DNF7
Transcription
DNF7
Medium Voltage Distribution DNF7 Air Insulated Switchgear 36 - 40.5 kV PARS TABLEAU [ Air Insulated Switchgear ] DNF7 DNF 7 Air Insulated Switchgear 36-40.5 kV CUSTOMER BENEFITS • Total safety for operators including full internal arc tested • Our AIS solution can be replaced by GIS in high ratings. • Immune to environmental influences • Ideal to convey high current load Wherever 36 or 40.5 kV power must be distributed and used with maximum availability and reliability, Pars Tableau has the time-proven equipment that best meets your needs. If you are looking for a convenient product with proven technology based on decades of experience designing and manufacturing substation switchgear, we have the answer in our DNF7 new generation for 40 kV substations. This innovative indoor air-insulated switchgear, with ratings up to 40 KA, is the first in its class catering to the needs of all process industries, distribution networks and any other application in electrical networks. The Fully Metal Clad Switchgear Robust For All Applications Based on its four distinct compartment design (circuit breaker, cables, busbar and low voltage equipment) and the use of earthed automatic shutters, DNF7 is highly reliable switchgear. The cubicle is of the true metal clad category. It meets the highest level of service continuity (LSC2B). Both busbar and cable compartments service continuity are ensured when normal maintenance is carried out in the circuit breaker compartment. As safety is a key point in this design, a provision for comprehensive shutter padlocking ensures total operator safety during maintenance work. DNF7 is equipped with either SF6 , or vacuum circuit breaker. Quality Quality Standards DNF7 has been designed and fully tested according to the latest IEC standards (IEC 62271-200/-100 and IEC 62271-1). All type tests have been performed in international recognized independent laboratories. DNF7 is manufactured in our ISO 9001-2000 and HSE certified factories. 2 PARS TABLEAU [ Air Insulated Switchgear ] DNF7 References List Oil ,Gas and Petrochemical Project Name End User Client MIS Masjed Soleyman Petroleum Engineering and Development Company (PEDEC) Tabdil energy paya.CO Azadegan oil field Petroleum Engineering and Development Company (PEDEC) Pars CO. Fajr Petrochemical 132/33 kV Fajr Petrochemical SSCO CO. Shiraz Ammonia and Urea Petrochemical Industries Design Equipment and parts Manufacturing Company, (PIDEMCO) Hirbodan CO. South Pars Gas Field Development Phase 13 Pars Oil and Gas Company (POGC) Parsian CO. West Karon Light &Heavy Crude Oil Pump Station &Power Transmission Lime Oil Transportation Petroleum Engineering and Development Company (PEDEC) Rampco Group Omidiyeh 132/33KV Power Line 132kv Existing Upper Substation Petroleum Engineering and Development Company (PEDEC) Substation Company South Pars Gas Field Development Phases 9 & 10 Pars Oil and Gas Company (POGC) Oil Industries Engineering and Construction Company (OIEC) Project Name Client Consolation Sabzevar steel complex MMTE Tara tarh Co. Andimeshk Khuzestan R.E.C Moshanir Co. Natanz steel complex Faraniroo Co. Ariya Co. Abarkooh sarmad steel complex Faraniroo Co. Ghodsniroo Co. Imam khomeini airport Imam khomeini airport Tabiran Co. Sirjan steel complex MMTE Kani mes Co. Bardsir steel complex Iranian sirjan complex Moniran Co. Khuzestan complex Khuzestan complex Darya pala Co. Industry Utility / Power Generation Project Name End User Client IRAQ Electricity United Nation Alstom of Turkey Turkmenistan electricity network renovation Turkmenistan electricity ministry Sunir Co. Dubai Mankhool 132/33kv S/S Dubai Electricity and Water Authority (DEWA) Dubai Electricity and Water Authority (DEWA) 36 kV SUB. Ports and shipping organization Dariyan CO. Ghods niroo Co. Besat & mahshahr sub’s Petrochemical free zone Co. Moshanir Co. Lishtar Khuzestan. R.E.C Moshanir Co. Andika Khuzestan. R.E.C Ghods niroo Co. 132/33 kV substation Khuzestan water & power Co. Sapta Co. 3 * for the complete Reference List , please refer to our web site. PARS TABLEAU [ Air Insulated Switchgear ] DNF7 Operator Safety First Pars Tableau’s DNF7 cubicle has been designed with operator safety as the number one priority. Internal ARC Classification (IAC) DNF7 has been sucessfully tested in an international recognized laboratory according to IEC 62271- 200 standards with the following classification : IAC AFLR 31.5 KA / 1s in all compartments. Ingress Protection The enclosure of DNF7 is designed with an ingress protection degree of IP4X. Clear, Visible Switching Devices The mechanism cover shows a visual display of circuit breaker ON/OFF condition, spring charged/ discharged and earthing switch ON/OFF. DNF7 has inspection windows for both breakers and cable compartments. This allows the positions of the withdrawable unit, earthing switch and the situation of the cable connection to be easily observed. Complete Set Of Interlocks All necessary positive interlocks are installed according to IEC standards and are designed to prevent: A closed circuit breaker being inserted into or withdrawn from the service position A circuit breaker being closed unless in the service or test position Closing of the earthing switch if the circuit breaker is in the service position Disengagement of secondary plug from socket when the circuit breaker is in service position. Necessary interlocks are also provided at the rear cable cover, which can only be opened when the breaker is tripped and brought to test position with the earthing switch closed. 4 PARS TABLEAU [ Air Insulated Switchgear ] DNF7 Technical Characteristics Rated voltage kV 36/40.5 Rated frequency Hz 50/60 Rated insulation level • Rated power frequency withstand voltage/1min. • Lightning impulse withstand voltage (peak value) kVrms kVp 70/80 170/180 Rated current of busbar A 1250/1600/2000/2500/3150 Rated current of T-off bar A 630/1250/1600/2000/2500/3150 Rated short time withstand current (3s) kA 25/31.5/40 Internal Arc Classification A FLR kA 31.5 / 1s Rated peak withstand current (peak value) kA 63/82/100 Ingress Protection Degree kA IP 4X * Width mm 1300 Height mm 2250 - 2350** Depth mm 2300 - 2750** * For higher IP please contact us. ** For 40.5 kV. Characteristics of The Components Vacuum, SF6 circuit breaker Sf6 & Vacuum Circuit Breakers from different suppliers could be used in this compartment based on customer request. Busbars Round, bare or sheated (on request), copper or aluminum bars. Rated current : up to 3150 A. Connection of MV cables The following types of connection are possible: dry type cables up to 4 x 630 mm. impregnated paper insulated cables. up to 300 mm2 single core and three core. Cable earthing switch (ES) This switch is dependently controlled or on request, can be of the type which operates rapidly and independently of the operator. permissible short time current, 1 s or 3 s: up to 40 KA rms. This cable earthing switch has a rated making capacity. Capacitive divider insulators located in the cable compartment supply neon indicators located in the immediate vicinity of the earthing switch control. of the conventional type with one or two secondary windings. functional of the bushing type very Low Voltage on insulated primary conductors. Voltage transformers (Vt’s) These devices can be used for application to cables or to busbars at a each cubicle housed in a case (at the rear or top) either of conventional type for fixed mounting without fuses. or functional and withdrawable with MV fuses incorporated. LV comparement this is integrated into but entirely distinct from the cubicle frame. it houses all the standard Low Voltage monitoring. control and indication devices comprising mainly. the protective equipment and auxiliary apparatus on cards mounted in a frame (48 cm rack). the terminals for the customer’s multiconductor cables, the cubicle tappings from common wires and the cubicle wiring. integral and accessible LV cable routes. 5 Current Transformers (Ct’s) these are located in the cable compartment and are : PARS TABLEAU [ Air Insulated Switchgear ] DNF7 Presentation of the functional units "Incoming" - "Outgoing" feeder with voltage transformer cables "Coupling" with voltage transformer bars Legend 1 Gas exhaust valves 2 Busbars 3 Gas exhaust duct (internal arc optional feature) 4 Busbar bypasses 5 Earthing switch 6 Voltage transformer compartment 7 Medium voltage cables 8 Cable fastening bottom plates 9 Current transformers 10 FP Ortholuor circuit breaker 11 Access door to circuit breaker compartment 12 Low voltage box 13 Low voltage wiring sheath 14 Handle (internal arc only optional feature) 15 Mounting of the lock cup optional feature + cable fastening bottom plates 6 PARS TABLEAU [ Air Insulated Switchgear ] DNF7 "Bus-riser" functional unit Legend 1 Gas exhaust duct 2 Upper busbar 3 Busbar bypasses 4 Lower busbar 5 Current transformer 6 Low voltage box 7 Low voltage wiring sheath 150 C **3000 1100 A Screw down points (screw 12) 1200 *800 55 1800 25 115 35 5 1300 TYPE (DNF7) 36 kV - 630 / 2000 A 36 kV - 630 / 2500 A 36 kV - 630 / 3150 A 36 UP To 40.5 kV - 630 / 3150 A A (mm) 2300 2400 2650 2750 B (mm) 365 365 465 565 C(mm) 500 500 750 750 * Minimum rear passage with voltage transformer cable = 1500 mm ** Minimum height under celing with voltage transformer bars = 3500 mm PARS TABLEAU 7 Cat. No. 01.2015 Design by:Hadi Tahmasebi +989122410032 WWW.PARSTABLEAU.COM info@parstableau.com