.6 0.08 41.3 58.5 72.6 78.7 0.17 1650 29.7 38.6 45.4 48.2 0.09 42.1 60.1 75.2 81.9 0.20 Airflow, cfm 400 450 13.6 14.3 15.3 16.2 16.3 17.3 16.7 17.7 0.04 0.04 20.1 21.1 23.8 25.3 26.2 28.1 27.1 29.1 0.08 0.10 Airflow, cfm 350 400 450 13.9 14.7 15.5 15.9 16.9 17.9 17.1 18.3 19.5 17.6 18.9 20.1 0.02 0.02 0.02 20.2 21.5 22.6 23.8 25.7 27.4 26.2 28.6 30.7 27.1 29.7 32.0 0.04 0.05 0.06 Airflow, cfm 670 760 850 17.9 18.7 19.4 21.3 22.5 23.5 23.7 25.1 26.4 24.6 26.1 27.5 0.05 0.06 0.07 26.4 27.5 28.5 33.4 35.4 37.1 38.6 41.3 43.7 40.7 43.7 46.5 0.11 0.13 0.16 Airflow, cfm 1175 1300 1425 27.1 27.9 28.6 34.2 35.5 36.7 39.3 41.1 42.7 41.4 43.4 45.2 0.05 0.06 0.07 38.7 39.8 40.7 52.9 55.1 57.0 63.9 67.2 70.3 68.5 72.4 76.0 0.11 0.13 0.15 Airflow, cfm 1775 1900 2025 30.2 30.7 31.2 39.6 40.4 41.3 46.7 48.0 49.1 49.7 51.1 54.5 0.10 0.12 0.13 42.7 43.3 43.8 61.6 63.0 64.3 77.7 80.0 82.2 84.9 87.7 90.3 0.22 0.25 0.28 350 12.9 14.3 15.2 15.6 0.03 18.9 22.1 24.1 24.9 0.06 500 14.9 17.0 18.2 18.7 0.05 22.1 26.7 29.8 31.0 0.11 550 15.5 17.7 19.1 19.6 0.06 22.9 28.0 31.4 32.8 0.13 600 16.0 18.4 19.9 20.4 0.07 23.7 29.2 33.0 34.5 0.15 500 16.1 18.8 20.6 21.3 0.03 23.6 29.0 32.7 34.2 0.07 550 16.7 19.6 21.6 22.3 0.03 24.5 30.4 34.6 36.3 0.08 600 17.2 20.4 22.5 23.3 0.04 25.3 31.8 36.3 38.2 0.09 940 20.0 24.4 27.5 28.8 0.09 29.4 38.7 45.9 49.0 0.19 1030 20.5 25.2 28.6 30.0 0.10 30.2 40.1 48.0 51.4 0.22 1100 20.9 25.8 29.4 30.8 0.11 30.7 41.1 49.5 53.1 0.24 1550 29.2 37.8 44.2 46.9 0.08 41.5 58.8 73.1 79.4 0.18 1675 29.8 38.8 45.6 48.5 0.09 42.2 60.4 75.8 82.5 0.20 1800 30.3 39.8 47.0 50.0 0.11 42.8 61.9 78.2 85.4 0.23 2150 31.6 42.0 50.2 53.8 0.14 44.3 65.5 84.3 92.8 0.31 2275 32.0 42.8 51.3 55.0 0.16 44.7 66.6 86.2 95.2 0.34 2400 32.3 43.4 52.3 56.1 0.17 45.1 67.6 88.0 97.5 0.37 fan powered terminals PERFORMANCE DATA Unit Size Rows One Row G Two Row • • • • • • • • • • • • gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 Head Loss 0.25 0.93 3.52 7.69 Airside DPs 0.52 1.95 7.34 15.97 Airside DPs Airflow, cfm 2300 2425 2550 2675 2800 2925 34.1 34.4 34.8 35.1 35.4 35.7 46.1 46.8 47.5 47.1 48.7 49.3 55.6 56.7 57.7 58.7 59.7 60.6 59.7 61.0 62.2 63.4 64.5 65.5 0.12 0.14 0.15 0.16 0.17 0.19 46.4 46.8 47.2 47.5 47.8 48.1 70.0 71.1 72.1 73.0 73.9 74.7 91.6 93.5 95.4 97.2 98.8 100.4 101.5 104.0 106.3 108.5 110.7 112.7 0.27 0.29 0.32 0.34 0.37 0.40 All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180BF entering water and 65BF entering air For temperature differentials other than 115B, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Connection size is 5/8” OD male solder Coils are not intended for steam applications and are labeled for a maximum water temperature of 200BF Coils are tested for leakage at test pressure of 500 psi Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. 3050 36.0 49.9 61.5 66.6 0.20 48.3 75.5 101.9 114.7 0.43 3175 36.3 50.4 62.3 67.5 0.22 N/A N/A N/A N/A N/A 3300 36.5 50.9 63.1 68.5 0.23 N/A N/A N/A N/A N/A Redefine your comfort zone™ | www.titus-hvac.com PTFS, ATFS, DTFS / WATER COIL HEATING CAPACITY (MBH) N Correction factors for other entering conditions: ∆T 50 60 70 80 90 100 115 125 140 150 Factor 0.44 0.52 0.61 0.70 0.79 0.88 1.00 1.07 1.20 1.30 PERFORMANCE DATA N23 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PERFORMANCE DATA N N24 N24 PTFS, ATFS, DTFS / RADIATED SOUND PERFORMANCE Size A06 B08 CFM 200 250 275 300 350 350 400 450 500 550 C10 550 650 800 950 1100 D12 1000 1150 1300 1450 1600 E14 1500 1650 1800 1950 2100 G16 2400 2500 2600 2700 2800 Discharge Ps Min ∆Ps Octave Band Sound Power, Lw 3 0.5" ∆Ps 4 5 6 7 NC 2 3 1.0" ∆Ps 4 5 6 7 NC 2 3 1.5" ∆Ps 4 5 6 7 NC 2 3 Fan Only 4 5 6 0.01 0.01 0.01 0.01 0.01 0.03 0.04 0.05 0.06 0.07 57 59 60 60 62 58 60 62 64 66 48 50 51 52 54 54 56 58 59 61 47 48 48 48 49 51 52 53 55 56 40 42 44 45 47 46 48 50 52 53 33 36 38 39 41 36 38 41 43 44 24 28 30 32 35 33 37 39 42 44 21 22 22 22 24 25 27 28 30 31 62 65 66 68 70 57 58 59 61 62 53 57 58 59 62 52 54 56 57 58 48 50 51 52 53 51 53 54 55 56 44 46 47 48 50 48 49 51 52 54 40 42 43 44 46 38 40 41 43 44 34 37 38 39 41 37 38 40 41 42 24 28 29 32 34 25 27 28 29 30 63 66 68 69 71 58 60 61 62 64 55 58 60 61 63 55 57 59 60 61 49 52 52 53 55 54 55 56 57 58 45 48 49 50 51 49 51 52 54 55 42 45 46 46 48 42 44 45 46 47 37 40 41 43 44 42 43 45 46 47 25 29 32 33 36 28 29 30 31 32 64 67 69 70 72 59 61 62 63 65 56 59 60 62 64 57 59 60 62 63 50 52 53 54 56 55 56 58 59 60 46 49 50 51 52 50 52 53 55 56 44 46 47 48 49 44 46 47 48 49 39 42 43 44 46 45 46 47 49 50 27 31 33 34 37 29 30 32 34 35 0.25 0.04 0.06 0.09 0.12 0.16 61 62 64 65 66 49 52 54 57 59 50 52 55 57 59 46 49 52 55 58 36 39 43 47 49 32 36 42 46 50 24 27 30 32 34 61 63 65 66 68 53 55 57 59 60 52 54 56 58 60 48 50 53 55 57 40 42 44 46 48 37 39 42 44 46 26 28 30 32 35 64 66 68 70 71 58 60 62 64 65 55 57 60 62 63 51 53 56 58 60 44 46 49 51 52 43 45 47 49 51 29 31 35 37 38 66 68 70 71 73 61 63 65 67 68 57 59 62 64 65 53 55 58 60 62 47 49 51 53 55 46 48 50 53 54 31 34 37 39 40 0.25 0.03 0.05 0.06 0.07 0.09 59 62 64 66 68 54 56 58 60 62 51 54 56 58 60 47 50 53 55 57 42 45 47 50 52 39 42 45 48 50 25 29 31 33 35 65 67 68 70 71 58 60 62 64 65 56 58 59 61 62 53 55 56 58 59 46 48 49 50 51 42 44 46 48 50 30 32 34 36 37 67 69 71 72 74 61 63 65 66 68 58 60 61 63 64 56 57 59 60 62 50 52 53 55 56 45 47 49 51 53 32 35 36 38 40 68 70 72 74 75 62 64 66 68 69 59 61 62 64 65 57 59 61 62 63 53 55 56 57 58 47 49 51 53 55 34 36 37 40 41 0.25 0.04 0.05 0.06 0.08 0.09 68 70 72 73 74 62 63 64 66 67 60 61 62 63 64 56 58 59 61 62 48 50 52 54 56 44 46 49 51 53 35 36 38 39 40 70 72 74 76 77 64 66 67 69 70 62 63 64 65 66 58 59 61 62 63 50 51 52 53 54 46 48 49 51 52 37 38 40 42 43 72 74 76 77 79 66 68 69 71 72 63 64 66 67 68 60 61 63 64 65 53 55 56 57 58 49 50 52 54 55 38 40 42 43 46 73 75 77 78 80 67 69 70 72 73 64 65 66 67 69 61 62 64 65 66 55 57 58 59 60 50 52 54 55 57 39 41 43 45 47 0.25 0.07 0.08 0.09 0.09 0.10 68 69 69 70 71 66 66 67 67 68 61 62 62 63 64 58 58 59 60 60 52 53 54 54 55 50 50 51 52 53 37 38 38 39 40 71 71 72 72 72 67 68 68 69 69 62 63 63 64 64 58 58 59 59 59 55 55 56 56 56 51 52 52 53 53 37 38 38 40 40 75 75 76 76 76 72 73 73 74 74 67 68 68 69 69 63 63 64 64 64 59 60 60 60 61 56 56 57 57 58 43 44 44 45 45 77 77 78 78 79 75 76 76 76 77 70 71 71 72 72 66 67 67 67 67 62 62 63 63 63 58 59 59 60 60 47 48 48 48 49 0.25 0.25 7 NC 2 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Size A06 B08 CFM 200 250 275 300 350 350 400 450 500 550 C10 550 650 800 950 1100 D12 1000 1150 1300 1450 1600 E14 1500 1650 1800 1950 2100 G16 2400 2500 2600 2700 2800 Discharge Ps Min ∆Ps Octave Band Sound Power, Lw 3 0.5" ∆Ps 4 5 6 7 NC 2 3 1.0" ∆Ps 4 5 6 7 NC 2 3 1.5" ∆Ps 4 5 6 7 NC 2 3 Fan Only 4 5 6 0.01 0.01 0.01 0.01 0.01 0.03 0.04 0.05 0.06 0.07 66 67 67 68 69 68 71 73 75 77 57 59 60 61 63 56 59 61 64 65 56 58 60 60 62 52 54 55 57 58 52 56 57 59 61 53 55 57 58 60 51 54 56 57 60 52 54 56 58 60 45 50 52 54 57 49 52 54 56 58 22 24 24 21 22 21 25 28 30 33 68 70 70 71 73 69 70 72 73 74 59 62 63 64 66 58 60 61 62 63 58 61 62 63 65 54 55 57 58 59 55 58 59 61 63 55 56 58 59 61 53 56 58 59 62 55 57 59 60 61 48 52 54 54 57 53 55 57 59 60 25 28 28 25 28 22 24 26 28 29 68 70 71 72 73 71 72 73 74 75 60 63 64 65 67 59 61 62 64 65 58 61 62 63 65 54 56 57 58 59 55 58 59 61 63 55 56 58 59 60 53 57 58 60 62 55 57 59 60 61 49 53 55 56 59 53 55 57 58 60 25 28 29 26 28 25 26 28 29 30 68 70 71 72 74 72 73 74 75 76 60 63 64 66 68 60 62 63 64 65 59 61 62 63 65 54 56 57 58 59 55 58 59 61 63 54 56 58 59 60 53 57 58 60 62 55 57 58 60 61 49 53 55 57 60 53 55 57 58 60 25 28 29 26 29 26 28 29 30 31 0.25 0.04 0.06 0.09 0.12 0.16 77 77 78 78 79 55 58 62 65 68 52 55 58 61 63 50 54 59 63 66 50 54 59 63 66 49 53 58 62 66 33 33 31 31 33 78 79 80 80 81 58 61 64 67 69 55 57 60 63 65 54 57 61 64 67 53 57 61 64 67 52 56 61 64 67 34 35 34 34 35 79 79 80 81 81 60 62 66 69 71 55 58 61 63 65 54 57 61 64 67 54 57 61 65 68 53 57 61 65 68 35 35 34 35 35 79 79 80 81 82 60 63 67 69 72 56 58 61 63 65 54 57 61 64 67 54 57 61 65 68 53 57 61 65 68 35 35 34 35 36 0.25 0.03 0.05 0.06 0.07 0.09 76 78 79 80 81 64 67 68 70 71 57 59 61 63 65 60 63 64 66 68 65 66 68 69 70 63 65 67 68 69 29 31 33 34 35 82 84 85 87 88 68 70 72 73 74 62 64 66 67 69 64 65 67 68 69 67 68 70 71 72 67 68 70 70 71 36 39 40 43 44 83 85 86 88 89 69 71 73 74 75 63 65 66 68 69 66 67 68 70 71 64 65 66 67 69 65 66 67 68 69 38 40 42 44 45 83 85 87 88 89 70 71 73 75 76 63 65 67 68 69 67 68 69 71 72 62 63 64 66 67 63 64 66 67 67 38 40 43 44 45 0.25 0.04 0.05 0.06 0.08 0.09 82 83 84 85 86 74 75 76 78 79 64 66 67 69 70 67 69 71 72 74 69 70 72 73 75 66 68 70 72 74 36 38 39 40 42 89 90 92 93 94 77 79 80 81 82 69 70 71 72 73 68 69 70 72 73 71 72 73 74 75 70 71 72 73 73 45 47 49 51 52 90 91 93 94 95 78 79 80 82 83 70 71 72 74 75 71 72 73 74 76 71 72 73 73 74 71 71 72 73 74 47 48 51 52 53 91 92 93 94 96 78 79 81 82 83 71 72 73 74 75 73 74 75 76 77 71 72 72 73 74 71 72 72 73 74 48 49 51 52 54 0.25 0.07 0.08 0.09 0.09 0.10 74 74 75 75 76 70 71 71 72 72 68 69 69 70 70 66 67 67 68 69 64 65 66 66 67 63 64 65 65 66 28 30 30 31 31 74 74 75 75 76 70 73 71 72 72 68 69 69 70 71 66 67 67 68 69 64 65 66 66 69 63 64 65 65 66 28 32 30 31 31 76 74 77 77 78 70 73 73 72 74 70 71 71 72 73 68 69 70 71 71 66 67 68 68 69 65 64 67 67 68 29 32 32 31 31 76 76 77 77 78 72 73 73 74 74 71 71 72 73 73 69 70 70 71 72 67 68 68 69 70 65 66 67 68 68 31 32 32 33 33 0.25 0.25 7 NC 2 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. N PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining Redefine your comfort zone™ | www.titus-hvac.com PTFS, ATFS, DTFS / DISCHARGE SOUND PERFORMANCE N25 fan powered terminals PTFS, ATFS, DTFS WITH ECM MOTOR / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE TFS w/ECM Size B TFS w /ECM Size A 800 500 450 700 400 350 600 CFM 300 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 250 500 200 150 400 100 50 300 0 0 0.1 0.2 0.3 0.4 0.5 0 0.6 0.1 Downstream Static Pressure (Inches of Water) N TFS w/ECM Size C 0.5 0.6 0.5 0.6 TFS w/ECM Size D 1900 1200 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 1800 1100 1700 1000 1600 1500 900 1400 1300 CFM CFM 800 1200 700 1100 600 1000 500 900 800 400 700 300 600 500 200 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0 0.6 5000 4500 2300 2200 4000 2100 3500 2000 1900 3000 CFM 1800 1700 CFM PERFORMANCE DATA 2400 1600 2500 2000 1500 1400 1500 1300 1200 1000 1100 500 1000 900 0 800 0 N26 N26 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) TFS w/ECM Size G TFS w/ECM Size E 2500 0.1 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 fan powered terminals PERFORMANCE DATA Redefine your comfort zone™ | www.titus-hvac.com PTFS, ATFS, DTFS WITH ECM MOTOR / PRIMARY AIR INLET PRESSURE PRIMARY AIR INLET PRESSURE / PTFS, ATFS, DTFS 3000 2000 1000 . 900 n. n. n. 6 in n. 12 i 10 i 800 14 i 12 i -E 1 . D e D-E B-C D-E B-C 8 in Airflow, 700 Siz e e e e z z z i z i i i S S S S B-C cfm 600 Size 500 400 300 200 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. Note: For selection procedure, See the section Engineering Guidelines and the topic ‘ECM Motors Fan Powered Terminals’ for additional information. N ECM ELECTRICAL DATA Unit Size Motor HP 1 A /3 1 B /3 1 C /3 1 D /2 3 E /4 G (2) 1 120V 5.0 5.0 5.0 7.7 9.6 25.6 208V 3.3 3.3 3.3 5.0 7.9 21.0 240V 2.8 2.8 2.8 4.3 6.8 18.2 277V 2.6 2.6 2.6 4.1 5.5 13.8 PERFORMANCE DATA N27 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTFS, ATFS, DTFS WITH ECM / RADIATED SOUND PERFORMANCE Size PERFORMANCE DATA G N28 N28 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 0.01 0.01 0.01 0.01 0.01 0.04 0.05 0.07 0.09 0.11 48 53 57 60 63 60 63 65 68 69 42 46 49 52 54 56 59 61 63 65 38 42 45 48 50 51 54 55 57 59 34 39 43 46 48 49 52 54 55 57 27 32 37 40 43 40 43 45 47 49 17 24 30 34 38 38 41 44 47 49 11 16 19 22 26 25 29 31 33 36 57 61 64 67 69 58 60 62 64 66 49 54 57 60 62 55 57 59 61 63 43 47 50 52 54 51 53 55 57 58 41 44 47 49 51 49 51 53 55 56 38 41 43 45 46 40 42 44 45 46 31 35 38 40 42 38 40 42 44 45 18 23 27 31 33 25 27 29 31 33 58 62 66 69 71 59 62 64 66 68 51 55 59 61 64 57 60 62 64 66 45 48 51 54 56 54 56 58 59 61 43 46 48 50 52 51 53 55 57 58 40 43 45 47 48 44 46 48 49 50 35 38 41 43 45 43 45 47 49 50 19 24 29 33 36 28 30 32 34 36 59 63 67 69 72 60 63 65 67 69 52 56 60 62 65 59 62 64 66 67 46 49 52 55 56 56 58 60 61 63 44 47 49 51 53 52 54 56 58 59 41 44 46 48 49 46 48 50 51 52 37 40 43 45 47 46 48 50 52 53 20 25 31 33 37 30 32 35 36 38 0.25 0.03 0.06 0.09 0.12 0.16 46 53 59 64 69 42 49 55 59 64 47 52 55 58 61 43 48 52 55 58 34 39 44 47 51 30 37 42 47 50 21 27 30 33 36 56 59 62 64 65 52 54 56 58 59 50 53 55 57 59 46 49 52 54 56 38 41 43 45 47 36 39 41 43 45 24 27 29 31 34 60 63 66 68 69 57 59 61 63 64 53 56 59 61 62 49 52 55 57 59 43 46 48 50 52 41 44 47 49 50 27 30 34 36 37 62 66 68 70 72 60 63 64 66 67 56 59 61 63 64 51 54 56 59 60 46 48 51 53 54 44 47 50 52 54 30 34 36 38 39 0.25 0.02 0.03 0.05 0.07 0.09 57 60 63 65 67 51 55 57 60 62 49 53 56 58 60 46 49 52 55 57 39 43 47 49 52 35 40 44 48 51 23 28 31 33 35 60 63 65 68 70 55 58 61 63 65 53 56 59 61 63 50 53 55 57 59 43 46 48 49 51 39 43 45 48 49 27 30 34 36 38 62 65 68 70 72 58 61 64 66 68 55 58 61 63 65 53 56 58 60 62 48 50 52 54 55 43 46 48 51 53 29 32 36 38 40 64 67 70 72 74 59 62 65 68 70 57 60 62 64 66 55 58 60 62 63 51 53 55 57 58 44 48 50 53 55 31 35 37 39 41 0.25 0.02 0.03 0.04 0.06 0.09 56 60 65 69 72 57 54 59 63 66 50 53 57 61 64 48 51 55 59 61 38 42 47 52 55 33 38 44 48 53 26 28 32 36 40 62 66 70 74 77 55 59 63 66 69 54 57 60 63 66 52 54 58 60 62 44 46 49 52 54 38 41 45 49 51 28 31 35 40 43 64 68 72 76 79 58 61 65 69 72 56 59 62 65 68 54 57 60 63 65 48 51 53 56 58 41 45 49 52 55 30 34 37 42 46 65 69 73 77 80 59 63 67 70 73 57 60 63 66 69 56 58 61 64 66 51 53 56 58 60 43 47 51 54 57 31 35 38 43 47 0.25 0.05 0.06 0.07 0.09 0.10 65 67 68 69 71 63 64 66 67 68 58 60 61 62 64 54 56 58 59 60 49 51 52 54 55 46 48 50 51 53 33 35 37 38 40 69 70 71 72 72 65 66 67 68 69 60 61 62 63 64 56 57 58 59 59 53 54 55 56 56 49 50 51 52 53 35 36 37 38 40 73 74 75 76 76 70 71 72 73 74 66 67 67 68 69 62 62 63 64 64 57 58 59 60 61 53 54 56 57 58 41 42 43 44 45 75 76 77 78 79 73 74 75 76 77 69 70 70 71 72 65 65 66 67 67 60 61 62 63 63 56 57 58 59 60 44 46 47 48 49 0.25 14 16 1.5" ∆Ps 6 8 E 1.0" ∆Ps 5 B 12 0.5" ∆Ps Fan Only 4 0.25 D Octave Band Sound Power, Lw 3 6 10 Min ∆Ps 2 A C N CFM Discharge Ps • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Size A06 B08 CFM 150 200 250 300 350 400 475 550 625 700 C10 500 650 800 950 1100 D12 800 1000 1200 1400 1600 E14 1000 1200 1500 1800 2100 G16 2000 2200 2400 2600 2800 Discharge Ps Min ∆Ps Octave Band Sound Power, Lw 0.5" ∆Ps Fan Only 1.0" ∆Ps 1.5" ∆Ps 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 0.01 0.01 0.01 0.01 0.01 0.04 0.05 0.07 0.09 0.11 56 60 63 65 67 74 75 76 77 77 50 54 57 59 61 63 65 66 67 68 51 55 58 60 62 58 59 60 61 62 47 52 56 59 62 59 60 62 63 64 45 50 54 57 60 58 60 61 63 64 41 47 51 54 57 57 59 60 62 63 10 15 19 18 21 29 30 31 33 33 59 63 66 69 71 67 70 73 75 78 53 57 61 63 65 57 60 63 66 68 55 58 61 63 65 51 54 57 59 61 51 55 59 62 64 53 57 59 62 64 49 53 57 60 63 54 57 60 63 65 45 50 54 57 60 51 55 59 62 64 13 19 22 22 25 20 24 28 30 34 60 64 67 69 72 68 71 74 76 78 54 58 61 64 66 57 61 64 67 69 55 58 61 63 65 52 55 57 59 61 51 55 59 62 64 54 57 60 62 64 49 53 57 60 63 54 57 60 63 65 46 51 55 58 60 51 55 59 62 64 15 20 24 23 26 21 25 29 31 34 60 64 67 70 72 68 71 74 76 79 54 59 62 64 66 58 61 64 67 69 55 58 61 63 65 52 55 57 60 61 50 55 59 62 64 54 57 60 62 64 49 53 57 60 63 54 57 60 63 65 46 51 55 58 61 51 55 59 62 64 15 20 24 24 26 21 25 29 31 35 0.25 0.03 0.06 0.09 0.12 0.16 70 72 74 75 76 62 64 65 67 68 57 59 60 61 62 58 60 62 63 64 58 61 62 64 65 57 59 61 63 64 24 26 26 28 29 67 70 73 76 78 57 62 65 68 71 52 56 59 62 64 52 57 61 64 67 50 56 60 64 67 49 55 59 63 67 20 24 25 29 31 68 71 74 77 79 58 62 66 69 72 52 56 59 62 64 52 57 61 64 67 51 56 60 64 67 49 55 60 64 67 21 25 26 30 33 68 72 75 77 79 58 63 66 69 72 52 56 60 62 65 52 57 61 64 67 51 56 61 64 67 49 55 60 64 67 21 26 28 30 33 0.25 0.02 0.03 0.05 0.07 0.09 69 71 73 74 75 59 61 63 65 66 54 56 58 59 60 57 59 61 62 63 59 61 62 64 65 58 60 61 63 64 22 24 25 27 28 68 71 74 76 78 53 57 61 65 67 53 57 61 64 67 55 59 62 65 68 53 58 62 65 68 51 57 61 65 68 19 22 26 29 31 68 71 74 76 78 55 59 63 67 69 55 60 63 67 69 57 61 65 68 70 54 59 63 66 69 53 58 62 66 69 19 22 26 30 32 68 71 74 76 78 56 61 64 68 71 57 61 65 68 71 59 63 66 69 71 55 60 64 67 70 53 59 63 67 70 19 23 27 30 33 0.25 0.02 0.03 0.04 0.06 0.09 77 78 80 82 83 62 67 71 75 79 55 59 63 67 70 59 62 67 70 74 59 62 67 71 75 55 60 65 70 74 30 31 34 36 39 77 79 82 84 85 70 72 75 77 79 64 66 69 71 73 64 66 69 71 73 66 68 71 73 75 63 66 69 72 75 30 33 36 39 40 78 80 82 84 86 72 74 76 79 80 66 69 71 74 76 67 69 72 74 75 67 70 73 75 77 65 68 71 74 76 31 34 36 39 42 78 80 82 84 86 72 75 77 80 81 68 70 73 75 77 69 71 73 75 77 69 71 74 76 78 66 69 72 75 77 31 34 37 40 42 0.25 0.05 0.06 0.07 0.09 0.10 71 73 74 75 76 68 69 70 71 72 66 67 68 69 70 62 64 66 67 69 61 63 64 66 67 61 62 63 65 66 26 27 28 30 31 71 73 74 75 76 68 69 70 71 72 66 67 68 69 70 62 64 66 67 69 61 63 64 66 69 61 62 63 65 66 26 27 28 30 31 71 73 76 77 78 70 69 70 73 74 68 67 70 71 73 64 66 68 70 71 61 65 66 68 69 61 62 65 67 68 28 27 29 32 33 71 73 76 77 78 70 69 72 73 74 68 69 71 72 73 65 67 69 70 72 63 65 67 68 70 63 64 65 67 68 28 28 31 32 33 0.25 0.25 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. N PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining Redefine your comfort zone™ | www.titus-hvac.com PTFS, ATFS, DTFS WITH ECM / DISCHARGE SOUND PERFORMANCE N29 Redefine your comfort zone™ | www.titus-hvac.com Series Fan Powered Terminals (continued) fan powered terminals TFS-F FANTOM IQ™ • Two casings for easy design layout • Integral patent pending FAST™ attenuator system, has internal and external attenuator sections • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional TITAN™ programmed ECM motor provides ultra-high efficiency, pressure independent operation • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections TFS-FANTOM IQ™ • 20-gauge galvanized steel casing N • Centered, rectangular discharge opening is designed for flanged duct connections • Top and bottom access panels can be removed for service open ceiling AVAILABLE MODELS: energy solutions See website for Specifications PTFS-F / Pneumatic Control ATFS-F / Analog Control DTFS-F / Digital Control OVERVIEW Quiet Operation The quietest fan powered terminal in the market is the TFS-F Fantom IQ™. The Fantom IQ™ utilizes the patent pending FAST™ attenuator system that greatly reduces radiated sound power levels. The unique FAST™ attenuator is shipped completely assembled inside the casing, and is easily pulled out and snapped into place for operation. TFS-F FANTON IQ™ The Titus TFS-F Fantom IQ™ terminal unit installed in an open ceiling environment of a corporate office N30 N30 fan powered terminals DIMENSIONS Redefine your comfort zone™ | www.titus-hvac.com TFS-F FANTOM UNIT DIMENSIONS TFS-F / Sizes B-E B 33/8 Primary Air Inlet with AeroCross Multipoint Center Averaging Sensor A 12 20 N 6¼ D W F X G Induced Air Inlet K Y Size B C D E ` Unit A 6 8 10 12 6 8 10 12 10 12 14 16 12 14 16 6 6 7 8 6 6 7 8 7 8 10 11 8 10 11 B X Y D 5 ⁄8 77⁄8 97⁄8 117⁄8 57⁄8 77⁄8 97⁄8 117⁄8 97⁄8 117⁄8 137⁄8 157⁄8 117⁄8 137⁄8 157⁄8 J H L TFS-F Fantom IQTM Series Unit Induced Air Inlet F G Height Width N H J K L 7 8 19 137⁄8 10 181⁄8 167⁄8 N 2 ⁄8 27⁄8 47⁄8 47⁄8 27⁄8 27⁄8 47⁄8 47⁄8 47⁄8 47⁄8 67⁄8 67⁄8 47⁄8 67⁄8 67⁄8 W Filter Size 37 11 x 14 39 18 x 17 7 125⁄8 8¾ 14 11½ 16 11 2¼ 43 165⁄8 15¾ 16½ 11¼ 20 145⁄8 2 46¾ DIMENSIONS All dimensions are in inches N31 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS HOT WATER COIL SECTION STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins • Connections: Male solder 5 /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit 1" COIL ROWS • 1-Row • 2-Row 9 STANDARD FEATURES • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls S M Hot Water Coil Section (Discharge Mounted) Unit Size M (1-Row) M (2-Row) R B, C 1 1 20½ D, E 1 1¼ 25 Note: R and S are inside dimensions ELECTRIC COIL SECTION N R • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls • Optional Lynergy Comfort Controlled SSR Electric Heat available SUPPLY VOLTAGE • • • • • OPTIONS • • • • • S 12½ 17½ Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 12 31 6¼ Heater Rack Access Cover 1" Typ. Electric Coil Section (Discharge Mounted) Unit Size U R S T B, C 113/8 14½ 11½ 23/8 D, E 11 17 15 31/8 R U DIMENSIONS Note: R and S are inside dimensions. See Electric Heat Coils in Section O for more information. N32 N32 9¾ ADDITIONAL ACCESSORIES (OPTIONAL) • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • 1” Liner • Fibre-Free Liner • SteriLoc Liner • EcoShield liner • Fan unit fusing • Hanger brackets • Camlocks on fan access door Unit Size B C D E Motor HP /6 /4 1 /3 3 /4 1 1 Electrical Data 120V FLA 2.3 4.0 8.5 8.6 S 208/240V FLA 0.9 1.8 3.6 4.2 277V FLA 0.8 1.4 3.0 4.5 All motors are single phase, 60(Hz). FLA = Full Load Amperage, as tested in accordance with UL 1995. All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye). For ECM electrical data see page N38 fan powered terminals PERFORMANCE DATA TFS-F Size B 700 1200 600 1100 550 1000 500 900 450 CFM CFM TFS-F Size C 1300 650 Redefine your comfort zone™ | www.titus-hvac.com PTFS-F, ATFS-F, DTFS-F / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE 400 800 700 350 600 300 500 250 400 200 150 300 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0 0.6 TFS-F Size D 2000 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 2600 1800 2500 1700 2400 0.6 TFS-F Size E 2700 1900 0.5 N 2300 1600 2200 1500 2100 CFM CFM 1400 2000 1300 1900 1200 1800 1100 1700 1000 1600 900 1500 800 1400 700 1300 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0 0.6 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil PRIMARY AIR INLET PRESSURE / PTFS-F, ATFS-F, DTFS-F PERFORMANCE DATA 3000 2000 1000 . 900 . . . n. 6 in 0 in 4 in 2 in 12 i 800 -E 1 . -C 1 -E 1 -C 1 D-E B D B 8 in Airflow, 700 Size D e e e e z z z i S Si Si Siz B-C cfm 600 Size 500 400 300 200 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. Note: For selection procedure, see the Engineering Guidelines and the topic, ‘Sizing Basic Terminals from Capacity Tables’. N33 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTFS-F, ATFS-F, DTFS-F / WATER COIL HEATING CAPACITY (MBH) Unit Size Rows One Row B Two Row Unit Size Rows One Row N C Two Row Unit Size Rows One Row D Two Row PERFORMANCE DATA Unit Size N34 N34 Rows One Row E Two Row gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 Head Loss 0.14 0.52 1.99 4.36 Airside DPs 0.14 0.54 2.10 4.66 Airside DPs Head Loss 0.14 0.52 2.00 4.37 Airside DPs 0.14 0.54 2.10 4.66 Airside DPs Head Loss 0.23 0.86 3.28 7.16 Airside DPs 0.48 1.80 6.80 14.85 Airside DPs Head Loss 0.23 0.86 3.28 7.16 Airside DPs 0.48 1.80 6.80 14.85 Airside DPs 200 10.7 11.7 12.4 12.6 0.01 14.9 16.7 17.8 18.2 0.01 250 11.9 13.3 14.1 14.5 0.01 16.9 19.4 20.9 21.5 0.02 300 13.0 14.7 15.7 16.1 0.01 18.7 21.7 23.7 24.4 0.03 400 14.7 16.9 18.3 18.9 0.02 21.5 25.7 28.6 29.7 0.05 490 16.0 18.6 20.4 21.0 0.03 23.4 28.7 32.3 33.8 0.06 580 17.0 20.1 22.1 22.9 0.04 25.0 31.2 35.6 37.4 0.08 800 24.0 29.3 32.9 34.3 0.03 34.3 44.5 51.8 54.7 0.06 925 25.2 31.1 35.3 36.9 0.03 36.1 47.7 56.3 59.8 0.08 1050 26.2 32.8 37.4 39.3 0.04 37.5 50.4 60.3 64.3 0.09 1400 28.5 36.5 42.4 44.9 0.07 40.5 56.7 69.7 75.3 0.15 1525 29.1 37.6 43.9 46.6 0.08 41.3 58.5 72.6 78.7 0.17 1650 29.7 38.6 45.4 48.2 0.09 42.1 60.1 75.2 81.9 0.20 Airflow, cfm 400 450 14.7 15.5 16.9 17.9 18.3 19.5 18.9 20.1 0.02 0.02 21.5 22.6 25.7 27.4 28.6 30.7 29.7 32.0 0.05 0.06 Airflow, cfm 670 760 850 17.9 18.7 19.4 21.3 22.5 23.5 23.7 25.1 26.4 24.6 26.1 27.5 0.05 0.06 0.07 26.4 27.5 28.5 33.4 35.4 37.1 38.6 41.3 43.7 40.7 43.7 46.5 0.11 0.13 0.16 Airflow, cfm 1175 1300 1425 27.1 27.9 28.6 34.2 35.5 36.7 39.3 41.1 42.7 41.4 43.4 45.2 0.05 0.06 0.07 38.7 39.8 40.7 52.9 55.1 57.0 63.9 67.2 70.3 68.5 72.4 76.0 0.11 0.13 0.15 Airflow, cfm 1775 1900 2025 30.2 30.7 31.2 39.6 40.4 41.3 46.7 48.0 49.1 49.7 51.1 54.5 0.10 0.12 0.13 42.7 43.3 43.8 61.6 63.0 64.3 77.7 80.0 82.2 84.9 87.7 90.3 0.22 0.25 0.28 350 13.9 15.9 17.1 17.6 0.02 20.2 23.8 26.2 27.1 0.04 For Performance Notes, see the next page 500 16.1 18.8 20.6 21.3 0.03 23.6 29.0 32.7 34.2 0.07 550 16.7 19.6 21.6 22.3 0.03 24.5 30.4 34.6 36.3 0.08 600 17.2 20.4 22.5 23.3 0.04 25.3 31.8 36.3 38.2 0.09 940 20.0 24.4 27.5 28.8 0.09 29.4 38.7 45.9 49.0 0.19 1030 20.5 25.2 28.6 30.0 0.10 30.2 40.1 48.0 51.4 0.22 1100 20.9 25.8 29.4 30.8 0.11 30.7 41.1 49.5 53.1 0.24 1550 29.2 37.8 44.2 46.9 0.08 41.5 58.8 73.1 79.4 0.18 1675 29.8 38.8 45.6 48.5 0.09 42.2 60.4 75.8 82.5 0.20 1800 30.3 39.8 47.0 50.0 0.11 42.8 61.9 78.2 85.4 0.23 2150 31.6 42.0 50.2 53.8 0.14 44.3 65.5 84.3 92.8 0.31 2275 32.0 42.8 51.3 55.0 0.16 N/A N/A N/A N/A N/A 2400 32.3 43.4 52.3 56.1 0.17 N/A N/A N/A N/A N/A fan powered terminals PERFORMANCE DATA • • • • • • • • • • • • Redefine your comfort zone™ | www.titus-hvac.com PTFS-F, ATFS-F, DTFS-F / WATER COIL HEATING CAPACITY (MBH) All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180BF entering water and 65BF entering air For temperature differentials other than 115B, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Connection size is 5/8” OD male solder Coils are not intended for steam applications and are labeled for a maximum water temperature of 200BF Coils are tested for leakage at test pressure of 500 psi Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Correction factors for other entering conditions: ∆T 50 60 70 80 90 100 115 125 140 150 Factor 0.44 0.52 0.61 0.70 0.79 0.88 1.00 1.07 1.20 1.30 N PERFORMANCE DATA N35 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTFS-F, ATFS-F, DTFS-F / RADIATED SOUND PERFORMANCE Octave Band Sound Power, Lw Size B08 C10 D12 N E14 CFM 375 400 450 500 550 600 700 800 900 1050 1000 1150 1300 1450 1600 1500 1650 1800 1950 2100 Discharge Ps 0.25 0.25 0.25 0.25 Min ∆Ps 0.03 0.04 0.05 0.06 0.07 0.05 0.07 0.09 0.11 0.15 0.03 0.05 0.06 0.07 0.09 0.04 0.05 0.06 0.08 0.09 0.5” ∆Ps Fan Only 2 56 57 59 61 63 62 63 63 64 65 62 64 66 68 69 70 71 73 74 75 3 43 44 47 49 51 49 51 53 54 56 52 54 55 57 58 63 65 67 68 70 4 42 43 45 47 48 46 48 49 51 53 47 49 51 52 53 56 58 59 61 62 5 35 36 38 40 41 39 42 44 46 49 42 44 46 48 49 51 52 54 55 57 6 35 35 36 36 37 35 37 38 40 42 37 40 42 43 45 46 48 50 51 53 7 32 32 33 33 34 33 34 36 37 38 31 35 38 40 43 42 44 46 48 50 NC 17 18 21 23 26 24 26 26 27 28 24 27 29 32 33 35 36 38 40 42 2 54 55 57 59 60 63 63 64 64 64 61 62 63 64 65 69 70 71 71 72 3 44 45 47 49 50 52 53 53 54 55 52 53 55 56 57 61 62 63 64 65 4 42 43 45 46 47 46 48 49 50 51 48 50 51 53 54 54 56 57 59 60 PERFORMANCE DATA • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining N36 N36 5 40 41 42 43 44 42 43 44 46 47 43 44 46 48 49 50 51 53 54 55 6 40 40 41 42 42 37 38 39 40 41 39 41 43 44 45 45 46 48 49 50 1.0” ∆Ps 7 37 37 38 39 40 33 34 35 36 37 35 37 39 40 41 41 43 44 45 46 NC 15 16 18 20 22 25 25 27 27 27 23 24 25 27 28 33 34 36 36 37 2 56 57 59 60 62 64 64 64 64 65 63 65 66 67 68 70 71 71 72 73 3 46 48 50 51 53 54 55 55 56 56 55 56 58 59 60 62 63 65 66 67 4 44 44 46 47 48 47 49 50 51 52 49 51 52 54 55 55 57 59 60 61 5 41 42 43 44 45 42 44 45 46 48 44 45 47 49 50 50 52 54 55 56 6 42 42 43 44 44 40 41 42 43 44 42 44 45 47 48 47 49 50 51 52 1.5” ∆Ps 7 40 40 41 42 43 39 40 41 41 42 40 42 43 45 46 45 46 48 49 50 NC 17 18 20 22 24 27 27 27 27 28 25 28 29 31 32 34 36 36 37 38 2 57 58 59 61 62 64 64 65 65 65 65 66 68 69 70 70 71 72 73 74 3 48 49 51 53 55 55 56 56 57 57 56 58 59 60 61 63 64 66 67 68 4 44 45 46 48 49 48 49 50 52 53 50 52 53 55 56 56 58 59 61 62 5 42 43 44 45 46 43 45 46 47 49 44 46 48 49 51 51 53 54 55 57 6 43 43 44 45 45 42 43 44 45 46 43 45 47 48 49 48 50 51 53 54 7 42 42 43 44 45 42 43 44 45 46 43 45 46 48 49 47 49 50 51 53 NC 18 19 20 23 24 27 27 28 28 28 28 29 32 33 34 34 36 37 38 40 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Octave Band Sound Power, Lw Size B08 C10 D12 E14 CFM 375 400 450 500 550 600 700 800 900 1050 1000 1150 1300 1450 1600 1500 1650 1800 1950 2100 Discharge Ps 0.25 0.25 0.25 0.25 Min ∆Ps 0.03 0.04 0.05 0.06 0.07 0.05 0.07 0.09 0.11 0.15 0.03 0.05 0.06 0.07 0.09 0.04 0.05 0.06 0.08 0.09 0.5” ∆Ps Fan Only 2 65 66 68 70 71 69 71 73 74 76 66 69 72 74 76 78 79 81 82 84 3 51 52 55 58 60 62 64 66 68 70 61 64 67 69 71 73 75 76 78 79 4 52 53 54 55 56 55 57 59 60 62 57 59 61 63 65 65 66 68 69 70 5 50 51 53 55 57 54 57 59 61 64 58 61 63 66 68 67 69 71 72 74 6 50 51 53 55 56 54 57 59 61 64 58 61 63 66 68 68 70 71 73 75 7 48 49 51 53 55 52 56 59 61 65 56 60 63 65 68 66 68 70 72 74 NC 17 19 21 24 25 22 25 25 26 29 20 24 27 29 31 32 34 36 38 39 2 64 65 68 70 72 67 68 69 70 71 67 68 70 71 72 77 79 80 82 83 3 54 56 58 60 62 60 62 63 65 66 62 63 65 66 68 72 74 76 77 78 4 52 53 54 56 58 54 56 57 59 60 56 58 60 62 63 64 65 67 69 70 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 5 53 54 55 57 59 53 56 58 60 62 57 60 62 65 67 65 67 69 70 72 6 51 52 54 56 58 52 55 57 60 62 56 59 61 63 66 64 66 68 70 72 1.0” ∆Ps 7 49 50 53 55 57 50 54 57 59 63 55 58 61 63 66 62 65 67 69 71 NC 16 17 21 24 26 20 21 21 23 27 19 22 25 27 30 31 33 36 37 38 2 65 66 68 70 72 68 69 70 71 71 69 70 72 73 74 78 80 82 83 84 3 54 56 58 60 62 61 63 64 65 67 62 64 65 67 68 73 75 76 78 79 4 51 52 54 56 57 54 56 57 59 60 56 58 60 62 63 64 66 67 69 70 5 52 53 55 57 59 53 56 58 60 62 56 59 62 64 66 66 68 69 71 73 6 51 52 54 56 58 52 55 58 60 63 56 59 61 63 65 65 67 69 71 72 1.5” ∆Ps 7 49 50 53 55 57 51 54 57 60 63 55 58 61 63 65 63 65 67 69 71 NC 17 19 21 24 26 21 22 21 24 27 20 22 25 27 29 32 34 36 38 39 2 65 66 68 70 72 69 70 70 71 72 70 72 73 74 75 79 81 82 84 85 3 54 56 58 60 62 61 63 64 65 67 62 64 66 67 68 73 75 77 78 80 4 51 52 54 56 57 54 56 57 58 60 56 58 60 62 63 64 66 67 69 70 5 52 53 55 57 59 53 56 58 60 62 56 59 61 64 66 66 68 70 71 73 6 51 52 54 56 58 52 55 58 60 63 56 59 61 63 65 65 67 69 71 73 7 49 50 53 55 57 51 55 58 60 64 55 58 61 63 65 63 66 68 70 72 NC 17 19 21 24 26 22 24 22 24 28 21 24 25 27 29 33 35 37 39 40 Redefine your comfort zone™ | www.titus-hvac.com PTFS-F, ATFS-F, DTFS-F / DISCHARGE SOUND PERFORMANCE N • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. PERFORMANCE DATA N37 fan powered terminals PTFS-F, ATFS-F, DTFS-F WITH ECM MOTOR / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE TFS-F w/ECM Size B 800 TFS-F w/ECM Size C 1200 1100 1000 700 900 800 CFM 600 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 700 600 500 500 400 400 300 200 300 0 0.1 0.5 0 0.6 TFS-F w/ECM Size D 1900 N 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 0.5 0.6 TFS-F w/ECM Size E 2500 2400 1800 2300 1700 2200 1600 2100 1500 2000 1400 1900 1800 1300 CFM CFM 1700 1200 1600 1100 1500 1000 1400 900 1300 1200 800 1100 700 1000 600 900 500 800 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) 0.5 0.6 0 0.1 0.2 0.3 0.4 Downstream Static Pressure (Inches of Water) No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil PERFORMANCE DATA PRIMARY AIR INLET PRESSURE / PTFS-F, ATFS-F, DTFS-F ECM ELECTRICAL DATA 3000 Unit Size Motor HP 120V 1 B 5.0 ⁄3 1 C 5.0 ⁄3 D 7.7 ½ E 9.6 ¾ 2000 1000 . 900 . . . . 6 in 2 in 0 in 4 in 2 in 800 -E 1 . -E 1 -C 1 -E 1 -C 1 8 in Airflow, 700 Size D ize D ize B ize D ize B S S S S B-C e cfm 600 z i S 500 400 300 200 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. N38 N38 Note: For selection procedure, See the section Engineering Guidelines and the topic ‘ECM Motors Fan Powered Terminals’ for additional information 208V 3.3 3.3 5.0 7.9 240V 277V 2.8 2.8 4.3 6.8 2.6 2.6 4.1 5.5 fan powered terminals PERFORMANCE DATA Octave Band Sound Power, Lw Size B08 C10 D12 E14 CFM 400 475 550 625 700 450 600 750 900 1050 800 1000 1200 1400 1600 1300 1500 1700 1900 2100 Discharge Ps 0.25 0.25 0.25 0.25 Min ∆Ps 0.04 0.05 0.07 0.09 0.11 0.03 0.05 0.07 0.11 0.15 0.02 0.03 0.05 0.07 0.09 0.03 0.04 0.06 0.07 0.09 0.5” ∆Ps Fan Only 2 59 61 63 64 65 50 55 59 62 65 55 59 62 65 67 65 68 70 72 74 3 49 51 52 53 54 41 47 51 54 57 46 50 53 56 58 56 59 62 65 67 4 46 47 49 50 51 41 46 49 52 55 42 45 48 51 53 52 55 57 60 62 5 40 42 44 45 46 33 39 44 48 51 38 42 44 47 49 47 50 53 55 57 6 36 40 44 48 51 27 34 38 42 45 33 37 40 43 45 42 45 48 51 53 7 31 36 41 44 48 21 28 33 37 40 28 33 37 40 43 37 41 44 47 50 NC 21 23 26 27 28 14 20 23 27 30 16 21 24 28 31 28 32 35 37 40 2 57 59 61 63 65 51 54 57 59 61 56 59 61 62 64 62 65 67 69 71 3 47 50 52 54 56 44 46 48 50 51 46 49 52 54 56 55 57 59 61 63 4 44 46 48 50 51 41 44 47 49 50 43 46 49 51 53 51 54 56 57 59 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 5 40 42 44 45 46 37 40 42 44 45 41 43 45 47 48 46 49 51 52 54 6 37 38 40 41 43 33 35 37 39 40 37 39 41 43 44 43 45 46 48 49 1.0” ∆Ps 7 32 33 35 36 37 28 30 32 33 35 32 35 37 39 40 39 41 42 44 45 NC 18 20 23 25 28 14 17 20 23 24 17 20 23 25 27 25 28 31 33 36 2 58 61 63 65 67 54 57 60 62 64 60 62 64 66 67 64 67 69 71 73 3 50 53 55 57 59 48 50 52 54 55 50 53 55 57 59 57 59 61 63 65 4 45 48 49 51 53 43 46 49 51 52 45 48 51 53 54 53 55 57 59 60 5 42 44 45 47 48 39 42 44 46 48 42 45 47 48 50 48 50 52 54 55 6 40 42 44 45 46 37 40 41 43 44 40 42 44 46 47 45 47 49 50 52 1.5” ∆Ps 7 39 40 42 43 44 36 38 40 41 42 38 40 42 44 46 43 45 47 48 50 NC 19 23 25 28 31 16 19 23 25 27 22 24 27 29 31 27 31 33 36 38 2 59 62 64 66 68 55 59 62 64 66 62 64 66 68 69 65 68 70 72 74 3 52 55 57 59 61 50 53 55 56 58 52 54 57 59 61 58 61 63 64 66 4 46 48 50 52 53 44 47 50 52 53 46 49 52 54 55 54 56 58 60 61 5 43 45 46 48 49 40 43 45 47 49 43 46 48 49 51 48 51 53 54 56 6 42 44 46 47 48 40 42 44 45 46 42 44 46 48 49 47 49 50 52 53 7 43 44 46 47 48 40 42 44 45 47 41 43 46 47 49 46 48 49 51 52 NC 20 24 27 29 32 17 20 24 27 29 24 27 29 32 33 28 32 34 37 40 Redefine your comfort zone™ | www.titus-hvac.com PTFS-F, ATFS-F, DTFS-F WITH ECM / RADIATED SOUND PERFORMANCE N • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings PERFORMANCE DATA N39 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTFS-F, ATFS-F, DTFS-F WITH ECM / DISCHARGE SOUND PERFORMANCE Octave Band Sound Power, Lw Size B08 C10 D12 N E14 CFM 400 475 550 625 700 450 600 750 900 1050 800 1000 1200 1400 1600 1300 1500 1700 1900 2100 Discharge Ps 0.25 0.25 0.25 0.25 Min ∆Ps 0.04 0.05 0.07 0.09 0.11 0.03 0.05 0.07 0.11 0.15 0.02 0.03 0.05 0.07 0.09 0.03 0.04 0.06 0.07 0.09 0.5” ∆Ps Fan Only 2 70 73 75 77 79 67 70 73 75 77 62 66 70 73 76 74 77 79 81 83 3 60 63 66 68 70 58 62 65 67 69 51 57 62 66 69 68 71 74 77 79 4 55 58 60 62 63 52 56 58 60 62 50 54 58 62 64 60 63 66 68 70 5 56 59 61 63 65 53 57 60 62 64 53 58 62 65 67 64 67 69 72 74 6 56 59 61 64 66 52 56 60 62 65 52 57 61 64 67 64 67 70 73 75 7 54 58 60 63 65 49 55 59 62 65 49 55 60 64 67 62 65 68 71 74 NC 24 28 30 33 35 20 24 25 28 30 13 19 24 28 30 26 30 33 37 39 2 65 68 71 74 76 63 65 67 69 70 61 65 67 70 72 69 71 74 76 77 3 56 60 63 66 68 54 57 60 62 64 53 56 59 62 64 64 67 70 73 75 4 53 56 58 60 62 49 53 56 59 61 53 56 59 62 64 58 61 63 66 68 PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining N40 N40 5 53 56 59 61 63 48 53 57 60 63 53 58 61 64 67 60 64 66 69 71 6 53 56 59 61 64 47 52 56 60 63 52 56 60 63 66 61 64 67 69 72 1.0” ∆Ps 7 51 55 58 61 63 45 51 56 60 63 50 55 59 63 66 58 62 65 68 71 NC 17 21 25 29 31 15 17 20 24 27 14 19 23 27 30 22 26 29 32 34 2 66 69 72 75 77 64 67 69 71 72 63 66 69 71 73 70 73 75 77 79 3 57 60 63 66 69 55 58 61 63 65 54 58 61 63 66 65 68 71 73 76 4 53 56 58 60 62 49 53 56 59 61 53 57 59 62 64 58 61 64 66 68 5 54 57 59 61 63 48 53 57 60 63 53 58 61 64 67 61 64 67 69 71 6 53 56 59 62 64 47 53 57 60 63 52 57 60 63 66 61 65 67 70 72 1.5” ∆Ps 7 52 55 58 61 63 45 52 56 60 64 51 55 60 63 66 59 62 66 69 71 NC 19 22 26 30 33 16 20 20 24 28 15 19 24 27 30 23 26 30 32 36 2 66 70 73 76 78 65 68 70 71 73 64 68 70 72 74 71 74 76 78 80 3 57 61 64 66 69 55 59 61 63 65 55 58 61 64 66 66 69 72 74 76 4 53 56 58 60 62 49 53 56 59 61 53 57 60 62 64 59 62 64 66 68 5 54 57 59 61 63 48 53 57 60 63 53 58 61 64 67 61 64 67 70 72 6 53 57 59 62 64 48 53 57 60 63 53 57 61 64 66 62 65 68 70 73 7 52 56 59 61 64 46 52 57 61 64 51 56 60 63 66 59 63 66 69 72 NC 19 24 28 31 34 17 21 21 25 28 15 20 24 27 30 24 27 31 33 36 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 for Appendix E. See Terminal Unit Engineering Guidelines • All NC levels determined using AHRI 885-2008 • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N41 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Titus is a charter member company and current participant in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990’s. It is currently administrated by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). The purpose of this program is to provide for the independent verification of manufacturers’ published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at www.ahrinet.org. In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types, and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’. These tests are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in AHRI Standard 880 ‘Performance Rating of Air Terminals’. Any failure to demonstrate the certified performance is punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible expulsion from the Certified Directory. Rated CFM 350 550 1100 1600 2100 2800 Fan Watts 110 210 430 690 870 2770 Min ∆Ps 0.01 0.07 0.16 0.09 0.09 0.10 Discharge H W 10 18.5 12.5 20.5 12.5 20.5 17.5 25 17.5 25 15 34 Unit Size A06 B08 C10 D12 E14 G16 Rated CFM 350 700 1100 1600 2100 2800 Fan Watts 90 210 340 460 690 2770 Min ∆Ps 0.01 0.11 0.16 0.09 0.09 0.10 Discharge H W 10 18.5 12.5 20.5 12.5 20.5 17.5 25 17.5 25 15 34 Fan Only Radiated Sound Power 2 3 4 5 6 63 54 50 48 43 69 65 59 57 49 69 64 61 58 51 67 62 60 57 52 72 66 64 61 55 71 68 64 60 55 Unit Size B08 C10 D12 E14 Rated CFM 550 1050 1600 2100 Fan Watts 210 470 790 870 Min ∆Ps 0.07 0.15 0.09 0.09 Discharge H W 12.5 20.5 12.5 20.5 17.5 25 17.5 25 Fan Only Radiated Sound Power 2 3 4 5 6 63 51 48 41 37 65 56 53 49 42 69 58 53 49 45 75 70 62 57 53 Unit Size B08 C10 D12 E14 Rated CFM 700 1050 1600 2100 Fan Watts 210 280 390 580 Min ∆Ps 0.11 0.15 0.09 0.09 Discharge H W 12.5 20.5 12.5 20.5 17.5 25 17.5 25 Fan Only Radiated Sound Power 2 3 4 5 6 65 54 51 46 51 65 57 55 51 45 67 58 53 49 45 74 67 62 57 53 PTFS, ATFS, DTFS, PTFS-F, ATFS-F, DTFS-F • Rated airflow (cfm) – Based on lesser of an inlet velocity of 2000 fpm or the maximum fan flow with 0.25 in wg of downstream pressure • Rated fan power (watts) – Based on fan operating at the rated airflow with 0.25 in wg of downstream pressure • Rated Min ∆Ps (in wg) – Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure at rated airflow with the primary damper full open and the unit fan set to match the primary flow • Rated ∆Ps (in wg) – A static pressure of 1.5 in wg applied to the inlet duct • Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220 7 35 44 50 50 53 53 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 72 64 56 52 49 65 63 60 56 49 73 68 65 62 55 75 69 65 63 58 80 73 69 66 60 79 77 72 67 63 7 38 49 50 51 53 53 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 72 65 56 53 49 69 67 63 59 52 72 67 64 60 54 74 70 66 63 58 80 73 69 66 60 79 77 72 67 63 7 34 38 43 50 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 62 55 49 46 45 65 57 53 49 46 70 61 56 51 49 74 68 62 57 54 7 48 40 43 50 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 68 61 53 49 48 66 58 53 49 46 69 61 55 51 49 74 66 61 56 53 7 46 50 54 55 57 60 Fan Only Discharge Sound Power 2 3 4 5 6 7 69 63 62 61 60 57 PTFS, ATFS, DTFS 77 65 58 60 60 58 79 68 63 66 66 66 81 71 65 68 70 69 86 79 70 74 75 74 76 72 70 69 67 66 7 47 53 54 55 57 60 Fan Only Discharge Sound Power 2 3 4 5 6 7 67 61 62 62 60 57 PTFS, ATFS, DTFS 77 68 62 64 64 63 with ECM 76 68 62 64 65 64 75 66 60 63 65 64 83 79 70 74 75 74 76 72 70 69 67 66 7 45 46 49 53 Fan Only Discharge Sound Power 2 3 4 5 6 7 PTFS-F, ATFS-F, 71 60 56 57 56 55 DTFS-F 76 70 62 64 64 65 76 71 65 68 68 68 84 79 70 74 75 74 7 48 47 49 52 Fan Only Discharge Sound Power 2 3 4 5 6 7 79 70 63 65 66 65 77 69 62 64 65 65 76 69 64 67 67 67 83 79 70 74 75 74 PTFS, ATFS, DTFS with ECM N PERFORMANCE DATA Unit Size A06 B08 C10 D12 E14 G16 Fan Only Radiated Sound Power 2 3 4 5 6 62 54 49 47 41 66 61 56 53 44 66 59 59 58 49 68 62 60 57 52 74 67 64 62 56 71 68 64 60 55 Product samples provided for certification testing are standard production units with standard ½ in dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions: Redefine your comfort zone™ | www.titus-hvac.com AHRI Directory of Certified Performance N41 Redefine your comfort zone™ | www.titus-hvac.com Series Fan Powered Terminals (continued) fan powered terminals TQS • Consistent, quiet design • Two casings for easy design layout • Built-in sound baffle for low sound levels, both radiated and discharge • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional ultra-high efficiency ECM motor available • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • Solid metal liner TQS • Bottom access panel can be removed for service • No external sound attenuators are required • 20-gauge galvanized steel casing N • Rectangular discharge opening is designed for flanged duct connections energy solutions AVAILABLE MODELS: PTQS / Pneumatic Control ATQS / Analog Control DTQS / Digital Control OVERVIEW Quiet Operation / with UltraLoc Liner™ / with UltraLoc Liner™ and ECM Motor TQS Designers choose Series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. N42 N42 See website for Specifications fan powered terminals DIMENSIONS Redefine your comfort zone™ | www.titus-hvac.com TQS UNIT DIMENSIONS DTQS with UltraLocTM / Sizes 2-7 B N 3 /8 3 20 J 12 K 6¼ A D Primary Air Inlet with AeroCrossTM Multipoint Center Averaging Sensor C W F Induced Air Inlet G 4½ E 1¼ H L TQS Series Unit with UltraLocTM Liner and ECM Motor Size 2, 3 4 5 6 7 Inlet Size A 6 8 10 12 8 10 12 14 10 12 14 16 12 14 16 14 16 6 6 7 8 6 7 8 10 7 8 10 11 8 10 11 10 11 B C 89/16 13¼ 101/16 21 D 57/8 77/8 97/8 117/8 77/8 97/8 117/8 137/8 97/8 117/8 137/8 157/8 117/8 137/8 157/8 137/8 157/8 E F G H J K L 14½ 14 3½ 171/8 11 4 407/8 17½ 16½ 9½ 201/8 14½ 2½ 467/8 N 27/8 27/8 47/8 47/8 27/8 47/8 47/8 67/8 47/8 47/8 67/8 67/8 47/8 67/8 67/8 67/8 67/8 W Filter Size 361/8 19 x 17 48¼ 27 x 20 N DIMENSIONS All dimensions are in inches N43 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS HOT WATER COIL SECTION STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins • Connections: Male solder 5 • /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit COIL ROWS • 1-Row • 2-Row • • • 120V, 1 ph, 60 Hz. 208/240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. R 1“ Typ. Hot Water Coil Section (Discharge Mounted) Unit Size M (1-Row) M (2-Row) R 2, 3, 4 1 1¼ 17 5, 6, 7 1 1¼ 25 ELECTRIC COIL SECTION STANDARD FEATURES N SUPPLY VOLTAGE • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls 9 S 15 17½ M S Note: R and S are inside dimensions • Optional Lynergy Comfort Controlled SSR Electric Heat available SUPPLY VOLTAGE • • • • • Electric Coil Section (Discharge Mounted) Unit Size U R S T 2, 3, 4 3½ 14 11 27/8 5, 6, 7 9½ 16½ 14½ 31/8 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) Note: R and S are inside dimensions See Electric Heat Coils in Section O for more information. 31 12 6¼ Heater Rack Access Cover 1" Typ. OPTIONS • • • • • R Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction U 9¾ DIMENSIONS ADDITIONAL ACCESSORIES N44 N44 (OPTIONAL) • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • Metal controller cover • Fan P/E switch for night setback control. See Section O for additional control options • 1” Liner • Fibre-Free Liner • SteriLoc Liner • UltraLoc Liner • EcoShield liner • Fan unit fusing • Hanger brackets • Camlocks on fan access door Unit Size Motor HP 2 3 4 5 6 7 1 ⁄6 ¼ 1 ⁄3 1 ⁄3 ¾ 1 Electrical Data 120V FLA 4.0 7.0 9.8 10.0 13.4 N/A S 208/240V FLA 1.8 3.0 4.1 4.3 7.2 9.0 T 277V FLA 1.3 2.4 2.9 3.3 5.4 6.5 All motors are single phase, 60(Hz). FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye) For ECM electrical data see page N50 fan powered terminals TQS WITH ULTRALOCTM FEATURES Titus UltraLoc Construction – “Engineered for IAQ” trapped between the liner and casing walls, providing a perfect home for mold growth. The Titus design is engineered using double edge construction. The UltraLoc design captures the insulation edges to insure that there is no exposed fiberglass. The edge construction shown below covers all four edges of the access panel. All internal corners are manufactured in the same manner to completely cover all edges. Double wall lined terminals are typically used in indoor air quality applications requiring that the unit be wiped down regularly. A concern with most double wall terminals is that the liner and casing edges meet, but do not overlap. This provides the potential for water to become No gap between inner metal liner and outer metal panel Inner metal liner Outer metal panel Redefine your comfort zone™ | www.titus-hvac.com As the concern about indoor air quality grows, the demand for metal lined fan boxes is increasing. We are happy to offer the best selling series fan powered terminal on the market with a premium solid double wall liner. UltraLoc is a solid metal liner over 1” insulation. All edges of the unit are covered to eliminate any exposed fiberglass and meet your IAQ concerns. Insulation N TQS WITH ULTRALOC N45 fan powered terminals PTQS, ATQS, DTQS WITH ULTRALOCTM LINER / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 2 1000 Unit Size 3 1400 900 Unit Size 4 1700 1300 1600 1200 1500 1100 1400 1000 1300 900 1200 700 CFM 600 500 400 CFM 800 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 800 1100 700 1000 600 900 500 800 400 700 300 200 100 300 0 0.1 0.2 0.3 0.4 0.5 0.6 0 Static Pressure - inches of Water N 0.1 0.3 0.4 0.5 600 0.6 0 Static Pressure - inches of Water 0.1 0.2 0.3 0.4 0.5 0.6 Static Pressure - inches of Water Unit Size 6 Unit Size 5 2000 0.2 Unit Size 7 3600 2400 3400 1800 2200 3200 3000 1600 2000 2800 2600 CFM CFM CFM 1400 1800 1200 2400 2200 2000 1600 1000 1800 1600 1400 800 1400 0 0.1 0.2 0.3 0.4 0.5 0 0.6 Static Pressure - inches of Water PERFORMANCE DATA 1200 1200 600 0.1 0.2 0.3 0.4 0.5 0 0.6 Static Pressure - inches of Water 0.2 0.3 0.4 0.5 0.6 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil PRIMARY AIR INLET PRESSURE / PTQS, ATQS, DTQS WITH ULTRALOCTM LINER 3000 2000 Airflow, CFM 1000 900 n. . . . . 16 i 800 2 in 0 in 4 in 2 in 5-7 -7 1 . -4 1 -7 1 -4 1 700 Size 8 in ize 5 ize 2 ize 5 ize 2 S S S S 2-4 600 Size 500 400 Note: For selection procedure, See the section Engineering Guidelines and the topic ‘ECM Motors - Fan Powered Terminals’ for additional information. 300 200 N46 N46 0.1 Static Pressure - inches of Water 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 Required Minimum Inlet Static Pressure, Inches Wg. 0.3 0.4 0.5 PERFORMANCE DATA The radiated sound paths for a fan-powered unit start at the fan motor/ blower assembly and the primary damper. This sound energy must either exit through the induction port or pass through the casing before reaching the plenum, ceiling tile, occupied space, and eventually the listener. AHRI 885 was developed to provide a standardized way to accurately predict sound levels in a space resulting from noise generated in the ceiling plenum above. It is important to understand that AHRI 885 was formulated to deal with noise from a point source. Terminal units with ‘soft’ liners behave very much like a point source, in that noise is emitted from all external casing surfaces in a roughly equal manner. This is not true for a dual wall unit, where the radiated sound is much more directional. With standard fiberglass and other ‘soft’ liners, sound is emitted from the casing in all directions with slightly more on the side that includes the induction port. Dual wall construction results in a casing with such a high transmission loss that virtually all radiated sounds exit through the induction port. This in effect concentrates and directs the sound energy across the ceiling rather than through it, resulting in lower than expected NC levels in the occupied space. Furthermore, the TQS with UltraLoc was carefully engineered to attenuate the second and third octave band frequencies for overall reduced sound levels. Radiated sound power tests were run for all TQS with UltraLoc units in accordance with AHRI 880. The resulting sound power figures make it appear that these units are louder than TQS units with ‘soft’ liners, but mock-up testing has shown lower NC levels. This is due to the fact that all sound generated, regardless of directionality, is measured in a reverberant field. In a mock-up situation, the sound from the induction port is directed into plenum where it is easily attenuated. Although it is difficult to estimate the resulting NC reduction for all unit sizes, it can be as high as 6 NC. AHRI Standard 885 calculations are based upon a ‘point source’ of sound energy. This type of idealized sound source would emit sound energy equally in all directions. While this is very true for single and dual duct terminals and somewhat true for fan-powered units (with other liners), it isn’t true for dual wall fan-powered units. The TQS with UltraLoc liner will have lower actual sound in application than the AHRI 885 NC data shows. Redefine your comfort zone™ | www.titus-hvac.com A NOTE ON RADIATED SOUND LEVELS FOR TQS WITH ULTRALOCTM LINER fan powered terminals N PERFORMANCE DATA N47 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PERFORMANCE DATA N N48 N48 PTQS, ATQS, DTQS WITH ULTRALOCTM LINER / RADIATED SOUND POWER LEVELS / FAN AND 100% PRIMARY Unit Size Inlet Size 2 8 3 10 4 12 5 12 6 14 7 16 Fan Only cfm 300 400 500 625 750 500 650 800 1000 1200 1000 1100 1200 1300 1400 1200 1300 1400 1550 1700 1500 1600 1750 1900 2100 1800 2100 2400 2750 3100 Sound Power Octave Bands 2 58 61 63 66 68 60 63 65 67 69 66 67 69 70 71 67 68 69 71 72 69 70 71 73 74 72 74 76 78 80 3 48 51 53 56 58 50 53 55 58 60 59 60 62 63 64 59 60 61 62 63 60 61 62 63 65 62 65 68 71 73 4 51 53 55 57 59 49 52 54 57 59 58 60 61 63 64 57 58 59 61 62 57 58 60 61 63 64 66 68 71 73 5 46 50 53 56 58 50 53 55 57 60 58 60 61 62 64 56 58 59 60 62 57 58 60 61 63 63 66 68 71 73 6 44 49 52 56 59 49 53 55 58 61 58 60 61 63 64 57 58 60 61 63 58 60 61 63 65 61 65 68 71 74 7 36 42 47 52 56 40 45 49 53 57 52 54 56 58 60 53 54 56 58 60 53 55 57 59 61 56 60 64 67 70 2 60 63 66 68 71 63 66 68 70 72 66 67 69 70 71 67 68 69 71 72 69 70 71 73 74 72 74 76 78 80 3 50 54 56 59 62 53 56 58 60 62 61 62 62 63 64 59 60 61 62 63 61 61 62 63 65 64 67 68 71 73 0.5” ∆Ps 4 5 51 46 53 50 55 53 57 56 59 58 51 52 54 54 56 55 57 57 59 60 60 60 62 62 63 63 63 62 64 64 57 56 58 58 59 59 61 60 62 62 59 59 60 60 61 60 61 61 63 63 66 65 66 68 68 68 71 71 73 73 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 6 46 51 52 56 59 52 55 55 58 61 60 62 63 63 64 59 58 60 61 63 60 61 61 63 65 64 67 68 71 74 7 39 45 47 52 56 43 47 49 53 57 54 56 58 58 60 53 54 56 58 60 55 55 57 59 61 59 62 64 67 70 Fan Plus 100% Primary 1.0” ∆Ps 2 3 4 5 6 7 62 54 53 49 49 42 66 58 56 53 53 46 68 61 58 56 56 50 71 64 60 59 59 54 73 67 62 61 61 58 66 58 55 55 55 46 69 61 57 57 58 50 71 63 59 59 60 53 73 65 61 61 62 57 75 67 63 63 64 59 70 63 61 61 61 55 71 64 63 62 62 57 72 65 64 64 64 59 73 66 65 65 65 61 75 67 66 66 66 62 70 62 59 58 59 57 71 63 60 59 60 58 72 64 61 61 61 59 74 65 63 60 61 61 75 66 64 62 63 62 71 62 59 59 60 57 72 63 60 60 62 58 73 64 61 61 63 60 75 66 63 63 65 61 76 67 63 64 66 63 75 66 67 66 65 59 77 68 69 69 68 63 79 70 71 71 71 66 81 73 73 73 73 69 82 75 75 75 75 70 2 65 69 72 75 77 71 73 75 78 79 74 75 76 77 78 73 74 75 77 78 72 73 74 76 77 77 79 81 82 84 3 60 64 67 70 73 65 67 69 71 73 66 67 68 69 70 65 65 66 67 68 63 64 65 67 68 68 70 72 74 76 2.0” ∆Ps 4 5 55 51 58 55 60 58 62 61 64 63 60 59 62 61 64 63 66 65 67 66 62 62 63 63 65 64 66 66 67 67 60 59 61 60 62 61 63 62 64 64 59 59 60 60 61 62 63 63 64 64 68 68 70 70 72 72 74 74 76 76 6 52 56 58 61 64 60 62 64 66 68 62 64 65 66 68 60 61 62 64 65 61 62 63 65 67 67 70 72 75 77 7 44 49 52 56 59 51 54 57 60 62 57 58 60 62 63 61 62 62 64 65 59 60 61 63 65 60 64 67 70 72 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Size CFM 208 350 400 500 625 725 310 650 750 900 1150 1400 412 850 1075 1300 1400 1500 512 1000 1200 1500 1650 1800 614 1500 1700 2000 2250 2500 716 1800 2150 2400 2700 3100 Discharge Ps Octave Band Sound Power, Lw Min ∆Ps 3 67 69 71 73 75 0.5”∆Ps 4 5 6 62 60 60 65 65 64 67 67 68 68 70 71 70 72 73 7 59 63 68 71 73 NC 28 31 36 39 39 2 73 78 80 82 84 3 67 69 71 73 75 1.0” ∆Ps 4 5 6 64 61 60 65 65 66 67 67 68 68 70 71 70 72 73 7 59 64 68 71 73 NC 28 34 36 39 39 2 73 78 80 82 84 3 67 69 71 73 75 1.5” ∆Ps 4 5 6 64 61 62 65 65 66 67 67 68 68 70 71 70 72 73 7 60 64 68 71 73 NC 28 34 36 39 39 0.25 0.05 0.06 0.10 0.16 0.21 2 73 76 78 80 82 3 65 67 70 72 73 Fan Only 4 5 6 62 60 60 64 63 64 65 66 67 67 68 69 68 70 72 0.25 0.08 0.11 0.16 0.26 0.39 71 73 76 78 80 65 67 69 71 73 61 63 65 66 68 59 62 63 65 67 60 63 65 67 68 57 60 63 65 68 25 25 29 31 34 71 73 76 78 80 65 67 69 71 73 61 63 65 66 68 59 62 63 65 67 60 63 65 67 68 57 60 63 65 68 25 25 29 31 34 71 73 76 80 82 65 67 69 73 74 61 63 65 68 70 59 62 63 67 68 60 63 65 68 70 57 60 63 67 69 25 25 29 34 36 71 75 78 80 82 65 69 71 73 74 61 65 66 68 70 59 63 65 67 68 60 64 66 68 70 57 62 64 67 69 25 28 31 34 36 0.25 0.09 0.15 0.21 0.25 0.28 78 79 80 81 82 72 73 74 75 76 66 67 68 69 69 66 68 69 70 71 66 67 68 69 70 64 66 67 68 69 31 33 34 35 36 80 81 82 83 83 74 75 76 77 78 68 69 70 71 71 68 69 70 71 71 68 69 70 71 70 66 67 69 70 69 34 35 36 38 38 80 81 82 83 82 74 75 76 77 76 68 69 70 71 69 68 69 70 71 71 68 69 70 71 70 66 67 69 70 69 34 35 36 38 36 80 81 80 81 82 74 75 76 75 76 68 69 68 69 69 68 69 69 70 71 68 69 68 69 70 66 67 67 68 69 34 35 36 35 36 0.25 0.07 0.10 0.16 0.19 0.23 85 86 86 87 88 69 70 71 72 73 69 70 71 72 73 67 69 70 71 72 66 68 69 70 71 65 66 67 69 70 40 42 42 43 44 87 88 88 87 88 69 70 71 72 73 71 72 71 72 73 67 69 71 73 74 68 68 69 70 71 65 66 69 71 72 43 44 44 43 44 85 86 86 87 88 69 70 71 72 73 71 72 71 72 73 67 69 71 73 74 68 68 69 70 71 65 66 69 71 72 40 42 42 43 44 85 86 86 87 88 71 72 73 72 73 71 72 71 72 73 67 69 71 73 74 68 69 69 70 71 65 66 69 71 72 40 42 42 43 44 0.25 0.10 0.13 0.17 0.22 0.27 81 82 83 84 86 72 73 75 77 79 69 70 71 73 74 69 70 71 73 75 68 69 71 72 74 66 67 69 71 73 35 36 38 39 42 83 84 85 86 86 74 75 77 78 79 71 72 73 74 74 70 72 73 75 75 70 71 72 74 74 68 69 71 72 73 38 39 40 42 42 83 84 85 86 88 74 75 77 78 80 71 72 73 74 76 70 72 73 75 76 70 71 72 74 76 68 69 71 72 74 38 39 40 42 44 83 84 85 86 88 74 75 77 78 80 71 72 73 74 76 70 72 73 75 76 70 71 72 74 76 68 69 71 72 74 38 39 40 42 44 0.25 0.08 0.12 0.15 0.19 0.25 83 85 86 87 89 73 75 77 79 81 70 72 74 76 78 70 73 75 77 79 70 72 75 77 79 68 71 73 76 78 38 40 42 43 45 85 85 86 87 89 75 77 77 79 81 72 74 74 76 78 72 74 75 77 79 72 74 75 77 79 70 73 73 76 78 40 40 42 43 45 85 85 86 87 89 75 75 77 79 81 72 72 74 76 78 72 73 75 77 79 72 72 75 77 79 70 71 73 76 78 40 40 42 43 45 83 85 86 87 89 73 75 77 79 81 70 72 74 76 78 70 73 75 77 79 70 72 75 77 79 68 71 73 76 78 38 40 42 43 45 7 59 63 66 69 71 NC 28 31 34 36 36 2 73 76 80 82 84 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. N PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts. • Sound performance based on units lined with standard dual density fiberglass lining Redefine your comfort zone™ | www.titus-hvac.com PTQS, ATQS, DTQS WITH ULTRALOCTM LINER / DISCHARGE SOUND POWER LEVELS / FAN AND 100% PRIMARY N49 fan powered terminals PTQS, ATQS, DTQS WITH ULTRALOCTM LINER AND ECM MOTOR / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 4 Unit Size 6 1600 2600 1400 2400 1200 2200 1000 2000 CFM CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 800 1600 400 1400 200 1200 1000 0 0.1 0.2 PERFORMANCE DATA 0.3 0.4 0.5 0 0.6 Static Pressure - Inches of Water 120V 7.7 12.8 208V 5.0 10.5 0.1 0.2 0.3 0.4 0.5 Static Pressure - Inches of Water ECM ELECTRICAL DATA Unit Size Motor HP 4 ½ 6 1 N50 N50 1800 600 0 N No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil 240V 4.3 9.1 277V 4.1 6.9 0.6 fan powered terminals PERFORMANCE DATA Fan Only Unit Size 4 6 7 Fan Plus 100% Primary 1.0” ∆Ps 2 3 4 5 6 7 2 3 2.0” ∆Ps 4 5 2 3 4 5 6 7 2 3 0.5” ∆Ps 4 5 6 7 12 300 575 850 1125 1400 56 62 66 68 70 47 53 58 60 63 45 53 57 61 63 45 52 57 60 63 43 51 57 60 63 35 45 51 55 58 61 65 68 68 70 51 56 58 60 63 48 55 57 61 63 47 52 57 60 63 45 51 57 60 63 37 45 51 55 58 66 69 71 72 74 57 61 63 65 67 52 58 61 64 66 50 56 60 63 65 49 56 60 63 66 40 49 54 58 61 71 74 75 77 78 65 68 70 71 72 57 62 65 67 69 54 60 63 66 68 54 61 65 67 70 44 52 57 61 64 14 1200 1500 1800 2100 2400 61 65 69 72 74 52 56 60 63 66 51 55 58 61 64 50 54 58 60 63 51 56 60 63 66 48 52 56 60 63 63 67 69 72 74 54 58 60 63 66 53 57 58 61 64 53 56 59 60 63 54 58 60 63 66 51 55 56 60 63 65 69 72 74 77 56 60 63 66 68 54 58 61 63 65 53 57 60 60 63 54 58 62 65 66 53 57 60 62 65 68 71 74 77 79 58 62 65 67 70 54 58 61 64 66 53 57 60 62 63 55 59 62 65 68 56 60 62 65 67 Inlet Size cfm Sound Power Octave Bands • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 6 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. Redefine your comfort zone™ | www.titus-hvac.com PTQS, ATQS, DTQS WITH ULTRALOCTM LINER AND ECM MOTOR / RADIATED SOUND POWER DATA N PTQS, ATQS, DTQS WITH ULTRALOCTM LINER AND ECM MOTOR / DISCHARGE SOUND POWER DATA Size CFM 412 300 575 850 1125 1400 614 1200 1500 1800 2100 2400 Discharge Ps Octave Band Sound Power, Lw Min ∆Ps 2 69 73 0.09 76 77 3 62 67 70 72 74 Fan Only 4 5 6 57 56 56 62 61 61 65 64 65 67 66 67 69 67 69 0.25 0.01 0.04 0.25 0.16 0.25 0.25 0.10 75 66 65 0.12 78 70 69 0.25 0.17 74 71 0.24 83 76 74 0.31 86 78 76 64 68 71 74 76 64 68 71 73 76 7 51 58 63 66 68 NC 30 35 37 39 41 2 69 73 76 78 80 3 62 67 72 74 76 0.5”∆Ps 4 5 6 57 56 56 62 61 61 67 66 66 69 68 69 71 70 71 7 51 58 64 68 71 NC 30 35 38 41 44 2 69 74 77 79 80 3 62 69 72 74 76 1.0” ∆Ps 4 5 6 57 56 56 64 63 63 67 66 67 70 68 69 71 70 71 7 51 58 65 68 71 NC 30 37 39 41 44 2 69 74 77 79 80 3 62 69 72 74 76 1.5” ∆Ps 4 5 6 57 56 56 64 63 63 67 66 67 70 68 69 71 70 71 7 51 58 65 68 71 NC 30 37 39 41 44 62 66 70 73 75 36 40 43 46 48 76 80 83 85 87 68 72 75 78 80 67 70 73 76 78 64 68 72 74 77 37 41 45 47 50 76 80 83 85 87 68 72 75 78 80 67 70 73 76 78 64 68 72 74 77 37 41 45 47 50 76 80 83 85 87 68 72 75 78 80 67 70 73 76 78 64 68 72 74 77 37 41 45 47 50 65 69 72 75 77 66 70 73 75 78 65 69 72 75 77 66 70 73 75 78 65 69 72 75 77 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 66 70 73 75 78 N51 Redefine your comfort zone™ | www.titus-hvac.com Series Fan Powered Terminals (continued) fan powered terminals TQS with IAQ • Consistent, quiet design • Two casings for easy design layout • Built-in sound baffle for low sound levels, both radiated and discharge • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Energy-efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Optional ultra-high efficiency ECM motor available • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections TQS with IAQ • Dual density insulation, coated to prevent air erosion, meets requirements of NFPA 90A and UL 181 N • 20 gauge, galvanized steel casing AVAILABLE MODELS: PTQS / Pneumatic Control ATQS / Analog Control DTQS / Digital Control OVERVIEW Quiet Operation / with Indoor Air Quality (IAQ) Inlet Designers choose Series flow terminals for their characteristics of constant air delivery and temperature blending. Nevertheless, these terminals maintain the VAV energy savings at the central fan. ADDITIONAL FEATURES TQS • Rectangular discharge opening is designed for flanged duct connections • Bottom access panel can be removed for service • No external sound attenuators are required • Additional IAQ (ventilation) inlet with damper outside air directly to zone N52 N52 See website for Specifications fan powered terminals DIMENSIONS Redefine your comfort zone™ | www.titus-hvac.com TQS WITH IAQ UNIT DIMENSIONS DTQS: Sizes 3-7 (Unit Size 2 is not available with IAQ Inlet) K B Primary Air Inlet with AeroCrossTM multi-point, center averaging sensor A G 12 6¼ D Induced Air Inlet C J 20 N 33/8 W F D2 P R E IAQ Air Inlet with AeroCrossTM multi-point center averaging sensor G 6¼ N 123/8 18 L 3 /8 3 H TQS Series Unit with IAQ Inlet Size 3 4 5 6 7 Primary Inlet Inlet Size 6 8 4 10 12 5 8 10 6 12 14 10 12 14 7 16 12 14 8 16 14 16 A 6 6 7 8 6 7 8 10 7 8 10 11 8 10 11 10 11 B C D 5 /8 77/8 97/8 117/8 77/8 97/8 117/8 137/8 97/8 117/8 137/8 157/8 117/8 137/8 157/8 137/8 157/8 D2 E F G H J K L M 7 8½ 101/8 101/8 181/8 N 2 /8 27/8 47/8 47/8 27/8 47/8 47/8 67/8 47/8 47/8 67/8 67/8 47/8 67/8 67/8 67/8 67/8 P R W 5 8½ 361/8 5½ 10 481/8 7 37/8 47/8 14½ 14 3½ 171/8 11 4 407/8 8¾ 17½ 16½ 9½ 201/8 14½ 2½ 467/8 11 57/8 67/8 77/8 DIMENSIONS All dimensions are in inches N53 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS HOT WATER COIL SECTION STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins • Connections: Male solder 5 /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit COIL ROWS • 1-Row • 2-Row • • • 120V, 1 ph, 60 Hz. 208/240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. R Hot Water Coil Section (Discharge Mounted) Unit Size M (1-Row) M (2-Row) R 3, 4 1 1¼ 17 5, 6, 7 1 1¼ 25 1“ Typ. S 15 17½ M 9 STANDARD FEATURES • Auto reset thermal cutouts (one per element). • 80/20 Nickel chrome heating elements. • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls • 277V, 1 ph, 60 Hz. • 208V, 3 ph, 60 Hz. • 480V, 3 ph, 60 Hz. (4 wire wye only) OPTIONS • • • • • • Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction Optional Lynergy Comfort Controlled SSR Electric Heat available SUPPLY VOLTAGE • 208V, 1 ph, 60 Hz. • 240V, 1 ph, 60 Hz. 12 31 6¼ Heater Rack Access Cover 1“ Typ. Electric Coil Section (Discharge Mounted) Unit Size U R S T 3, 4 3½ 14 11 27/8 5, 6, 7 9½ 16½ 14½ 31/8 R U Note: R and S are inside dimensions See Electric Heat Coils in Section O for more information DIMENSIONS ADDITIONAL ACCESSORIES N54 N54 S Note: R and S are inside dimensions ELECTRIC COIL SECTION N SUPPLY VOLTAGE (OPTIONAL) • Induced air filter, 1” thick disposable construction type • Fan disconnect switch (not available on units with optional electric coils) • Metal controller cover • Fan P/E switch for night setback control. See Section O for additional control options • 1” Liner • Fibre-Free Liner • SteriLoc Liner • UltraLoc Liner • EcoShield liner • Fan unit fusing 9¾ • Hanger brackets • Camlocks on fan access door Unit Size Motor HP 3 4 5 6 7 ¼ 1 ⁄3 1 ⁄3 ¾ 1 Electrical Data 120V FLA 7.0 9.8 10.0 13.4 N/A S 208/240V FLA 3.0 4.1 4.3 7.2 9.0 277V FLA 2.4 2.9 3.3 5.4 6.5 All motors are single phase, 60(Hz). FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are same voltage as electric coil (when supplied), with exception that 277V motors are used with 480V 3 Phase coils (four wire wye) For ECM electrical data see page N50 TQS WITH INDOOR AIR QUALITY (IAQ) INLET FEATURES Building owners are becoming more aware of the health concerns related to poor IAQ. Indoor air is a combination of outside air and indoor air distributed throughout a building. Indoor air pollution is caused by an accumulation of contaminants that primarily come from inside the building. ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, specifies the minimum ventilation rates and indoor air quality that will be acceptable to human occupants. The standard is intended to minimize the potential for adverse health effects. Standard 62 defines the outdoor air quality acceptable for ventilation, outdoor air treatment when necessary, ventilation rates for residential, commercial, institutional, vehicular, and industrial spaces, the criteria for reduction of outdoor air quantities when recirculated air is treated by contaminant-removal equipment, and the criteria for variable ventilation when the air volume in the space can be used as a reservoir to dilute contaminants. In January 2000, the Environmental Protection Agency (EPA) released a report on the Energy Costs and IAQ Performance of Ventilation Systems and Controls. The study discusses the benefits (thermal and economic) of the various systems in the three climates, most of these issues will not be discussed in this catalog. The study found that core zones consistently received less outdoor air than the perimeter zones. The core of a building is typically the zone with the largest occupancy levels and therefore would require more outdoor air than the perimeters. Outside air control is typically handled by the central air handling unit. Due to varying conditions in individual zones, the outside air supplied by the air handler may not meet the minimum requirement for the zone. By supplying outside air directly to the zone using the TQS with IAQ inlet, the minimum ventilation requirement for the zone can be maintained. Redefine your comfort zone™ | www.titus-hvac.com Titus Offers the Inlet for the TQS. The demand for fresh air inlets on series fan powered terminals has been growing to address the growing IAQ concerns. Titus introduces the IAQ inlet option on the TQS premiere fan powered terminal. fan powered terminals N TQS WITH IAQ N55 fan powered terminals PTQS, ATQS, DTQS WITH IAQ / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 4 Unit Size 3 1600 1800 1400 1600 1200 1400 CFM 1000 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 1200 800 1000 600 800 400 600 200 0 0.1 0.2 0.3 0.4 0.5 0 0.6 Static Pressure - Inches of Water 0.2 0.3 Unit Size 6 Unit Size 5 N 0.1 2200 2700 2000 2500 0.4 0.5 0.6 Static Pressure - Inches of Water Unit Size 7 3500 3300 1800 3100 2900 2300 2700 1600 2500 CFM CFM CFM 2100 1400 1900 2300 2100 1200 1900 1700 1000 1700 1500 1500 800 1300 600 1300 0 0.1 0.2 0.3 0.4 0.5 0.6 1100 0 Static Pressure - Inches of Water 0.1 0.2 0.3 0.4 0.5 0.6 0 Static Pressure - Inches of Water 0.1 0.2 PTQS, ATQS, DTQS WITH IAQ INLET AND ECM MOTOR - AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 6 Unit Size 4 2800 2600 1400 2400 1200 2200 2000 CFM 1000 CFM PERFORMANCE DATA No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil 1600 800 1800 1600 1400 600 1200 400 N56 N56 1000 800 200 0 0.1 0.2 0.3 0.4 0.5 0.6 Static Pressure - Inches of Water 0 0.1 0.3 0.4 0.5 0.6 Static Pressure - Inches of Water 0.2 0.3 0.4 0.5 0.6 Static Pressure - Inches of Water Low Profile Series Terminals fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com FLS • Only 10½ inches high, in all sizes. Especially useful where building height limits dictate shallow ceiling plenums. • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Primary airflow balancing connections • Adjustment points are easily accessible through ceiling opening • Energy efficient fan motor, permanent split capacitor type, mounted in vibration isolators • Adjustable SCR fan speed control, with minimum voltage stop • Single point electrical, pneumatic main and thermostat connections • Dual density insulation, coated to prevent air erosion, meets requirements of NFPA 90A and UL 181 FLS • Heavy gauge, galvanized steel casing energy solutions AVAILABLE MODELS: See website for Specifications N PFLS / Pneumatic Control AFLS / Analog Control DFLS / Digital Control OVERVIEW Constant Volume / Low Profile The FLS is a Low Profile Series Fan Powered Terminal designed for small ceiling plenum applications. At a height of 10 ½”, they are especially useful where building height limits dictate shallow ceiling plenums. FLS N57 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS FLS UNIT DIMENSIONS DFLS: Sizes 2-3 M 95/8 D B 20 N 33/8 6¼ Primary Air Inlet with AeroCrossTM Multipoint Center Averaging Sensor E F C A W Induced Air Inlet J G N L K H DFLS: Sizes 4 M 9 D B 20 N 3 6¼ Induced Air Inlet C E Primary Air Inlet with AeroCrossTM Multipoint Center Averaging Sensor F W A Induced Air Inlet J G DIMENSIONS Size N58 N58 2, 3 4 Inlet Size 8 Dia. 8 x 16 H L K A 9 20½ B 6¼ 6¾ C 2½ 11¼ D E F 2¼ 17/8 5 /8 21½ 14 /8 123/8 5 5 G 8¾ 8¾ H 10½ 10½ J K L M N W Filter Size /8 1 /8 40¼ 40¼ 1 11/8 3 ¾ 26 43 10 x 15 10 x 15 7 11/8 All dimensions are in inches 1 /8 7 fan powered terminals DIMENSIONS SUPPLY VOLTAGE • 120V, 1 ph, 60 Hz. • 208/240V, 1 ph, 60 Hz. • 277V, 1 ph, 60 Hz.. STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins • Connections: Male solder 5 /8” for both 1- and 2-row. Left or right hand connections. • Galvanized steel casing • Flanged duct connection • Coil is installed at discharge of unit 9½ ¾" Typ. R COIL ROWS Unit Size 2, 3 4 • 1-Row • 2-Row R 21 28 U S 37/8 7½ 8¾ Note: R is an inside dimension ELECTRIC COIL SECTION STANDARD FEATURES • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls Unit Size 2, 3 4 R 10½ 203/8 OPTIONS • • • • • • Redefine your comfort zone™ | www.titus-hvac.com HOT WATER COIL SECTION SUPPLY VOLTAGE Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction Optional Lynergy Comfort Controlled SSR Electric Heat available • • • • • 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 31" 9¾ N 83/8 1" Typ. R U 10½ 203/8 Note: R is an inside dimension See Electric Heat Coils in Section O for more information ADDITIONAL ACCESSORIES • Induced air filter, 1” thick disposable construction type • Fan toggle disconnect switch (Not available on units with optional electric coils) • Fan PE switch for night shutdown (PFLS). See Section O for additional control options. • Hanger brackets • Fan motor fusing • Fibre Free Liner • Foil Face Liner Heater Rack Access Cover • 1- or 2-row hot water coil • Fan relay/pressure switch for night setback (AFLS) Unit Size Motor HP 2 3 4 ⁄6 1 ¼ (2) 1⁄6 Electrical Data Motor Full Load Amps 120V 208/240V 3.9 1.6 5.8 2.4 8.2 3.4 ECM ELECTRICAL DATA Unit Size Motor HP 1 3 ⁄3 4 (2) 1⁄3 120V 5.0 10.0 208V 3.3 6.6 240V 2.8 5.6 277V 2.6 5.2 Note: All motors are single phase, same voltage as electrical coils (when supplied), with exception that 277 volt motors are used with 480 volt, three phase coils (four wire wye) 277V 1.2 1.8 2.5 DIMENSIONS (OPTIONAL) U N59 fan powered terminals PFLS, AFLS, DFLS / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 2 Unit Size 3 900 800 700 1900 1100 1700 1000 1500 900 1300 CFM CFM 800 1100 500 400 300 700 900 600 700 500 500 300 400 200 0 0.1 0.2 0.3 0.4 0.5 0 0.6 0.1 0.2 0.3 0.4 0.5 0.6 0 Static Pressure (inches of water) Static Pressure (inches of water) N Unit Size 4 1200 600 CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 0.1 0.2 0.3 0.4 0.5 0.6 Static Pressure (inches of water) No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil PRIMARY AIR CFM RANGES Inlet Size Total cfm Range 8 8 x 16 0-900 0-1860 PFLS TITUS II Pneumatic Controller Minimum Maximum *145-590 265-900 325-1320 590-1860 PFLS TITUS I Pneumatic Controller Minimum Maximum *190-590 265-900 420-1320 590-1860 AFLS TITUS TA1 Analog Electronic Controller Minimum Maximum *145-900 145-900 325-1860 *325-1860 DFLS Typical Digital Controller Minimum Maximum *145-900 145-900 *325-1860 325-1860 Note 1: An asterisk (*) indicates Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced Note 2: For selection procedure, see the section, Engineering Guidelines and the topic ‘ECM Motors - Fan Powered Terminals’ for additional information PFLS, AFLS, DFLS WITH ECM MOTOR / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 4 1200 2300 1100 2100 1000 1900 900 1700 800 1500 CFM CFM PERFORMANCE DATA Unit Size 3 700 600 1100 500 900 400 700 300 0 0.1 0.2 0.3 0.4 0.5 Static Pressure (inches of water) N60 N60 1300 0.6 500 0 0.1 0.2 0.3 0.4 0.5 Static Pressure (inches of water) 0.6 fan powered terminals PERFORMANCE DATA Unit Size Rows gpm One Row 2-3 Two Row Unit Size Rows 4 Two Row • • • • • • 350 400 Airflow, cfm 450 500 550 600 650 0.09 0.36 1.38 3.01 Airside DPs 11.2 12.7 13.6 14.0 0.02 12.0 13.7 14.8 15.2 0.03 12.7 14.5 15.8 16.3 0.04 13.2 15.3 16.7 17.3 0.04 13.8 16.0 17.6 18.2 0.05 14.2 16.7 18.4 19.0 0.06 14.7 17.3 19.1 19.8 0.07 15.0 17.9 19.8 20.6 0.08 1.0 2.0 4.0 6.0 0.21 0.78 2.97 6.50 Airside DPs 17.5 20.1 21.8 22.5 0.05 18.8 22.0 24.1 24.8 0.06 20.0 23.7 26.1 27.0 0.08 22.9 27.9 31.4 32.7 0.13 23.6 29.1 32.9 34.4 0.16 24.3 30.2 34.3 36.0 0.18 450 500 550 21.1 22.0 25.2 26.6 28.0 29.7 29.1 31.0 0.10 0.11 Airflow, cfm 600 650 700 750 800 1.0 2.0 4.0 6.0 0.12 0.45 1.70 3.72 Airside DPs 15.2 17.6 19.1 19.7 0.03 15.8 18.4 20.1 20.8 0.03 16.4 19.2 21.1 21.9 0.04 16.9 19.9 22.0 22.8 0.04 17.4 20.6 22.8 23.7 0.05 17.8 21.3 23.6 24.6 0.06 18.2 21.9 24.4 25.4 0.06 18.6 22.4 25.1 26.2 0.07 1.0 2.0 4.0 6.0 0.25 0.95 3.62 7.93 Airside DPs 23.2 27.8 30.8 32.0 0.06 24.3 29.4 32.8 34.2 0.07 25.2 30.9 34.7 36.2 0.08 26.1 32.3 36.5 38.2 0.10 26.9 33.6 38.2 40.0 0.11 27.7 34.8 39.8 41.8 0.12 28.4 35.9 41.3 43.5 0.14 29.0 36.9 42.7 45.0 0.16 Head Loss All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180BF entering water and 65BF entering air For temperature differentials other than 115B, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Connection size is ½” OD male solder Coils are not intended for steam applications and are labeled for a maximum water temperature of 200BF Coils are tested for leakage at test pressure of 500 psi Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Correction factors for other entering conditions: ∆T 50 60 70 80 90 100 115 125 140 150 Factor 0.44 0.52 0.61 0.7 0.79 0.88 1 1.07 1.2 1.3 N PERFORMANCE DATA • • 300 1.0 2.0 4.0 6.0 gpm One Row • • • • Head Loss Redefine your comfort zone™ | www.titus-hvac.com PFLS, AFLS, DFLS / WATER COIL HEATING CAPACITY (MBH) N61 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA N PFLS, AFLS, DFLS / RADIATED SOUND PERFORMANCE Size CFM Discharge Ps 208 350 400 500 600 700 308 500 600 700 850 1000 426 (8 x 16) 800 1000 1200 1400 1600 Octave Band Sound Power, Lw Min ∆Ps 0.25 0.05 0.07 0.11 0.16 0.22 2 62 63 66 68 70 3 50 52 55 58 60 Fan Only 4 5 6 50 47 38 52 48 40 54 51 43 56 53 45 57 55 47 7 29 30 34 36 38 NC 24 27 29 32 35 2 64 65 68 70 70 3 54 56 59 62 64 0.5”∆Ps 4 5 6 52 49 41 54 50 43 56 53 45 58 55 47 60 57 47 7 32 33 36 38 38 NC 27 28 32 34 35 2 65 66 69 71 73 3 58 60 63 65 68 1.0” ∆Ps 4 5 6 55 51 44 56 52 45 59 55 48 61 57 50 62 59 52 7 36 37 39 41 43 NC 29 30 34 36 38 2 66 67 70 72 73 3 61 62 65 68 70 2.0” ∆Ps 4 5 6 56 52 47 58 53 49 60 56 51 62 58 53 64 60 54 7 39 40 43 45 46 NC 30 32 35 38 41 0.25 0.11 0.16 0.22 0.32 NA 60 63 66 69 71 54 57 59 62 64 57 58 59 61 62 45 48 50 54 57 36 40 43 47 51 23 28 32 37 41 32 33 34 36 38 65 67 69 71 NA 60 63 65 67 NA 57 58 61 63 NA 52 53 55 58 NA 43 45 47 50 NA 33 34 36 39 NA 31 33 36 38 NA 68 69 71 73 NA 64 67 69 72 NA 61 62 63 66 NA 55 57 59 61 NA 48 50 52 53 NA 39 40 42 43 NA 36 37 40 43 NA 70 71 73 74 NA 66 69 71 73 NA 62 63 65 67 NA 57 59 60 63 NA 51 53 54 57 NA 43 44 45 47 NA 37 40 42 44 NA 0.25 0.02 0.03 0.05 0.07 0.09 56 59 61 63 64 52 55 58 60 62 53 56 58 60 62 49 53 55 58 60 40 43 47 49 51 26 31 36 39 42 28 31 33 35 38 59 62 65 67 68 56 59 62 64 65 56 59 61 62 64 53 56 58 60 62 46 48 51 53 54 37 40 41 44 46 30 34 36 37 39 60 63 66 68 69 59 61 64 65 67 58 61 63 65 66 56 58 60 63 64 50 53 55 56 57 46 48 49 50 52 32 36 38 40 41 61 64 66 68 70 61 64 66 68 69 60 63 65 66 67 59 61 63 64 66 54 56 57 59 60 51 53 54 56 57 35 38 40 41 42 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. PFLS, AFLS, DFLS / DISCHARGE SOUND PERFORMANCE PERFORMANCE DATA Size N62 N62 CFM Discharge Ps 208 350 400 500 600 700 308 500 600 700 850 1000 426 (8 x 16) 800 1000 1200 1400 1600 Octave Band Sound Power, Lw Min ∆Ps 0.25 0.05 0.07 0.11 0.16 0.22 2 39 45 54 61 67 3 39 44 53 60 66 Fan Only 4 5 6 53 56 64 56 59 66 61 63 70 65 66 73 68 69 76 7 61 63 68 72 75 NC 25 27 31 35 38 2 57 59 64 68 72 3 52 54 60 65 69 0.5”∆Ps 4 5 6 56 56 64 59 59 66 63 63 70 67 66 73 70 69 76 7 61 63 68 72 75 NC 25 27 31 35 38 2 58 61 65 70 72 3 56 59 63 68 71 1.0” ∆Ps 4 5 6 57 56 64 60 59 66 64 63 70 68 66 73 71 69 76 7 61 63 68 72 75 NC 25 27 31 35 38 2 59 62 66 71 74 3 58 61 66 70 74 2.0” ∆Ps 4 5 6 58 56 64 60 59 66 65 63 70 68 66 73 71 69 76 7 61 63 68 72 75 NC 25 27 31 35 38 0.25 0.11 0.16 0.22 0.32 NA 74 76 78 80 81 67 70 72 75 77 64 66 68 70 72 62 64 66 68 70 61 64 66 69 71 58 61 64 67 70 29 31 34 34 37 74 76 80 82 NA 69 72 74 77 NA 64 66 68 70 NA 64 66 68 70 NA 64 66 68 69 NA 60 63 66 67 NA 29 32 36 37 NA 74 76 80 82 NA 69 72 74 77 NA 64 66 68 72 NA 64 66 66 68 NA 63 66 68 69 NA 60 63 66 67 NA 29 32 36 37 NA 74 76 80 82 NA 69 72 74 77 NA 64 66 68 72 NA 64 64 66 68 NA 63 64 66 69 NA 60 63 66 67 NA 29 32 36 37 NA 0.25 0.02 0.03 0.05 0.07 0.09 59 62 64 65 67 60 62 64 65 67 59 62 65 67 69 60 63 66 68 70 55 60 64 67 70 49 54 59 62 66 17 19 23 26 30 62 65 67 69 71 60 62 66 67 69 61 64 67 67 69 64 66 69 70 72 66 70 72 73 75 60 64 66 68 71 24 28 30 31 34 63 66 68 70 72 62 65 67 68 70 62 65 68 70 72 64 67 69 71 73 65 68 70 72 74 60 64 66 68 71 24 28 30 31 34 63 67 69 71 73 63 66 68 69 71 63 66 68 70 72 64 67 70 71 73 64 66 69 71 73 60 64 66 68 71 24 28 30 31 34 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N63 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Titus is a charter member company and current participant in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990’s. It is currently administrated by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). The purpose of this program is to provide for the independent verification of manufacturers’ published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at www.ahrinet.org. In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types, and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’. These tests are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in AHRI Standard 880 ‘Performance Rating of Air Terminals’. Any failure to demonstrate the certified performance is punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible expulsion from the Certified Directory. Product samples provided for certification testing are standard production units with standard ½ in dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions: PTQS, ATQS, DTQS, PFLS, AFLS, DFLS • Rated airflow (cfm) – Based on lesser of an inlet velocity of 2000 fpm or the maximum fan flow with 0.25 in wg of downstream pressure • Rated fan power (watts) – Based on fan operating at the rated airflow with 0.25 in wg of downstream pressure • Rated Min ∆Ps (in wg) – Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure at rated airflow with the primary damper full open and the unit fan set to match the primary flow • Rated ∆Ps (in wg) – A static pressure of 1.5 in wg applied to the inlet duct • Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220 PTQS, ATQS, DTQS Unit Size 208 310 412 512 614 716 Rated CFM 500 900 1300 1500 2000 2400 Fan Watts 340 570 700 860 1400 1800 Min ∆Ps 0.10 0.16 0.21 0.16 0.17 0.15 Discharge H W 15 17 15 17 15 17 17.5 25 17.5 25 17.5 25 Fan Only Radiated Sound Power 2 3 4 5 6 63 59 54 47 41 62 58 55 49 41 69 64 60 55 48 69 63 59 57 51 70 67 61 58 52 76 67 67 62 58 Min ∆Ps 0.22 0.22 0.09 Discharge H W 8.75 21 8.75 21 8.75 28 Fan Only Radiated Sound Power 2 3 4 5 6 70 60 57 55 47 66 59 59 50 43 64 62 62 60 51 7 37 36 42 45 47 54 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 67 62 57 51 46 70 62 58 52 46 74 67 63 57 51 74 67 62 60 53 76 70 64 60 55 80 71 69 64 61 7 38 32 42 Fan Plus 100% Primary Radiated Sound Power 2 3 4 5 6 73 70 64 60 54 73 71 65 60 54 70 69 67 66 60 7 43 41 46 48 50 57 Fan Only Discharge Sound Power 2 3 4 5 6 7 77 68 62 60 60 59 73 65 61 57 57 55 77 72 65 62 62 61 77 68 67 64 63 63 77 68 67 65 64 64 81 68 68 66 65 65 7 46 45 57 Fan Only Discharge Sound Power 2 3 4 5 6 7 67 66 68 69 76 75 78 72 68 66 66 64 67 67 69 70 70 66 Redefine your comfort zone™ | www.titus-hvac.com AHRI Directory of Certified Performance N PFLS, AFLS, DFLS Rated CFM 700 700 1600 Fan Watts 250 350 800 PERFORMANCE DATA Unit Size 208 308 426 N63 Redefine your comfort zone™ | www.titus-hvac.com Low Profile Series Powered Terminals (continued) fan powered terminals DLSC • Low profile design under 12” high on all sizes for application on shallow ceiling plenums • Pressure independent primary airflow control • Casing manufactured of 20 gauge G40 galvanized steel. Mechanically sealed, leak resistant construction with less than 2% of nominal CFM at 1.5” wg static pressure. • Standard internal liner, ½ EcoShield Matted faced for resistance to air erosion. Contains no harmful irritants or chemicals with EPA registered antimicrobial inhibitor and meets requirements of NFPA 90A and UL 181. • Ultra high efficiency ECM brushless DC motor with microprocessor based controller DLSC • Fan airflow controlled by a manual or remote PWM speed controller • Titus AeroCross™ multipoint center averaging inlet velocity sensor with +/- 5% accuracy across the complete airflow range N • Fully gasketed heavy duty round damper manufactured of heavy gauge galvanized steel with metal shaft rotating in Delrin selflubricating bearings • Primary airflow balancing connections for CFM measurement energy solutions AVAILABLE MODEL: See website for Specifications DLSC / Basic Unit OVERVIEW Fan Powered Induction The DLSC is a fan powered terminal unit that features a sensible cooling coil. It has been designed to work as part of a dedicated outdoor air system (DOAS). These systems provide an alternate solution to addressing ASHRAE 62.1 ventilation requirements. ADDITIONAL FEATURES DLSC • Single point electrical connections • Rectangular discharge opening is designed for flanged duct connections • Double wall condensate pan with 7/8” drain connection • High efficiency sensible cooling and booster heating coils factory installed on return air inlet • Removable bottom access panel for easy service/maintenance • UL Class2 control transformer 24V secondary voltage • ETL Certified N64 N64 Cutaway view of LSC terminal unit fan powered terminals DIMENSIONS DLSC / Unit Size 3 10 5/8 6 5/16 2 3/16 Damper Shaft 40 5/16 Control Enclosure 20 1/16 9 9/16 3 1/4 3 3/16 5 13/16 Primary Air Damper 6 1/4 9 SUPPLY AIR ECM Motor PWM Board PRIMARY AIR 5 9/16 Aerocross Velocity Sensor 26 Redefine your comfort zone™ | www.titus-hvac.com DLSC DIMENSIONS 2 7/8 5/16 2 1/4 5 9 9/16 1 5/8 Water Coil RETURN AIR 7/8 1 15/16 36 1/16 8 3/4 Condensate Pan (7/8" Sweat Connection) 12 1 1/16 N DIMENSIONS All dimensions are in inches N65 fan powered terminals DLSC DIMENSIONS DLSC / Unit Size 4 (With Round Primary Air Inlet) 10 5/8 6 13/16 1 13/16 Damper Shaft Control Enclosure 40 5/16 20 1/16 3 3/16 3 1/4 9 9/16 5 13/16 6 1/4 ECM PWM Board PRIMARY AIR 20 1/2 Primary Air Damper 5 5/8 Aerocross Velocity Sensor SUPPLY AIR Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS MOTOR/BLOWER 43 11 5/16 N 5.0 9 9/16 1 1/16 1 5/8 Water Coil RETURN AIR 7/8 1 15/16 36 1/8 Condensate Pan (7/8" sweat connection) 8 3/4 12 DLSC / Unit Size 4 (With Rectangular Primary Air Inlet) 1 13/16 10 5/8 6 13/16 Damper Shaft Control Enclosure 40 1/4 20 1/16 3 7/16 3/4 1 3/8 1 3/8 9 9/16 7 13/16 6 1/4 DIMENSIONS 43 Primary Air Damper 15 13/16 Aerocross Velocity Sensor 13 9/16 11 5/16 9 9/16 5.0 1 1/16 7/8 8 3/4 N66 N66 PRIMARY AIR 20 1/2 SUPPLY AIR ECM PWM Board 1 15/16 RETURN AIR 36 1/8 1 5/8 Condensate Pan (7/8" sweat Connection) 13 5/16 All dimensions are in inches fan powered terminals PERFORMANCE DATA Coil Type / Pipe Connection STANDARD FEATURES Galvanized steel casing ½” copper tubes 0.016 wall thickness Aluminum ripple fins Connections type - male sweat Flanged connection if ducted without filters • Coils are installed at the return air inlet of the unit Coil • • • • • 36 1/8 10 TYP HW Connections /8 /8 7 /8 7 /8 5 /8 5 5 /8 5 Return Air - Cooling / Heating Coils Flange Connection (With Filter) COIL PLAN VIEW COIL FRONT VIEW 3 1/16 CW Connections 2 Row Cooling 2 Row Cooling + 1 Row Heating 4 Row Cooling 4 Row Cooling + 1 Row Heating Return Air - Cooling / Heating Coils Flange Connection (No Filter) 3/4 TYP Redefine your comfort zone™ | www.titus-hvac.com WATER COIL SECTION ∅3/16 - 12 PLCS 3/4 TYP 2 3/8 4 3/4 6 8 3/4 2 3/8 3/4 Right hand unit shown All dimensions are in inches ELECTRIC COIL SECTION STANDARD FEATURES Safety auto reset thermal cutouts (one per heater element) 80/20 Nickel chrome heating elements Magnetic contactors for stepped heating Airflow safety switch Terminal block Flanged connection • • • • • • 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3ph, 60 Hz. (4 wire WYE only) • • • • • 3/4 3/4 8 7/8 3/4 N Right hand unit shown All dimensions are in inches OPTIONS Mercury contactors for silence operation Fuse Block Door Interlock Disconnect Switch Secondary Manual reset thermal cutout Dust-tight construction Lynergy Comfort Controlled solid state relay electric heat: - Accepts the following control signals PWM heat 2 Stage heat 0-10V / 0-20mA 2-10V / 4-20mA Incremental T-stat Binary 3 point floating - Discharge temperature limit sensor/control • • • • • • PERFORMANCE DATA SUPPLY VOLTAGE 38 3/4 N67 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA Unit Size 3 / Electric Heater Option ELECTRIC HEATER ENCLOSURE 1 ELECTRIC HEATER 10 1/2 1 1/8 N 9.75 8 7/16 1 Unit Size 4 / Electric Heater Option ELECTRIC HEATER ENCLOSURE 1 ELECTRIC HEATER 20 1/2 PERFORMANCE DATA 11 1/4 N68 N68 8 7/16 9 3/4 1 ADDITIONAL ACCESSORIES (OPTIONAL) • • • • • • Return air pleated filter - MERV8 Return air filter flange for duct applications Motor fuses Unit hanger brackets Discharge air slip & drive connection kit Unit disconnect switch ECM ELECTRICAL DATA Unit Size Motor HP 1 3 ⁄3 4 (2) 1⁄3 120V 5.0 10.0 208V 3.3 6.6 240V 2.8 5.6 277V 2.6 5.2 fan powered terminals PERFORMANCE DATA Inlet Size Notes: 1. An asterisk (*) indicates factory cfm settings (except zero) will not be made below this range because control accuracy is reduced Minimum and Maximum Range Settings (cfm) Total Range (cfm) Minimum Maximum 4 0-225 45*-225 45*-225 6 8 8 x 16 0-500 0-900 0-1860 80*-500 145*-900 325*-1860 80*-500 145*-900 325*-1860 2. For selection procedure, see the section “Engineering Guidelines” and the topic “ECM Motors - Fan Powered Terminals” for additional information DLSC / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE (ECM MOTOR STD) LSC Size 3 LSC Size 4 1000 Redefine your comfort zone™ | www.titus-hvac.com PRIMARY AIR CFM RANGES 1900 900 1700 800 N 1500 1300 700 1100 600 900 500 700 400 300 500 300 0 0.1 0.2 0.3 0.4 0.5 0.6 0 0.1 0.2 0.3 0.4 0.5 0.6 PERFORMANCE DATA N69 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA DLSC HOT WATER COIL • All coil performance in accordance with AHRI 410-2001 • Heating and cooling capacities are in MBH (1,000 Btu/h) • For differentials between EAT and EWT above 18°, multiply MBH by correction factors below • Refer to submittal documentation for pipe sizes and connection locations • Air temperature drop / rise = 927 x MBH /gpm • Water temperature drop / rise = 2.04 x MBH /gpm • Coils are rated to 200°F (No steam applications) • Coils are tested for leakage at test pressure of 500 psi • Water flows less than those shown may result in water laminar flow and reduced heating/cooling capacities. Whenever possible, reduce the number of coil rows to increase water velocity into turbulent range. Correction factors for other entering conditions: N ∆T(BF) 3 8 13 18 23 28 33 Cooling Factor 0.17 0.50 0.75 1.00 1.33 1.61 1.91 ∆T(BF) 60 65 70 75 80 85 90 Heating Factor 1.14 1.07 1.00 0.93 0.86 0.79 0.71 DLSC / WATER COIL CAPACITY (MBH) Coil Rows 2 PERFORMANCE DATA 4 400 500 600 700 800 Cooling Coil Performance (MBH) Induced Airflow, cfm 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1.0 2.0 3.0 4.0 5.0 0.40 1.50 3.30 5.75 8.90 Airside ∆Ps 2.6 3.5 3.7 3.8 4.0 0.03 3.0 3.9 4.3 4.6 4.7 0.04 3.3 4.4 4.9 5.2 5.4 0.06 3.5 4.8 5.4 5.7 6.0 0.08 3.7 5.1 5.8 6.2 6.5 0.10 4.0 5.4 6.2 6.7 7.2 0.12 4.0 5.7 6.6 7.0 7.7 0.15 4.2 5.9 6.9 7.5 8.0 0.18 4.3 6.2 7.2 7.8 8.3 0.21 4.5 6.4 7.5 8.1 8.6 0.23 4.7 6.9 8.1 9.0 9.5 0.26 4.8 7.1 8.4 9.2 9.7 0.29 4.9 7.3 8.7 9.5 9.9 0.32 4.9 7.5 8.9 9.8 10.4 0.36 5.0 7.6 9.1 10.1 10.7 0.40 1.0 2.0 3.0 4.0 5.0 6.0 0.30 1.00 2.30 4.00 6.20 8.90 Airside ∆Ps 4.0 5.0 5.5 6.0 5.8 5.8 0.06 4.5 6.0 6.6 6.7 7.0 7.2 0.09 4.9 6.7 7.6 7.8 8.2 8.4 0.12 5.3 7.5 8.4 8.7 9.3 9.5 0.16 5.4 7.8 9.2 9.5 10.2 10.6 0.20 5.6 8.3 9.9 10.3 11.1 11.5 0.25 5.8 8.7 10.5 11.0 11.9 12.4 0.30 5.9 9.0 11.0 11.6 12.6 13.2 0.36 6.0 9.4 11.6 12.1 13.3 14.0 0.42 6.2 10.0 12.0 13.0 14.0 14.6 0.48 6.4 10.3 12.4 13.7 14.6 15.3 0.52 6.5 10.5 12.8 14.2 15.2 15.9 0.58 6.5 10.7 13.1 14.7 15.7 16.6 0.65 6.6 10.9 13.5 15.1 16.3 17.0 0.70 6.7 11.1 13.8 15.5 16.7 17.6 0.80 1400 1500 1600 1700 1800 11.5 16.0 19.9 21.6 0.12 11.6 16.4 20.4 22.2 0.14 11.8 16.7 20.7 22.7 0.15 11.9 16.9 21.3 23.3 0.17 12.0 17.2 21.7 23.8 0.19 Water Flow (gpm) Head Loss (ft WG) EAT: 75BF, EWT: 57BF Coil Rows 1 Water Flow (gpm) 0.5 1.0 2.0 3.0 Head Loss (ft WG) 0.3 1.2 4.6 10.0 Airside ∆Ps 400 500 600 700 800 Heating Coil Performance (MBH) Induced Airflow, cfm 900 1000 1100 1200 1300 8.3 10.2 11.6 12.1 0.01 8.9 11.2 12.9 13.6 0.02 9.4 12.1 14.1 14.9 0.03 9.8 12.8 15.1 16.0 0.04 10.1 13.5 16.0 17.1 0.05 10.5 14.0 16.8 18.0 0.06 EAT: 70BF, EWT: 140BF (Do not use EWT 180BF - ECM motor may overheat) N70 N70 Operating Range ECM Motor Blower LSC3 Min / Max Airflow 410/850 CFM LSC4 Min / Max Airflow 500/1750 CFM 10.7 14.5 17.5 18.8 0.07 11.0 15.0 18.2 19.6 0.08 11.2 15.4 18.8 20.3 0.09 11.3 15.7 19.4 21.0 0.11 fan powered terminals PERFORMANCE DATA Size CFM 3 500 600 700 850 4 800 1000 1200 1400 1600 Discharge Ps Octave Band Sound Power, Lw Min ∆Ps 0.25 0.11 0.16 0.22 0.32 2 60 63 66 69 3 54 57 59 62 Fan Only 4 5 6 57 45 36 58 48 40 59 50 43 61 54 47 7 23 28 32 37 NC 32 33 34 36 2 65 67 69 71 3 60 63 65 67 0.5”∆Ps 4 5 6 57 52 43 58 53 45 61 55 47 63 58 50 7 33 34 36 39 NC 31 33 36 38 2 68 69 71 73 3 64 67 69 72 1.0” ∆Ps 4 5 6 61 55 48 62 57 50 63 59 52 66 61 53 7 39 40 42 43 NC 36 37 40 43 2 70 71 73 74 3 66 69 71 73 1.5” ∆Ps 4 5 6 62 57 51 63 59 53 65 60 54 67 63 57 7 43 44 45 47 NC 37 40 42 44 0.25 0.02 0.03 0.05 0.07 0.09 56 59 61 63 64 52 55 58 60 62 53 56 58 60 62 26 31 36 39 42 28 31 33 35 38 59 62 65 67 68 56 59 62 64 65 56 59 61 62 64 37 40 41 44 46 30 34 36 37 39 60 63 66 68 69 59 61 64 65 67 58 61 63 65 66 46 48 49 50 52 32 36 38 40 41 61 64 66 68 70 61 64 66 68 69 60 63 65 66 67 51 53 54 56 57 35 38 40 41 42 49 53 55 58 60 40 43 47 49 51 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts 53 56 58 60 62 46 48 51 53 54 56 58 60 63 64 50 53 55 56 57 59 61 65 64 66 54 56 57 59 60 • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. DLSC / DISCHARGE SOUND PERFORMANCE Size CFM Discharge Ps 3 500 600 700 850 4 800 1000 1200 1400 1600 Redefine your comfort zone™ | www.titus-hvac.com DLSC / RADIATED SOUND PERFORMANCE N Octave Band Sound Power, Lw Min ∆Ps 0.25 0.11 0.16 0.22 0.32 2 69 71 73 75 3 65 68 70 73 Fan Only 4 5 6 63 62 61 65 64 64 67 66 66 69 68 69 7 58 61 64 67 NC 24 28 30 32 2 69 71 75 77 3 67 70 72 75 0.5”∆Ps 4 5 6 63 64 64 65 66 66 67 68 68 69 70 69 7 60 63 66 67 NC 25 29 31 34 2 69 71 75 77 3 67 70 72 75 1.0” ∆Ps 4 5 6 63 64 63 65 66 66 67 66 68 71 68 69 7 60 63 66 67 NC 25 29 31 34 2 69 71 75 77 3 67 70 72 75 1.5” ∆Ps 4 5 6 65 64 63 65 64 64 67 66 66 71 68 69 7 60 63 66 67 NC 25 29 31 34 0.25 0.02 0.03 0.05 0.07 0.09 54 57 59 60 62 58 60 62 63 65 59 62 65 67 69 49 54 59 62 66 14 18 23 25 29 57 60 62 64 66 58 60 64 65 67 61 64 67 67 69 60 64 66 68 71 14 17 21 22 24 58 61 63 65 67 60 63 65 66 68 62 65 68 70 72 60 64 66 68 71 16 20 22 23 25 58 62 64 66 68 61 64 66 67 69 63 66 68 70 72 60 64 66 68 71 17 21 23 24 27 60 63 66 68 70 55 60 64 67 70 66 70 72 73 75 64 67 69 71 73 65 68 70 72 74 64 67 70 71 73 64 66 69 71 73 • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. PERFORMANCE DATA • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the difference between atmospheric pressure and the inlet static pressure with the primary damper full open and the unit fan set to match the primary flow • Sound power levels are in dB, ref 10-12 watts 64 66 69 70 72 N71 Redefine your comfort zone™ | www.titus-hvac.com Parallel Fan Powered Terminals fan powered terminals TQP • Two casing sizes ease in design layout • Pressure independent primary airflow control • AeroCross™ multi-point, center averaging inlet velocity sensor • Primary airflow balancing connections • Adjustments are easily accessible through ceiling opening • Energy efficient fan motor, permanent split capacitor type mounted with vibration isolators • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • Dual density insulation, coated to prevent air erosion, meets requirements of NFPA 90A and UL 181 TQP • 20 gauge, galvanized steel casing with leak resistant construction N • Rectangular discharge opening is designed for flanged duct connections • Bottom access panel can be removed for service energy solutions AVAILABLE MODELS: PTQP / Pneumatic Control ATQP / Analog Control DTQP / Digital Control OVERVIEW Parallel Flow TQP In a Parallel Flow terminal, the fan is outside the primary airstream and runs intermittently, when the primary air is off. Parallel flow or variable volume Fan Powered terminals operate in two distinct modes: variable volume, constant temperature when handling high cooling loads; and constant volume, variable temperature when heating or handling light cooling loads. N72 N72 See website for Specifications fan powered terminals DIMENSIONS Redefine your comfort zone™ | www.titus-hvac.com TQP UNIT DIMENSIONS DTQP / Sizes 2-6 3 B N H 12 20 6¼ A D Primary Air Inlet with AeroCrossTM Multipoint Center Averaging Sensor C W F Induced Air Inlet 1 1¼ G E N K J L TQP Parallel Unit Size 2, 3 4 5 6 Inlet Size A 6 8 10 12 8 10 12 14 10 12 14 16 12 14 16 6 6 7 8 6 7 8 10 7 8 10 11 8 10 11 B C D 5 /8 77/8 97/8 117/8 77/8 97/8 117/8 137/8 97/8 117/8 137/8 157/8 117/8 137/8 157/8 E F G H J K L 7 89/16 16¾ 101/16 24½ N 2 /8 27/8 47/8 47/8 27/8 47/8 47/8 67/8 47/8 47/8 67/8 67/8 47/8 67/8 67/8 W Filter Size 36¼ 19 x 17 48¼ 27 x 20 7 14½ 14 3½ 171/8 11 21/8 407/8 17½ 16½ 9½ 201/8 14½ 31/8 467/8 DIMENSIONS All dimensions are in inches N73 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS HOT WATER COIL SECTION STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins, 10 per inch • Connections: Male solder 5 /8” for both 1- and 2-row. Right hand only. • Galvanized steel casing • Flanged duct connection • Coil is installed at induced air inlet COIL ROWS • 1-Row • 2-Row Unit Size 2, 3, 4 5, 6 • • • 120V, 1 ph, 60 Hz. 208/240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. R 1" Typ. Hot Water Coil Section (Inlet Mounted) M (1-Row) M (2-Row) R 1 1¼ 17 1 1¼ 25 S 15 17 M S 9 Note: R and S are inside dimensions ELECTRIC COIL SECTION STANDARD FEATURES N SUPPLY VOLTAGE • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements. • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls OPTIONS • Interlocking disconnect • Main power supply fuses • Mercury contactors Electric Coil Section (Discharge Mounted) Unit Size U R S T 2, 3, 4 3½ 14 11 17/8 5, 6 8½ 16½ 14½ 2¼ • Manual reset thermal cutout • Dust-tight construction • Optional Lynergy Comfort Controlled SSR Electric Heat available SUPPLY VOLTAGE • • • • • 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 31 Heater Rack Access Cover Note: Coil control box replaces standard terminal unit control box 1" Typ. Note: R and S are inside dimensions R See Electric Heat Coils in Section O for more information U 9¾ ADDITIONAL ACCESSORIES DIMENSIONS (OPTIONAL) N74 N74 • Induced air filter, 1” thick, disposable construction type • Fan unit fusing • Toggle type disconnect switch (not available on units with optional electric coils) • 1” liner • Fibre-Free liner • SteriLoc liner • EcoShield liner • Hanger brackets • Camlocks on fan access door Unit Size Motor HP 2 3 4 5 6 ⁄6 1 /4 1 ⁄3 ⁄3 1 1 ¾ S Electrical Data Motor Amperage Ratings 120V 208/240V FLA FLA 3.6 1.5 5.3 2.6 7.8 3.2 9.2 3.3 12.3 6.3 T 277V FLA 1.3 2.2 2.9 3.2 5.4 FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are single phase, same voltage as electric coil (when supplied), with exception that 277 voltage motors are used with 480 volt / 3 phase coil (4 wire wye) ECM ELECTRICAL DATA Unit Size Motor HP 3 ½ 4 ½ 5 1 6 1 120V 7.7 7.7 12.8 12.8 208V 5.0 5.0 10.5 10.5 240V 4.3 4.3 9.1 9.1 277V 4.1 4.1 6.9 6.9 FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are single phase, same voltage as electric coil (when supplied), with exception that 277 voltage motors are used with 480 volt / 3 phase coils (4 wire wye) fan powered terminals PERFORMANCE DATA Inlet Size Total cfm Range 6 8 10 12 14 16 0-500 0-900 0-1400 0-2000 0-3000 0-4000 PTQP TITUS II, IIA Pneumatic Controller Minimum Maximum *80-330 150-500 *145-590 265-900 *230-925 415-1400 *325-1330 600-2000 *450-1800 840-3000 *580-2350 1100-4000 PTQP TITUS I Pneumatic Controller Minimum Maximum *105-350 150-500 *190-590 265-900 *300-925 415-1400 *425-1330 600-2000 *575-1800 810-3000 *750-2350 1100-4000 ATQP TITUS TA1 Analog Electronic Controller Minimum Maximum *80-500 80-500 *145-900 145-900 *230-1400 230-1400 *325-2000 325-2000 *450-3000 450-3000 *580-4000 580-4000 DTQP Typical Digital Controller Minimum Maximum *45-500 45-500 *90-900 90-900 *145-1400 145-1400 *190-2000 190-2000 *300-3000 300-3000 *385-4000 385-4000 Note: An asterisk (*) indicates factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure dependent units, minimum cfm is always zero and there is no maximum. PTQP, ATQP, DTQP / PRIMARY AIR INLET PRESSURES: SIZES 2-4 Redefine your comfort zone™ | www.titus-hvac.com PRIMARY AIR CFM RANGES 3000 Airflow, CFM 2000 1000 900 800 700 600 500 400 300 -4 12 2 Size in. Size 0 in. 2-4 1 -4 8 2 Size Size 200 100 N in. 0.01 0.02 0.03 0.04 0.05 0.06 0.08 2-4 6 in. 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. PTQP, ATQP, DTQP / PRIMARY AIR INLET PRESSURES: SIZES 5-6 3000 1000 900 800 700 600 500 Size 5 in. -6 16 5-6 Size . 14 in Size 2 in. 0 in. 5-6 1 e z i S 5-6 1 400 300 200 100 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 Required Minimum Inlet Static Pressure, Inches Wg. PERFORMANCE DATA Airflow, CFM 2000 Note: See section Engineering Guidelines and topic ‘Sizing Basic Terminals from Capacity Table’ to select and size terminal units N75 fan powered terminals PTQP, ATQP, DTQP / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 2 1000 Unit Size 3 Unit Size 4 1600 2000 1400 1800 900 800 1600 1200 700 600 1400 500 400 300 CFM 1000 CFM CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 800 1200 1000 600 800 200 400 100 0.1 0.2 0.3 0.4 0.5 0.1 0.6 Static Pressure - Inches of Water 2000 0.4 0.5 0.6 0.2 2300 2100 CFM 1200 1000 1900 1700 800 1500 600 1300 400 1100 0.1 0.2 0.3 0.4 0.5 0.1 0.6 Static Pressure - Inches of Water 0.2 0.3 0.4 0.5 0.6 Static Pressure - Inches of Water PTQP, ATQP, DTQP WITH ECM / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE TQP w/ECM Size 6 TQP w/ECM Size 4 2800 1500 2600 2400 1300 CFM CFM 2200 1100 900 2000 1800 1600 700 1400 500 1200 N76 N76 300 1000 0 0.1 0.2 0.3 0.3 0.4 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil 2500 1400 0.1 0.4 Static Pressure - Inches of Water 0.5 0.6 0 0.1 0.5 0.6 Static Pressure - Inches of Water 2700 1600 CFM 0.3 Unit Size 6 2900 1800 PERFORMANCE DATA 0.2 Static Pressure - Inches of Water Unit Size 5 2200 200 400 200 0 N 600 0.2 0.3 0.4 Static Pressure - Inches of Water 0.5 0.6 fan powered terminals PERFORMANCE DATA TQP / SIZE 3 - ECM MOTOR Redefine your comfort zone™ | www.titus-hvac.com PTQP, ATQP, DTQP WITH ECM / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE TQP / SIZE 5 - ECM MOTOR N TQP / SIZE 6 - ECM MOTOR TQP w/ECM Size 4Size 4 TQP w/ECM 1300 1300 1100 1100 900 700 700 500 300 500 0 300 2800 2600 2600 2400 2400 2200 2200 2000 2000 1800 1800 1600 1600 1400 1400 1200 1200 1000 0.1 0 0.2 0.1 0.3 0.2 0.4 0.3 0.5 0.4 Static Pressure - Inches of Water of Water Static Pressure - Inches 0.6 0.5 0.6 0 1000 0.1 0 0.2 0.1 0.3 0.2 0.4 0.3 0.5 0.4 Static Pressure - Inches of Water of Water Static Pressure - Inches 0.6 0.5 0.6 PERFORMANCE DATA 900 CFM 1500 CFM CFM 1500 TQP w/ECM Size 6Size 6 TQP w/ECM 2800 CFM TQP / SIZE 4 - ECM MOTOR N77 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTQP, ATQP, DTQP / WATER COIL HEATING CAPACITY (MBH) Unit Size Rows One Row 2 Two Row Unit Size Rows One Row 3 N Two Row Unit Size Rows One Row 4 Two Row Unit Size Rows One Row PERFORMANCE DATA 5 Two Row Unit Size Rows One Row 6 Two Row N78 N78 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 GPM 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 gpm 1.0 2.0 4.0 6.0 1.0 2.0 4.0 6.0 Head Loss 0.15 0.56 2.14 4.69 Airside DPs 0.31 1.18 4.50 9.86 Airside DPs Head Loss 0.15 0.56 2.15 4.70 Airside DPs 0.31 1.19 4.52 9.88 Airside DPs Head Loss 0.15 0.56 2.15 4.70 Airside DPs 0.32 1.19 4.53 9.91 Airside DPs Head Loss 0.23 0.86 3.27 7.16 Airside DPs 0.47 1.79 6.79 14.84 Airside DPs Head Loss 0.23 0.86 3.28 7.17 Airside DPs 0.48 1.80 6.82 14.88 Airside DPs 180 9.2 10.1 10.6 10.8 0.01 13.0 14.4 15.1 15.4 0.01 230 10.4 11.6 12.3 12.5 0.01 15.1 17.0 18.1 18.6 0.02 280 11.5 12.9 13.8 14.1 0.01 16.9 19.4 20.8 21.4 0.03 400 13.4 15.4 16.7 17.2 0.02 20.3 24.0 26.4 27.5 0.05 510 14.8 17.3 18.9 19.6 0.03 22.6 27.5 30.7 32.0 0.07 620 15.9 18.8 20.8 21.6 0.04 24.5 30.4 34.4 36.0 0.09 800 17.3 20.9 23.4 24.4 0.07 26.8 34.2 39.6 41.7 0.15 870 17.8 21.6 24.2 25.3 0.08 27.6 35.5 41.3 43.7 0.17 940 18.2 22.2 25.1 26.2 0.09 28.3 36.7 43.0 45.6 0.19 800 21.9 26.7 30.0 31.3 0.03 31.4 40.7 47.3 50.0 0.06 910 22.9 28.2 31.9 33.4 0.03 32.8 43.2 50.9 54.0 0.07 1020 23.7 29.6 33.7 35.4 0.04 34.0 45.5 54.2 57.8 0.09 1300 25.5 32.5 37.5 39.6 0.06 36.4 50.3 61.4 66.1 0.13 1450 26.3 33.8 39.3 41.6 0.07 37.3 52.4 64.7 70.0 0.16 1600 26.9 34.9 40.9 43.4 0.09 38.2 54.3 67.8 73.6 0.19 Airflow, cfm 330 380 430 12.4 13.2 13.8 14.0 15.1 16.0 15.1 16.3 17.4 15.5 16.7 17.9 0.02 0.02 0.02 18.5 19.8 21.0 21.4 23.3 25.0 23.3 25.6 27.7 24.0 26.4 28.7 0.03 0.04 0.05 Airflow, cfm 730 840 950 16.8 17.6 18.3 20.1 21.3 22.3 22.4 23.9 25.2 23.4 24.9 26.3 0.06 0.07 0.09 26.0 27.3 28.4 32.8 35.0 36.9 37.7 40.6 43.2 39.6 42.9 45.8 0.12 0.16 0.19 Airflow, cfm 1010 1080 1150 18.6 19.0 19.2 22.8 23.4 23.9 25.8 26.6 27.2 27.1 27.9 28.6 0.10 0.11 0.12 28.9 29.5 30.0 37.8 38.8 39.8 44.5 46.0 47.4 47.3 49.0 50.6 0.21 0.24 0.27 Airflow, cfm 1130 1240 1350 24.5 25.2 25.8 30.8 31.9 32.9 32.3 36.8 38.1 37.1 38.8 40.3 0.05 0.06 0.06 35.0 35.9 36.7 47.5 49.4 51.1 57.2 60.0 62.5 61.2 64.5 67.5 0.10 0.12 0.14 Airflow, cfm 1750 1900 2050 27.5 28.1 28.6 36.0 37.0 37.9 42.4 43.8 45.1 45.1 46.7 48.2 0.10 0.12 0.13 38.9 39.6 40.2 56.0 57.6 59.0 70.5 73.1 75.5 77.0 80.1 83.0 0.22 0.25 0.28 For Performance Notes, see the next page 480 14.5 16.8 18.4 19.0 0.03 22.1 26.6 29.6 30.8 0.06 530 15.0 17.6 19.3 20.0 0.03 23.0 28.0 31.4 32.8 0.07 580 15.5 18.3 20.1 20.9 0.04 23.9 29.4 33.1 34.6 0.09 1060 18.9 23.2 26.4 27.6 0.11 29.3 38.6 45.6 48.5 0.23 1170 19.4 24.1 27.4 28.8 0.13 30.1 40.1 47.8 51.0 0.27 1280 19.9 24.8 28.4 29.9 0.15 30.8 41.4 49.8 53.3 0.32 1220 19.6 24.4 27.9 29.3 0.14 30.5 40.7 48.7 52.1 0.29 1290 19.9 24.9 28.5 30.0 0.15 30.9 41.5 49.9 53.5 0.32 1360 20.2 25.3 29.1 30.7 0.16 31.3 42.3 51.1 54.9 0.35 1460 26.3 33.8 39.4 41.7 0.07 37.4 52.6 64.9 70.3 0.16 1570 26.8 34.7 40.6 43.1 0.08 38.0 54.0 67.2 72.9 0.18 1680 27.3 35.5 41.7 44.3 0.09 38.6 55.3 62.3 75.4 0.20 2200 29.0 38.7 46.3 49.5 0.15 40.7 60.2 77.7 85.7 0.32 2350 29.4 39.4 47.4 50.8 0.17 41.1 61.4 79.8 88.2 0.36 2500 29.8 40.2 48.5 52.1 0.19 41.5 62.5 81.7 90.6 0.40 fan powered terminals PERFORMANCE DATA • • • • • • • • All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180BF entering water and 75BF entering air For temperature differentials other than 105B, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Connection size is 5/8” OD male solder Coils are not intended for steam applications and are labeled for a maximum water temperature of 200BF Coils are tested for leakage at test pressure of 500 psi Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Redefine your comfort zone™ | www.titus-hvac.com • • • • Correction factors for other entering conditions: ∆T 50 60 70 80 90 100 115 125 140 150 Factor 0.52 0.6 0.69 0.78 0.87 0.96 1.08 1.15 1.28 1.38 N PERFORMANCE DATA N79 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PERFORMANCE DATA N N80 N80 PTQP, ATQP, DTQP / RADIATED SOUND PERFORMANCE / PRIMARY AIR ONLY Unit Size Inlet Size 2-3 6 2-4 8 2-4 10 2-4 12 4 14 5 10 5-6 12 5-6 14 5-6 16 cfm 300 350 400 450 500 600 650 700 750 800 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.24 0.32 0.40 0.50 0.17 0.20 0.24 0.27 0.31 0.18 0.22 0.26 0.31 0.37 0.17 0.23 0.30 0.38 0.47 0.22 0.32 0.43 0.56 0.71 0.16 0.19 0.23 0.28 0.32 0.15 0.21 0.27 0.35 0.43 0.12 0.18 0.24 0.32 0.40 0.16 0.23 0.32 0.42 0.53 2 57 58 58 59 60 63 63 64 64 64 66 67 68 68 69 68 69 71 72 73 69 70 71 72 73 66 67 68 69 69 66 67 69 70 71 69 70 71 72 73 68 69 70 71 71 3 51 53 54 55 56 56 57 58 59 60 57 58 59 60 60 59 60 61 62 62 61 62 63 63 64 56 57 58 59 60 58 59 60 61 62 61 62 63 63 64 61 61 62 63 63 1.0”∆Ps 4 5 6 47 39 35 49 41 37 51 42 38 52 44 40 53 45 41 51 44 37 52 45 38 52 46 38 53 46 39 53 47 40 54 49 39 54 49 40 54 50 40 55 50 41 55 50 41 56 50 40 57 50 41 57 51 42 58 51 43 59 51 44 56 49 45 57 49 46 58 50 46 58 50 47 59 51 47 49 45 39 50 46 40 50 47 40 51 47 41 52 48 41 52 46 41 53 47 42 54 48 42 55 49 43 56 50 44 56 49 45 57 49 46 58 50 46 58 50 47 59 51 47 55 49 45 57 50 45 58 50 46 58 51 46 59 51 47 7 31 32 33 34 35 29 30 30 31 31 30 30 31 31 32 31 32 33 34 34 38 38 39 39 40 32 33 33 33 34 33 34 34 35 36 38 38 39 39 40 37 37 38 38 38 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with primary damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 21 23 25 27 28 26 27 28 29 30 29 31 32 32 33 32 33 36 37 38 33 35 36 37 38 29 31 32 33 33 29 31 33 34 36 33 34 36 37 38 32 33 34 36 36 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 NC 60 54 51 41 38 35 25 61 56 52 43 40 36 27 61 57 54 45 41 37 29 62 58 55 46 43 38 30 63 59 57 47 44 39 32 66 60 55 47 41 34 30 66 61 55 48 42 34 30 67 62 56 49 42 35 31 67 63 56 50 43 35 33 67 63 57 50 43 35 33 70 61 58 53 44 34 34 71 62 58 54 44 35 36 71 63 58 54 45 35 36 72 64 59 54 45 36 37 72 64 59 55 46 36 37 72 63 59 54 44 35 37 73 64 60 55 45 36 38 75 65 61 55 46 37 41 76 66 62 55 47 38 42 77 66 62 55 48 39 43 72 66 60 54 50 44 37 74 67 61 54 51 44 40 75 67 62 55 51 45 41 76 68 63 55 52 45 42 77 68 63 55 52 45 43 69 60 52 48 43 37 33 70 61 53 49 44 38 34 71 62 54 50 45 38 36 72 63 55 51 45 39 37 73 64 56 51 46 39 38 69 61 55 49 45 38 33 71 63 56 50 46 39 36 72 64 57 52 47 40 37 74 65 59 52 48 40 40 75 66 60 53 48 41 41 72 66 60 54 50 44 37 74 67 61 54 51 44 40 75 67 62 55 51 45 41 76 68 63 55 52 45 42 77 68 63 55 52 45 43 72 65 59 54 49 42 37 73 66 60 55 50 43 38 74 66 61 55 50 43 40 75 67 62 55 51 43 41 76 68 63 56 51 44 42 2 62 63 64 64 65 68 68 69 69 69 72 73 74 74 75 75 76 77 79 80 75 77 78 79 80 71 72 73 74 75 72 73 75 76 77 75 77 78 79 80 75 76 77 78 78 3 56 58 59 60 61 63 64 64 65 66 64 65 66 66 67 66 67 68 68 69 69 70 71 71 72 62 63 64 65 66 64 65 66 67 68 69 70 71 71 72 68 69 69 70 71 2.0” ∆Ps 4 5 6 53 43 40 55 45 42 56 47 43 58 48 45 59 49 46 57 50 44 58 51 44 59 51 45 59 52 46 60 52 46 60 56 47 61 57 48 61 57 48 62 57 49 62 58 49 62 57 47 63 58 48 63 58 49 64 58 50 65 59 51 63 57 54 64 58 54 65 58 55 66 59 55 67 59 56 55 50 46 56 51 47 57 52 48 58 53 48 58 54 49 57 52 48 59 53 49 60 54 50 61 55 51 62 56 51 63 57 54 64 58 54 65 58 55 66 59 55 67 59 56 62 57 53 63 58 53 64 58 54 65 59 54 66 59 55 7 38 39 40 41 42 37 37 38 38 38 38 38 39 39 39 38 39 40 41 42 48 48 49 49 49 41 41 42 42 43 42 43 43 44 44 48 48 49 49 49 46 47 47 47 48 NC 28 30 31 33 34 33 34 34 35 36 37 38 40 40 41 41 42 43 46 47 41 43 45 46 47 36 37 38 40 41 37 38 41 42 43 41 43 45 46 47 41 42 43 45 45 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N89 for AHRI Certified Performance Listings. fan powered terminals PERFORMANCE DATA Unit Size Inlet Size 6 2-4 8 2-4 10 2-4 12 2-4 14 5-6 10 5-6 12 5-6 14 5-6 16 300 350 400 450 500 600 650 700 750 800 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.24 0.32 0.40 0.50 0.17 0.20 0.24 0.27 0.31 0.18 0.22 0.26 0.31 0.37 0.17 0.23 0.30 0.38 0.47 0.22 0.32 0.43 0.56 0.71 0.16 0.19 0.23 0.28 0.32 0.15 0.21 0.27 0.35 0.43 0.12 0.18 0.24 0.32 0.40 0.16 0.23 0.32 0.42 0.53 2 68 69 70 70 71 73 74 74 74 75 75 76 77 77 78 75 77 78 79 80 76 78 79 81 82 76 77 78 78 79 73 75 77 78 79 75 77 78 80 81 76 77 79 80 81 3 55 56 57 57 58 60 61 62 63 64 60 61 62 63 63 62 63 64 64 65 59 60 62 63 64 55 56 57 58 59 56 57 59 59 60 59 60 62 63 64 61 63 64 65 66 1.0”∆Ps 4 5 6 45 39 38 46 41 39 48 43 40 49 44 41 50 45 42 49 46 41 50 47 42 50 47 42 51 48 43 51 49 43 52 49 44 53 50 45 54 51 45 55 51 46 55 52 46 54 49 45 56 50 47 57 51 48 58 52 49 59 53 49 55 49 46 56 50 47 58 51 49 59 52 50 60 53 51 50 46 43 51 48 43 52 49 44 53 50 45 54 50 46 52 47 44 54 48 45 55 49 46 57 50 47 58 51 48 54 49 46 55 50 47 57 51 49 58 52 50 59 53 51 56 50 47 58 52 49 59 53 50 61 54 51 62 55 52 7 36 37 38 38 39 37 38 38 39 39 39 40 40 41 41 40 41 42 43 44 40 42 43 44 46 38 39 40 40 41 39 40 42 43 44 40 42 43 44 46 41 43 44 46 47 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with primary damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 21 22 24 24 25 28 29 29 26 28 28 29 30 30 31 28 30 31 33 34 29 31 33 35 36 29 30 31 31 33 25 28 30 31 33 28 30 31 34 35 29 30 33 34 35 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 NC 71 58 48 42 41 40 25 71 59 50 44 42 41 25 72 60 51 45 43 41 26 73 60 52 47 44 42 28 73 61 54 48 46 43 28 76 64 53 49 46 42 31 76 65 54 50 46 43 31 76 66 54 51 47 43 31 77 67 55 51 47 44 30 77 68 55 52 48 44 30 78 65 56 53 49 44 31 79 66 57 53 49 45 33 80 66 58 54 50 45 34 81 67 59 55 51 46 35 82 68 59 56 51 47 36 79 66 58 53 50 44 33 80 67 59 54 51 46 34 82 68 61 55 52 47 36 83 69 62 56 53 48 38 84 69 63 57 54 49 39 80 62 58 53 50 45 34 82 64 60 54 51 46 36 83 65 62 55 53 48 38 85 67 63 56 54 49 40 86 68 64 57 55 50 42 79 58 54 49 46 42 33 80 60 55 51 47 43 34 81 61 56 52 48 44 35 82 62 57 53 49 45 36 83 63 57 53 50 45 38 77 60 56 51 48 44 30 79 61 57 52 49 45 33 81 62 59 53 50 46 35 82 63 60 54 51 47 36 83 64 61 55 52 48 38 79 62 57 53 50 45 33 81 64 59 54 51 46 35 82 65 61 55 53 48 36 84 67 62 56 54 49 39 85 68 63 57 55 50 40 80 65 60 54 51 45 34 81 67 62 56 53 47 35 83 68 63 57 54 49 38 84 69 65 58 55 50 39 85 70 66 59 57 51 40 2 72 73 74 74 75 77 78 78 79 79 81 82 83 84 84 82 83 84 86 87 83 85 86 88 89 81 82 83 84 85 80 82 83 85 86 82 84 85 87 88 83 84 86 87 88 3 60 61 62 63 63 67 68 69 70 70 68 69 69 70 71 69 70 71 72 72 65 66 68 69 70 61 62 63 65 65 62 64 65 66 67 65 66 68 69 70 68 69 71 72 73 2.0” ∆Ps 4 5 6 50 44 43 52 46 45 54 47 46 55 49 47 56 50 47 56 52 49 57 52 49 57 53 50 58 54 50 58 54 51 59 55 52 60 56 53 61 57 53 61 58 54 62 58 54 61 56 53 62 57 54 63 58 55 64 59 56 65 60 57 61 56 53 63 57 54 64 58 55 65 59 57 67 60 58 56 51 49 57 53 50 58 54 51 59 55 52 60 55 52 58 54 51 60 55 52 61 56 53 62 57 54 63 58 55 60 56 53 62 57 54 63 58 55 64 59 57 66 60 58 63 57 54 65 59 55 66 60 57 68 61 58 69 62 59 7 43 43 44 45 45 46 46 47 47 48 48 48 49 50 50 47 49 50 51 52 48 49 51 52 53 46 47 47 48 49 47 48 49 50 51 48 49 51 52 53 48 50 52 53 54 NC 26 28 29 29 30 33 34 34 33 33 35 36 38 39 39 36 38 39 42 43 38 40 42 44 45 35 36 38 39 40 34 36 38 40 42 36 39 40 43 44 38 39 42 43 44 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N89 for AHRI Certified Performance Listings. N PERFORMANCE DATA 2-4 cfm Redefine your comfort zone™ | www.titus-hvac.com PTQP, ATQP, DTQP / DISCHARGE SOUND PERFORMANCE / PRIMARY AIR ONLY N81 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PTQP, ATQP, DTQP / SOUND PERFORMANCE / FAN ONLY Size 2 3 4 N 5 6 CFM 200 300 400 500 600 450 550 680 800 900 850 950 1100 1200 1300 800 1100 1200 1375 1500 1400 1600 1800 2000 2200 RADIATED Octave Band Sound Power, Lw Discharge Fan Only Ps 2 3 4 5 6 7 61 54 56 49 44 38 66 59 59 53 48 43 0.25 71 63 61 56 51 47 74 65 63 58 53 50 76 68 64 60 55 52 68 60 60 55 48 42 69 61 61 56 50 44 0.25 70 63 63 58 52 46 71 64 64 59 53 48 72 64 64 59 54 49 72 63 63 59 53 48 73 65 64 60 54 49 74 66 66 62 56 52 0.25 74 67 67 63 57 53 75 68 67 64 58 54 71 63 61 55 51 46 74 67 64 60 56 52 0.25 75 67 65 61 57 53 76 69 66 62 59 56 77 70 67 64 61 57 72 68 64 59 56 51 74 70 65 60 58 53 0.25 75 71 66 62 59 56 76 72 68 63 61 57 77 73 69 65 62 59 NC 30 34 36 40 42 35 36 38 39 39 38 39 41 42 42 36 40 41 42 43 39 41 42 43 44 DISCHARGE Octave Band Sound Power, Lw Fan Only 2 3 4 5 6 7 69 62 59 50 47 45 72 66 62 54 50 48 74 69 64 56 53 50 76 71 65 58 55 52 78 73 67 59 57 53 70 64 60 52 48 44 71 65 61 53 49 46 72 67 63 54 51 48 72 67 63 55 52 50 73 68 64 56 53 51 74 69 65 57 54 52 75 69 66 58 55 53 75 70 67 59 57 55 76 71 67 59 58 56 76 72 68 60 59 57 73 65 59 52 52 48 75 68 62 56 55 53 75 68 63 57 56 54 76 69 64 58 58 56 77 70 65 59 59 57 74 68 62 56 56 53 75 69 64 58 58 55 76 70 65 60 59 57 78 71 66 61 61 59 79 72 67 62 62 61 PERFORMANCE DATA FAN ONLY RADIATED N82 N82 • Radiated sound is the noise transmitted through the unit casing and emitted from the induction port • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N89 for AHRI Certified Performance Listings. • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork NC 26 26 29 31 34 24 25 26 21 23 27 28 28 30 31 25 28 28 29 30 26 28 29 31 33 FAN ONLY DISCHARGE • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI Certified. See page N89 for AHRI Certified Performance Listings. Low Profile Parallel Terminals fan powered terminals • Only 10½ inches high, in all sizes. Especially useful where building height limits dictate shallow ceiling plenums. • Pressure independent primary airflow control • AeroCross™ multi-point inlet velocity sensor with center averaging • Primary airflow balancing connections • Opposed blade primary air control damper • Adjustment points are easily accessible through ceiling opening • Energy efficient fan motor, permanent split capacitor type, mounted with vibration isolators • Adjustable SCR fan speed control with minimum voltage stop • Single point electrical, pneumatic main, and thermostat connections • Dual density insulation, coated to prevent air erosion, meets requirements of NFPA 90A and UL 181 FLP • Rectangular discharge opening is designed for flanged duct connections • Bottom access panel can be removed for service • Heavy gauge, galvanized steel casing with leak resistant construction energy solutions AVAILABLE MODELS: Redefine your comfort zone™ | www.titus-hvac.com FLP See website for Specifications N PFLP / Pneumatic Control AFLP / Analog Control DFLP / Digital Control OVERVIEW Parallel Flow The FLP is a Low Profile Parallel Fan Powered Terminal designed for small ceiling plenum applications. At a height of 10 ½”, they are especially useful where building height limits dictate shallow ceiling plenums. FLP N83 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS FLP UNIT DIMENSIONS DFLP / Sizes 2-4 D 9 M 6¼ A W F Induced Air Inlet Induced Air Inlet F J G K G K L H Size 2 Size 4 Model FLP Parallel Unit Unit Inlet Size A Size 2 6, 8 10 4 14 x 8 157/8 B C D E F G H J 81/8 77/8 13/8 13/8 11/8 1 61/8 91/8 16¼ 16½ 8½ 8¼ 10½ 10½ 7 /8 1¼ DIMENSIONS N84 N84 C E J N D 3 Primary Air Inlet with AeroCrossTM Multipoint Center Averaging Sensor E B 20 N 9 All dimensions are in inches K L M N W Filter Size /8 1 40¼ 40¼ 1 1 2 ¾ 30 361/8 18 X 10 18 X 10 7 fan powered terminals DIMENSIONS Size 2 Size 4 STANDARD FEATURES • ½” copper tubes • Aluminum ripple fins, 10 per inch • Connections: Male solder, ½” U U R R COIL ROWS • 1-Row • 2-Row 1" Typ SUPPLY VOLTAGE 8¾ ¾" Typ 8¾ 41/8 • 120V, 1 ph, 60 Hz. • 208/240V, 1 ph, 60 Hz. • 277V, 1 ph, 60 Hz. Unit Size 2 4 Note: R is an inside dimension ELECTRIC COIL SECTION STANDARD FEATURES • Auto reset thermal cutouts (one per element) • 80/20 Nickel chrome heating elements • Magnetic contactors, where required, on pneumatic units • Airflow safety switch • Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) • Flanged connection Unit Size 2 4 R 103/9 165/8 • Control transformer for DDC or Analog electronic controls • Pneumatic electric switch for pneumatic parallel fan terminals only • Fan relay for DDC fan terminals • Magnetic contactor per step on terminals with DDC or analog electronic controls • Interlocking disconnect • Main power supply fuses • Mercury contactors • • • • • 208V, 1 ph, 60 Hz. 240V, 1 ph, 60 Hz. 277V, 1 ph, 60 Hz. 208V, 3 ph, 60 Hz. 480V, 3 ph, 60 Hz. (4 wire wye only) 31" 9¾" 83/8" 1" Typ. R Standard control box cover (no disconnect switch) is attached with sheet metal screws, not hinged. See Electric Heat Coils in Section O for more information U Heater Rack Access Cover Note: R is an inside dimension ADDITIONAL ACCESSORIES Unit Size 2 4 Electrical Data Motor Full Load Amps Motor HP 120V 208/240V 277V 1 4.3 1.8 1.3 ⁄6 ¼ 5.4 2.3 1.7 Note: All motors are single phase 60Hz, same voltage as electric coils (when supplied), with exception that 277 volt motors are used with 480 volt, 3 phase coils (four wire wye) ECM ELECTRICAL DATA Unit Size Motor HP 1 2 ⁄3 1 4 ⁄3 120V 5.0 5.0 208V 3.3 3.3 240V 2.8 2.8 277V 2.6 2.6 FLA = Full Load Amperage, as tested in accordance with UL 1995 All fan motors are single phase, same voltage as electric coil (when supplied), with exception that 277 voltage motors are used with 480 volt / 3 phase coils (4 wire wye) DIMENSIONS • Induced air filter, 1” thick, disposable construction type • Toggle disconnect switch (not available on units with optional electric coils) • Fibre-Free Liner • Foil Face Liner • EcoShield Liner • Hanger brackets • Fan unit fusing N SUPPLY VOLTAGE Control box cover is as shown when optional door interlock disconnect switch is used. (OPTIONAL) S 127/8 187/8 • Manual reset thermal cutout • Dust-tight construction • Optional Lynergy Comfort Controlled SSR Electric Heat available OPTIONS U 18½ 185/8 R 16¼ 163/8 Redefine your comfort zone™ | www.titus-hvac.com HOT WATER COIL SECTION N85 fan powered terminals PFLP, AFLP, DFLP / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE Unit Size 4 Unit Size 2 800 1000 700 900 800 600 700 500 CFM CFM Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA 600 400 500 300 400 200 300 200 100 0 0.1 0.2 0.3 0.4 0.5 0 0.6 0.1 Static Pressure (inches of water) N Total cfm Range 6 8 8 x 14 0-500 0-900 0-1860 0.3 0.4 0.5 0.6 No Coil or with Electric Coil 1 Row Water Coil 2 Row Water Coil PRIMARY AIR CFM RANGES Inlet Size 0.2 Static Pressure (inches of water) PFLP TITUS II Pneumatic Controller Minimum Maximum *80-330 150-500 *145-590 265-900 325-1320 590-1860 PFLP TITUS I Pneumatic Controller Minimum Maximum *105-350 150-500 *190-590 265-900 420-1320 590-1860 AFLP TITUS Analog TA1 Electronic Controller Minimum Maximum *80-500 80-500 *145-900 145-900 325-1860 325-1860 DFLP Typical Digital Controller Minimum Maximum *80-500 80-500 *145-900 145-900 325-1860 325-1860 Note 1: An asterisk (*) indicates Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced Note 2: For selection procedure, see the section Engineering Guidelines and the topic “ECM Motors - Fan Powered Terminals” for additional information PFLP, AFLP, DFLP WITH ECM / AIRFLOW VS. DOWNSTREAM STATIC PRESSURE FLP w/ECM Size 4 1000 900 700 800 600 700 500 600 CFM CFM PERFORMANCE DATA FLP w/ECM Size 2 800 400 400 300 300 200 200 100 100 0 0 0 0.1 0.2 0.3 0.4 Static Pressure - Inches of Water N86 N86 500 0.5 0.6 0 0.1 0.2 0.3 0.4 Static Pressure - Inches of Water 0.5 0.6 fan powered terminals PERFORMANCE DATA Unit Size Rows gpm One Row 2 Two Row Unit Size Rows 4 Two Row • • • • • • 350 400 Airflow, cfm 450 500 550 600 650 0.08 0.30 1.16 2.54 Airside DPs 9.1 10.3 11.1 11.4 0.03 9.7 11.1 12.0 12.3 0.04 10.2 11.7 12.8 13.2 0.05 10.6 12.3 13.5 13.9 0.07 11.0 12.9 14.1 14.6 0.08 11.4 13.4 14.7 15.3 0.09 11.7 13.8 15.3 15.9 0.11 12.0 14.2 15.8 16.4 0.13 1.0 2.0 4.0 6.0 0.17 0.66 2.53 5.55 Airside DPs 14.7 16.9 18.4 18.9 0.07 15.7 18.4 20.2 20.8 0.10 16.7 19.7 21.8 22.6 0.12 18.9 23.0 25.9 27.1 0.20 19.5 24.0 27.1 28.4 0.24 20.1 24.8 28.2 30.0 0.27 450 500 550 17.5 18.3 21.0 22.0 23.3 24.6 24.2 25.7 0.15 0.17 Airflow, cfm 600 650 700 750 800 1.0 2.0 4.0 6.0 0.08 0.30 1.16 2.54 Airside DPs 10.6 12.3 13.5 13.9 0.07 11.0 12.9 14.1 14.6 0.08 11.4 13.4 14.7 15.3 0.09 11.7 13.8 15.3 15.9 0.11 12.0 14.2 15.8 16.4 0.13 12.3 14.6 16.3 17.0 0.14 12.5 15.0 16.7 17.5 0.16 12.8 15.3 17.2 17.9 0.18 1.0 2.0 4.0 6.0 0.18 0.67 2.54 5.56 Airside DPs 17.5 21.0 23.3 24.2 0.15 18.3 22.0 24.6 25.7 0.17 18.9 23.0 25.9 27.1 0.20 19.5 24.0 27.1 28.4 0.24 20.1 24.8 28.2 29.6 0.27 20.6 25.6 29.2 30.7 0.31 21.0 26.4 30.2 31.8 0.34 21.5 27.0 31.1 32.9 0.38 Head Loss All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180BF entering water and 75BF entering air For temperature differentials other than 105B, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Connection size is ½” OD male solder Coils are not intended for steam applications and are labeled for a maximum water temperature of 200BF Coils are tested for leakage at test pressure of 500 psi Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Correction factors for other entering conditions: ∆T Factor 50 0.52 60 0.62 70 0.69 80 0.78 90 0.87 100 0.96 115 1.08 125 1.15 140 1.28 150 1.38 N PERFORMANCE DATA • • 300 1.0 2.0 4.0 6.0 gpm One Row • • • • Head Loss Redefine your comfort zone™ | www.titus-hvac.com PFLP, AFLP, DFLP / WATER COIL HEATING CAPACITY (MBH) N87 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PFLP, AFLP, DFLP - RADIATED SOUND PERFORMANCE - PRIMARY AIR ONLY Size CFM NC 28 29 30 31 32 2 65 66 66 67 68 3 59 60 62 63 64 2.0” ∆Ps 4 5 6 54 47 42 55 48 42 56 48 43 56 49 43 57 49 44 7 NC 36 29 37 30 38 32 39 33 39 35 206 0.15 0.21 0.27 0.35 0.43 208 600 650 700 750 800 0.15 0.17 0.2 0.23 0.26 67 67 68 69 69 60 61 62 63 64 54 55 56 56 57 49 49 50 50 51 44 44 45 46 46 39 39 40 40 41 31 31 32 33 34 68 69 70 70 71 62 63 64 65 66 56 57 57 58 59 50 51 51 52 52 46 46 47 47 48 41 42 42 43 43 32 33 34 35 36 69 70 71 71 72 64 64 65 66 67 58 58 59 59 60 51 51 52 53 53 47 47 48 49 49 42 43 44 44 45 34 34 36 36 37 1250 1400 1550 1700 1850 0.58 0.73 0.89 1.07 1.27 68 68 69 NA NA 60 61 61 NA NA 58 58 59 NA NA 56 57 58 NA NA 49 49 50 NA NA 45 46 47 NA NA 33 33 34 NA NA 70 71 72 72 73 64 64 65 65 65 61 62 62 63 63 60 61 62 63 64 52 53 54 54 55 50 51 52 53 54 36 37 37 38 38 72 73 74 74 75 66 66 67 67 68 63 64 65 65 66 63 64 65 66 67 55 56 56 57 57 54 55 56 57 58 38 39 40 40 41 PFLP, AFLP, DFLP - RADIATED SOUND PERFORMANCE - FAN ONLY 2 4 PERFORMANCE DATA 7 NC 33 27 34 28 35 28 35 30 36 31 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 63 58 53 46 41 34 64 59 54 47 42 36 65 60 55 48 42 36 66 61 55 48 43 37 67 62 56 49 43 38 300 350 400 450 500 Size N88 N88 3 56 57 58 60 61 1.0”∆Ps 4 5 6 52 45 40 53 46 40 53 47 41 54 47 41 55 48 42 2 61 62 63 64 65 422 (8x14) N Min ∆Ps CFM 300 400 500 600 650 400 500 600 700 850 Discharge Ps 0.25 0.25 Octave Band Sound Power, Lw Fan Only 2 3 4 5 6 7 NC 58 61 65 67 68 62 65 68 70 72 54 57 60 61 62 59 62 64 65 67 54 57 59 61 62 61 63 65 66 67 48 52 55 57 58 51 54 57 60 63 40 44 48 50 51 42 46 50 52 56 28 33 37 40 42 32 36 40 43 47 28 31 34 36 37 36 38 40 41 42 fan powered terminals PERFORMANCE DATA Size Min DPs CFM 3 57 60 61 63 65 1.0”DPs 4 5 6 50 44 39 52 46 42 53 47 44 55 49 45 56 50 47 7 NC 32 15 34 18 36 20 38 21 40 24 Octave Band Sound Power, Lw 1.5” DPs 2 3 4 5 6 7 66 60 53 47 42 35 68 62 55 49 44 37 69 64 57 50 46 39 71 66 58 52 48 41 72 68 59 53 50 42 NC 19 21 23 25 27 2 68 70 71 72 74 3 62 65 67 68 70 2.0” DPs 4 5 6 56 49 44 57 51 47 59 52 49 60 54 50 62 55 52 7 NC 36 21 39 24 41 26 43 27 44 30 206 300 350 400 450 500 0.15 0.21 0.27 0.35 0.43 2 63 65 67 68 69 208 600 650 700 750 800 0.15 0.17 0.2 0.23 0.26 71 72 73 74 74 68 69 70 71 72 58 59 60 61 61 53 54 55 56 56 50 51 52 53 54 42 44 45 46 47 27 28 30 30 31 74 75 75 76 77 71 72 73 74 75 61 62 63 64 65 56 57 58 59 59 53 54 55 56 57 45 46 47 48 49 31 32 33 33 34 76 76 77 78 79 73 74 75 76 77 64 65 65 66 67 58 59 60 61 61 55 56 57 58 59 47 48 49 50 51 33 34 36 36 37 1250 1400 1550 1700 1850 0.58 0.73 0.89 1.07 1.27 74 75 75 NA NA 68 68 69 NA NA 63 64 64 NA NA 58 59 60 NA NA 55 56 57 NA NA 49 50 51 NA NA 26 28 28 NA NA 78 78 79 79 80 72 72 73 73 73 67 68 68 69 69 64 64 65 65 66 59 59 60 61 62 54 55 56 56 57 31 31 33 33 34 80 81 81 82 82 75 75 76 76 76 70 70 71 71 72 67 68 68 69 69 61 62 63 64 64 57 58 59 59 60 34 35 36 36 36 422 (8x14) PFLP, AFLP, DFLP / DISCHARGE SOUND PERFORMANCE / FAN ONLY Size CFM 300 400 500 600 650 400 500 600 700 850 2 4 Octave Band Sound Power, Lw Fan Only Discharge Ps 0.25 0.25 2 3 4 5 6 7 NC 67 69 71 72 73 74 76 77 78 80 63 65 67 68 69 68 70 71 73 75 59 61 62 64 64 65 66 68 69 71 55 57 59 60 61 62 65 67 69 71 50 52 54 56 56 57 60 62 64 66 46 49 51 53 54 57 60 63 66 69 21 24 26 27 28 29 31 33 34 34 Redefine your comfort zone™ | www.titus-hvac.com PFLP, AFLP, DFLP / DISCHARGE SOUND PERFORMANCE / PRIMARY AIR ONLY N PFLP, AFLP, DFLP / SOUND POWER LEVELS / FAN ONLY / HEATING CYCLE Discharge Sound Power Octave Bands 3 4 5 6 cfm 7 2 2 300 400 500 600 700 58 62 65 67 69 54 57 60 61 63 54 57 59 61 63 48 52 55 57 59 40 44 48 50 52 28 33 37 40 43 59 61 63 64 66 59 61 63 64 65 58 60 61 63 64 55 57 59 60 61 50 52 54 56 57 46 49 51 53 54 4 400 500 600 700 800 62 65 68 70 72 59 62 64 65 67 61 63 65 66 67 51 54 57 60 62 42 46 50 52 55 32 36 40 43 45 67 69 70 71 72 65 67 68 70 71 64 65 67 68 69 62 65 67 69 70 57 60 62 64 66 57 60 63 66 68 2 7 PERFORMANCE DATA Radiated Sound Power Octave Bands 3 4 5 6 Size N89 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA N AHRI Directory of Certified Performance Titus is a charter member company and current participant in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990’s. It is currently administrated by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). The purpose of this program is to provide for the independent verification of manufacturers’ published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at www.ahrinet.org. Product samples provided for certification testing are standard production units with standard ½ in dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions: PTQP, ATQP, DTQP, PFLP, AFLP, DFLP • Rated primary airflow (cfm) – Based on an inlet velocity of 2000 fpm • Rated fan only airflow (cfm) – Per manufacturer with 0.25 in wg of downstream pressure • Rated fan power (watts) – Based on fan operating at the rated fan only airflow with 0.25 in wg of downstream pressure • Rated Min ∆Ps (in wg) – Minimum static pressure drop from the unit inlet to discharge at rated airflow with damper full open and the unit fan off • Rated ∆Ps (in wg) – A static pressure drop of 1.5 in wg from unit inlet to discharge with the unit fan off • Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220 In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types, and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’. These tests are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in AHRI Standard 880 ‘Performance Rating of Air Terminals’. Any failure to demonstrate the certified performance is punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible expulsion from the Certified Directory. PFLP, AFLP, DFLP / FAN ONLY Fan Only Radiated Sound Power Discharge Discharge Sound Power Unit Size Fan CFM Fan Watts H W 2 3 4 5 6 7 2 3 4 5 6 7 206 650 360 8.125 10 68 62 62 58 51 42 73 69 64 61 56 54 208 650 360 8.125 10 68 62 62 58 51 42 73 69 64 61 56 54 422 850 400 7.875 15.875 72 67 67 63 56 47 80 75 71 71 66 69 PFLP, AFLP, DFLP / PRIMARY ONLY PERFORMANCE DATA Primary Only N90 N90 Radiated Sound Power Discharge Sound Power Unit Size Fan CFM Fan Watts Pri CFM Min DPs 2 3 4 5 6 7 2 3 4 5 6 7 206 400 0.27 400 0.27 65 60 55 48 42 36 69 64 57 50 46 39 208 700 0.2 700 0.20 70 64 57 51 47 42 75 73 63 58 55 47 422 1550 0.89 1550 0.89 72 65 62 62 54 52 79 73 68 65 60 56 For AHRI TQP Performance Data, see the next page fan powered terminals PERFORMANCE DATA Fan Only Discharge Radiated Sound Power Discharge Sound Power Unit Size Fan CFM Fan Watts H W 2 3 4 5 6 7 2 3 4 5 6 7 206 208 210 212 306 308 310 312 406 408 410 412 510 512 514 516 610 612 614 616 400 400 400 400 680 680 680 680 950 950 950 950 1375 1375 1375 1375 1600 1600 1600 1600 340 340 340 340 570 570 570 570 700 700 700 700 860 860 860 860 1400 1400 1400 1400 11 11 11 11 11 11 11 11 11 11 11 11 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 16.5 16.5 16.5 16.5 16.5 16.5 16.5 16.5 71 71 71 71 70 70 70 70 73 73 73 73 76 76 76 76 74 74 74 74 63 63 63 63 63 63 63 63 65 65 65 65 69 69 69 69 70 70 70 70 61 61 61 61 63 63 63 63 64 64 64 64 66 66 66 66 65 65 65 65 56 56 56 56 58 58 58 58 60 60 60 60 62 62 62 62 60 60 60 60 51 51 51 51 52 52 52 52 54 54 54 54 59 59 59 59 58 58 58 58 47 47 47 47 46 46 46 46 49 49 49 49 56 56 56 56 53 53 53 53 74 74 74 74 72 72 72 72 75 75 75 75 76 76 76 76 75 75 75 75 69 69 69 69 67 67 67 67 69 69 69 69 69 69 69 69 69 69 69 69 64 64 64 64 63 63 63 63 66 66 66 66 64 64 64 64 64 64 64 64 56 56 56 56 54 54 54 54 58 58 58 58 58 58 58 58 58 58 58 58 53 53 53 53 51 51 51 51 55 55 55 55 58 58 58 58 58 58 58 58 50 50 50 50 48 48 48 48 53 53 53 53 56 56 56 56 55 55 55 55 Redefine your comfort zone™ | www.titus-hvac.com PTQP, ATQP, DTQP / FAN ONLY N PTQP, ATQP, DTQP / PRIMARY ONLY Primary Only Fan CFM Fan Watts Pri CFM Min DPs 206 208 210 212 306 308 310 312 406 408 410 412 510 512 514 516 610 612 614 616 400 700 1100 1600 400 700 1100 1600 400 700 1100 1600 1100 1600 2100 2800 1100 1600 2100 2800 0.32 0.24 0.26 0.30 0.32 0.24 0.26 0.30 0.32 0.24 0.26 0.30 0.23 0.27 0.24 0.32 0.23 0.27 0.24 0.32 400 700 1100 1600 400 700 1100 1600 400 700 1100 1600 1100 1600 2100 2800 1100 1600 2100 2800 0.32 0.24 0.26 0.30 0.32 0.24 0.26 0.30 0.32 0.24 0.26 0.30 0.23 0.27 0.24 0.32 0.23 0.27 0.24 0.32 2 61 67 71 75 61 67 71 75 61 67 71 75 71 72 75 74 71 72 75 74 Radiated Sound Power 3 4 5 6 57 54 45 41 62 56 49 42 63 58 54 45 65 61 55 46 57 54 45 41 62 56 49 42 63 58 54 45 65 61 55 46 57 54 45 41 62 56 49 42 63 58 54 45 65 61 55 46 62 54 50 45 64 57 52 47 67 62 55 51 66 61 55 50 62 54 50 45 64 57 52 47 67 62 55 51 66 61 55 50 7 37 35 35 37 37 35 35 37 37 35 35 37 38 40 45 43 38 40 45 43 2 72 76 80 82 72 76 80 82 72 76 80 82 81 81 82 83 81 81 82 83 Discharge Sound Power 3 4 5 6 60 51 45 43 66 54 51 47 66 58 54 50 68 61 55 52 60 51 45 43 66 54 51 47 66 58 54 50 68 61 55 52 60 51 45 43 66 54 51 47 66 58 54 50 68 61 55 52 61 56 52 48 62 59 53 50 65 61 55 53 68 63 57 54 61 56 52 48 62 59 53 50 65 61 55 53 68 63 57 54 7 41 43 45 47 41 43 45 47 41 43 45 47 44 46 48 49 44 46 48 49 PERFORMANCE DATA Unit Size N91 fan powered terminals Redefine your comfort zone™ | www.titus-hvac.com Electric Coils N FEATURES CONSTRUCTION FEATURES Integral electric heating coils are available as an option on Titus fan powered terminals. These heating coils have been specifically designed for use with Titus fan powered terminals and are factory mounted at the discharge outlet of the fan terminal unit. For safe operation, the electronic coil controls are interlocked with the recirculating fan to allow the electric coil to energize only after the fan is running. Each complete terminal, with coil installed, has been tested by ETL in accordance with UL standards. The NEMA 1 electrical enclosure includes a single point electrical connection for heater and fan. Each unit is provided with a specific wiring diagram. STANDARD FEATURES • • • • • • • • • • Auto reset thermal cutouts (one per element) 80/20 Nickel chrome heating elements Magnetic contactors, where required, on pneumatic units Airflow safety switch Line terminal block (277/1∅, 208/240/3∅, or 480/3∅ 4 wire) Flanged connection Control transformer for DDC or Analog electronic controls Pneumatic electric switch for pneumatic parallel fan terminals only Fan relay for DDC fan terminals Magnetic contactor per step on terminals with DDC or analog electronic controls Model Unit Size 2 3 ATQS DTQS PTQS 4 5 6 ELECTRIC COILS 7 2 ALFS DFLS PFLS 3 4 Number of steps available 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 208/240V 1 Phase kW Range Min Max 1.0 8 (208V) 1.5 8 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 1.5 6.0 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 277V 1 Phase kW Range Min Max 1.0 1.5 8.0 2.0 1.0 1.5 11.5 2.0 1.0 1.5 11.5 2.0 1.0 1.5 11.5 2.0 1.0 1.5 11.5 2.0 1.0 11.5 1.5 2.0 1.0 1.5 6.0 2.0 1.0 1.5 9.0 2.0 1.0 11.5 1.5 2.0 OPTIONAL FEATURES • • • • • Interlocking disconnect Main power supply fuses Mercury contactors Manual reset thermal cutout Dust-tight construction RECOMMENDED COIL SELECTION DATA The table below is a guide for electric heating coil capacities that are available for Titus fan powered terminal units A coil can be selected for any capacity within the kW range in each column heading 208V 3 Phase kW Range Min Max 480V 3 Phase kW Range Min Max 1.5 8.5 2.5 8.5 2 1.5 14.0 2.5 14.0 3 1.5 14.0 2.5 16.0 1.5 14.0 2.5 19.0 5 1.5 14.0 2.5 26.0 6 1.5 14.0 2.5 30.0 1.5 6.0 2.5 6.0 1.5 9.0 2.5 9.0 1.5 14.0 2.5 14.0 Note: kW’s shown are for standard electric heaters. Lynergy and SCR type heater kW’s may vary. Model ATQP DTQP PTQP ALFP DFLP PFLP Unit Size 4 2 4 B C ATFS DTFS PTFS 3 2.0 (240V) 2.0 1 2 1.0 1.5 1.0 1.5 3 2.0 9 (208V) 10.5 (240V) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 D E N92 N92 277V 1 Phase kW Range Min Max 1.0 1.5 7.0 2.0 1.0 1.5 11.5 2.0 1.0 1.5 11.5 2.0 1.0 1.5 11.5 2.0 1.0 11.5 1.5 2.0 1.0 1.5 6.0 2.0 1.0 11.5 1.5 2.0 1.0 1.5 6.0 2.0 1.0 1.5 11.0 1 2 208/240V 1 Phase kW Range Min Max 1.0 7 (208V) 1.5 7 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 1.5 6.0 2.0 1.0 8 (208V) 1.5 9 (240V) 2.0 1.0 1.5 6.0 2.0 1.0 9 (208V) 1.5 10.5 2.0 (240V) 1.0 9 (208V) 1.5 10.5 Number of steps available 208V 3 Phase kW Range Min Max 480V 3 Phase kW Range Min Max 1.5 6.5 2.5 8.5 1.5 13.0 2.5 14.0 1.5 14.0 2.5 16.0 1.5 14.0 2.5 19.0 1.5 14.0 2.5 26.0 1.5 6.0 2.5 6.0 1.5 14.0 2.5 14.0 1.5 6.0 2.5 6.0 1.5 11.0 2.5 11.0 11.5 1.5 15.0 2.5 18.0 11.5 1.5 15.0 2.5 24.0 2.0 1.0 1.5 2.0