Operations Manual - Fieldpiece Instruments

Transcription

Operations Manual - Fieldpiece Instruments
Quick Start
TRUE RMS
AUTO OFF
03
TYPE K
COM
Safety Information
Never ground yourself when taking electrical
measurements. Do not touch exposed metal
pipes, outlets, fixtures, etc., which might be
at ground potential, while taking measurements. Keep your body isolated from ground
by using dry clothing, rubber shoes, rubber
mats, or any approved insulating material.
Disconnect the test leads before opening the
case. Inspect the test leads for damage to the
insulation or exposed wire. Replace if suspect.
Keep your fingers behind the finger guards on
the probes while taking measurements.
When disconnecting from a circuit, disconnect
the“RED”lead first, then the common“BLACK”
lead. Use one handed testing when possible.
Work with others.
Turn off power to the circuit under test before
cutting, unsoldering, or breaking the circuit.
Do not measure resistance (ohms) when circuit
is powered. Isolate load by disconnecting
from circuit.
Disconnect the meter from circuit before turning
any inductor off, including motors, transformers, and solenoids. High voltage transients
can damage the meter beyond repair.
06
Specifications
Display: 4000 count
Do not use during electrical storms.
Do not apply more than rated voltages between
input and ground.
Isolate capacitors from system and discharge
them safely before testing.
Temperature switch prevents leaving thermocouple plugged in while measuring voltage.
When measuring high frequency AC current, do
not exceed the rated 400AAC of the clamp.
Failure to adhere may cause the clamp to heat
up dangerously.
All voltage tests: All voltage ranges will
withstand up to 600V. Do not apply more than
600VDC or AC rms.
Symbols used:
Caution, risk of electric shock
! Caution, refer to manual.
Ground
Double insulation
07
30V
MAX
05
III
AUTO OFF CAT
600V
TYPE K
Functions
TEMP
30V
MAX
Temperature (°F/°C) SC240 and SC260 only
Backlight: 5 minute duration with auto-off. Blue color. SC260 only AUTO OFF
TYPE K
Overrange: (OL) or (-OL) is displayed
Measurement rate: 3 times per second, nominal
COM
Zero: Automatic
Operating environment: 32°F to 122°F (0°C to 50°C) at <70%
relative humidity
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH
(with battery removed)
Accuracy: Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Temperature coefficient: 0.1 x (specified accuracy) per °C [0°C to
19°C (32°F to 66°F), 28°C to 50° C(82°F to 122°F)]
APO (Auto Power Off): Approx. 30 minutes
Power: 9V, NEDA 1604A, IEC 6LR61 9V alkaline battery
Battery life: 200 hours typical alkaline (SC220/SC240); 150 hours
typical alkaline (SC260)
Low battery indication: Battery icon blinks and "LO.bt" is displayed
when the battery voltage drops below the operating level
Dimensions: 205.5mm(H) x 67.4mm(W) x 45.1mm(D)
Weight: Approx. 265g including battery
Altitude: Up to 6562 ft (2000m)
Overload protection: 600 VDC or 600VAC rms unless otherwise
stated
Test leads: Use UL listed test leads that comply to UL61010-031
rated CATIII 600V or above. Included test leads are gold-plated
and have removeable safety caps.
WARNINGS
!
DISCONNECT AND UNPLUG TEST LEADS before opening case.
TEST NCV FUNCTION ON KNOWN LIVE WIRE before using.
DO NOT APPLY VOLTAGE greater than 30VAC or 60VDC to the
thermocouple or the jacks when the rotary dial is on °F°C. (Use
only Type K thermocouples)
DO NOT APPLY VOLTAGE TO THE JACKS when the rotary dial is on
microamps. Even low voltages can cause a current overload and
potentially harm the meter.
04
TEMP
COM
CAT
III
600V
Plug
30V any Type K thermocouple directly into the meter to measure
MAX
temperature.
Cold junction is located inside the meter and allows for
TEMP CAT III
extremely
accurate measurements even in rapidly changing ambient
600V
temperatures (going from rooftop to freezer). No adapter is required.
See Temp Calibration section for calibration instructions.
Range: -30°F to 752°F, (-35°C to 400°C) Resolution: 0.1°
CAT III
600V
Accuracy: ±(1°F)* 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 32°F to 392°F, ±(1%+1°C) 0°C to 200°C
±(2%+6°F) -30°F to 32°F, ±(2%+3°C) -35°C to 0°C
±(2%+6°F) 392°F to 752°F, ±(2%+3°C) 200°C to 400°C
Sensor type: Type K thermocouple *After field calibration
Overload protection: 30 VDC or 30VAC rms
NCV
°F°C
AAC
VAC
VDC
MFD
NCV
°F°C
AAC
VAC
VDC
Select VDC and measure DC voltages on circuit boards on more
advanced HVACR systems.
Ranges: 4V, 40V, 400V, 600V Resolution: 0.001V
Accuracy: ±(0.5% + 2)
Input impedance: 10MΩ (4V), 9.1MΩ (40V-600V)
Voltage AC (VAC) (50Hz-500Hz)
09
Test power lines (120, 220, 480), test 24V going to controls, and
test for transformer failure.
Ranges: 4V, 40V, 400V, 600V Resolution: 0.001V
Accuracy: ±(1.2% + 8)
±(1.5% + 8) on 600V range
True RMS: model SC260 only Crest factor: ≤ 3
Audio/Visual Hi-V indicator: >16VAC/35VDC
Input impedance: 10MΩ (4V), 9.1MΩ (40V-600V)
TYPE K
30V
MAX
COM
Unplug Leads and Slide
TEMP Switch to the Right
Voltage DC (VDC)
Please operate the instrument following all instructions
of the operator's manual to avoid impairing the safety
of the product.
08
AUTO OFF
MFD
600V
02
CAT III
01
COM
600V
CATIII 600V, class II and pollution degree 2
indoor use comply with CE, RoHS compliant.
CATIII is for measurements performed in the
building installation.
30V
MAX
CAT III
TEMP
WEEE
AUTO OFF
30V
MAX
TYPE K
TEMP
C-Tick (N22675)
SC240
COM
AUTO OFF
EN61010-1
EN61010-2-032
EN61010-2-033
EMC EN61326-1
e
Rang
TYPE K
M/m
M/m
SC260
UL 61010-1, Third Edition
Select
Selec
t
AAC
VAC
VDC
AAC
VAC
VDC
MFD
NCV
°F°C
HOLD
Models SC260
SC240 SC220
Certifications
Fieldpiece
NCV
°F°C
OPERATOR'S
MANUAL
Display
Controls
The new SC200 series compact clamp meters
MFD
are designed for everyday HVACR service. Their
SEL
compant pocketable design makes them easy
Fieldpiece
AAC
TRUE
RMS
NCV
VAC
Manual Range (Range) Mode
to take on any job.
VDC
°F°C
MFD
Hang the SC260 to any metallic surface with
Maximum Reading
SEL
SEL
SEL
Minimum
Reading
its newly designed swivel magnet to keep Fieldpiece
your
A
AC
TRUE RMS
SEL
NCV
V
AC
SEL
Data Hold Mode
hands free to do more. Test variable frequency
VDC
MFD
°F°C
SEL
AutoAUTO
SelectOFF
Mode ( / / /MFD)
drives more accurately with True RMS and easily
TRUE
RMS
Fieldpiece
TRUE
RMS
AUTO
OFFOFF
AAC
TRUE
RMS
AUTO
Continuity
Test
see your measurements in low lighting withNCV
the
VAC TRUE RMS
TRUE K-TYPE
RMS AUTO OFF
30V30V
30V
K-TYPE
MAXMAX
K-TYPE
bright blue blacklight (SC260 only).
MAX
Diode
Test
°F°C
MFD VDC
TEMP
30V
TEMP
K-TYPE
TEMPMAX
Save time with the new Auto Select mode.
Resistance TEMP
Test (ohms)
AAC
Fieldpiece
CAT
III
Simply set the dial to ( / / /MFD) and NCV Rotate dial
use.RMS AUTO OFF
CAT
Capacitance
Test (farads)
III III
VAC to the function you want to
CAT
TRUE
600V
TRUE
TRUERMS
RMS AUTO
AUTOOFF
OFF
600V
VDC
600VUnit (10
°F°C
CAT-9­III
connect TRUE
your leads.
Your
meter
will
automatically
Nano
, one billionth)
30V
TRUE
RMS
AUTO OFF 30V
TRUE
RMS
AUTO
OFF
RMS AUTO OFF
MFD
30V600V
K-TYPE
K-TYPE
MAX
MAX
MAX
select the appropriate
measurement depending
Select a parameter. Ohms/Continuity/
Micro Unit
(10−6, oneK-TYPE
millionth)
S
TEMP
30V OFF 30V
TRUE RMS
AUTO
30V
TEMP
TEMP
K-TYPE K-TYPE
AAC elect
K-TYPE
M/m
−3
MAX
MAX
MAX
on what it detects.
Move from a cold freezer
to
Diode/MFD. °F/°C (SC240/26030V
only). TEMP
Milli Unit (10 , one thousandth)
NCV
VAC
TEMP
TEMP
MAX
CAT K-TYPE
III
VDC SC260
CATIIIIII
°F°C
a hot rooftop and get accurate temperature
KiloOFF
Unit (103,CAT
one
thousand)
TEMP600V
TRUE RMS AUTO
TRUE
TRUERMS
RMS AUTO
AUTOOFF
OFF
600V
6600V
CAT
III
S
CAT
III
e
CAT
III
le
measurements that
lesser thermometers cannot
Toggle backlight (SC260 only). TRUE RMS
Mega Unit (10 , one million)
ct
M/m AUTO
600VOFF
600V 30V
600V
30V
30V
K-TYPE
K-TYPE
K-TYPE
MAX
CAT III
MAX
MAX(SC240/SC260
measure properly
only).
30V
TRUE
OFF
TEMP
600V RMS AUTO
TEMP
TEMP
SC260
K-TYPE
MAX
Test for proper flame rectification micro amp
Freeze maximum and minimum
TEMP OFF
TRUE read-
RMS30VAUTO
Select
K-TYPE
MAX
CAT
III
M/m
CAT
CAT
III
III
DC current on heating systems (SC220 only).
ing. Hold for 1 second to clear30V
.
TEMP 600V
600V
600V
K-TYPE
MAX
CAT
III
All SC200 compact clamp meters are built to
(SC240/SC260 only)
SC260
TEMP 600V
CAT III
withstand the rigors of HVACR service with high
600V
e AUTO
Sele
CAT
III
g
n
OFF
ct
impact plastic and a display you can read in
very
Manually
select
a
range
(SC220/240).
a
R
M/m
600V
30V
TYPE K
hot or very cold environments.
MAX
SC240
TEMP
HOLD
COM Freeze the display.
MFD
Compact
Clamp
Meters
INRUSH
INRUSH
Description
1.For electrical testing, connect test leads to
"COM" and "+" jacks.
2. Rotate the dial to your desired measurement.
3. Connect to test points and read measurement.
4. For temperature testing, remove test leads,
slide TEMP switch to the right and connect
Type K thermocouple (SC240/SC260 only).
HOLD
SEL
F AAC
SEL
O°F°C
SEL
Hz F VAC
NCV
V
DC
HzMFD
SEL
F
A
AC
%
INRUSH
°F°C Hz
F VAC VDC NCV
MFD
%
°C
INRUSH
NCV
Hz °F
INRUSH
Battery Life (replace
9V if blinking)
°F°C
SEL
SEL
SEL
INRUSH
Auto
Power
Off
Enabled
SEL
SEL
High Voltage Warning (>16VAC/35VDC)
SEL
%
Fieldpiece
Fieldpiece
Hz
Hz
°C
°C
°F
°F
MFD
NCV
°F°C
10
AAC
VAC
VDC
SC56
SC56
12
Temp. Calibration
600V
CAT III
TEMP
COM
TYPE K
V
30 X
MA
T III
CA600V
MP
TE
OFF
TO
M
CO
K
AU
PE
TY
0
26
SC
t
Selec
/M
m
S
RM
AAC VACVDC
ce
UE
TR
T III
CA600V
V
30 X
MA
MP
M
CO
TO
OFF
TE
PE
TY
K-
AU
0
26
SC
V
NC
°C
°F
pie
ld
D
MF
UE
TR
ce
S
RM
AAC VACVDC
t
Selec
/M
m
30V
MAX
Battery Replacement
CAT III
AUTO OFF
600V
30V
MAX
When the battery is low, the
battery icon will
TEMP
COM
empty and blink for 30 seconds. “LO.bt” will
display and meter will power off.
CAT III
Turn dial to OFF position, disconnect test
leads and remove the battery cover. Remove
old battery and replace with a standard 9V
battery only.
600V
CAT III
COM
600V
DC
18
K-TYPE
K-TYPE
Obtaining Service
AUTO OFF
30V
MAX
TYPE K
Call Fieldpiece InstrumentsTEMP
for one-pricefix-all out-of-warranty service
pricing. Send
TEMP
COM
III
check or money order for the CAT
amount
quoted.
Send the meter freight prepaid to Fieldpiece
CAT III
Instruments. Send proof of date and location
of purchase for in-warranty service. The meter
will be repaired or replaced, at the option
of Fieldpiece, and returned via least cost
transportation.
For international customers, warranty for
products purchased outside of the U.S. should
be handled through local distributors.
TYPE K
AUTO
OFF
COM
30V
MAX
600V
This meter is warranted against defects in
material or workmanship for one year from
date of purchase. Fieldpiece will replace or
repair the defective unit, at its option, subject
to verification of the defect.
This warranty does not apply to defects
resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable
use of the instrument.
Any implied warranties arising from the sale of
a Fieldpiece product, including but not limited
to implied warranties of merchantability and
fitness for a particular purpose, are limited to
the above. Fieldpiece shall not be liable for loss
of use of the instrument or other incidental or
consequential damages, expenses, or economic
loss, or for any claim of such damage, expenses,
or economic loss.
State laws vary. The above limitations or
exclusions may not apply to you.
600V
TYPE K
TEMP
TEMP
CAT
CATIIIIII
600V
600V
Limited Warranty
COM
30V
MAX
TEMP
SC240
TYPE K
30V
30V
MAX
MAX
600V
CAT III
AC
SC240
DC
Clean the exterior with a dry cloth. Do not
use liquid.
30V
MAX
600V
DC
AC
Maintenance
30V
MAX
TYPE K
AC
17
AAC
VAC
VDC
NCV
°F°C
AC
AC
MFD
DC
AAC
VAC
VDC
TYPE K
Select
NCV
°F°C
MFD
AC
15
TRUE RMS
Fieldpiece
For SC240/260 only.
SaveAtime
and let your
NCV
V
V
°F°C
meter select the appropriate test Aparameter. Set
NCV
V
V
the selector switch to /°F°C / /MFD
and use
your test
leads
to
take
the
measurement.
The
TRUE RMS AUTO OFF
clamp meter
will
automatically
display
an
ohms,
30V
MAX
diode, continuity,
or K-TYPE
capacitance reading. In
TEMP
lect
S
elect and Range buttons
M/m
Auto Select mode, Sethe
TRUE
TRUERMS
RMS AUTO
AUTO
OFF
OFFM/m
SC260SC240
III
are disabled. CAT
600V
MFD
AC
Auto power off or APO will automatcially turn
A
off your meter after 30
of inactivty. By
NCVminutes
V
V
°F°C
default it is activated and APO will show on the
Select
M/m
display. To disable, turn meter off. Hold
SC260
(SC240/260) and power on the meter by turning
the selector dial to any range. For SC220, follow
elect hold Range and power on.
the same procedure Sbut
M/m
B
AAC
VAC
VDC
MFD
AC
TRUE RMS
AUTO OFF
Select
M/m
AAC
VAC
VDC
DO NOT SWITCH FROM J2
Range
NCV
°F°C
HOLD
Fieldpiece
Auto Power
Off
Fieldpiece
AUTO OFF
30V
MAX
Range
M/m
SC240
AAC
VAC
VDC
MFD
NCV
°F°C
Fieldpiece
C
AAC
VAC
VDC
Fieldpiece 14
MFD
HOLD
MFD
NCV
°F°C
TRUE RMS
Press and hold
for two seconds. Meter
will beep and HOLD will blink on LCD. After 6
Fieldpiece
seconds the measurement on screen will
freeze
automatically. Press
to exit this mode.
TEMP CAL
MFD
TYPE K
HOLD
AAC
VAC
VDC
NCV
°F°C
MFD
Record and freeze the maximum and
Select
M/m once to
minimum measurements. Press
A
SC260
freeze the maximum reading.
MAX
will
show on
NCV
V
Select
V
°F°C
M/m
display. Press
again to freeze the minimum
Select
M/m
reading. MINSC260
will show on display. Press
SC260
again to display real-time measurement
with both maximum and minimum readings
recording in the background. MAXAUTO
MINOFF
will blink
Select
M/m for one
on display. Press and hold
TEMP second
COM
SC260
AUTO
OFF
to exit Max/Min mode.
OFF
Max/Min functionality
is disabled in AUTO
Auto
TEMP
COM
CAT III
Select mode.
TEMP
Auto Hold
A
Auto Select Mode
TRUE RMS
Max/Min SC240Fieldpiece
and SC260 only
1. Bright LED and beeper warn when testing voltages >16VAC/35VDC. High Voltage warning.
2. Switch to the NCV function (non contact voltage) and point clamp claw towards suspected
voltage source. Monitor the bright RED LED
and beeper to see if the source is “hot.”
3.Temperature switch prevents the thermocouple plugging in while measuring voltage.
SEL
Fieldpiece
TRUE RMS
NCV
°F°C
Safety Features
For accuracies of ±1°F, calibrate to a known
temperature. A glass of stabilized ice water
is very close to 32°F (0°C) and is usually very
convenient but any known temperature can be
used. For SC240/SC260 models only.
16
13
AAC
VAC
VDC
SEL
SEL
Test any isolated power line, compressor or capacitor wire. True
RMS on SC260 only.
Ranges: 40A, 400A Resolution: 0.01A Crest factor: ≤ 3
Accuracy: ±(2.0% + 10) 50-60Hz Jaw Opening: 1.2in (30 mm)
True RMS: model SC260 only Overload Protection: 400AAC
! Note: AAC through the clamp and voltage through the test
Fieldpiece
leads can be measured simultaneously. However,
if only AAC is
TRUE RMS
measured through the clamp, test leads and MFD
thermocouple must
be unplugged
from the meter.
Fieldpiece
AAC
VAC
VDC
NCV
µADC
Fie
NCV
°F°C
CAT III
600V
1. Select the °F °C range.
2. Plug thermocouple to be
calibrated into the Type K jack.
3. Unscrew A and B and remove
the battery cover.
4. Stabilize a large cup of ice
water. Stir the ice with the
water until temperature stays
at a stable value.
5. Immerse the thermocouple
probe and let it stabilize. Keep
stirring water to prevent microenvironments.
6. Do not let the thermocouple
come in direct contact with ice.
7. Use a small screwdriver to
adjust calibration pot C below
the battery as close to 32°F
(0°C) as you would like.
Note: J1-J2 switch is for autocalibration purposes only. Not
intended for use in the field.
AAC
VAC
VDC
NCV
°F°C
Amps AC (AAC)
Continuity ( )
CAT
CATIIIIII
600V
600V
Use NCV to check for 24VAC from a thermostat or live voltage up
to 600VAC. Always test on a known live source before using. A three
segment graph and RED LED will display the presence of voltage. The
audible beep increases from intermittent to continuous as intensity of
field (EF) increases.
AC Voltage Detection Range: 24VAC to 600VAC (50-60Hz)
AAC
VAC
VDC
MFD
Set to / / /MFD and measure continuity to test
if a circuit is open or closed or press SELECT once to manully select
RMS continuity.
AUTO Use
OFF
this feature to check fuses as well. A steady “beep”
V
and
green
LED
indicate
you have continuity.
K-TYPE
X
TRUE
AUTO OFF
TEMP
Range:RMS
400Ω Resolution:
0.1Ω Response time: 100ms
Audible
beep:
<30Ω
30V
UE
UERMS
RMSMAX
AUTO
AUTOOFF
OFFK-TYPE
CAT
III
Overload
Protection:
600VDC or 600VAC rms
TEMP
30V
30V600V
K-TYPE
K-TYPE
11
MAX
MAX
MFD
HOLD
Used for “ohming out” a compressor.
to
test the resistance between the motor poles because the values are
SEL
typically very low.
Ranges: 40Ω, 400Ω,
4kΩ, 40kΩ, 400kΩ, 4MΩ, 40MΩ
SEL
SEL
Resolution: 0.01Ω
Accuracy: ±(1.0% + 15) 40Ω, ±(1.0% + 5) 400Ω to 400kΩ,
±(1.5% + 5) 4MΩ, ±(3.0% + 5) 40MΩ
Auto Select Ranges: 4KΩ to 4MΩ, >400Ω (SC240/SC260 only)
Overload Protection: 600VDC or 600VAC rms
TEMP
TEMP
Non Contact Voltage (NCV)
AAC
VAC
VDC
pie
NCV
°F°C
CAT
CATIIIIII
600V
600V
0.01Ω
resolution is useful
NCV
°F°C
600V
CAT
CATIIIIII
600V
600V
MFD
HOLD
Microamps for flameOrectifier test on a heater control. Connect
Hz
leads between flame sensor
probe
and
control
module
and
turn
F AAC
heating unitMFD
on to read µA
measurement.
AC VDC When the flame is on,
FV
% be a measurable µADC
there should
signal, typically under 10µADC.
NCV
Hz
HOL
HOL
Compare
measurement
to
manufacturer’s
°C
OO Hz
Hz specification to determine
°F
if replacement is necessary. FF AAAC
AC
INRUSH
AC
ACV
FFVV
VDC
DC
MFD
MFD
Ranges: 400µA,
4000µA Resolution:
0.1µA
%
%
NCV
NCV1V, 8V on 4000µA
Hz
Hz+ 2) Voltage burden:
Accuracy: ±(1.0%
°C
°C
Overload °F
Protection:
600VDC or 600VAC rms
°F
INRU
INRU
MFD
V
NC
°C
°F
TEMP
TEMP
Set to / / /MFD to test diodes for proper forward
and reversed-biased functions. Press SELECT twice to manually select
TRUE RMS theAUTO
OFF
diode test.
A constant beep and green LED indicate continuity.
30V
Test
current:
1.0mA
(Approx.) Accuracy: ±(1.5% + 5)
K-TYPE
MAX
TRUE
RMS
OFF typical
TEMP
Open
circuitAUTO
volts: 3.2VDC
VisualAUTO
indicator:
Green LED Audible beep: <0.03V
30V
TRUE
TRUERMS
RMS
AUTOOFF
OFF
K-TYPE
MAXIII
CAT
Auto
Select
Threshold:
Forward voltage drop <0.8V (SC240/SC260
TEMP
600V
30V
30V
K-TYPE
only) K-TYPE
MAX
MAX
TEMP
TEMP
Discharge Cap First!
Overload
600VDC or 600VAC rms
CATProtection:
III
AAC
VAC
VDC
MFD
Resistance
SEL (Ω)
NCV
°F°C
MicroAmps DC (µADC) SC220 only
D
MF
MFD
O Start
Hz and run capacitors are one of the most failure prone
components
F AAC in a HVACR system. Disconnect from power and resistors
F VAC terminals.
VDC Discharge capacitor before testing. HOLD
D between
If dIS.C is
O Hz
displayed,NCV
capacitor
not fully discharged. Set
to
/
F AisAC
HOLD
HOLD / /
OOto
Hz
Hz
VAC VDC
F
MFD
test
capacitance
of
motor
start
and
run capacitors
MFD
TRUE
RMSINRUSH
AUTO
OFF or press
AAC
AC
% FF A
NCV select
three
to manually
MFD.
Hz
V
AC
ACtimes
FFV
VVDC
DC
MFD
MFDSELECT
30V
°C
K-TYPE
40nF,
400nF, 4µF,
40µF, 400µF, 4mF
Resolution: 1pF
NCV
MAX
Hz
Hz°FRanges: 4nF,NCV
Accuracy: ±(3% + 20) 4nF, ±(3% +TEMP
5) 40nF to 400µF,
INRUSH
±(5% + 20) 4mF
TRUE
TRUERMS
RMS
AUTO
AUTOOFF
OFF
INRUSH
INRUSH
CAT
III
Auto Select Ranges: 4nF to 400µF,
>500pF
600V
30V
30V
K-TYPE
MAX
Overload Protection: 600VDC orMAX
600VAC rms K-TYPE
SC56
SC56
Diode Test ( )
ld
Fie
Capacitance (MFD) SC240
and SC260 only
HOLD
19
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2014; v15