Cable Management System

Transcription

Cable Management System
Catalogue Nº 219
SUBSIDIARIES:
PEMSA UK:
Unit 2. Hunslet Trading Estate
Severn Road, LEEDS LS10 1BL
Tel.: 0113 277 9090
Fax.: 0113 277 5939
sales@pemsa.co.uk
Metal tray and channel system for cable support and management
PEMSA PORTUGAL:
Estrada de Polima. Centro Industrial de
Abóboda Edificio Fase 2. 2ºK
2785-543 São Domingos de Rana
Tel: +351 21 444 5725
Fax: +351 21 444 5727
pemsa.portugal@pemsa-rejiband.com
PEMSA FRANCE:
ZI Le clos aux pois. 12 Rue de la Closerie,
91090 LISSES
Tél.: 01 60 86 75 65
Telécopie: 01 60 87 11 83
service-client@pemsa.fr
www.pemsa.fr
HEADQUARTERS:
PEMSA SPAIN:
Galileo Galilei, 22-24. P.E. La Garena
28806 Alcalá de Henares. Madrid
Tel: +34 91 802 34 88
Fax: +34 91 802 33 81
info@pemsa-rejiband.com
Cable Management System
Metal tray and channel system
for cable support and management
www.pemsa-rejiband.com
cod. CYNW. E305934
F o r f u r t h e r i n f o r m a t i o n re g a rd i n g t h e s e c e r t i f i c a t e s p l e a s e c h e c k w i t h i n t h e d o c u m e n t .
Depósito Legal: M-12392-2008
Catalogue Nº 219
E-mail: info@pemsa-rejiband.com
General Catalogue
General
Catalogue
Origin, development and current position
Pemsa was founded in Madrid in 1969, and today it is a company engaged in
the manufacture of metal tray and channel systems for the support and
management of medium and low voltage electric cables, as well as the
manufacture of flexible tubing, connectors, compression glands and accessories.
Pemsa heads the ranking of Spanish manufacturers of metal cable trays and
is second at the European level as manufacturer of wire mesh cable trays of
electrically welded steel. Moreover, Pemsa is one of the top 10 leading European
manufacturers.
New facilities
At the end of 2002, the company
inaugurated its new facilities at Alcalá
de Henares, (Madrid). The current
surface area exceeds 45,000 m2, of
which 10,500 m2 consists of building
space, including 1500 m2 assigned
to offices and administrative
departments.The new factory is
equipped with the most modern
technology available in the world today. This technology also extends to the
warehouse and central offices, which include the various commercial and
marketing departments, the Technical Office, Production, Quality, Exports,
Logistics and Customer Service. The capacity of these new facilities may be
doubled in the future.
Metal tray and channel system for
cod. CYNW. E305934
F o r f u r t h e r i n f o r m a t i o n re g a rd i n g t h e s e c e r t i f i c a t e s p l e a s e c h e c k w i t h i n t h e d o c u m e n t .
Innovation and quality
Since the beginning, Pemsa has been
distinguished by the design and
manufacture of innovative products that
facilitate assembly and installation.
Thus, Pemsa was the first Spanish
manufacturer to introduce the
"Rejiband" wire mesh cable tray into
the market, its star product leading the
market and the commercial brand that
has become a generic name.
New products were subsequently
introduced in the sector, such as the
Rejitech system, specifically designed
for ceilings and false ceilings; or
Inducanal, a special metal channel with
reduced dimensions for installations
over large surface areas.
Currently, the company has one of the
most complete product catalogues on
the market, with the greatest number
of solutions for metal trays, supports
and structures.
Moreover, Pemsa has enjoyed ISO 9001
certification since 1997, one of the first
European manufacturers to obtain it.
cable support and management.
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 1
Commercial network
Pemsa currently has five commercial offices, located in
Madrid, Catalunya, the Basque
Country, Levante and Andalusia,
as well as commercial representatives distributed throughout
Spanish territory.
The export office is located at
our central offices in Alcalá de
Henares, (Madrid).
Chronological milestones
1969: First facility on Calle Nicaragua in Madrid, with 80 square metres.
1974: Transfer to facilities in Coslada (Madrid), 600 square metres.
1978: Launch of the rejiband® tray.
1995: New facilities in Mejorada del Campo (Madrid), with a surface area of 6000 square metres.
1997: 5000 square meter expansion of the surface area at the Mejorada facilities.
1998: Launch of the pemsaband® tray.
2002 (September): Transfer to the new general facilities in Alcalá de Henares (Madrid), with a surface
area of 45000 square metres and the possibility of doubling this capacity.
2003 (January): Opening of Pemsa UK Ltd., its first branch abroad, and the opening of two new offices.
2003 (May): Opening of the second branch abroad: Pemsa Portugal.
2004 (January): Enlargement of Production lines of Flexible Conduits.
2006 (May): Pemsa, Global Supplier of Cable Management. Expansion of product range of Conduits,
Metallic rigid Conduits, Halogen Free Conduits.
2006 (June): Enlargement of Pemsa UK Store and Facilities
2006 (October): Purchase of Production line of Metallic Trays of PINAZO company, increasing the production capacity of pemsaband® line.
2008: Opening of new branches in France.
2009: 40th Anniversary of Pemsa.
International presence: new branches abroad
Pemsa has initiated a new stage of international expansion by direct presence, namely its own brand,
which is integrated into the strategic plan of the company. This materialised in 2003 with the opening of
three branches abroad: Pemsa UK, Pemsa Portugal and Pemsa France.
Furthermore, Pemsa has already established a presence in a long list of countries throughout the five
continents: Europe: Austria, Belgium, Cyprus, Denmark, Slovakia, France, Germany, Greece, Hungary,
Ireland, Italy, Latvia, Poland, Sweden, the Czech Republic, the Netherlands and United Kingdom.
America: Antilles, Chile, Costa Rica, Ecuador, El Salvador, Guatemala, Mexico, Nicaragua, Panama and
USA. Asia: Dubai, Indonesia, Lebanon and Macau. Africa: Angola, Israel and Morocco; Oceania: New
Zealand.
2
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 2
The metal tray
and channel system
that provides:
Graphic labels
Allow perfect identification of all elements of
the rejiband® system.
- Facilitate storage.
- Allow product identification during the entire manufacturing process.
A
B
- Include the following: 13-digit EAN bar code, reference number, the units it
contains, type of finish and part dimensions.
Protective packaging
With heat-sealed film and identification label.
It ensures maximum protection and perfect storage.
B
A
CE Marking
All products in this catalogue comply with CE directives.
EAN code
All products in this catalogue have been assigned their corresponding 13-digit, European bar code
(EAN).
3
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 3
SUPPORTS
New range of Reinforced
Supports
Pemsa introduce a new range of reinforced supports that
unify the system connection for their rejiband® and
pemsaband® trays and have the following advantages and
new features:
ADVANTAGES
Click new and fast system, in the opposite direction to load
forces, which guarantees the fixing of the tray to support
and prevent their displacement.
Unified Standard and Click range giving reduction in
logistical references for the client.
DISTINCT CHARACTERISTICS
O
PA
N TA
D
TE
Reinforced Strength
D
PA
TE
NTE
The bracket has been designed
with curves for greater strength
and load bearing capacity.
Click System
Fixing pin for quickly securing
the tray thus avoiding
movement in any direction.
Lateral Grooves
PA
TE
D
O
PA
Increases the load resistance of
the bracket and reinforces the
area supporting the tray.
N TA
D
TE
Detail of fixing
Click System
NTE
Side Pressing
Fully embossed side enhances
the strength of the bracket and
improves it’s load capacity.
Back Pressing
Embossed back increases the
resistance of the bracket and
prevents any bending.
4
4
Detail of fixing with
Reinforced joint clamp
11:30
Página 4
D
E
NT
E
P
New Range of Accessories
pemsaband
TE
G
27/11/09
PA
PEMSA-CAT 219-2-12-REV
N DIN
®
90º Bend, Crossover, Tee, Side Entry, with their corresponding covers.
New Parts, Inside and Outside Risers. Full range in all heights, 35, 60 and 85.
Finishes P.G. and H.D.G.
90º Bend 300, height 60
Crossover 400, height 85
Click System Joint. There is
no need to use joints to
connect the accessories to
the straight sections of
pemsaband.
Accesory Covers overlap on the tray,
improving stiffness and tightness of
the assembly.
DN20 precut conduit exits.
In heights 60 and 85 for installation
fittings or glands of M20, PG11 or
PG13.
Inside Riser
5
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 5
The rejiband®
BYCRO tray from PEMSA respects the
environment and meets the RoHS standard.
Pemsa has made a series of improvements to its rejiband® tray and its Bycro finish now
offers the following advantages and features:
Pemsa leads the market with its bichromed electro-galvanised rejiband® tray. Using the latest generation processes and products, the
Bycro finish is fully compliant with the current RoHS legislation and RAEE directives.
Pemsa is committed to protecting the environment by eliminating hexavalent chromium in its electro-galvanising plants. Its rejiband®
trays are manufactured without products that are harmful, contaminating or have an adverse effect on the environment.
The BYCRO finish still offers superb anti-corrosion protection.
N TA
PA
TE
D
O
PA
TE
D
The BYCRO finish has a unique iridescent gold
finish and superb technical properties.
NTE
The reference and coding systems for the product
remain the same.
Pemsa continues to lead the way with its rejiband®
BYCRO tray which incorporates superior anticorrosion properties but is free of hexavalent
chromium (Cr VI) and other heavy metals in
compliance with 2002/95/CE RoHS. Pemsa
continues to offer its customers a tray which
guarantees greater safety, a better finish and an
optimum price/quality ratio while protecting our
environment.
UL Classified
rejiband® ELECTRICAL CONTINUITY GUARANTEED.
This certification ensures, when using rejiband® basket, that the correct electrical
continuity between trays exists which could, under certain circumstances, be used as a
protective earth without using any additional protective conductor. Any protective conductor
would connect all earthed points of an installation to the earth conductor, in order to eliminate
the risks through indirect contact.
The UL Classified mark, achieved by PEMSA, is the result of testing electrogalvanized
rejiband® basket trays (35, 60 & 100mm flange) joined with the Reinforced Joint Clamp. It
certifies that the requirements of the NEMA VE 1-2000 Metal Cable Tray Systems standards
are met in accordance with the Canadian Electrical Code and the National Electrical Code, NEC.
The value of the UL CLASSIFIED marking
UL is one of the most renowned safety certification institutions worldwide. A UL marked product is an item that has been successfully
tested by the UL in accordance with certain safety requirements. These tests ensure the use of this product does not bring any significant
risk of fire, electric shock or any other linked danger. The safety requirements are equally met in the long term, since UL performs periodic
checks and verifications at the manufacturer’s premises.
6
4
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 6
Fire Resistance
1000 ºC for 90 minutes.
rejiband® basket tray has successfully exceeded the fire resistance tests
defined by the German Standard DIN 4102-12 “Fire behaviour of building
materials and elements, Fire resistance of electric cable systems required
to maintain circuit integrity”, by withstanding 1000 ºC (1832ºF) temperature
for 90 minutes, thus obtaining the E90 certification.
In case of fire, rejiband® basket tray does not harm either the people or
the installation itself (no fumes of toxic, corrosive or opaque nature at all),
and ensures enough structural resistance and the power supply to the
most critical systems (emergency lighting, fire detection, etc).
For further information, consult pages 122 and 123.
pemsa pro is the brand new software developed by Pemsa for the calculation and selection of Wire Mesh Tray, Steel Cable Tray and Channel Systems.
This program allows the user to enter and define all parameters of the installation, and
produces a choice of the most suitable trays, along with the required accessories, brackets,
clamps, etc, in order to correctly configure a specific electrical installation. The cable type
can also be chosen, thanks to the extensive data base of the main cable manufacturers.
pemsa pro provides an easy and intuitive process, via a complete set of on-screen menus,
that allows the user to enter all features of the installation.
The software has two modes: Quick Calculation and Installation Calculation. The latter
allows the breakdown of the project into floors, areas, sections and sub-sections in order to
obtain a detailed definition of the installation.
pemsa pro contains a vast collection of 3D tray assemblies, and a powerful tool for visualising these graphics. The views can be exported and inserted into any report or technical
document.
Last but not least, the software produces a complete report with all of the technical data
and prices of the individual components required for the installation.
7
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 7
Pemsa Metal Trays and Channels
rejiband
®
The market-leading electrically welded steel mesh trays, with a safety edge that prevents
personal injury and cable damage.
Easy to handle, its "cut, bend and link" system allows easy adaptation to every installation
and provides assembly time saving exceeding 30%.
AS
PA
P
D
O
PA
TE
ME
It is lightweight, offers maximum ventilation and cleanliness, provides great strength and
elasticity, and allows the addition of accessories during construction.
N TA
D
TE
NTE
It has a very wide range of accessories: "Click," Omega and reinforced supports; fibre optic
outlet systems, etc., as well as various finishes and materials:
electrolytic zinc coating, hot-dip galvanising, AISI 304 and 316 stainless steel.
pemsaband System
®
A
SM
EP
The in-line manufactured sheet metal tray using an automatic, integrated process starting
with steel sheet rolls. Pemsa have optimized its range of metal tray by developing three
different ranges of pemsaband® tray: pemsaband® SX, RX and LX
pemsaband® SX
Metal tray with the base embossed and perforated, It comes packaged to protect the
corners and interior parts and also to facilitate handling and transport.
The slotted perforations provide maximum strength for equal weight and thickness.
pemsaband® SX has at a new joggled coupling system which increases the ease of
connection between lengths and substantially reduces installation time. Thanks to this Click
system, you do not need any coupler just two screws for assembly.
The range of pemsaband® SX trays are designed and manufactured to the highest standards
of quality, based on the product standard IEC 61537. This quality is confirmed by the N mark
from AENOR, which guarantees all of its technical characteristics, and the E90 Fire
Resistance Certification.
Full range on heights 35, 60, 85 and 100. Widths of 100 to 600 mm.
pemsaband® RX
Perforated and solid tray manufactured from thicker material to withstand higher loads. High
load capacity. Thickness = 1.5 mm. Available in 60, 85 and 100 depths.
pemsaband® LX
Perforated and embossed tray with Rapid Click Coupling System in 35 and 60 depths.
Overall length is 3.05 metres.
Furthermore, cables are protected. All this ranges of pemsaband®, longitudinal strength is
increased through the shaped ends of the lateral edges. The fitted cover is secure and easy
to install, without the need for clamps or bolts.
The pemsaband® metal channel requires the use of a cover. This channel may be delivered
with perforations, depending on the required IP.
Perforated metal channel with cover: IP 2x.
Solid metal channel with IP 4x cover.
Comparison of the allowable load values of various cable trays
Measurements of trays
8
PVC tray
Rejiband tray
Pemsaband SX tray
110 N/m
220 N/m
340 N/m
460 N/m
520 N/m
480 N/m
750 N/m
780 N/m
1150 N/m
1760 N/m
1040 N/m
1040 N/m
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 8
P
ME
AS
false floor
DD
IBANBAN
REJREJI
SA
PEM
DD
IBANBAN
REJREJI
The rejiband® tray has a specific system for installation under false floors. This system allows quick,
flexible and easy installation, thereby ensuring maximum cleanliness and ventilation.
DD
IBANBAN
REJREJI
SA
PEM
DD
IBANBAN
REJREJI
SA
DD
SA
PEM
IBANBAN
REJREJI
SA
PEM
DD
IBANBAN
REJREJI
PEM
The rejiband® false floor is supplied with a complete range of specific supports and accessories for
these types of installation.
SA
PEM
Supports and structures
They are basic in a tray installation. If they are not appropriate, the entire installation will fail.
When selecting these elements, the load capacity of the support and the corrosion resistance are the main considerations.
Pemsa has a complete range of installation solutions:
• Supports for Ceiling / False Ceiling installations • Supports for Floor / False Floor installations.
• Supports for Vertical / Horizontal Wall installations • Supports for Ceiling / Pendulum installations.
• Supports for installations Outdoors / Indoors / In highly corrosive environments.
• Structures for special installations.
rejitech
®
Installation on ceilings and false ceilings
This is a specific tray for ceilings and false ceilings. It is a tray made of high-strength, electrically welded wire mesh, which provides multiple advantages.
Its design prevents the accumulation of dust and dirt. It provides maximum cleanliness and
faster and easier handling.
N TA
PA
TE
D
O
PA
TE
D
The reduction in installation time exceeds 55%, given that it has been designed to be fastened to the ceiling by a single bolt. Its open design ensures lateral access to cables.
NTE
The savings in materials exceeds 40%, and given that it is manufactured in 2 metre lengths,
transport is highly simplified and it can be easily transported in a small van.
Furthermore, it provides for easy and effortless cable handling, given that the cables are
completely visible.
inducanal
®
This is a metal channel of reduced size, appropriate for industrial installations.
It has great impact resistance and resistance to temperature, and is manufactured with perforations that facilitate cable outlets.
The Inducanal metal channel requires the use of the IP 2x cover.
Characteristics and benefits of Pemsa Metal Trays
• They eliminate the possibility of trays acting as fire propagation elements.
• They eliminate the risk of inhalation of toxic gases or halogens.
• They facilitate sufficient time and visibility in order to completely evacuate personnel, and facilitate access to
fire sources for firemen.
• They eliminate harmful effects to equipment, or electronic or computer circuits, due to the corrosive effect of
smoke on these elements.
IN BRIEF: The use of rejiband® and pemsaband® metal trays significantly improves the safety of
owners and users of electrical installations.
9
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 9
rejiband®
Cable Management System!!
rejiband®
FEATURES:
Open Structure
Superior Strength to
Weight Ratio
Inventory Management
Design Criteria
Fire Resistance E90
Adaptability
BYCRO Coating
www.pemsa-rejiband.com
ER-0058/1997
10
cod. CYNW. E305934
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 10
rejiband®
Wire mesh tray
Wall installation
Ceiling installation with rods
Ceiling installation
False floor installation
Page
12
30-31
38-39
44-45
50
rejitech®
Wire mesh tray
false ceiling installation
52
pemsaband® system
Index
Steel cable tray
The sheet metal tray
with slotted perforations
Pemsaband SX
Pemsaband RX
Pemsaband LX
Wall installation
Ceiling installation with rods
Ceiling installation
56
60
65
67
80-81
86-87
92-93
inducanal®
Reduced dimension metal channel
98
Supports
& Structures
102
Screws
107
Technical information
Recommendations for the correct
installation of cable trays
Technical information EN 61537
Choosing the right tray and support system
Surface treatment to prevent corrosion
Electrical continuity
Earthing
Electromagnetic Compatibility (CEM)
Pemsa Metal Tray Systems:
Behaviour in the event of fire
Fire Resistance, E90 Certification
Fire test in the tunnels of El Padrún
109
113
113
115
117
118
119
121
122
124
Index by products
126
Index by references
128
11
PEMSA-CAT 219-2-12-REV
27/11/09
11:30
Página 11
rejiband
®
Mesh cable tray
Corrosion (White)
500
440
400
350
- Enhanced Protection against Corrosion
- Safety Edge
- Chrome-VI free
- Compliant with RoHS 2002/95/CE
and WEEE 2002/96/CE
ER-0058/1997
12
HOURS
BYCRO Wire Mesh
rejiband® Featuring:
300
290
250
200
150
100
50
0
E.G.
E.B./BYCRO
Laboratory Tests performed under
ASTM B117 Standard proves the
excellent behaviour of Pemsa BYCRO
finish against corrosion.
cod. CYNW. E305934
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 1
The “Click” System
for supports and accessories
Exclusive, developed and patented
by Pemsa. It brings quick fastening
with no need for bolts or special
tools, giving savings of up to 30%.
Fit
Bend
Bend
Fit
It takes just one
movement to
fasten the item
down securely.
Quick fastening,
with no bolts
needed.
CABLE OUTLET
(page 28)
FOOT (page 50)
CLICK CONNECTOR
(page 22)
SUPPORT 60 (page 32)
13
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 2
Rejiband 35
Length 3000 mm.
N TA
TE
PA
TE
D
O
PA
D
E.G.
NTE
H.D.G.
BYCRO
S.S. 304
S.S. 316
A
Ref.
100
60211100
0.65
60221100
0.65
60231100
0.70
60251100
0.65
200
60211200
1.01
60221200
1.01
60231200
1.08
60251200
300
60211300
1.38
60221300
1.38
60231300
1.46
60251300
400
60211400
1.77
60221400
1.77
60231400
2.02
60251400
/m
Ref.
/m
Ref.
/m
/m
mm2
m
60261100
0.65
2220
24
1.00
60261200
1.01
4900
18
1.36
60261300
1.38
7580
18
1.73
60261400
1.74
10200
12
Ref.
/m
Ref.
Rejiband 60
Length 3000 mm.
N TA
TE
PA
TE
D
O
PA
D
E.G.
NTE
H.D.G.
BYCRO
S.S. 304
S.S. 316
A
Ref.
060
60212060
0.67
60222060
0.67
60232060
0.71
60252060
0.67
100
60212100
0.95
60222100
0.95
60232100
1.01
60252100
150
60212150
1.01
60222150
1.01
60232150
1.07
60252150
200
60212200
1.31
60222200
1.31
60232200
1.39
300
60212300
2.07
60222300
2.07
60232300
400
60212400
2.52
60222400
2.52
500
60212500
2.97
60222500
600
60212600
3.42
60222600
/m
/m
mm2
m
60262060
0.67
2410
24
0.94
60262100
0.94
4310
24
1.00
60262150
1.00
6900
24
60252200
1.30
60262200
1.30
9490
18
2.19
60252300
1.66
60262300
1.66
14200
12
60232400
2.66
60252400
2.02
60262400
2.02
19300
6
2.97
60232500
3.13
60252500
2.38
60262500
2.38
24400
6
3.42
60232600
3.61
60252600
2.74
60262600
2.74
29500
6
Ref.
/m
Ref.
/m
Ref.
/m
Ref.
Rejiband 100
Length 3000 mm.
N TA
TE
PA
TE
D
O
PA
D
E.G.
NTE
H.D.G.
BYCRO
S.S. 304
S.S. 316
A
Ref.
200
60213200
2.06
60223200
2.06
60233200
2.17
60253200
1.65
60263200
1.65
17600
6
300
60213300
2.51
60223300
2.51
60233300
2.65
60253300
2.01
60263300
2.03
27300
6
400
60213400
2.96
60223400
2.96
60233400
3.12
60253400
2.37
60263400
2.37
37100
6
500
60213500
3.41
60223500
3.41
60233500
3.60
60253500
2.73
60263500
2.76
46800
6
600
60213600
3.86
60223600
3.86
60233600
4.07
60253600
3.09
60263600
3.12
56500
6
/m
Ref.
/m
Ref.
/m
Ref.
/m
Ref.
/m
mm2
m
Angle tray
Rejitech
(false-ceiling tray)
BYCRO
E.G.
100
60215020
/m
A
/m
mm2
m
0.66
2500
16
Ref.
0.66
60225020
A
O
PA
TE
14
/m
0.67
/m
m
0.71
18
Ref.
60230000
S.S. 316
/m
0.67
/m
m
0.67
18
Ref.
60260000
Length 3000 mm.
Length 2000 mm.
Weight in kilos
Ref.
109 60250000
NTE
Material: Steel
Working temperature range: -50 ºC / 150 ºC
H.D.G.
S.S. 304
N TA
D
TE
Ref.
109 60220000
D
Ref.
PA
A
BYCRO
E.G.
BYCRO
P.G.
H.D.G.
S.S.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 304 or AISI 316
Página 3
Rejiband 35
MAXIMUM SAFE WORKING LOAD (Kg/m)
1 kg = 9.8 N
E.G., BYCRO and H.D.G.
STAINLESS STEEL
Width:
Width:
100 - 200 - 300
400
400
100 - 200 - 300
400
60
60
55
55
50
50
45
35
45
400
40
Kg/m
40
35
30
30
25
100 - 200 - 300
25
100 - 200 - 300
20
20
15
1,0
1,5
15
2,0
1,0
Distance between supports (meter)
1,5
MAXIMUM SAFE WORKING LOAD (Kg/m)
E.G., BYCRO and H.D.G.
60 - 100 - 150
200
300 - 400
600
1 kg = 9.8 N
STAINLESS STEEL
Width:
500
60 - 100 - 150
200 - 300 - 400
600
110
180
100
90
600
100
300 - 400
80
70
500
Kg/m
120
60
80
50
200 - 300 - 400
60
200
40
40
60 - 100 - 150
1,5
20
2,0
1,0
Distance between supports (meter)
1,5
2,0
Distance between supports (meter)
Rejiband 100
MAXIMUM SAFE WORKING LOAD ((Kg/m)
E.G., BYCRO and H.D.G.
300 - 400
1 kg = 9.8 N
STAINLESS STEEL
Width:
200
30
60 - 100 - 200
20
1,0
200
300 - 400
500 - 600
500 - 600
130
290
120
260
110
500 - 600
230
100
210
90
180
Kg/m
500 - 600
80
300 - 400
150
300 - 400
70
120
60
200
90
200
50
60
1,0
1,5
Distance between supports (meter)
600
120
140
500
500
200
160
Width:
2,0
Distance between supports (meter)
Rejiband 60
Width:
Kg/m
11:33
Kg/m
27/11/09
2,0
Kg/m
PEMSA-CAT 219-13-20-REV-
40
1,0
1,5
2,0
Distance between supports (meter)
Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170% without ever reaching the
collapse point. Guaranteed only using our reinforced joint clamp.
Tray section joints be situated at a support distance of between L/4 and L/5, L being the distance between supports.
At completed tray extreme ends, tray support distance should be a maximum of 0.4L without any type of joint.
15
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 4
MAKING ACCESSORIES ON SITE
(bends, T-sections, etc.)
cut - bend - join
How to cut the grid
Always use ASYMMETRICAL-CUT WIRE CUTTERS
Cut as close as you can to where the
horizontal and vertical rods cross each
other, at the position shown:
Avoid using
parting tools to
cut the grid
It damages the rod’s protection
The cutting leaves burrs
● It contaminates the
surroundings
● The sparks can cause
accidents
● It encourages rusting
●
●
Cut position
16
Side cutting
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 5
WHAT YOU NEED
Bolt cutters
Reinforced joint clamp
450
68000058
1.6
Pack
unit
1
600
68000059
2.8
1
0.027
PA
64010062
0.026
50
Ref.
64060061
/u
0.028
Pack
unit
50
E.B.
/u
0.010
H.D.G.
Ref.
64030062
Part clamp
Captive bolt
64010060
/u
0.01
D
Ref.
O
D
PA
64030060
NTE
Splice plate
0.016
67010053
0.016
67030047
Central hanging plate
M8
M10
M8 = ø9x16
M10 = ø11x18
M8
M10
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
50
Ref.
64060062
/u
0.01
Pack
unit
50
Ref.
/u
64020060
0.016
Pack
unit
50
Ref.
/u
64060060
0.017
Pack
unit
50
E.B.
/u
0.065
H.D.G.
Ref.
0.009
Pack
unit
S.S. 316
/u
E.G.
Ref.
64020062
/u
E.B.
/u
H.D.G.
N TA
Ref.
S.S. 316
E.G.
Ref.
PA
0.026
Pack
unit
S.S. 316
/u
E.G.
Ref.
TE
64020061
/u
NTE
Connector plate
TE
Ref.
D
O
64030061
/u
E.B.
/u
H.D.G.
Ref.
D
PA
64010061
N TA
TE
Ref.
E.G.
Ref.
JUST 3 PARTS!
● Captive bolt
● Simplifies assembly
● 20% improvement
in mechanical performance
TE
A
Ref.
67020053
/u
0.065
Pack
unit
10
S.S. 316
/u
0.069
E.G.
Ref.
67060053
/u
0.064
Pack
unit
10
E.B.
Type
A
Ref.
9x16
67010046
0.032
67020046
0.029
20
11x18
-
-
67020146
0.028
20
/u
H.D.G.
Ref.
/u
Pack
unit
S.S. 316
Type
A
Ref.
9x16
67030046
0.031
67060046
0.030
20
11x18
67030146
0.032
67060146
0.032
20
/u
Ref.
/u
E.G.
E.B.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromated UNE - EN 12329
H.D.G.
S.S.
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 304 or AISI 316
Pack
unit
17
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 6
Examples of assembly
90º BENDS
CUT
For 100-600 mm wide trays
A
B
N
100
300
100
150
400
200
200
400
200
300
500
300
400
600
400
500
700
500
600
800
600
Reinforced joint clamp (page 22)
For 60 mm wide trays
50
0
1
260
0
CU
10
T
Reinforced joint clamp (page 22)
18
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 7
90º BENDS
For 100-150 mm wide trays
CU
T
Reinforced joint clamp (page 22)
For 200-600 mm wide trays
CU
T
A
B
N
200
525
100
300
625
200
400
725
300
500
825
400
600
925
500
Reinforced joint clamp (page 22)
Central hanging plate x 2 (page 17)
DIN 603 M6x20 screw (page 107)
M6 nut (page 107)
19
PEMSA-CAT 219-13-20-REV-
27/11/09
11:33
Página 8
90º BENDS
For 300-600 mm wide trays
L
CU
T
X
ADJUST
A
B
L
X
300
570
1300
5
400
840
1700
7
500
920
2100
9
Part clamp (page 24)
600
1300
2300
10
Splice plate (page 24)
Reinforced joint clamp (page 22)
LEVEL CHANGE
CU
T
BEND
20
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 1
CUT
REDUCER
Reinforced joint clamp (page 22)
Part clamp (page 24)
Splice plate (page 24)
T-JOINTS
CU
T
Reinforced joint clamp (page 22)
21
PEMSA-CAT 219-21-37-REV
27/11/09
PARTS
11:36
Página 2
(for Rejiband fitting)
Reinforced joint clamp
E.G.
E.B.
Ref.
64010061
Ref.
/u
Pack
unit
PA
TE
0.027
64020061
0.026
50
D
O
PA
/u
N TA
D
TE
NTE
H.D.G.
S.S. 316
Ref.
/u
64030061
0.026
Ref.
/u
64060061
Pack
unit
0.028
50
JUST 3 PARTS¡
● Captive bolt
● Simplifies assembly
● 20% improvement in mechanical performance
Click connector
E.G.
Ref.
D
AN
JIB TY
RE CURI
SE
PA
TE
D
O
PA
N TA
D
TE
NTE
Ref.
/u
64010020
●
●
●
●
E.B.
0.072
/u
64020030
Pack
unit
0.072
25
Quick fitting
No bolts
No special tools
Electrical continuity guaranteed
Side joint-plate
E.G.
Ref.
64010041
E.B.
/u
0.048
H.D.G.
Ref.
64030041
Wire end cap
Ref.
64020041
/u
Pack
unit
0.048
50
S.S. 316
/u
0.05
Ref.
64060041
/u
Pack
unit
0.048
50
BLACK POLYETHYLENE
Ref.
68000049
/u
0.001
Pack
unit
100
Working temperature range: -50 ºC / +60 ºC
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
22
E.G.
E.B.
H.D.G.
S.S. 316
Electrogalvanised UNE - EN 12329
Bichromate Electrolytic zinc-plating UNE - EN 12329
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 3
Examples of assembly
CONNECTORS NEEDED EVERY 3 METERS
WIDE
060
100
150
200
300
400
500
600
2
2
2
2+1
2+1
2+2
2+2
2+2
Wire end cap (page 22)
CONNECTORS NEEDED EVERY 3 METERS
WIDE
100
150
200
300
400
500
600
NER
SAFE
FAS
T
E
T
Y
2
2
2+1
2+1
2+2
2+2
2+2
23
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 4
Splice plate
E.G.
Ref.
E.B.
/u
67010053
0.065
H.D.G.
Ref.
Part clamp
0.069
E.G.
Ref.
Captive bolt
Ref.
67060053
/u
0.064
Pack
unit
10
0.016
Ref.
64020060
/u
0.016
Pack
unit
50
N TA
O
PA
10
E.B.
/u
64010060
0.065
Pack
unit
D
TE
67020053
/u
S.S. 316
/u
67030047
Ref.
H.D.G.
D
PA
TE
S.S. 316
NTE
Ref.
64030060
/u
0.016
Ref.
64060060
/u
0.017
Pack
unit
50
Earth terminal
BRASS
Suitable for cable
sizes 16-35 mm2
Ref.
68000032
/u
0.024
Pack
unit
20
New design. More economical. Less weight.
Zinc paint spray
Ref.
Contents: 400 ml.
68000052
/u
0.52
Pack
unit
1
Store and transport temperature range:
-20 ºC / +40 ºC
Working temperature:
-50 ºC / +150 ºC
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
24
E.G.
E.B.
H.D.G.
S.S. 316
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 5
Examples of assembly
CONNECTORS NEEDED EVERY 3 METERS
WIDE
100
150
200
300
400
500
600
4
4
4
6
8
8
8
2
2
2
2+1
2+2
2+2
2+2
CONNECTORS NEEDED FOR EACH SUPPORT
WIDE
100
150
200
300
400
500
600
1
1
2
2
2
3
3
EARTH CONNECTION
Suitable for cable
sizes 16-35 mm2
25
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 6
Rejifix
Rejifix
• Inexpensive and reusable.
• Allows contignous cable placement.
• No screws or other fixing elements
are required.
• Manufactured using fire retarding ABS
plastic material.
Colour
Ref. nº
Wide
m/roll
/u
Pack
unit
0.14
89011000 BLACK 10 mm 25 m
1
Working temperature range: -40 ºC / +60 ºC
Suitable for
installations: voice,
data, fibre optic...
Fixing support for Rejiband
ABS
Ref.
Pack
unit Working temperature range:
-5 ºC / +90 ºC
20
/u
68000010
0.008
For fastening the ties or cleats that hold the cables supported on the Rejiband wire mesh tray.
Rejiband box support
PLASTIC
Ref.
• Inexpensive.
• Hand installation by preassure.
• No accessories required.
• Efficiently isolated so as not to
permit electric contact between box
and tray.
/u
68000040
0.01
Pack
unit
20
Working temperature range:
-15 ºC / +60 ºC
Press Fit
Identification plate
No text - for
marking by the user
PLASTIC
Working temperature range:
-5 ºC / +105 ºC
26
Ref.
89010000
/u
0.01
Pack
unit
50
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 7
Examples of assembly
Rejifix
IDENTIFICATION PLATE:
TO USE FOR IDENTIFICATION
pemsa
es
abl
c
a
dat
ce-/3
i
)
o
V e7
any
p
n
i
7
m
L nt o
Pla (C
Press Fit
REJIBAND BOX SUPPORT
27
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 8
Cover
P.G.
3m length
/m
m
060
73021060
0.47
73031060
0.62
73061060
0.62
24
100
73021100
0.74
73031100
0.84
73061100
0.85
24
150
73021150
1.02
73031150
1.14
73061150
1.16
12
200
73021200
1.30
73031200
1.60
73061200
1.48
12
300
73021300
2.11
73031300
2.30
73061300
2.11
6
400
73021400
2.74
73031400
3.68
73061400
2.74
6
500
73021500
4.22
73031500
4.54
73061500
3.37
6
600
73021600
5.01
73031600
5.39
73061600
4.00
6
A
Ref.
25
67020610
0.26
67030610
0.30
50
67020611
0.38
67030611
0.43
80
67020612
0.53
67030612
0.60
/m
Ref.
P.G.
E N TA
/m
H.D.G.
/m
Ref.
S.S. 316
Ref.
/m
Ref.
/m
m
67060610
0.26
60
67060611
0.38
48
67060612
0.53
36
D
PA
TE
D
O
PA
S.S. 316
Ref.
Divider plate
T
H.D.G.
A
NTE
A
3m length
The PG finish on the 25, 50 and 80 flange comes packaged for correct storage.
HD and stainless steel finishing is supplied in plastic tensed strip
packaging for easy storage.
Identification label
PLASTIC LABEL
PA
/u
68000020
0.002
Pack
unit
50
D
O
PA
TE
Ref.
Working temperature range:
-20 ºC / +60 ºC
N TA
D
TE
NTE
Connector plate
E.G.
Ref.
64010062
E.B.
0.01
H.D.G.
Ref.
/u
/u
64020062
0.009
Pack
unit
Ref.
50
64030062
S.S. 316
/u
0.01
Ref.
64060062
/u
0.01
Pack
unit
50
Universal bracket
P.G.
Ref.
62026011
H.D.G.
/u
0.169
S.S. 316
Ref.
/u
62036011
0.182
Ref.
62066011
/u
0.176
Pack
unit
10
For fixing boxes,
use M5 bolts
Gland bracket
Data outlet
Press Fit
For conduit size:
M20 PG 13
M20 PG 16
M25 PG 21
Weight in kilos
28
10
E.G.
E.B.
P.G.
H.D.G.
S.S. 316
TE
N TA
TE
D
0.063
Pack
unit
O
Material: Steel
Working temperature range: -50 ºC / +150 ºC
67020040
POLYPROPYLENE
/u
D
0.063
Ref.
PA
67010040
E.B.
/u
PA
E.G.
Ref.
Press Fit
NTE
Ref.
67020039
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
/u
0.011
Pack
unit
10
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 9
Examples of assembly
3m length
BEND
Divider plate (page 28)
Identification label
Fastest
Mounting
Identification
label!
BEND
29
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 10
Wall assembly
Horizontal
Side support 60
Mini Universal
Bracket
Omega Bracket
Omega bracket
on channel
250 N
500 N
580/1660 N
580/1660 N
page 32
page 32
page 34
page 34
150
page 34
page 34
200
page 34
page 34
300
page 34
page 34
Admissible load
❶
TRAY WIDTH:
060
100
page 32
400
500
600
❶ Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug and supports
reinforced with the PEMSA structural reinforcement
30
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 11
Horizontal
Rejiband
Security
Pemsa
Inclined
Rejiband
Security
Pemsa
Medium Duty
Cantilever
Medium Duty
Cantilever
on channel
1180/2530 N
1180/2530 N
Rejiband
Security
Vertical
Pemsa
Adjustable Medium
Duty Cantilever
1210/2060 N
Mini Universal Bracket
Stand off Bracket
500 N
1000 N
REINFORCED SUPPORTS
GREATER LOAD-BEARING CAPACITY
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
page 36
page 36
page 36
page 32
NOTE!!
E
FIT SUITABL
W
E ALL!
PLUGS IN TH
31
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 12
Side support 60
N
E.G.
AxB
E.B.
Ref.
250 104x30
N
/u
62011060
0.041
250 104x30
0.04
Ref.
Pack
unit
/u
62061060
0.041
25
0
Rejiband 60x6
D
PA
D
O
PA
25
Essential for
N TA
TE
0.041
S.S. 316
/u
62031060
Pack
unit.
/u
62021060
H.D.G.
AxB
Ref.
TE
Ref.
NTE
Mini universal bracket
N
P.G.
AxB
Ref.
510 65x87
Stand off bracket
N
62026010
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
32
0.088
P.G.
A
Ref.
1000
H.D.G.
/u
Ref.
62036010
S.S. 316
/u
0.098
H.D.G.
/u
Ref.
Ref.
/u
62066010
0.092
Pack
unit
10
S.S. 316
/u
Ref.
/u
Pack
unit
180
67030539
0.17
67030541
0.24
67060541
0.13
10
350
67030540
0.32
67030542
0.35
67060542
0.21
10
E.G.
E.B.
P.G.
H.D.G.
S.S.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 13
Examples of assembly
HORIZONTAL
VERTICAL
Part clamp (page 24)
33
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 14
Omega Click bracket
• Including new Omega plug (preassembled) and
new Omega protector • Guarentees and improves the performance of the OMEGA SUPPORTS
• Makes feating easier and aids proper fitting of the support.
N
P.G.
AxB
H.D.G.
Ref.
/u
Ref.
/u
Pack
unit
1180 100x145
62023103
0.27
62033103
0.28
5
1040 150x145
62023153
0.31
62033153
0.32
5
1150 200x145
62023203
0.48
62033203
0.51
5
870 300x145
62023303
0.62
62033303
0.65
5
580 400x145
62023403
0.75
62033403
0.79
5
Working temperature range: -5 ºC / +90 ºC
Omega bracket
• Including new Omega plug (preassembled) and
new Omega protector • Guarentees and improves the performance of the OMEGA SUPPORTS
• Makes feating easier and aids proper fitting of the support.
P.G.
AxB
N
H.D.G.
Ref.
/u
Ref.
S.S. 316
/u
(PGHDG)
Ref.
N
/u
(S.S.) Pack
unit
100x145
62021103
0.26
62031103
0.28
1180
62061103
0.35
1660
5
150x145
62021153
0.30
62031153
0.32
1040
62061153
0.40
1390
5
200x145
62021203
0.47
62031203
0.50
1150
62061203
0.47
1130
5
300x145
62021303
0.60
62031303
0.63
870
62061303
0.60
860
5
400x145
62021403
0.73
62031403
0.77
580
62061403
0.73
590
5
Working temperature range: -5 ºC / +90 ºC
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
34
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 15
Examples of assembly
Wall mounting
Channel mounting
Channel mounting
(Turn and click)
M10x35 screw (page 107)
Washer 10 (page 107)
Heavy duty channel (page 104)
Channel nut M10 (page 104)
Safety plug
Allen screw M10x20 (page 107)
Wall plug M10
M10x35 screw (page 107)
Click System
Fit
Economy
Speed
Fit
Bend
Bend
35
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 16
Medium Duty Cantilever
P.G.
30
35
P.G.
AxB
N
Ref.
NEW!
A
B
PA
TE
Pack
unit
100x54
62025103
0.18
2530
4
150x54
62025153
0.23
1890
4
200x54
62025203
0.38
1560
4
300x54
62025303
0.53
1240
4
400x92
62025403
0.76
1220
4
500x92
62025503
0.93
1210
4
600x92
62025603
1.09
1200
4
D
O
PA
7X20
D
T
E N TA
/u
NTE
Medium Duty Cantilever
40
H.D.G.
12X16
AxB
30
30
H.D.G.
N
Ref.
NEW!
A
B
/u
S.S. 316
Ref.
N
/u
Pack
unit
100x50
62035103
0.23
2060
62065103
0.19
1930
4
150x50
62035153
0.28
1870
62065153
0.24
1720
4
200x50
62035203
0.33
1780
62065203
0.28
1610
4
300x50
62035303
0.42
1690
62065303
0.37
1500
4
400x77
62035403
0.77
1840
62065403
0.70
1580
4
500x77
62035503
1.92
1640
62065503
0.84
1380
4
600x77
62035603
1.06
1210
62065603
0.98
1180
4
35
PA
TE
D
O
PA
7X20
N TA
D
TE
NTE
Heavy Duty Cantilever
12X16
40
AxB
30
H.D.G.
N
Ref.
30
A
117
NEW!
B
/u
Pack
unit
300x77
63033303
0.79
2490
4
400x77
63033403
0.99
2160
4
500x77
63033503
1.19
2000
4
600x77
63033603
1.38
1840
4
7X20
35
O
PA
N TA
D
TE
D
PA
TE
NTE
Adjustable Medium Duty Cantilever
Ø12
46
AxB
47
104
A
NEW!
B
PA
TE
7X20
35
Pack
unit
100x74
62037103
0.54
2060
4
150x74
62037153
0.59
1870
4
200x74
62037203
0.63
1780
4
300x74
62037303
0.73
1690
4
400x74
62037403
1.08
1840
4
500x74
62037503
1.23
1640
4
600x74
62037603
1.37
1210
4
Delivered unassembled. All pieces included.
NTE
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
36
N
/u
D
O
PA
N TA
D
TE
H.D.G.
Ref.
P.G.
H.D.G.
S.S.
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-21-37-REV
27/11/09
11:36
Página 17
Examples of assembly
SUPPORTS
6
3
5
4
Wall mounting
1
5
4
2
Channel assembly
1 Medium Duty Cantilever
H.D.G.
2 Medium Duty Cantilever
P.G.
3 Heavy duty channel 41x21 G.C. (page 104)
4 Hexagonal screw M10 (page 107)
5 Washer M10 (page 107)
6 Channel nut M10 (page 104)
DISTINCT CHARACTERISTICS
Reinforced Strength
The bracket has been designed
with curves for greater strength
and load bearing capacity
Click System
Fixing pin for quickly securing
the tray thus avoiding
movement in any direction.
Detail of fixing
Click System
Lateral Grooves
Increases the load resistance of
the bracket and reinforces the
area supporting the tray.
Side Pressing
Fully embossed side enhances
the strength of the bracket and
improves it’s load capacity.
Back Pressing
Embossed back increases the
resistance of the bracket and
prevents any bending.
Detail of fixing with
Reinforced joint clamp
37
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 1
Fitting to ceiling
with threaded rods
Admissible load
❶
250 N
890 N
890 N
690 N
100
page 40
page 40
page 40-42
150
page 40
page 40
page 40-42
200
page 40
page 40
page 40-42
TRAY WIDTH:
060
page 40
300
400
500
600
+ EASY CABLE LAYING
❶ Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug and supports
reinforced with the Pemsa structural reinforcement
38
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 2
with threaded rods
690 N
800 N
1760/2000 N
1760/3320 N
4310/4890 N
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
page 40-42
+ ASSEMBLY TIME SAVING
NOTE!!
E
FIT SUITABL
E WALL!
PLUGS IN TH
39
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 3
Side support 60
Rod Connector M8
N TA
PA
TE
D
O
PA
TE
D
Essential for
Rejiband 60x60
NTE
E.B.
N
AxB
E.G.
Ref.
250 104x30
N
AxB
/u
62011060
0.041
Ref.
/u
Pack
unit
0.041
4000
67020067
/u
Pack
unit
0.016
50
25
S.S. 316
/u
62031060
Ref.
62021060
H.D.G.
Ref.
250 104x30
N
E.B.
0.04
Ref.
/u
62061060
Pack
unit
0.04
25
Threaded rod
M6/M8/M10
N
E.G.
AxB
Ref.
M6
E.B.
/u
Ref.
/u
Pack
unit
67010140
0.12
67020140
0.12
-
-
50
1890 M6x1000
67010141
0.24
67020141
0.24
67060141
0.24
50
N
AxB
E.B.
Ref.
/u
Pack
unit
67020044
0.16
67060044
0.16
50
4000 M8x1000
67020045
0.32
67060045
0.32
50
M10 5000 M10x1000 67020145
0.49
67060145
0.49
50
Type
A
N
M8
M10
M8 = ø9x16
M10 = ø11x18
E.G.
Ref.
E.B.
/u
Ref.
/u
Pack
unit
9
700
67010046
0.032
67020046
0.029
20
11
700
-
-
67020146
0.028
20
Type
A
N
9
700
67030046
0.031
67060046
0.030
20
11
700
67030146
0.032
67060146
0.032
20
M8
M10
Click Central Suspension
S.S. 316
/u
M8 4000 M8x500
Central hanging plate
Type
A
A
H.D.G.
Ref.
N
S.S. 316
/u
E.G.
Ref.
M6 6.2x15.5 890
M8 8.2x15.5 890
M10 10.2x15.5 890
Ref.
/u
Pack
unit
E.B.
/u
Ref.
/u
Pack
unit
67010143
0.045
67020143
0.045
20
67010043
0.044
67020043
0.044
20
67010243
0.044
67020243
0.044
20
N TA
D
Type
PA
TE
D
O
PA
Ref.
1890 M6x500
Ref.
TE
S.S. 316
/u
NTE
A
Used for hanging wire mesh tray from the ceiling,
it is suitable por Rejiband trays in 100, 150 and
200 widths.
N
H.D.G.
Ref.
M6 6.2x15.5 890
M8 8.2x15.5 890
M10 10.2x15.5 890
S.S. 316
/u
Ref.
/u
Pack
unit
67030143
0.047
67060143
0.044
20
67030043
0.047
67060043
0.044
20
67030243
0.047
67060243
0.044
20
Variable ceiling rod bracket
Ceiling bracket
Use with
s
M8/M10 rod
H.D.G.
N
P.G.
Ref.
67030060
Ref.
/u
0.094
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
40
Pack
unit
10
1275
E.G.
E.B.
P.G.
H.D.G.
S.S.
67030061
/u
0.15
Pack
unit
1
Electrogalvanised UNE - EN 12329
Bichromate Electrolytic zinc-plating UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 4
Examples of assembly
Position
Bend
Only 1 part
with 2 nuts!
MAX. - 700 N
Click central suspension (page 40)
Threaded rod M8 (page 40)
M10x35 screw (page 107)
Central hanging plate (page 40)
Variable ceiling rod bracket (page 40)
Beam clamp hanging assembly (p. 42)
Threaded rod M-10
Fitting to ceiling
Side support 60 (page 40)
41
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 5
Mesh channel
N
P.G.
A
Ref.
H.D.G.
/u
Ref.
/u
Pack
unit
1 rod
2 rods
3320
4890
200
63022203
0.23
63032203
0.24
10
2540
4740
300
63022303
0.33
63032303
0.34
10
1760
4600
400
63022403
0.42
63032403
0.45
10
-
4460
500
63022503
0.52
63032503
0.55
10
-
4310
600
63022603
0.62
63032603
0.65
10
Working Temperatura with Safety Plug: -5 ºC / +105ºC
Safety plug
PA
TE
D
O
PA
N TA
D
TE
NTE
incluided for better performance
on widths 200-400
Mesh Click channel
PATENTEDPATENTADO
N
P.G.
A
H.D.G.
Pack
unit
1 rod
2 rods
3320
4890
200
63021203
0.23
63031203
0.25
10
2540
4740
300
63021303
0.34
63031303
0.35
10
1760
4600
400
63021403
0.43
63031403
0.45
10
-
4460
500
63021503
0.53
63031503
0.56
10
-
4310
600
63021603
0.63
63031603
0.66
10
Ref.
/u
Ref.
/u
Working Temperatura with Safety Plug: -5 ºC / +105ºC
With safety plug incluided!
Beam clamp hanging assembly
(*) The Loads depends of type of assembly.
Please view the below pictures.
NS
NS
NS
KG
KG
2000 N
950 N
25
KG
2000 N
≥ 30º
45º
E.B.
N
Ref.
(*)
67020048
/u
0.34
Pack
unit
NS
KG
NS
1
2500 N
700 N
Horizontal angle
hanger
NS
KG
KG
800 N
Vertical angle
hanger
A
A
PASSIVATED
N
A
Ref.
690
/u
PASSIVATED
Pack
unit
1.5-5
68000721
0.05
100
4-10
68000722
0.05
100
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
42
N
A
Ref.
690
/u
Pack
unit
1.5-5
68000731
0.04
100
4-10
68000732
0.04
100
E.B.
Bichromate Electrolytic zinc-plating UNE - EN 12329
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 6
Examples of assembly
(A) Fitting with one rod
LAYING
+ EASY CABLE
ME SAVING
+ ASSEMBLY TI
NOTE!
With safety plug included!
(B) Fitting with two rods
Threaded rod M10 (page 40)
Safety plug
Hexagonal nut M10+washer (page 107)
Mesh Click channel (page 42)
Threaded rod M8 (page 40)
Mesh Click channel (page 42)
Hexagonal nut M8 (page 107)
Cost comparison
(A)
(B)
40
100
43
PEMSA-CAT 219-38-44-REV
27/11/09
11:38
Página 7
Fitting to ceiling
Omega System
❶
Bending Moment 1 ❷
Bending Moment 2 ❷
Vertical Force
320/960 N
2100/3810 N
3370 N
3370 N
-
120 Nm
410 Nm
410 Nm
-
110 Nm
150 Nm
150 Nm
100
page 46
page 34-36-46
page 34-36-46
page 34-36-46
150
page 46
page 34-36-46
page 34-36-46
page 34-36-46
200
page 46
page 34-36-46
page 34-36-46
page 34-36-46
300
page 46
page 34-36-46
page 34-36-46
page 34-36-46
400
page 46
TRAY WIDTH:
500
600
ANGLE TRAY
❶ Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug and supports
reinforced with the Pemsa structural reinforcement
44
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 1
reinforced pendant bracket
3780 N
3780 N
4270 N
7270 N
700 N
360 Nm
360 Nm
930 Nm
930 Nm
-
430 Nm
430 Nm
730 Nm
730 Nm
-
REINFORCED SUPPORTS GREATER
LOAD-BEARING CAPACITY
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 36-48
page 48
❷
Values obtained in accordance with International Standard UNE - EN 61537
(Section H) relating to the information for safe installation of trays with
horizontal supports. For further information please contact PEMSA.
* Bending moment 1 : Resulting bending moment on ceiling plane.
* Bending moment 2 : Resulting bending moment from cantilever bracket.
NOTE!!
E PLUGS
FIT SUITABL
L!
IN THE WAL
45
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 2
Omega ceiling bracket
D
NTE
PA
N
H.D.G.
Ref.
O
PA
TE
P.G.
A
N TA
D
TE
/u
Ref.
S.S. 316
/u
(PGHDG)
Ref.
N
/u
(S.S.)
Pack
unit
100
62022103
0.42
62032103
0.44
760
62062103
0.56
940
4
150
62022153
0.62
62032153
0.66
960
62062153
0.62
780
4
200
62022203
0.67
62032203
0.72
800
62062203
0.69
630
4
300
62022303
0.82
62032303
0.86
650
62062303
0.82
470
4
400
62022403
0.94
62032403
0.99
340
62062403
0.94
320
4
• Including Omega plug (preassembled) and Omega
protector • Guarentees and improves the performance of the OMEGA
SUPPORTS • Makes feating easier and aids proper fitting of the support.
Omega Click ceiling bracket
N
P.G.
AxB
Ref.
H.D.G.
/u
Ref.
/u
Pack
unit
760
100
62029103
0.42
62039103
0.45
4
960
150
62029153
0.63
62039153
0.67
4
800
200
62029203
0.70
62039203
0.74
4
650
300
62029303
0.84
62039303
0.88
4
340
400
62029403
0.92
62039403
1.02
4
Including Omega plug
(preassembled) and Omega
Protector.
Click system.
Fast fixing of tray without the
need of bolts
Omega pendant bracket
P.G.
A
Ref.
H.D.G.
/u
Ref.
S.S. 316
/u
Ref.
46
Pack
unit
300
62021303
0.42
62031303
0.45
62061303
0.45
5
400
62021403
0.63
62031403
0.67
62061403
0.67
5
500
62021503
0.70
62031503
0.74
62061503
0.74
5
600
62021603
0.84
62031603
0.88
62061603
0.88
5
Including Omega plug
(preassembled) and Omega
Protector.
Material: Steel
Working temperature range: -5 ºC / +90 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
/u
P.G.
H.D.G.
S.S.
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 3
Examples of assembly
4
100/400
LOAD
300/600
According to Omega Ceiling bracket table.
100/400
S.S. 316
2100
3810
Bending Moment 1
120
110
Bending Moment 2
110
130
300/600
P.G., H.D.G.
Vertical Force
100/400
S.S. 316
3370
3370
Bending Moment 1
410
410
Bending Moment 2
150
190
300/600
P.G., H.D.G.
Vertical Force
100/400
M10x35 screw+washer (page 107)
M10x20 screw+washer+nut (page 107)
M10x60 screw+washer+nut (page 107)
Safety plug
Omega bracket 100 (page 34)
Omega Click bracket 100/300 (page 34)
100/400
100/400
P.G., H.D.G.
S.S. 316
Vertical Force
3370
3370
Bending Moment 1
410
410
Bending Moment 2
150
190
47
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 4
Heavy duty pendant drop
N
BM 1
BM 2
A
H.D.G.
Ref.
/u
Pack
unit
3780
360
430
500
67030660
1.51
1
3780
360
430
1000
67030661
2.47
1
N
BM 1
BM 2
A
Double heavy duty pendant drop
150
80
A
H.D.G.
Ref.
/u
Pack
unit
4270
930
730
500
67030662
2.48
1
4270
930
730
1000
67030663
4.40
1
N
BM 1
BM 2
A
Heavy duty pendant channel
P.G.
Ref.
360
430
500
67030646
0.87
1
3780
360
430
1000
67030647
1.76
1
Angle tray fastener
E.B.
P.G.
67030645
/u
0.62
Pack
unit
1
M10x20 hexagonal cone
point screw not included.
Angle tray
BYCRO
H.D.G.
Ref.
60220000
/u
0.67
Ref.
60230000
Ref.
67020051
Ref.
Length: 3000 mm
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
60260000
/u
m
0.67
18
/u
0.18
Pack
unit
10
S.S. 304
/u
0.71
Ref.
60250000
S.S. 316
48
Pack
unit
3780
Heavy duty pendant boss
Ref.
/u
BYCRO/E.B. Electrolytic Bichromated UNE - EN 12329
P.G.
Pre-galvanised UNE - EN 10142
H.D.G.
Hot-dip galvanised UNE - EN-ISO 1461
S.S.
Passivated stainless steel AISI 316
/u
m
0.67
18
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 5
Examples of assembly
Fit every 1 m.
M8x60 screw+nut+serrated washer (page 107)
M10x20 screw (page 107)
Channel nut (page 104)
M10x20 hexagonal cone point screw (page 107)
49
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 6
rejiband
false floor
D
AN
IB
EJ
R
®
D
AN
IB
EJ
R
SA
M
PE
D
AN
IB
EJ
R
SA
M
PE
D
AN
IB
EJ
R
SA
M
PE
D
AN
IB
EJ
R
SA
M
PE
D
AN
IB
EJ
R
SA
M
PE
RE
JIB
AN
D
SA
M
PE
Rejiband 35
Floor foot
POLYSTYRENE
Ref.
68000060
Rejiband 60
Pack
unit
/u
0.02
100
Working temperature range:
-5 ºC / +60 ºC
V2 according to UL 94
O
PA
N TA
D
TE
Press Fit
D
PA
TE
NTE
Information: page 14
Gland bracket
Reinforced
joint-clamp
Information: page 28
PA
O
TE
For conduit size:
D
PA
Information: page 22
N TA
D
TE
NTE
M20 PG 13
M20 PG 16
M25 PG 21
Floor foot adhesive
Comprises adhesive + hardener
Contents:
enough for aprox. 100 feet
Store and transport temperature range:
+5 ºC / +40 ºC
Working temperature range:
-5 ºC / +60 ºC
Earth terminal
BRASS
Ref.
Ref.
68000065
50
/u
1.80
Pack
unit
1
68000032
/u
0.024
Pack
unit
20
Information: page 24
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 7
Examples of assembly
Press Fit
Quick, easy installation
For proper maintenance, the rack
should be at least 40 mm away
from the floor.
If the rack crosses pipes, the
rack must always be above the
pipes.
Rejiband ensures the highest
cleaning and ventilation levels.
A
B
Auxiliary material
Cost
needed, per meter
comparison
A
M10x20 screw (page 107)
Stand off bracket (page 32)
Part Clamp (page 24)
Exp. plug M10
100
B
Floor foot (page 50)
Floor foot adhesive (p. 50)
25
51
PEMSA-CAT 219-45-52-REV
27/11/09
11:40
Página 8
rejitech
®
Wall and ceiling mounting in reduced
spaces and false ceilings
PA
TE
D
O
PA
N TA
D
TE
NTE
YES
- Quick Installation without joints and bends
- The assembly work can be done by just one person
- Tidy cabling
- Easy to modify
NO
- Minimum height
- Cables can be inserted from the side
- Maximum ventilation
52
11:44
Página 1
65
O
PA
ERTED
CABLES INS
IDE
FROM THE S
N TA
D
TE
TE
D
27/11/09
PA
PEMSA-219-53-90-REV
NTE
Comparative study
rejitech® - PVC CONDUITS
Space needed (for the same number of cables)
PVC CONDUITS
REJITECH
Length: 1m for same cable capacity
48
80
48
48
48
48
48
36
36
36
65
1000
100
Fittings needed (per meter)
REJITECH
-
PVC CONDUITS
M6 plug
M6 screw
Ceiling fastener
Rejitech 100x60
1
1
1
1
-
M6 plugs
PG 48 clamp
PG 36 clamp
PVC pipes
11.25
7.5
3.75
6.3
Assembly time (per meter)
-
Mark
Drill
Fit plug
Screw
Cable
1
1
1
1
1
-
Mark
Drill
Fit plug
Screw on cramps
Cable
9
11.25*
11.25*
27
9
COST Comparison
20
100
* 0.8 per meter.s/MI.BT.019
53
PEMSA-219-53-90-REV
27/11/09
11:44
Página 2
Rejitech
E.G.
(Support of cables for installation on
ceilings and false ceilings and walls
in reduced spaces).
A
Ref.
100
60215020
BYCRO
/m
/m
mm2
m
0.66
2500
16
Ref.
0.66
60225020
Length 2000 mm
Sag for a distance of 1m between supports
A
12
60
Sag (mm)
PA
TE
D
O
PA
D
T
E N TA
10
Maximum sag
8
6
4
NTE
2
0
0
1
2
3
4
50
6
7
8
9
10
11 12
Load (Kg/metre)
Ceiling fastener (Press Fit)
E.G.
E.B.
S I S T E M A
CLICK
Ref.
Ø 11x16
/u
67010052
0.028
Ref.
67020052
/u
Pack
unit
0.028
25
Ø 7x23
Box support for Rejitech
E.B.
S I S T E M A
CLICK
Ref.
67020041
Ø 7x50
10
Mount to boxes with M6 screw.
E N TA
PA
TE
D
O
PA
0.023
Pack
unit
D
T
/u
NTE
Rejitech versatile application.
Wall and ceiling installation in false ceilings and
spaces with reduced accessibility.
65
False ceiling installation
65
Wall installation
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Advantages
-
Reduced space.
Fast installation.
No need for brackets.
Suitable for light loads.
E.G.
Electrogalvanised UNE - EN 12329
BYCRO/E.B. Electrolytic Bichromate UNE - EN 12329
Weight in kilos
54
PEMSA-219-53-90-REV
27/11/09
11:44
Página 3
Examples of assembly
Assembly without
connectors
Ceiling fitting
Rejitech
Assembly in just three steps
1
2
click
3
1m
Fit plugs+M6 screws
Fit ceiling fasteners every 1
meter aprox. on the Rejitech
Fit and screw in assembly 2
Fiting boxes
1
Attach the box to the support
2
Insert assembly 1 in Rejitech
3
Swivel assembly 2 onthe
Rejitech
55
PEMSA-219-53-90-REV
27/11/09
11:44
Página 4
pemsabandSystem
®
Steel cable tray
Metal Sheet Cable Tray manufactured under a
fully automated and integrated process with
feeders of metal sheet coils.
Its exclusive design shows clearly distinguising
advantages.
56
PEMSA-219-53-90-REV
27/11/09
11:44
Página 5
®
Pemsa have optimized its range of metal tray by developing three different ranges of pemsaband tray:
Metal tray with the base embossed and perforated, it comes packaged to protect the corners and interior
parts and also to facilitate hadling and transport.
The slotted perforations provide maximum strength for equal weight and thickness.
pemsaband SX has at a new joggled coupling system which increases the ease of connection
between lenghts and substantially reduces installation time.
Thanks to this Click system, you do not need
1
2
3
any coupler just two screws for assembly.
NT
G
D
P
E
TE
E
PA
®
N DIN
ck
Cli
030/000246
®
The range of pemsaband SX trays are designed and manufactured to the highest standards of
quality, based on the product standard IEC 61537. This quality is confirmed by the N mark from AENOR,
which guarantees all of its technical characteristics, and the E90 Fire Resistance Certification.
Full range on heights 35, 60, 85 and 100. Widths of 100 to 600 mm.
NT
G
D
P
E
TE
E
PA
High load capacity. Thickness = 1.5 mm.
Perforated and solid tray manufactured from thicker material
to withstand higher loads.
Available in 60, 85 and 100 depths.
N DIN
Perforated and embossed tray with Rapid Click Coupling System
in 35 and 60 depths.
Over all length is 3.05 metres.
®
Furthermore, cables are protected. All this ranges of pemsaband ,
presents the following features.
Embossed
perforations
Fixing with
countersunk
screws
Maximum
strength to
weight ratio
Safety edge
Self fix lid
cover
Well-finished
side/edge
P
P
®
The pemsaband metal channel requires the use of a cover. This channel may be delivered with
perforations, depending on the required IP.
Perforated metal channel with cover: IP 2x. Solid metal channel with IP 4x cover.
TRAY
+
+
COVER
=
SECURE TRUNKING
=
PE
M
SA
PE
M
SA
57
PEMSA-219-53-90-REV
27/11/09
11:44
Página 6
Page
1 - Joiner
2 - Bend joiner
3 - Divider plate
4 - Hinge riser/dropper
5 - Reducer
6 - Cover
7 - Universal bracket
8 - Adjustable bend
9 - 90º gusseted bend
10 - T-intersection
11 - Side entry
12 - Cross-joint
13 - Channel beam clamp
58
68
68
68
70
70
70
72
72
74
74
76
76
106
Page
14
15
16
17
18
-
Mesh channel
Fitting with one rod
Fitting with two rods
Cantilever bracket H.D.G.
P.G. heavy duty cantilever
90
91
91
84
84
Page
19
20
21
22
-
Channel
Edge protectors
Channel nut
Double heavy duty pendant
104
70
104
96
PEMSA-219-53-90-REV
27/11/09
11:44
Página 7
59
PEMSA-219-53-90-REV
27/11/09
11:44
Página 8
The base of the tray is embossed and perforated, certified by the AENOR N mark and E90 DIN-410212. It comes packaged to protect the corners and interior parts and also to facilitate handling and
transport.
TE
NT
D
G
P
E
E
PA
P.G. Finish
N DIN
ø8x20
Length 3050 mm
Useful Tray 3000 mm
50
B
S
m
3000 m
Tray = m
l
fu
e
s
U
0m
L=305
A
Rapid Click Coupling System
with 35 and 60 depths.
Click Perforated 35
Click Perforated 60
P.G.
P.G.
/m
S
mm2
m
AxB
Ref.
/m
S
mm2
0.97
2890
24
100x60
75522100
m
1.25
5360
24
1.70
8040
12
1.99
10700
12
2.56
16100
6
75522400
3.13
21700
6
500x60
75522500
4.65
26800
6
600x60
75522600
5.35
32200
6
AxB
Ref.
100x35
75521100
150x35
75521150
1.21
4360
12
150x60
75522150
200x35
75521200
1.67
5790
12
200x60
75522200
300x35
75521300
2.24
8710
12
300x60
75522300
400x35
75521400
2.81
11600
6
400x60
500x35
75521500
4.25
14400
6
600x35
75521600
4.96
17300
6
Embossed
perforations
Fixing with
countersunk screws
Safety
edge
System uses couplers with
85 and 100 depths.
Well-finished
circular flange
Perforated 85
Perforated 100
P.G.
S
mm2
P.G.
AxB
Ref.
200x85
75223200
2.24
15700
6
300x85
75223300
2.80
23600
6
200x100 75224200
2.43
18600
6
400x85
75223400
4.17
31400
6
300x100 75224300
2.99
28100
6
500x85
75223500
4.90
39300
6
400x100 75224400
4.40
37400
6
600x85
75223600
5.59
47200
6
500x100 75224500
5.14
46800
6
/m
m
AxB
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Ref.
/m
S
mm2
P.G.
Self fix
cover
m
P
P
Maximum
strength to
weight ratio
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
60
PEMSA-219-53-90-REV
27/11/09
11:44
Página 9
H.D.G. Finish
Connects with couplers and comes
in 3 metre lengths.
Perforated 35
H.D.G.
Perforated 60
H.D.G.
/m
S
mm2
m
AxB
Ref.
/m
S
mm2
1.28
2870
24
100x60
75232100
m
1.64
5330
24
1.96
8040
12
2.28
10700
12
2.94
16100
6
75232400
4.35
21400
6
500x60
75232500
5.18
26800
6
600x60
75232600
5.96
32200
6
AxB
Ref.
100x35
75231100
150x35
75231150
1.59
4330
12
150x60
75232150
200x35
75231200
1.92
5790
12
200x60
75232200
300x35
75231300
2.57
8710
12
300x60
75232300
400x35
75231400
3.91
11500
6
400x60
500x35
75231500
4.74
14400
6
600x35
75231600
5.52
17300
6
Embossed
perforations
Fixing with
countersunk screws
Safety
edge
System uses couplers with
85 and 100 depths.
Well-finished
circular flange
Perforated 85
Perforated 100
H.D.G.
S
mm2
H.D.G.
AxB
Ref.
200x85
75233200
2.61
15700
6
300x85
75233300
3.94
23500
6
200x100 75234200
2.83
18600
6
400x85
75233400
4.71
31400
6
300x100 75234300
4.21
28000
6
500x85
75233500
5.55
39300
6
400x100 75234400
4.98
37400
6
600x85
75233600
6.33
47200
6
500x100 75234500
5.81
46800
6
/m
m
AxB
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Ref.
/m
S
mm2
P.G.
Self fix
cover
m
P
P
Maximum
strength to
weight ratio
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
61
Página 10
Width:
MAXIMUM SAFE WORKING LOAD (Kg/m)
Width:
100 - 150
1 kg = 9.8 N
200 - 300
120
120
110
110
100
100
90
90
80
80
70
70
60
100 - 150
1.5
1.6
1.7
1.8
1.9
50
50
40
40
2.0
1.5
1.6
1.7
1.8
1.9
MAXIMUM SAFE WORKING LOAD (Kg/m)
Width:
200
500 - 600
300 - 400
170
170
160
160
150
150
140
140
130
130
120
120
110
110
100
100
90
100 - 150
1 kg = 9.8 N
Kg/m
200
90
300 - 400
80
80
70
70
60
60
500 - 600
50
50
40
1.5
1.6
1.7
1.8
1.9
40
2.0
1.5
Distance between supports (metre)
1.7
1.8
1.9
MAXIMUM SAFE WORKING LOAD (Kg/m)
Width:
300
200
400 - 500 - 600
140
140
130
130
120
120
110
110
100
100
90
90
80
300
80
400 - 500 - 600
70
70
60
60
50
50
40
1.5
1.6
1.7
1.8
Distance between supports (metre)
2.0
1 kg = 9.8 N
Kg/m
200
1.6
Distance between supports (metre)
Pemsaband SX 85
Width:
2.0
Distance between supports (metre)
Pemsaband SX 60
100 - 150
60
200 - 300
Distance between supports (metre)
Width:
Kg/m
Pemsaband SX 35
Kg/m
11:44
1.9
2.0
Kg/m
27/11/09
Kg/m
PEMSA-219-53-90-REV
40
1.5
1.6
1.7
1.8
1.9
2.0
Distance between supports (metre)
Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170% without ever reaching the
collapse point. Guaranteed only using our joiner and central joiner for widths from 300 up to 600.
Tray section joints be situated at a support distance of between L/4 and L/5, L being the distance between supports.
At completed tray extreme ends, tray support distance should be a maximum of 0.4L without any type of joint.
62
PEMSA-219-53-90-REV
27/11/09
11:44
Página 11
solid
Solid, smooth base tray certified by the AENOR N mark and E90 DIN-4102-12. It comes packaged to
protect the corners and interior parts and also to facilitate handling and transport.
NT
G
D
P
E
TE
E
PA
P.G. Finish
N DIN
ø8x20
Length 3050 mm
Useful Tray 3000 mm
50
m
3000 m
Tray =
Useful 050 mm
L=3
S
Solid 35
A
Solid 60
P.G.
B
Rapid Click Coupling System
with 35 and 60 depths.
P.G.
/m
S
mm2
m
AxB
Ref.
/m
S
mm2
1.05
2890
24
100x60
75622100
m
1.32
5360
24
1.83
8040
12
2.15
10700
12
2.79
16100
6
75622400
3.43
21700
6
500x60
75622500
5.07
26800
6
600x60
75622600
5.87
32200
6
S
mm2
m
AxB
Ref.
100x35
75621100
150x35
75621150
1.33
4360
12
150x60
75622150
200x35
75621200
1.84
5790
12
200x60
75622200
300x35
75621300
2.48
8710
12
300x60
75622300
400x35
75621400
3.11
11600
6
400x60
500x35
75621500
4.68
14400
6
600x35
75621600
5.48
17300
6
System uses couplers with
85 and 100 depths.
Solid 85
Solid 100
P.G.
AxB
Ref.
200x85
75423200
300x85
400x85
/m
S
mm2
P.G.
m
AxB
Ref.
/m
2.42
15700
6
75423300
3.05
23600
6
200x100 75424200
2.61
18600
6
75423400
4.58
31400
6
300x100 75424300
3.24
28100
6
500x85
75423500
5.37
39300
6
400x100 75424400
4.82
37400
6
600x85
75423600
6.15
47200
6
500x100 75424500
5.60
46800
6
Material: Steel
Working temperature range: -50 ºC / +150 ºC
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
63
PEMSA-219-53-90-REV
27/11/09
11:44
Página 12
solid
H.D.G. Finish
M
E
P
A
S
PEMSA
Connects with couplers and comes
in 3 metre lengths.
Rapid Click Coupling System
with 35 and 60 depths.
Solid 35
Solid 60
H.D.G.
H.D.G.
/m
S
mm2
m
AxB
Ref.
/m
S
mm2
1.36
2870
24
100x60
75432100
m
1.73
5330
24
2.09
8040
12
2.45
10700
12
3.19
16100
6
75432400
4.74
21400
6
500x60
75432500
5.63
26800
6
600x60
75432600
6.51
32200
6
AxB
Ref.
100x35
75431100
150x35
75431150
1.73
4330
12
150x60
75432150
200x35
75431200
2.09
5790
12
200x60
75432200
300x35
75431300
2.81
8710
12
300x60
75432300
400x35
75431400
4.30
11500
6
400x60
500x35
75431500
5.18
14400
6
600x35
75431600
6.07
17300
6
System uses couplers with
85 and 100 depths.
Safety
edge
Solid 85
Solid 100
H.D.G.
AxB
Ref.
/m
S
mm2
H.D.G.
m
AxB
Ref.
/m
S
mm2
m
200x85
75433200
2.81
15700
6
300x85
75433300
4.29
23500
6
200x100 75434200
3.03
18600
6
400x85
75433400
5.17
31400
6
300x100 75434300
4.55
28000
6
500x85
75433500
6.06
39300
6
400x100 75434400
5.44
37400
6
600x85
75433600
6.95
47200
6
500x100 75434500
6.33
46800
6
Material: Steel
Working temperature range: -50 ºC / +150 ºC
P.G.
Well-finished
circular flange
Self-fix
cover
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
64
PEMSA-219-53-90-REV
27/11/09
11:44
Página 13
High load capacity. Thickness = 1.5 mm.
Perforated and solid tray manufactured from thicker material to withstand higher loads.
The entire range can be supplied on request.
Available in 60, 85 and 100 depths.
NEW
CHECK
AVAILABILITY
ø8x20
P.G. Finish
Perforated 60
Perforated 85
P.G.
Thickness
mm
1,5
AxB
Ref.
100x60
76122100
/m
S
mm2
m
2.22
5260
24
Perforated 100
P.G.
AxB
Ref.
/m
S
mm2
P.G.
m
S
mm2
m
4.49
18400
6
5.52
27700
6
400x100 76124400
6.56
37100
6
500x100 76124500
7.64
46400
6
S
mm2
m
AxB
Ref.
200x60
76122200
3.54
10500
12
200x85
76123200
4.06
15400
6
300x60
76122300
4.65
15800
6
300x85
76123300
5.17
23300
6
200x100 76124200
400x60
76122400
5.69
21200
6
400x85
76123400
6.21
31100
6
300x100 76124300
500x60
76122500
6.79
26500
6
500x85
76123500
7.32
39000
6
600x60
76122600
7.89
31900
6
600x85
76123600
8.42
46800
6
/m
H.D.G. Finish
Perforated 60
Perforated 85
H.D.G.
Thickness
mm
1,5
AxB
Ref.
100x60
76132100
/m
S
mm2
m
2.78
5230
24
Perforated 100
H.D.G.
AxB
Ref.
/m
S
mm2
H.D.G.
m
AxB
Ref.
/m
200x60
76132200
3.86
10500
12
200x85
76133200
4.42
15400
6
300x60
76132300
5.06
15800
6
300x85
76133300
5.62
23300
6
200x100 76134200
4.88
18400
6
400x60
76132400
6.19
21200
6
400x85
76133400
6.76
31100
6
300x100 76134300
6.01
27700
6
500x60
76132500
7.40
26500
6
500x85
76133500
7.97
39000
6
400x100 76134400
7.14
37100
6
600x60
76132600
8.59
31900
6
600x85
76133600
9.16
46800
6
500x100 76134500
8.33
46400
6
Material: Steel
Working temperature range: -50 ºC / +150 ºC
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
65
PEMSA-219-53-90-REV
27/11/09
11:44
Página 14
solid
NEW
M
E
P
A
S
CHECK
AVAILABILITY
PEMSA
Perforated 85
P.G. Finish
Perforated 100
P.G.
Thickness
mm
1,5
AxB
Ref.
/m
S
mm2
P.G.
m
S
mm2
m
4.85
18400
6
6.03
27700
6
400x100 76324400
7.21
37100
6
500x100 76324500
8.39
46400
6
S
mm2
m
AxB
Ref.
200x85
76323200
4.50
15400
6
300x85
76323300
5.68
23300
6
200x100 76324200
400x85
76323400
6.86
31100
6
300x100 76324300
500x85
76323500
8.03
39000
6
600x85
76323600
9.21
46800
6
/m
Perforated 85
H.D.G. Finish
Perforated 100
H.D.G.
Thickness
mm
1,5
Material: Steel
Working temperature range: -50 ºC / +150 ºC
AxB
Ref.
/m
S
mm2
H.D.G.
m
AxB
Ref.
/m
200x85
76333200
4.89
15400
6
300x85
76333300
6.17
23300
6
200x100 76334200
5.37
18400
6
400x85
76333400
7.45
31100
6
300x100 76334300
6.55
27700
6
500x85
76333500
8.73
39000
6
400x100 76334400
7.83
37100
6
600x85
76333600
10.00
46800
6
500x100 76334500
9.11
46400
6
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
66
PEMSA-219-53-90-REV
27/11/09
11:44
Página 15
NT
G
D
P
E
TE
E
PA
Perforated and embossed tray with Rapid Click Coupling System in 35 and 60 depths. Overall length is
3.05 metres.
N DIN
NEW
ø8x20
50
B
S
m
3000 m
Tray =
Useful
mm
L=3050
A
P.G. Finish
Perforated Click 35
Perforated Click 60
P.G.
P.G.
/m
S
mm2
m
AxB
Ref.
/m
S
mm2
0.70
2950
840
100x60
75822100
m
0.90
5420
720
1.29
8120
492
1.50
10800
360
2.23
16300
204
75822400
2.74
21600
180
500x60
75822500
3.73
27200
156
600x60
75822600
4.30
32400
72
AxB
Ref.
100x35
75821100
150x35
75821150
0.87
4440
504
150x60
75822150
200x35
75821200
1.26
5860
420
200x60
75822200
300x35
75821300
1.69
8810
252
300x60
75822300
400x35
75821400
2.46
11700
288
400x60
500x35
75821500
3.42
14500
240
600x35
75821600
3.98
17400
138
Material: Steel
Working temperature range: -50 ºC / +150 ºC
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
67
PEMSA-219-53-90-REV
27/11/09
11:45
Página 16
Joiner
P.G.
A
7
H.D.G.
35
71021005
0.039
71031005
0.042
Pack
unit
50
60
71022005
0.101
71032005
0.117
50
85
71023005
0.152
71033005
0.169
25
Ref.
/u
Ref.
/u
Central Joiner
P.G.
A
Ref.
ø7x45
Use only with
300-600 trays
H.D.G.
/u
Ref.
/u
Pack
unit
300
71020300
0.37
71030300
0.39
10
400
71020400
0.49
71030400
0.52
10
500
71020500
0.61
71030500
0.64
10
600
71020600
0.74
71030600
0.77
10
Divider plate
PA
TE
D
O
PA
S I S T E M A
CLICK
N TA
D
TE
NTE
P.G.
A
Ref.
A
H.D.G.
/m
m
25
67020610
0.26
/m
67030610
Ref.
0.30
60
50
67020611
0.38
67030611
0.43
48
80
67020612
0.53
67030612
0.60
36
The PG finish come packaged for correct storage.
HD and stainless steel finishing is supplied in plastic tensed strip
packaging for easy storage.
Length 3 m
Identification label
PLASTIC LABEL
Ref.
O
PA
N TA
D
TE
68000020
D
PA
TE
NTE
/u
0.002
Pack
unit
50
Working temperature range:: -20 ºC / +60 ºC
Stand off bracket
A
40
07 x 50
07 x 30
P.G.
A
40
N
A
Ref.
012 x 25
07 x 30
1000
H.D.G.
/u
Ref.
P.G.
67030539
0.17
67030541
0.24
10
350
67030540
0.32
67030542
0.35
10
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
68
Pack
unit
180
012 x 25
Material: Steel
Working temperature range: -50 ºC / +150 ºC
/u
PEMSA-219-53-90-REV
27/11/09
11:45
Página 17
Examples of assembly
2
4
PE
1
PE
MS
MS
A
A
PE
MS
PE
A
PE
MS
A
AS
ME
MS
A
P
1
1
2
1
2
3
2
1
PE
MS
4
PE
MS
A
A
1 DIN 603 M6x12 screw (page 107)
2 M6 serrated hexagon flange nut (p. 107)
3 Joiner coupler (page 68)
4 Central joiner (page 68)
69
PEMSA-219-53-90-REV
27/11/09
11:45
Página 18
Riser/Dropper
7
P.G.
A
Ref.
35
150
18
71021006
0.027
Ref.
Bolts not included
60
44
Ref.
71031006
P.G.
A
A
H.D.G.
/u
0.03
Pack
unit
4
H.D.G.
/u
71022006
/u
0.072
Ref.
71032006
/u
0.078
Pack
unit
4
Four units required for each riser/dropper
Protector
(for ends & edges)
ARMOUR PVC
Ref.
71000000
/m
m
0.15
10
Working temperature range::
-5 ºC / +60 ºC
Delivered in meters
Reducer
ø7x20
P.G.
A
A
0
10
H.D.G.
35
71021007
0.037
71031007
0.041
Pack
unit
4
60
71022007
0.074
71032007
0.081
4
A
Ref.
/m
m
060
73021060
0.47
73031060
0.62
24
100
73021100
0.74
73031100
0.84
24
150
73021150
1.02
73031150
1.14
12
200
73021200
1.30
73031200
1.60
12
300
73021300
2.11
73031300
2.30
6
400
73021400
2.74
73031400
3.68
6
500
73021500
4.22
73031500
4.54
6
600
73021600
5.01
73031600
5.40
6
Ref.
Cover
/m
Ref.
P.G.
A
S I S T E M A
CLICK
Length 3 m
Self-fix installation
(no bolts or nuts needed)
Material: Steel
Working temperature range: -50 ºC / +150 ºC
P.G.
H.D.G.
/m
Ref.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
Weight in kilos
70
/m
PEMSA-219-53-90-REV
27/11/09
11:45
Página 19
Examples of assembly
PE
MS
A
1
2
3
PE
MS
A
3
AS
ME
P
1
AS
ME
P
TRAY + COVER
=
SAFETY TRUNKING
IP 2X (Pemsaband Perforated)
4X (Pemsaband Solid)
PE
MS
A
1 DIN 603 M6x12 screw (page 107)
2 Edge protector (page 70)
3 M6 serrated hexagon flange nut (page 107)
71
PEMSA-219-53-90-REV
27/11/09
11:45
Página 20
Universal bracket
(Pemsaband)
Connector plate
Ø7
109
ø7x20
0
17
E.G.
P.G.
Ref.
H.D.G.
Ref.
/u
70420911
0.18
0.19
H.D.G.
Ref.
/u
64010062
Pack
unit
/u
70430911
E.B.
Ref.
0.01
Ref.
/u
64020062
0.009
/u
64030062
0.01
Pack
unit
50
10
For fixing BOXES, use M-5 bolts
Adjustable bend Click
NEW
S I S T E M A
CLICK
PA
TE
D
O
PA
N TA
D
TE
NTE
P.G.
AxB
Ref.
H.D.G.
/u
Ref.
P.G.
/u
Pack
unit
AxB
H.D.G.
Ref.
/u
Ref.
/u
Pack
unit
35 100x35
70028110
0.22
70038110
0.24
1
60 100x60
70028210
0.30
70038210
0.32
1
150x35
70028115
0.36
70038115
0.39
1
150x60
70028215
0.45
70038215
0.48
1
200x35
70028120
0.49
70038120
0.52
1
200x60
70028220
0.57
70038220
0.61
1
300x35
70028130
0.85
70038130
0.91
1
300x60
70028230
0.96
70038230
1.03
1
Colour Width m/roll
/u
Rejifix
● Self-adhesive for data cables and
telecommunications.
● Does not damage the cables. Re-usable.
Ref. nº
89011000 NEGRO
10 mm
25 m
Contents: 400 ml.
Ref.
68000052
/u
0.52
Pack
unit
1
Store and transport temperature range: -20 ºC / +40 ºC
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
72
1
Working temperature range: -5 ºC / +90 ºC
Zinc paint spray
Material: Steel
Working temperature range: -50 ºC / +150 ºC
0.14
Pack
unit
E.G.
E.B.
P.G.
H.D.G.
Spray
OR
ZINC
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-53-90-REV
27/11/09
11:45
Página 21
Examples of assembly
1
4
PE
MS
A
PE
MS
A
PE
M
SA
2
3
Connector plate
3
2
Suitable for 16-35 mm2
Al/Cu cables
90º
Adjustable
180º
4
1
PE
MS
A
AS
P
ME
1 DIN 603 M6x12 screw (page 107)
2 DIN 603 M6x20 screw + nut M6 (page 107)
3 Connector plate (page 72)
4 M6 serrated haxagon flange nut (page 107)
73
PEMSA-219-53-90-REV
27/11/09
11:45
Página 22
TE
Ref.
NT
D
G
P
E
P.G.
AxB
E
PA
90º Bend Click
N DIN
B
A
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
0.36
70030110
0.41
1
70020115
0.56
70030115
0.63
1
200x35
70020120
0.78
70030120
0.88
1
300x35
70020130
1.32
70030130
1.48
1
100x60
70020210
0.48
70030210
0.54
1
150x60
70020215
0.69
70030215
0.78
1
200x60
70020220
0.93
70030220
1.04
1
300x60
70020230
1.49
70030230
1.68
1
400x60
70020240
2.19
70030240
2.46
1
500x60
70020250
3.00
70030250
3.38
1
600x60
70020260
3.95
70030260
4.44
1
200x85
70020320
1.06
70030320
1.20
1
300x85
70020330
1.66
70030330
1.87
1
400x85
70020340
2.39
70030340
2.69
1
500x85
70020350
3.24
70030350
3.65
1
600x85
70020360
4.21
70030360
4.74
1
P.G.
A
D
PA
E
G
P
0.27
73030100
0.30
1
73020150
0.43
73030150
0.48
1
200
73020200
0.62
73030200
0.70
1
300
73020300
1.10
73030300
1.24
1
400
73020400
1.70
73030400
1.92
1
500
73020500
2.44
73030500
2.74
1
600
73020600
3.29
73030600
3.70
1
NT
D
G
P
N DIN
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
Ref.
/u
Pack
unit
70022110
0.47
70032110
0.52
1
70022115
0.69
70032115
0.78
1
200x35
70022120
0.94
70032120
1.06
1
300x35
70022130
1.15
70032130
1.73
1
100x60
70022210
0.60
70032210
0.68
1
150x60
70022215
0.83
70032215
0.93
1
200x60
70022220
1.09
70032220
1.22
1
300x60
70022230
1.70
70032230
1.91
1
400x60
70022240
2.43
70032240
2.74
1
500x60
70022250
3.29
70032250
3.71
1
600x60
70022260
4.28
70032260
4.82
1
200x85
70022320
1.23
70032320
1.38
1
300x85
70022330
1.85
70032330
2.09
1
400x85
70022340
2.60
70032340
2.93
1
500x85
70022350
3.48
70032350
3.92
1
600x85
70022360
4.48
70032360
5.05
1
P.G.
A
Ref.
E
G
D
P
N DIN
A
Weight in kilos
H.D.G.
/u
150x35
NT
74
P.G.
100x35
Tee Click Cover
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Pack
unit
73020100
Ref.
A
PA
/u
150
AxB
B
E
Ref.
100
E
PA
Tee Click
TE
H.D.G.
/u
NT
A
E
Pack
unit
70020110
N DIN
TE
/u
150x35
Ref.
E
Ref.
100x35
90º Bend Click Cover
TE
H.D.G.
/u
E.G.
E.B.
P.G.
H.D.G.
H.D.G.
/u
Ref.
/u
Pack
unit
100
73022100
0.36
73032100
0.40
1
150
73022150
0.55
73032150
0.62
1
200
73022200
0.77
73032200
0.87
1
300
73022300
1.31
73032300
1.48
1
400
73022400
1.98
73032400
2.23
1
500
73022500
2.77
73032500
3.12
1
600
73022600
3.69
73032600
4.15
1
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-53-90-REV
27/11/09
11:45
Página 23
TE
NT
G
D
P
E
E
PA
Examples of assembly
N DIN
Click System. It is not necessary to use joints toattach to the
accessories straight sections of
pemsaband.
6
2
1
5
DN20 precut conduit exits. In
heights 60 and 85 for installation
fittings or glands of M20, PG11 or
PG13.
5 90º Bend Click 60x300 (page 74)
6 90º Bend Click Cover 60x300 (page 74)
Covers accessories are overlap on
the tray, improving the tightness and
stiffness of the assembly.
4
3
1
2
1 Shoulder screw c/DIN 603 M6x12
3 Tee Click 35x300 (page 74)
2 Serrated hexagon flange nut M6
4 Tee Click Cover 300 (page 74)
(page 107)
In the schemes of the page does not show the covers straight to help better display accessories.
75
PEMSA-219-53-90-REV
27/11/09
11:45
Página 24
Side Entry Click
P.G.
AxB
TE
D
G
P
E
N DIN
A
B
Lets build a Tee at any place and trays can be
of different width (eg. 300-100)
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
0.29
70033110
0.32
1
70023115
0.35
70033115
0.39
1
200x35
70023120
0.41
70033120
0.46
1
300x35
70023130
0.53
70033130
0.59
1
100x60
70023210
0.35
70033210
0.40
1
150x60
70023215
0.41
70033215
0.47
1
200x60
70023220
0.47
70033220
0.53
1
300x60
70023230
0.59
70033230
0.67
1
400x60
70023240
0.71
70033240
0.80
1
500x60
70023250
0.83
70033250
0.94
1
600x60
70023260
0.95
70033260
1.07
1
200x85
70023320
0.54
70033320
0.61
1
300x85
70023330
0.66
70033330
0.75
1
400x85
70023340
0.78
70033340
0.88
1
600x85
70023350
0.90
70033350
1.02
1
600x85
70023360
1.02
70033360
1.15
1
Ref.
D
/u
Pack
unit
100
73023100
0.19
73033100
0.22
1
150
73023150
0.24
73033150
0.27
1
200
73023200
0.29
73033200
0.32
1
300
73023300
0.38
73033300
0.43
1
400
73023400
0.47
73033400
0.53
1
500
73023500
0.57
73033500
0.64
1
600
73023600
0.66
73033600
0.75
1
P.G.
AxB
NT
TE
E
D
PA
Ref.
G
N DIN
Ref.
G
P
N DIN
A
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
Pack
unit
0.58
70034110
0.65
1
70024115
0.84
70034115
0.94
1
200x35
70024120
1.12
70034120
1.26
1
300x35
70024130
1.78
70034130
2.00
1
100x60
70024210
0.73
70034210
0.82
1
150x60
70024215
0.98
70034215
1.10
1
200x60
70024220
1.26
70034220
1.42
1
300x60
70024230
1.92
70034230
2.16
1
400x60
70024240
2.70
70034240
3.04
1
500x60
70024250
3.61
70034250
4.06
1
600x60
70024260
4.64
70034260
5.23
1
200x85
70024320
1.40
70034320
1.58
1
300x85
70024330
2.06
70034330
2.32
1
400x85
70024340
2.84
70034340
3.20
1
500x85
70024350
3.75
70034350
4.22
1
600x85
70024360
4.78
70034360
5.38
1
P.G.
A
E
NT
TE
G
D
P
N DIN
A
76
/u
70024110
Ref.
Weight in kilos
Ref.
150x35
Crossover Click cover
Material: Steel
Working temperature range: -50 ºC / +150 ºC
H.D.G.
/u
100x35
B
PA
H.D.G.
/u
E
PA
P.G.
A
Crossover Click
E
Pack
unit
70023110
A
E
/u
150x35
ENT
P
E
Ref.
100x35
Side entry Click cover
T
H.D.G.
/u
NT
E
PA
Ref.
E.G.
E.B.
P.G.
H.D.G.
H.D.G.
/u
Ref.
/u
Pack
unit
100
73024100
0.46
73034100
0.52
1
150
73024150
0.80
73034150
0.77
1
200
73024200
1.11
73034200
1.05
1
300
73024300
1.82
73034300
1.73
1
400
73024400
2.66
73034400
2.55
1
500
73024500
3.63
73034500
3.51
1
600
73024600
4.72
73034600
4.61
1
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-53-90-REV
27/11/09
11:45
Página 25
G
E
NT
D
P
Click System. It is not necessary to use joints toattach to the
accessories straight sections of
pemsaband.
TE
E
PA
Examples of assembly
N DIN
4
3
1
2
3
Covers accessories are overlap on
the tray, improving the tightness and
stiffness of the assembly.
Side entry Click 60x300 (page 76)
4 Side entry Click cover 300 (page 76)
6
5
DN20 precut conduit exits.
In heights 60 and 85 for installation fittings
or glands of M20, PG11 or PG13.
1
Shoulder screw c/DIN 603 M6x12
2 Serrated hexagon flange nut M6
5
Crossover Click 85x300 (page 76)
6
Crossover Click cover (page 76)
(page 107)
In the schemes of the page does not show the covers straight to help better display accessories.
77
PEMSA-219-53-90-REV
27/11/09
11:45
Página 26
Inside Riser Click
P.G.
AxB
TE
D
G
P
E
N DIN
B
A
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
0.33
70035110
0.38
1
70025115
0.43
70035115
0.48
1
200x35
70025120
0.53
70035120
0.60
1
300x35
70025130
0.75
70035130
0.84
1
100x60
70025210
0.42
70035210
0.48
1
150x60
70025215
0.54
70035215
0.61
1
200x60
70025220
0.65
70035220
0.74
1
300x60
70025230
0.89
70035230
1.00
1
400x60
70025240
1.12
70035240
1.26
1
500x60
70025250
1.35
70035250
1.52
1
600x60
70025260
1.58
70035260
1.78
1
200x85
70025320
0.73
70035320
0.82
1
300x85
70025330
0.96
70035330
1.08
1
400x85
70025340
1.19
70035340
1.34
1
500x85
70025350
1.43
70035350
1.61
1
600x85
70025360
1.66
70035360
1.87
1
/u
/u
Pack
unit
D
G
73025100
0.13
73035100
0.15
1
150
73025150
0.19
73035150
0.21
1
200
73025200
0.25
73035200
0.28
1
300
73025300
0.36
73035300
0.40
1
400
73025400
0.47
73035400
0.53
1
500
73025500
0.59
73035500
0.66
1
600
73025600
0.70
73035600
0.79
1
P.G.
Ref.
NT
D
G
B
/u
Ref.
/u
Pack
unit
100x35
70026110
0.31
70036110
0.35
1
150x35
70026115
0.35
70036115
0.39
1
200x35
70026120
0.43
70036120
0.49
1
300x35
70026130
0.61
70036130
0.68
1
100x60
70026210
0.38
70036210
0.43
1
150x60
70026215
0.47
70036215
0.52
1
200x60
70026220
0.55
70036220
0.62
1
300x60
70026230
0.72
70036230
0.81
1
400x60
70026240
0.90
70036240
1.01
1
500x60
70026250
1.07
70036250
1.20
1
600x60
70026260
1.24
70036260
1.40
1
200x85
70026320
0.68
70036320
0.76
1
300x85
70026330
0.85
70036330
0.96
1
400x85
70026340
1.02
70036340
1.15
1
500x85
70026350
1.19
70036350
1.34
1
600x85
70026360
1.37
70036360
1.54
1
Outside Riser Cover Click
P.G.
A
Ref.
E
NT
TE
G
D
P
N DIN
A
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
78
H.D.G.
E
P
N DIN
The finished P.G. is given in plane for later assembly.
The finished H.D.G. is given shaped.
PA
Ref.
100
AxB
A
E
H.D.G.
E
PA
Ref.
Outside Riser Click
PA
P.G.
A
A
E
Pack
unit
70025110
N DIN
TE
/u
150x35
NT
P
E
Ref.
100x35
Inside Riser Cover Click
TE
H.D.G.
/u
NT
E
PA
Ref.
E.G.
E.B.
P.G.
H.D.G.
H.D.G.
/u
Ref.
/u
Pack
unit
100
73026100
0.28
73036100
0.32
1
150
73026150
0.40
73036150
0.45
1
200
73026200
0.52
73036200
0.59
1
300
73026300
0.76
73036300
0.85
1
400
73026400
0.99
73036400
1.12
1
500
73026500
1.23
73036500
1.39
1
600
73026600
1.47
73036600
1.65
1
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-53-90-REV
27/11/09
11:45
Página 27
Examples of assembly
NEW PIECES
Inside Riser
Outside Riser
Heights 35, 60, 85
G
PA
NT
D
P
E
TE
E
Click System. It is not necessary to use joints toattach to the
accessories straight sections of
pemsaband.
N DIN
4
2
3
3 Outside Riser Click
60x200 (page 78)
1
4 Outside Riser Cover
Click 200 (page 78)
5 Inside Riser Click 60x200
Covers accessories are overlap on
the tray, improving the tightness and
stiffness of the assembly.
(page 78)
6 Inside Riser Cover
Click 200 (page 78)
6
5
DN20 precut conduit exits.
In heights 60 and 85 for installation fittings
or glands of M20, PG11 or PG13.
1
Shoulder screw c/DIN 603 M6x12 (page 107)
2 Serrated hexagon flange nut M6 (page 107)
79
PEMSA-219-53-90-REV
27/11/09
11:45
Página 28
Wall assembly
Horizontal
Rejiband
Security
Pemsa
Rejiband
Security
Pemsa
Rejiband
Security
Pemsa
Medium Duty
Cantilever
Rejiband
Security
Pemsa
Medium Duty Cantilever
on channel
Omega support
Omega support
on channel
580/1180 N
580/1180 N
1200/2530 N
1200/2530 N
100
page 82
page 82
page 84
page 84
150
page 82
page 82
page 84
page 84
200
page 82
page 82
page 84
page 84
300
page 82
page 82
page 84
page 84
400
page 84
page 84
500
page 84
page 84
600
page 84
page 84
Admissible
load
❶
TRAY WIDTH:
❶ Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug and supports
reinforced with the PEMSA structural reinforcement.
80
PEMSA-219-53-90-REV
27/11/09
11:45
Página 29
Horizontal
Heavy Duty Cantilever
Heavy Duty Cantilever
on channel
1840/2490 N
1840/2490 N
Inclined
Vertical
Adjustable Medium Duty
Cantilever
Stand off bracket
1210/2060 N
1000 N
R E I N F O R C E D S U P P O R T S G R E AT E R
L O A D - B E A R I N G C A PA C I T Y
page 84
page 32
page 84
page 32
page 84
page 32
page 84
page 84
page 84
page 32
page 84
page 84
page 84
page 32
page 84
page 84
page 84
page 32
page 84
page 84
page 84
page 32
NOTE!!
E
FIT SUITABL
E WALL!
PLUGS IN TH
81
PEMSA-219-53-90-REV
27/11/09
11:45
Página 30
Omega bracket
O
PA
N TA
D
TE
ø11x30
D
PA
TE
NTE
B
11
50
7x20
A
● Including Omega plug (preassembled) and Omega protector. ● Guarantees and improves the performance of the OMEGA
SUPPORTS. ● Makes fitting easier and aids
proper fitting of the support.
N
P.G.
AxB
Ref.
H.D.G.
/u
Ref.
Pack
unit
/u
1180 100x145
62021103
0.26
62031103
0.28
5
1040 150x145
62021153
0.30
62031153
0.32
5
1150 200x145
62021203
0.47
62031203
0.50
5
870 300x145
62021303
0.60
62031303
0.63
5
580 400x145
62021403
0.73
62031403
0.78
5
Working temperature range: -5 ºC / +90 ºC
Examples of assembly
1 Hexagonal set screw M10x35 (page 107)
2 Washer M10 (page 107)
3 Safety plug
3
2
1
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
82
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-53-90-REV
27/11/09
11:45
Página 31
Others Omega System Products
Omega ceiling bracket
N
P.G.
A
Ref.
/u
Pack
unit
760
100
62022103
0.42
62032103
0.44
4
D
PA
960
150
62022153
0.62
62032153
0.66
4
800
200
62022203
0.67
62032203
0.72
4
650
300
62022303
0.82
62032303
0.86
4
340
400
62022403
0.94
62032403
0.99
4
NTE
200
TE
O
PA
Ref.
N TA
D
TE
H.D.G.
/u
ø7x20
50
11
● Including Omega plug (preassembled) and Omega
protector. ● Guarantees and improves the performance of the
OMEGA SUPPORTS. ● Makes fitting easier and aids
proper fitting of the support.
A
Omega pendant bracket
P.G.
A
50
Ref.
H.D.G.
/u
Ref.
/u
Pack
unit
300
62021303
0.42
62031303
0.45
5
400
62021403
0.63
62031403
0.67
5
500
62021503
0.70
62031503
0.74
5
600
62021603
0.84
62031603
0.88
5
A
Including Omega plug (preassembled) and
new Omega protector.
ø7x20
11
For further information about these products and the asembly to ceiling, please consult pages 92 to 95.
83
PEMSA-219-53-90-REV
27/11/09
11:45
Página 32
Medium Duty Cantilever
P.G.
30
35
P.G.
AxB
NEW!
A
B
7X20
PA
TE
/u
Pack
unit
100x54
62025103
0.18
2530
4
150x54
62025153
0.23
1890
4
200x54
62025203
0.38
1560
4
300x54
62025303
0.53
1240
4
400x92
62025403
0.76
1220
4
500x92
62025503
0.93
1210
4
600x92
62025603
1.09
1200
4
D
O
PA
E N TA
D
T
N
Ref.
NTE
Medium Duty Cantilever
40
H.D.G.
12X16
30
AxB
NEW!
30
H.D.G.
N
Ref.
A
B
/u
S.S. 316
Ref.
N
/u
Pack
unit
100x50
62035103
0.23
2060
62065103
0.19
1930
4
150x50
62035153
0.28
1870
62065153
0.24
1720
4
200x50
62035203
0.33
1780
62065203
0.28
1610
4
300x50
62035303
0.42
1690
62065303
0.37
1500
4
400x77
62035403
0.77
1840
62065403
0.70
1580
4
500x77
62035503
1.92
1640
62065503
0.84
1380
4
600x77
62035603
1.06
1210
62065603
0.98
1180
4
35
PA
TE
D
O
PA
7X20
N TA
D
TE
NTE
Heavy Duty Cantilever
12X16
40
AxB
30
H.D.G.
N
Ref.
/u
30
NEW!
A
117
B
Pack
unit
300x77
63033303
0.79
2490
4
400x77
63033403
0.99
2160
4
500x77
63033503
1.19
2000
4
600x77
63033603
1.38
1840
4
7X20
35
O
PA
N TA
D
TE
D
PA
TE
NTE
Adjustable Medium Duty Cantilever
Ø12
46
AxB
47
104
A
NEW!
B
PA
TE
7X20
35
Pack
unit
100x74
62037103
0.54
2060
4
150x74
62037153
0.59
1870
4
200x74
62037203
0.63
1780
4
300x74
62037303
0.73
1690
4
400x74
62037403
1.08
1840
4
500x74
62037503
1.23
1640
4
600x74
62037603
1.37
1210
4
Delivered unassembled. All pieces included.
NTE
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
84
N
/u
D
O
PA
N TA
D
TE
H.D.G.
Ref.
P.G.
H.D.G.
S.S.
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
PEMSA-219-53-90-REV
27/11/09
11:45
Página 33
Exemples of assembly
SUPPORTS
6
5
4
Wall mounting
3
1
5
2
1 Medium duty cantilever
P.G.
2 Medium duty cantilever
Channel mounting
4
H.D.G.
3 Heavy duty channel 41x21 H.D.G. (page 104)
4 Hexagonal screw M10 (page 107)
5 Washer M10 (page 107)
6 Channel nut M10 (page 104)
PA
TE
D
O
PA
DISTINCT CHARACTERISTICS
N TA
D
TE
Reinforced Strength
NTE
The bracket has been designed with
curves for greater strength and load
bearing capacity.
Click System
Fixing pin for quickly
securing the tray thus
avoiding movement in any
direction.
Lateral Grooves
Increases the load resistance
of the bracket and reinforces
the area supporting the tray.
PA
TE
D
O
PA
N TA
D
TE
NTE
Side Pressing
Fully embossed side
enhances the strength of the
bracket and improves it’s
load capacity.
Back Pressing
Embossed back increases the resistance of
the bracket and prevents any bending.
85
PEMSA-219-53-90-REV
27/11/09
11:45
Página 34
Ceiling assembly
With threaded rods
Admissible
load
❶
690 N
690 N
1275 N
100
page 88-91
page 88-91
page 88-91
150
page 88-91
page 88-91
page 88-91
TRAY WIDTH:
200
page 88-91
300
400
500
600
+ EASY CABLE LAYING
❶Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug.
86
PEMSA-219-53-90-REV
27/11/09
11:45
Página 35
With threaded rods
1760/2760 N
800 N
1760/2000 N
1760/3320 N
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
page 88-91
4310/4890 N
page 88-91
page 88-91
page 88-91
+ ASSEMBLY TIME SAVING
NOTE!!
E PLUGS
FIT SUITABL
ING!
IN THE CEIL
87
PEMSA-219-53-90-REV
27/11/09
11:45
Página 36
Horizontal angle hanger
Vertical angle hanger
A
PASSIVATED
PASSIVATED
N
A
A
Ref.
/u
N
Pack
unit
A
Ref.
Pack
unit
690
1.5-5
68000721
0.05
100
690
1.5-5
68000731
0.04
100
690
4-10
68000722
0.05
100
690
4-10
68000732
0.04
100
Ceiling bracket
Variable ceiling rod bracket
H.D.G.
P.G.
N
Ref.
2760
50
/u
67030060
/u
0.094
N
Pack
unit
10
Ref.
1275
67030061
/u
0.15
Pack
unit
1
Use with M8/M10 rods
40
Rod connector M8
E.B.
Ref.
30
67020067
/u
0.016
Pack
unit
50
Threaded M6/M8/M10
N
E.G.
AxB
67010140
0.12
67020140
0.12
Pack
unit
50
67010141
0.24
67020141
0.24
50
4000 M8x500
M8
4000 M8x1000
-
-
67020044
0.16
50
-
-
67020045
0.32
50
M10 5000 M10x1000
-
-
67020145
0.49
50
Ref.
M6
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
88
E.B.
1980 M6x500
1980 M6x1000
E.G.
E.B.
P.G.
H.D.G.
/u
Ref.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
/u
PEMSA-219-53-90-REV
27/11/09
11:45
Página 37
Examples of assembly
1
1
5
3
2
4 1
4 1
6
7
1
5
2
6
Threaded rod M8 (page 88)
Fitting to ceiling (page 88)
3 M10x40 screw (page 107)
4 Threaded rod M10 (page 88)
7
Fitting to sloping ceiling (page 88)
Beam clamp hanging assembly (p. 90)
Threaded rod M-10 (page 88)
89
PEMSA-219-53-90-REV
27/11/09
11:45
Página 38
Mesh channel
N
4890
200
63022203
0.23
63032203
0.24
10
2540
4740
300
63022303
0.33
63032303
0.34
10
1760
4600
400
63022403
0.42
63032403
0.45
10
-
4460
500
63022503
0.52
63032503
0.55
10
-
4310
600
63022603
0.62
63032603
0.65
10
7x20
/u
Ref.
/u
Working Temperature range with safety plug: -5 ºC / +105 ºC
E N TA
D
PA
TE
D
O
PA
Ref.
NTE
Safety plug included
for better performance on
widths 200-400
Fitting with one rod
Fitting with two rods
PE
MS
A
PE
MS
A
Beam clamp hanging assembly
(*) The Loads depends of type of assembly. Please
view the below pictures.
25
NS
NS
KG
KG
2000 N
950 N
NS
KG
2000 N
≥ 30º
45º
E.B.
N
Ref.
(*)
67020048
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
90
/u
0.34
Pack
unit
1
Pack
unit
3320
A
T
H.D.G.
2 rods
25
25
P.G.
A
1 rod
NS
KG
NS
2500 N
700 N
KG
NS
KG
800 N
E.B.
Electrolytic Bichromate UNE - EN 12329
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-91-108-REV
27/11/09
11:48
Página 1
Examples of assembly
(A) Fitting with one rod
LAYING
+ EASY CABLE
ME SAVING
+ ASSEMBLY TI
1
3
I
PE
MS
A
1
II
4
4
TURN & CLICK
Safety plug included
for better performance
on widths 200-400
2
3
3
NOTE!
I
II
Safety plug included!
(B) Fitting with two rods
5
5
PE
MS
A
4
6
1 Threaded rod M10 (page 88)
2 Safety plug
3 Hexagonal nut M10 + washer (page 107)
4 Mesh channel (page 90)
5 Threaded rod M8 (page 88)
6 Hexagonal nut M8 (page 107)
Cost comparison
(A)
(B)
40
100
91
PEMSA-219-91-108-REV
27/11/09
11:48
Página 2
Fitting to ceiling
Omega System
❶
Bending moment 1 ❷
Bending moment 2 ❷
Vertical Force
340/760 N
2100 N
3370 N
3370 N
-
120 Nm
410 Nm
410 Nm
-
110 Nm
150 Nm
150 Nm
100
page 94-95
page 94-95
page 94-95
page 94-95
150
page 94-95
page 94-95
page 94-95
page 94-95
200
page 94-95
page 94-95
page 94-95
page 94-95
300
page 94-95
page 94-95
page 94-95
page 94-95
400
page 94-95
page 94-95
page 94-95
page 94-95
TRAY WIDTH:
500
600
❶ Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170%
without ever reaching the collapse point. Guaranteed only for our hanger with security plug and supports
reinforced with the PEMSA structural reinforcement.
92
PEMSA-219-91-108-REV
27/11/09
11:48
Página 3
reinforced pendant bracket
3780 N
4270 N
7270 N
3780 N
360 Nm
930 Nm
930 Nm
360 Nm
430 Nm
730 Nm
730 Nm
430 Nm
REINFORCED SUPPORTS GREATER
LOAD-BEARING CAPACITY
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
page 96-97
NOTE!!
E
FIT SUITABL
❷ Values obtained in accordance International Standard UNE-EN 61537
L!
(Section H) relating to the information for safe installation of trays with PLUGS IN THE WAL
horizontal supports. (See page 111)
93
PEMSA-219-91-108-REV
27/11/09
11:48
Página 4
Omega ceiling bracket
N
P.G.
A
Ref.
Pack
unit
100
62022103
0.42
62032103
0.44
4
D
PA
/u
760
960
150
62022153
0.62
62032153
0.66
4
800
200
62022203
0.67
62032203
0.72
4
650
300
62022303
0.82
62032303
0.86
4
340
400
62022403
0.94
62032403
0.99
4
D
PA
NTE
200
TE
Ref.
O
N TA
TE
H.D.G.
/u
ø7x20
50
11
A
● Including Omega plug (preassembled) and Omega
protector. ● Guarantees and improves the performance of the
OMEGA SUPPORTS. ● Makes fitting easier and aids
proper fitting of the support.
Omega pendant bracket
P.G.
A
50
Ref.
H.D.G.
/u
Ref.
62021303
0.42
62031303
0.45
5
400
62021403
0.63
62031403
0.67
5
500
62021503
0.70
62031503
0.74
5
600
62021603
0.84
62031603
0.88
5
A
11
94
P.G.
Pack
unit
300
Including Omega plug (preassembled) and
new Omega protector.
ø7x20
Material: Steel
Working temperature range: -5 ºC / +90 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
/u
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-91-108-REV
27/11/09
11:48
Página 5
Examples of assembly
4
Rejiband
Security
200
1
Pemsa
A
SM
EP
100/400
LOAD
According to Omega Ceiling bracket table.
300/600
1
2
Rejiband
Security
Pemsa
100/400
Vertical Force
2100
Bending Moment 1
120
Bending Moment 2
110
SA
M
PE
6
5
1
300/600
4
2
Rejiband
Security
Pemsa
100/400
Vertical Force
3370
Bending Moment 1
410
Bending Moment 2
150
5
1
3
SA
M
PE
300/600
4
3
6
Rejiband
3
1
2
3
4
5
6
M10x35 screw+washer (page 107)
M10x20 screw+washer+nut (page 107)
M10x60 screw+washer+nut (page 107)
Safety plug
Omega bracket 100 (page 34)
Omega Click bracket 100/300 (page 34)
Rejiband
Security
4
Pemsa
100/400
Security
Pemsa
100/400
Rejiband
Security
Pemsa
100/400
Vertical Force
3370
Bending Moment 1
410
Bending Moment 2
150
95
PEMSA-219-91-108-REV
27/11/09
11:48
Página 6
Heavy duty pendant drop
N
BM 1
BM 2
H.D.G.
A
Ref.
150
Pack
unit
3780
360
430
500
67030660
1.51
1
3780
360
430
1000
67030661
2.47
1
N
BM 1
BM 2
A
ø12x20
80
A
/u
115
Double heavy duty pendant drop
H.D.G.
Ref.
150
Pack
unit
4270
930
730
500
67030662
2.48
1
4270
930
730
1000
67030663
4.40
1
N
BM 1
BM 2
A
ø12x20
80
A
/u
115
Heavy duty pendant channel
21
A
P.G.
Ref.
41
/u
ø 8,5
50
3780
360
430
500
67030646
0.87
1
3780
360
430
1000
67030647
1.76
1
20x11
Heavy duty pendant boss
140
47
P.G.
106
108
Ø 12x20
Ref.
67030645
/u
0.62
Pack
unit
1
106
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
96
Pack
unit
P.G.
Pre-galvanised UNE - EN 10142
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-91-108-REV
27/11/09
11:48
Página 7
Examples of assembly
1
5
3
2
4
3
2
1 M8x60 screw+nut+serrated washer (page 107)
2 M10x20 screw (page 107)
3 Channel nut (page 104)
4 Heavy duty cantilever (page 84)
5 Heavy duty pendant channel (page 96)
97
PEMSA-219-91-108-REV
27/11/09
11:48
Página 8
8
5
10
4
9
6
1
3
7
1 Inducanal (page 99)
2 Central hanging plate 7 (page 100)
3 Threaded rod M6 (page 100)
4 Joiner 60 (page 100)
5 DIN 603 M6x12 screw (page 107)
6 90º bend (page 100)
7 Universal bracket (page 100)
8 Cover (page 100)
9 Omega bracket (page 34)
10 M6 serrated hexagon flange nut (page 107)
98
2
PEMSA-219-91-108-REV
27/11/09
11:48
Página 9
B
S
A
ø8x20
90
30
ø23
3000
ø21
120
110
100
90
Ref.
3600
60x60
80
P.G.
AxB
75122060
/u
1.11
Kg
S
70
Pack
unit
60
24
50
Recommended distance
between supports: 2 m.
40
1.5
1.6
1.7
1.9
2.0
Metres
60
Safety edge
1.8
Wellfinished
side/edge
Self fix lid
cover
Push
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
P.G.
Pre-galvanised UNE - EN 10142
Values obtained from test according to the UNE-EN 61537 standard, with a safety coefficient of 170% without ever reaching the collapse point.
Tray section joints be situated at a support distance of between L/4 and L/5, L being the distance between supports.
At completed tray extreme ends, tray support distance should be a maximum of 0,4L without any type of joint.
99
PEMSA-219-91-108-REV
27/11/09
11:48
Página 10
Inducanal cover
P.G.
A
/m
m
0.47
24
Ref.
73021060
60
Length 3 m.
A
Joiner
P.G.
A
Ref.
7
71022005
60
Central hanging plate 7ø 7x14
0.101
50
E.G.
Type
35
Ref.
Pack
unit
/u
67010144
M6
Pack
unit
/u
0.032
20
59
Threaded rod M6
A
N
E.G.
AxB
Ref.
B
Universal bracket
(Pemsaband)
E.B.
/u
Ref.
67010140
0.12
67020140
0.12
50
1980 M6x1000
67010141
0.24
67020141
0.24
50
P.G.
H.D.G.
Ref.
/u
70420911
0.175
Ref.
/u
70430911
0.194
Pack
unit
10
For fixing BOXES, use M-5 bolts
0
17
90º Bend
B
P.G.
AxB
Ref.
A
60x60
/u
71022062
90º Bend cover
Ref.
60
0.13
Pack
unit
1
P.G.
A
72020062
/u
0.027
Pack
unit
1
A
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
100
Pack
unit
1980 M6x500
109
ø7x20
/u
E.G.
E.B.
P.G.
H.D.G.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
Pre-galvanised UNE - EN 10142
Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-91-108-REV
27/11/09
11:48
Página 11
Examples of assembly
3
1
2
Press fit assembly (no bolts no nuts required).
Cover remains fixed even in vertical position.
4
2
1
1
6
5
1
7
2
8
1 M6 serrated hexagon flange nut (p 107)
2 DIN 603 M6x12 screw (page 107)
3 Joiner 60 (page 100)
4 Threaded rod M6 (page 100)
5 Central hanging plate 7 (page 100)
6 Universal bracket (page 100)
7 90º bend (page 100)
8 Omega bracket (page 34)
101
PEMSA-219-91-108-REV
27/11/09
11:48
Página 12
Supports &
structures
In any industrial, electrical, pneumatic, hydraulic or other such installation, the support system
(supports and structures) is at least as important as the conduits themselves.
If the support system is not suitable, the whole installation will fail, with the attendant service cost.
To avoid this, and to achieve a satisfactory installation from the outset, Pemsa
has developed a comprehensive range of SUPPORTS according to the EN 61537 standard,
with a STRUCTURE system made in steel with Sendzimir
and Hot-dip Galvanisation protection. This range, with its accessories,
makes weld-free setting up and modifying easy for all the structures
commonly found in such industrial installations.
PA
TE
D
O
PA
N TA
D
TE
NTE
102
PEMSA-219-91-108-REV
27/11/09
11:48
Página 13
List of supports and usage modes
WALL MOUNTING
CEILING MOUNTING
LOAD
*
Use
Page
LOAD
*
Use
250
R
32
250
R
Page
32
40
R
510
(1)
R
1760
2760
32
R
580
1180
(2)
40
P
R
34
40
1275
82
P
88
P
88
R
1210
2530
(2)
36
P
890
(2)
40
84
M6
M8
M10
R
1210
2060
R
36
P
1890
5000
84
R
40
P
88
I
100
R
40
R
1210
2060
(2)
36
P
700
84
R
1840
2490
R
36
P
(1)
1760
3320
42
P
84
R
R
Rejiband
P
Pemsaband
I
Inducanal
*
Per support, in Newtons, as
per IEC 61537
1760
4890
(1)
42
P
R
340
960
(1)
90
46
P
R
2100
3370
94
46
P
R
(1) Security plug included
(2) With structural reinforcement
90
94
48
3780
P
96
103
PEMSA-219-91-108-REV
27/11/09
11:48
Página 14
Heavy duty channel 41x41
ø11x20
50
P.G.
e
mm
Ref.
2.5
67030053
e
mm
Ref.
2.5
67030052
H.D.G.
/u
2.61
S.S. 316
Ref.
67030057
/u
2.64
Ref.
67060057
/u
2.53
Pack
unit
3
11
41
e
22
41
Length 3 m.
Heavy duty channel 41x21
ø11x20
50
11
P.G.
H.D.G.
/u
1.77
S.S. 316
Ref.
67030055
/u
1.80
Ref.
67060055
e
20,5
22
41
Length 3 m.
Light duty channel 41x41
Ø11x20
50
11
41
P.G.
e
mm
Ref.
1.5
67030074
/m
m
1.61
3
/m
m
1.14
3
e
22
41
Length 3 m.
Light duty channel 41x21
Ø11x20
50
P.G.
e
mm
Ref.
1.5
67030075
11
20,5
e
22
Length 3 m.
Channel nut
41
E.G.
Type
67020055
0.020
-
-
Pack
unit
100
67020058
0.025
67060058
0.03
100
Ref.
M6
M10
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
104
S.S. 316
/u
Ref.
/u
E.G.
P.G.
Electrogalvanised UNE - EN 12329
Pre-galvanised UNE - EN 10142
H.D.G.
S.S.
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
/u
1.73
Pack
unit
3
PEMSA-219-91-108-REV
27/11/09
11:48
Página 15
TECHNICAL DATA
Y
Axis x-x
Dimensions
Jx cm
X
X
4
Wx cm
Axis y-y
3
r xx
Jy cm
4
Wy cm3
r yy
41x41x2.5
6.11
3.00
1.42
9.15
4.41
1.75
41x21x2.5
0.95
0.95
0.71
5.29
2.55
1.66
r xx
Jy cm
Y
Y
Axix x-x
Dimensions
Jx cm
X
X
4
Wx cm
Axis y-y
3
4
Wy cm3
r yy
41x41x1.5
4.25
2.03
1.45
6.10
2.94
1.75
41x21x1.5
0.73
0.67
0.74
3.60
1.73
1.64
Y
J - Moment of inertia
W - Section modules
r - Radius of gyration
Q1
L
41x41x2.5
41x21x2.5
41x41x1.5
41x21x1.5
Q1
Q2
Q1
Q2
Q1
Q2
Q2
Q2
500
719
3620
230
2010
308
3050
200
1850
1000
360
2900
78
1065
79
2010
55
1230
1500
206
2160
35
570
35
-
25
-
2000
115
1580
20
-
20
-
13
-
L
Q2
L
mm
L - Distance between supports in mm.
L
Q1 - Uniformly distributed load expressed in DN=kg for f=
250
Q2 - Máximum load on column expressed in DN=kg
105
PEMSA-219-91-108-REV
27/11/09
11:48
Página 16
Accesories for assembly on channel.
1
2
3
4
5
6
7
8
9
M
Description
Finish
/u
Pack
unit
1
Angle bracket
67030201
H.D.G.
0.15
1
2
Angle bracket
67030202
H.D.G.
0.32
1
3
Splice plate N3
67030205
H.D.G.
0.24
1
4
Tee plate N4
67030203
H.D.G.
0.31
1
5
Tee plate N5
67030204
H.D.G.
0.45
1
6
Clamp 21
67030206
H.D.G.
0.29
1
7
Clamp 41
67030207
H.D.G.
0.36
1
8
Channel floor boss
67030064
H.D.G.
1.45
1
9
Channel beam clamp 67030101
E.G.
0.35
2
Material: Steel
Working temperature range: -50 ºC / +150 ºC
Weight in kilos
N= Load capacity per support in Newtons
as per Standard UNE-EN 61537
106
Ref.
E.G.
Electrogalvanised UNE - EN 12329
H.D.G. Hot-dip galvanised UNE - EN-ISO 1461
PEMSA-219-91-108-REV
27/11/09
11:48
Página 17
Screws
E.G.
Washer
Type
Ref.
E.B.
/u
Pack
unit
0.002
67020063
0.002
67060063
0.002
100
67020061
0.002
67020013
0.004
67060064
0.002
100
PASSIVATED
/u
M8
67020084
0.001
100
67020086
0.001
100
E.G.
Type
Ref.
M10x20
/u
67020065
Hexagonal cone point screw
0.03
Ref.
M10x20
E.G.
/u
67020098
50
Pack
unit
0.023
E.B.
Ref.
Pack
unit
E.B.
Type
/u
Pack
unit
M10
Allen screw
10
H.D.G.
/u
Ref.
S.S. 316
/u
Ref.
/u
Pack
unit
M6x12
67010099
0.005
-
-
67030099
0.005
-
-
100
M6x20
67010100
0.007
67020100
0.007
67030100
0.007
67060100
0.007
100
Hexagonal set screw
E.G.
Type
Ref.
Serrated hexagon
flange nut
Type
M6
Hexagonal nut
64010059
0.003
67020054
0.008
100
67020092
0.040
100
M10x20
67020059
0.023
100
M10x35
67020077
0.029
100
M10x60
67020010
0.042
100
Ref.
64020059
H.D.G.
/u
0.003
E.G.
Type
Ref.
Working temperature range: -50 ºC / +150 ºC
Pack
unit
M8x65
E.B.
/u
/u
M6x15
E.G.
Ref.
Weight in kilos
/u
67020083
Ref.
Ref.
Ref.
M8
Type
Type
/u
M10
Serrated washer
Shoulder screw
c/DIN 603
S.S. 316
Ref.
Ref.
64030059
S.S. 316
/u
0.003
E.B.
/u
Ref.
Ref.
64060059
/u
0.003
Pack
unit
50
S.S. 316
/u
Ref.
/u
Pack
unit
M8
67020095
0.005
67020062
0.005
67060062
0.005
100
M10
67020079
0.008
67020014
0.008
67060014
0.008
100
E.G.
E.B.
Electrogalvanised UNE - EN 12329
Electrolytic Bichromate UNE - EN 12329
H.D.G.
S.S.
Hot-dip galvanised UNE - EN-ISO 1461
Passivated stainless steel AISI 316
107
PEMSA-219-91-108-REV
27/11/09
11:48
Página 18
Examples of assembly
2
1
3
4
5
1
1
1 Highly reinforced rail (p. 104)
2 Clamp 41 (page 106)
3 M8/10 rod (page 40)
4 M10x20 Allen screw (page 107)
5 Vertical support (page 106)
6 M10 rail nut (page 104)
7 Angle Bracket (page 106)
6
7
1
7
5
108
5
5
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 1
Recommendations
for the correct installation
of cable trays
(BS-EN 61537, BS 20.460, REBT 2002, ITC-BT 20 and 21) Standards
1.- LOCATION
3.1.- DISTANCE BETWEEN TRAYS
Must NOT be installed under water, steam, gas, tubing,
etc.
For correct cable ventilation, at least the minimum distance indicated in the drawing must be maintained.
Security
Pemsa
Rejiband
Security
Pemsa
Rejiband
Security
Pemsa
Rejiband
Security
Pemsa
300
Rejiband
2.- PROTECTION
22
5
The trays are for conveying cables, NOT FOR PROTECTING THEM.
In the majority of installations, the characteristics of current cables makes it unnecessary to protect them.
If necessary, use the appropriate covers.
3.- VENTILATION
Cables heat up while being used due to the passage of
current.
At the same ambient temperature and power, this heating can increase according to the type of tray being
used (open or closed).
With less ventilation, a greater cable cross section is
required and, as a result, cost increases.
Maximum ventilation: rejiband® or ladder-type trays.
Medium ventilation: perforated metal sheet trays.
Minimum ventilation: solid metal sheet trays.
3.2.- DISTANCE TO WALLS
When trays are fastened to a wall on supports, a separation of at least 20 mm must be maintained between
the tray and the wall in order to allow for cable ventilation.
At Pemsa, all wall supports have a total length of 50
mm more than the width of the tray to be installed,
thereby complying with legislation in force.
Example: A 300 support has a length of 350 mm.
50
The use of solid bottom trays is, in most cases, due to
aesthetic criteria.
L
109
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 2
4.- MARKINGS
Trays should facilitate labelling through markings.
les
cab
a
t
da
ce)
Voie 7/3
any
Lin nt 7 omp
C
a
(
Pl
pemsa
5.- SUPPORTS
These are fundamental in a tray installation. If they are
not suitable, the whole installation will be flawed. The
following factors should be borne in mind when choosing them:
• The load-bearing capacity of the support.
• Its corrosion resistance.
• Ease of installation.
The recommended distance between supports or bearing points is normally 1500 mm. When this distance is
changed, the performance of the tray changes.
When attaching the supports to the wall or ceiling, particular attention must be paid to the fixings used, making sure it is right for the characteristics of the building.
The use of CHANNEL (page 104) gives better load distribution, whilst also facilitating adjustment.
0
150
0
150
0
150
6.- RECOMMENDED POSITIONS FOR SUPPORTS
( Same for rejiband® steel wire cable trays. )
Rejiband
300 máx. (400/600)
150 máx. (100/300)
Only
heavy loads
Rejiband
300 máx. (400/600)
150 máx. (100/300)
Only
heavy loads
Rejiband
300 máx. (400/600)
150 máx. (100/300)
Rejiband
300 máx. (400/600)
150 máx. (100/300)
110
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 3
400
max.
Rejiband
300 max. (400/600)
150 max. (100/300)
400
max.
400
max.
400
max.
Rejiband
300 max. (400/600)
150 max. (100/300)
400
max.
400
max.
0
40 ax.
m
400
max.
7.- TRAY AND SUPPORT DEFORMATION
The weight of cables deforms trays, the most visible point being
in the centre between supports.
L
The allowable value (F) of deformation is purely aesthetic, always
taking care not to exceed the values indicated by the manufacturer, which, in accordance with international standard IEC
61537, should be as follows:
F max=L/100 mm.
F
L
F
On supports, maximum F deformation and twisting occurs at the ends.
The standard requires that the maximum F =
L/20 mm.
The deformation, F is called deflection, and is
expressed in mm.
8.- INFORMATION FOR A SAFE INSTALLATION OF PENDANTS WITH
CANTILEVER BRACKETS (ANNEX H. IEC 61537)
M1
The SWL (Safe Working Load) of a pendant with cantilever brackets is determined by the following conditions:
F
a. The connection of the pendant to the ceiling; defined by the Bending
Moment 1 (M1).
b. The connection of the cantilever bracket and the pendant; defined by
Bending Moment 2 (M2).
M2
c. The pendant itself by bending; defined by resulting Vertical Force (F).
Installation of the assembly (including the pendant) is considered to be safe if
all the following are satisfied.
M1 Nm
1. M1 and F are in the safe area of the figure.
2. The applied load on each bracket is lower than the corresponding SWL
declared for test. (paragraph 10.8.1 IEC – 61537).
3. The Bending Moment of the pendant itself is lower than the SWL for the
pendant length.
FN
111
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 4
9.- CONNECTORS
The trays are shipped in pre packed lengths of 2 or 3
meters. The pieces called CONNECTORS are used for
connecting them. For mechanical purposes, the weakest points in a tray installation are the joints . Only the
use of the right number of CONNECTORS in the right
positions as recommended by the manufacturer can
ensure that the entire system will perform satisfactorily.
The ideal spot for employing the CONNECTOR is at L/5
from the nearest support.
Fitting the CONNECTORS between L/4 and L/5 is the
most advisable approach.
L
ALL THE LOAD AND PERFORMANCE VALUES
GIVEN IN THIS CATALOGUE WERE OBTAINED
FROM TESTS CARRIED OUT IN ACCORDANCE
WITH INTERNATIONAL EN 61537 STANDARD
It is often found that similar trays from different manufacturers give different values. This may be due to the
load tests not being carried out in accordance with this
standard.
For proper comparisons to be made between two similar trays from different manufacturers, check that the
values given were found under equivalent test conditions.
L/5
11.- EARTHING (ELECTRICAL CONTINUITY)
All metal tray systems must have proper electrical continuity. However, to ensure safety, it is advisable to make
an earth connection using a suitable conductor for each
part of the system.
L/4
L
This CANNOT be done on painted or epoxy-coated
trays without removing the protective layer at that point
and at the join-points between the various lengths,
which will inevitably lead to oxidisation WITHOUT
ENSURING safety.
L/5
L/4
The CONNECTORS should NOT be fitted at point L/2
(half-way between the supports), or on the supports.
When L=1.5 meters, which is the commonest case,
the use of 3-meter lengths ensures the best placing
of the joints, unlike using 2-meter lengths.
L
L/2
NO
L
When the trays have to go through a wall, the trays
should have a clear space of approximately 100 mm on
each side. The earth connection must always be
maintained.
NO
0
10
L/2
0
10
10.- LOAD-BEARING CAPACITY
This is the load (uniformly distributed, NOT concentrated)
that a tray can safely cope with.
It is expressed in kilos or kg per running meter, in the
form of graph curves or tables.
1 kg = 9.81 Newtons
The values are obtained through experiments carried out
in accordance with the pertinent standards.
112
12.- THROUGH-WALL MOUNTING
If the characteristics of the two rooms separated by the
wall are different and may pose risks associated with
moisture, gas or fire, the hole in the wall should be
blocked off using suitable systems from among those
available.
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 5
Technical Information
According to IEC 61537 Standard
CLASSIFICATION ACCORDING TO IEC 61537 STANDARD
Material:
Flame Spreading Resistance:
Electrical Continuity Characteristics:
Electrical Conductivity Characteristics:
Coating Material:
Metallic
Non Flame Spreading
With Continuity
With Conductivity
Metallic
Transport, store, installation and application temperature range:
Minimum: -40 ºC
Maximum: +150 ºC
Perforation base Area Classification:
Pemsaband® Solid:
Pemsaband® Standard:
Rejiband®:
Classification A
Classification B
Classification D
Impact Resistance:
Up to 20 J
Useful dimensions of the Rejiband Tray
(wide and height in mm)
Flange
Useful height
Width
Useful wide
35
26
60
42.5
60
50
100
82.5
100
90
150
132.5
200
180.5
300
280.5
400
380.5
500
480.5
600
580.5
Torque settings for screwed connections
(in Nm)
Hardness Max. Torque Setting
According to ISO
8.8
898-1/898-7
According to ISO
4.6-4.8
898-1/898-7
According to ISO
4.8
898-1/898-7
According to ISO
4.6-4.8
898-1/898-7
Type of Screw
Allen M1Allen Screw M10x20
Ex.Cone point M10x20
C/DIN 603 M6x12/20
Ex.Cone point M6x15/x85 and
M10x10/30/58
Choosing the right tray
and support system
You need to know the following factors in order to select
a tray system:
• The weight and diameter of the cables intended for
use in the installation, and in future extensions.
• Any non-distributed loads planned (lamp fittings, electrical boxes etc.)
• The distance that can be allowed between supports or
bearing points.
• The corrosion protection needed.
• The nature of the installation (open, closed etc.)
• The method of installation (wall, ceiling, floor etc.)
• The need for earthing.
• Electromagnetic compatibility
TRAY SIZE. When the cables involved are known, check
their weight per meter and cross-section in the manufacturer’s catalogue. Add 30-50% to each of these values to allow for future extensions.
THE TOTAL CROSS-SECTION NEEDED is found by
adding up all the cross-section values of the cables
planned and any future cables, plus the filling coefficient. The calculation involved is:
S=
K (100+a)
∑n
100
Where:
S = total section needed in mm2
K = fill coefficient: 1.2 small cables
1.4 power cables
a = space reserved for future extensions (30-50%)
∑n = The sum of the sections of the cables to be
installed in the cable tray.
When the value of “S” is known, the total weight per
meter of the cables “P” is found from the catalogue,
113
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 6
increasing the value by that same percentage. This value
“P”, in kilos/meters, is converted into Newtons, since
that is the unit used in the rack load-capacity graphs.
The calculation for “P” gives 29.46 kg/m, which when
increased by 30% gives 38.3 kg/m. Converting this to
Newtons gives 375.3 Newtons per meter.
Conversion:
Check on page 15 or 62 whether the cable tray chosen
on the grounds of “S” have this load-bearing capacity.
1 kilo~9.8 Newtons
With reference to these S and P values, find the most
suitable S and P values in the tray catalogue, erring on
the side of excess.
If an exceptional load is planned at some point in the
installation, select a tray with higher performance values
for there.
For example: Find the tray section needed for installing
these cables:
5 cables, 4x35
10 cables, 4x25
4 cables, 4x25
2 cables, 4x4
mm.
kg.m.
mm2
26.8
24.1
23
14.5
1.86
1.42
1.31
0.36
563.8
456
415.2
165
4x35
4x25
3x25
4x4
“S” is calculated by applying the formula:
K (100+a)
S=
∑n
The calculation for ∑n will be:
= 2.819 mm
= 4.560 mm2
= 1.661 mm2
= 330 mm2
They must have sufficient load-bearing capacity to withstand safely the system of trays plus the accessories
selected, and must have the same degree of protection
against corrosion.
K = 1.4 and a = 30%, will be:
9.370=17.053 mm2
100
Find the nearest value on page 12 or 56, erring on the
side of excess, which will correspond to a cable tray:
REJIBAND, 400 x 60, total section 18.610 mm
or
PEMSABAND, 400 x 60, total section 22.540 mm2
2
114
For more information, see the chapter on this (page 115).
There are other types of plastic coverings based on various products: PVC, Polyethylene, Polypropylene,
Epoxy resin etc. These are more attractive in appearance, but give results that are very inferior to zinc-based
coatings. They are fragile, and the range of working temperatures is much narrower than zinc.
SELECTING THE TYPE OF SUPPORT. Once the tray
has been chosen, suitable supports in terms of the type
and method of installation must be chosen.
The section that tray must have, where
1.4 (100+30)
P.G. Sendzimir galvanizing
E.G. Electrogalvanizing
E.B. Electrogalvanized bichromate (Yellow)
H.D.G. Hot-dipgalvanized
S.S. Stainless steel
METHOD OF INSTALLATION. On the wall, ceiling or
the floor. See Rejiband, pages 30-31-38-39-44-45.
Pemsaband, pages 80-81-86-87-92-93.
2
9.370 mm2
S=
To remedy this, various surface-treatment processes
based on zinc are used.
TYPE OF INSTALLATION. Open, with or without covers, and closed. The latter are used when greater
mechanical protection is needed. In this case, the crosssection of the cables must be increased to offset the
poorer ventilation.
100
5x563.8
10x456
4x415.2
2x165
This material oxidises easily, causing significant economic losses. In the case of trays, there may also be
quality of service problems.
The commonest and most successful in industry are, in
order of efficacy:
mm2
mm2
mm2
mm2
The following is found in the cable manufacturer’s catalogue:
Cable
Cable
Cable
Cable
PROTECTION AGAINST CORROSION
Most tray systems available are made of steel.
Pemsa gives the load-bearing capacity of all its
supports in accordance with standard IEC 61537, and
the capacity of their protective finish.
When the Safe Working Load (SWL) for the rack chosen
is known in Newtons per meter, the support must be
able to withstand the value of this SWL x L, where:
L = the distance between the supports in meters.
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 7
Surface treatment
to prevent corrosion
CORROSION. Corrosion is an electro-chemical phenomenon that arises from contact between two different
metals, or a metal and the environment (air, water,
gases) surrounding it.
All metals are liable to corrosion to some extent.
The end result of the corrosion process is the total
destruction of the metal affected.
In view of the high costs stemming from corrosion, there
are various industrial coatings that can be applied on the
surface in order to retard the appearance of corrosion.
The duration of the protection achieved depends on the
thickness of the protective coating, expressed in
microns (1 micron = 0.001 mm), the type of coating
used, and the aggressiveness of the environment.
TABLE I
Estimated service life in years of the
Thickness
protective coating in different atmosin microns
pheres...
30
40
80
100
Industrial Marine
Urban
Rural
7-14
9-18
5-10
7-15
13-25
15-35
13-28
20-40
4-12
6-18
11-33
14-40
The thickness of the coating applied varies from 8 to 12
microns - see table II. The Standard recommends applying a chrome-conversion layer (UNE 112-050).
Recommended for indoor installations in a dry
atmosphere with no aggressive contaminants.
BYCRO-E.B. Electrogalvanized bichromate
(yellow colour) BS - EN12329
This involves the above process plus subsequent treatment
that improve the anti-corrosion performance - see table II.
The thickness of the coat applied is 8-12 microns.
The process as used by Pemsa involves no CYANIDE and
no CHROME VI.
Recommended for use in dry, contaminant-free
atmospheres.
Better performance than P.G. and E.G.
H.D.G. Hot-Dip galvanising
UNE - EN ISO 1461
Used for all kinds of products.
It involves immersing the individual pieces to be protected into a bath full of zinc at 450 ºC after the parts
have been machined.
The average thickness of the protective coating is 70
microns.
In the case of steel, the most highly developed industrial process is zinc coating.
All the steel products made by Pemsa are protected by
one of the following coatings:
P.G.
Sendzimir galvanising
UNE - EN 10142
(NOT TO BE CONFUSED WITH HOT-DIP GALVANIZING)
Used solely for protecting sheet metal of below 3 mm in
thickness.
Produced by dipping the rolls of steel in a zinc bath at
450 ºC.
This technique is widely used in the manufacture of barcut parts and stamped parts. The cuts arising in the
machining are partially regenerated by the galvanic pair
formed by the steel and the zinc.
The thickness of the protecting coating is from 8 to 15
microns.
Recommended for indoor installations in a dry
atmosphere with no aggressive contaminants.
E.G. Electrogalvanizing (white colour)
UNE - EN12329
This involves protecting parts made of iron and steel
electrolytically using zinc.
Recommended for outdoor, marine, rural, industrial
and aggressive indoor installations.
STAINLESS STEELS
These are carbon steels alloyed with chromium, nickel,
magnesium and molybdenum. The best-known ones are
AISI 304 (18/8) and AISI 316.
Contrary to widespread belief, these steels ALSO SUFFER CORROSION, though their performance when
properly handled is generally much better than any type
of protective coating.
Their specific behaviour is the result of the chromium
and nickel spontaneously generating a film of chromium oxide in the presence of an oxidising environment,
this film then preventing subsequent oxidisation. The
film is very delicate, and can be broken by blows,
machining, welding etc.
Stainless steels are easily CONTAMINATED, thus losing
their properties, when they are machined with tools that
use other types of steel. In such cases, the protective
film must be generated by a chemical-attack process.
To solve this problem, after the manufacturing work
(punching, welding), PEMSA subjects all its REJIBAND
S.S. rack and accessories to a special process for
regenerating the protective layer known as THERMICRON.
115
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 8
A 304 STAINLESS STEEL AISI-304
For guideline purposes, since each installation is different, the following protective coatings can be advised:
Suitable for:
• Fresh water
• Industrial atmosphere
• Marine atmosphere
• Normal chemical industry
• FOOD INDUSTRY
(except high temperatures)
TABLE III
TABLE FOR CHOOSING SURFACE TREATMENTS
IN VIEW OF THE ENVIRONMENT
Bycro
Inox. Inox.
EB PG HDG 304 316
TYPE
EG
Specially recommended for:
Indoor
B
B
B
B
B
B
• Marine and coastal areas
• Aggressive chemical environments
• High temperature food industry applications.
Indoor, near sea
NR
P
NR
B
B
B
P
B
P
B
B
B
A 316 STAINLESS STEEL AISI-316
Outdoor, dry climate
Laboratory tests carried out in a salt-spray chamber in
accordance with ASTM-B117 produced the following
results:
TABLE II
Corrosion resistance
in hours
E.B./BYCRO Electrolytic zinc coating,
E.G.
H.D.G.
S.S.
Outdoor, near sea
NR NR NR
P
P
B
Coast
NR NR NR
P
NR
B
Sulphurous
NR NR NR
P
P
B
Mineral acids
NR NR NR
P
P
B
Ammonium
NR NR NR
P
P
B
Caustic soda
NR NR NR
P
P
B
birchromate (yellow)
440
Electrolytic zinc coating (white)
290
Organic acids
NR NR NR
P
B
B
>600
Hydrocarbons
NR NR NR
P
B
B
Chlorine
NR NR NR NR
P
B
B
B
Hot-dip galvanizing
Stainless steel AISI 304
No trace after 450
An approximate way of finding out how laboratory values translate into real-world values is:
1 laboratory hour = 1 week
In the case of an industrial marine atmosphere, divide
the above results by 2.
P
Food industry
B: Good
P
P: Possible
P
P
NR: Not recommended
Recommended by Pemsa
CORROSION
E.B./BYCRO
440
E.G.
290
0
50
100
150
200
250
300
HOURS
116
350
400
450
500
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 9
Electrical continuity
To ensure electrical safety in a cable-carrying tray installation, the installation must have suitable electrical continuity.
The design of the joining has decisive importance in the
R1 value, as do the material, the surface finish and the
method of assembly.
This is stipulated in Standard IEC 61537 section 11.1,
which gives the pertinent tests for checking this.
Contact between different materials or finishes encourages oxidisation, thereby reducing electrical continuity.
The same condition may arise through insufficient contact pressure at the join point.
This is done in this way: measuring the electrical-resistance values at the most unfavourable point R1 (joining
between racks) and R2 (material resistance) measured
across two points that are 500 mm apart in the same
straight run.
YS AND
EMBLE TRA
DO NOT ASS
INISHES
IFFERENT F
D
H
IT
W
S
T
JOIN
The maximum admissible values according to IEC
61537 are:
R1< 50 mΩ
R2< 5 mΩ
R1
In tests performed at Pemsa’s request in the Central
Laboratory of the Electrical Engineering Office under
number 99 121006 on 10/12/99, involving various samples of rejiband® and pemsaband®., the values given in
the following tables were found:
R2
G
RESISTANCE (mΩ)
Rack
mm
Tigtening
torque at
connectors
R1
R2
3 Nm
0,18
0,79
4 connectors
-
1,41
0,79
2 connectors
3 Nm
1,11
1,38
2 connectors
-
2,86
1,38
4 connectors
3 Nm
1,18
0,73
4 connectors
-
0,39
0,73
100x60
2 connectors
3 Nm
2,57
4,58
100x60
2 connectors
3 Nm
0,27
0,35
3 Nm
0,12
0,22
Connector used
and number
4 connectors
600x60
E.B. / BYCRO
D
AN
RITY
REJIB
SECU
REJIBAND
100x60
600x60
D
AN
RITY
REJIB
SECU
P.G.
PEMSABAND
Inox 304
H.D.G.
D
AN
RITY
REJIB
SECU
2 side connectors
400x60
1 central connector
117
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 10
Earthing
If it is deemed, in view of the installation, to be necessary to have an independent earth conductor, its section must
be at least 16 mm2, and must be mounted on the outside throughout the tray system, connected using the right
accessories to each length of the installation.
A cable-carrying tray system comprises straight lengths and accessories (bends, crossovers, Tee-joints) joined
together using suitable fasteners.
The electrical continuity in the system ifself (in the case of metal trays), which is necessary to achieve proper earthing and to ensure personal safety, can be adversely affected by a wide range of causes (oxidisation, nuts coming
loose, insulating coatings, etc.). To avoid this, it is advisable to install an independent earth circuit by connecting up
every single element in the system (trays and accessories) to a suitable sized conductor - with a section of at least
16 mm2.
In the case of trays that are painted or coated with epoxy resin, the electrical continuity needed in the system is broken. In such cases, arranging an earth connection is absolutely essential.
That is a difficult operation, since it can only be done by removing the protective layer by mechanical means at the
earth-connection point. This inevitably creates an oxidisation zone which further hinders the earthing.
That is why electrically safe tray systems must be made of metal with metal coating or made solely of insulating
material.
The earth connection is to be made using the right parts - see rejiband® page 24 or pemsaband® page 72.
PE
MS
A
118
Rejiband
Pemsaband
page 24
page 72
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 11
Electromagnetic Compatibility (CEM)
Power supply cables and signal cables can share the same cable conveyance systems (Trays,
Channels, etc.).
Adequate separation must be provided (by distance or shielding) between power cables and signal cables. Power
cables and signal cables must cross at right angles.
In order to prevent disturbances, the minimum separation between power cables and signal cables depends on many
factors, such as the following:
a) The level of immunity from the various electromagnetic interference (surges, overcurrents,
lighting impulses, ring waves, continuous waves, etc.) of the equipment connected to the signal
cabling system.
b) The connection of the equipment to the grounding system.
c) The local electromagnetic environment (the simultaneous appearance of disturbances:
for example, harmonics added to discharges and to continuous waves).
d) The electromagnetic spectrum.
e) The distances that the cables run parallel to each other (the coupling zone).
f) The kind of cable.
g) Cable attenuation against coupling.
h) The quality of the connections between the connectors and the cable.
i) The type of cable conveyance system and its accessories.
Separation between signal cabling and power cabling
Distance
Without a dividing
wall or with a non
metal divider(1)
Aluminium divider
Unshielded power cable and
unshielded signal cable
200 mm
100 mm
50 mm
✔
Unshielded power cable and
shielded signal cable (2)
50 mm
20 mm
5 mm
✔
Shielded power cable and
unshielded signal cable
30 mm
10 mm
2 mm
✔
Shielded power cable and
shielded signal cable (2)
0 mm
0 mm
0 mm
✔
Type of instalation
Steel divider
1) It is assumed that in the event of a metal divider, the design of the cable conveyance system will provide shielding attenuation
that is approximate to the material used in the divider.
2) Shielded signal cables must comply with the EN 50288 series.
119
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 12
Electromagnetic Compatibility (CEM)
Metal systems for cable conveyance: trays, channels, etc.
Metal systems for cable conveyance should always be connected to the local ground at both ends. Over long distances (more than 50 m), additional connections to the ground systems are recommended at irregular intervals. All
ground connections should be as short as possible.
Non-metal systems for cable conveyance: trays, channels, etc.
In order to improve the EMC behaviour of non-metal systems for cable conveyance, when devices connected to the
wiring systems with unshielded cables are not affected by low frequency disturbances, it is advisable to add a cable
to the cable conveyance system, such as a parallel ground conductor connected at both ends to the local ground
system. Connections should be made to metal parts with low impedance (for example, to a large piece of the sheet
metal of an electrical cabinet).
The parallel ground conductor should be designed to resist the common mode and fault currents.
Grounds and equipotential connections
Overview. The basic purposes of connection and grounding applicable to unshielded and shielded wiring systems
are as follows:
- Safety: to limit contact voltage and provide a return path in the event of a fault to ground;
- EMC: to have zero potential and equipotentiality, which provide a shielding effect.
Source: UNE-EN 50174-2
Rejiband installed with a divider.
120
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 13
Pemsa Metal Tray Systems: Behaviour in
the event of fire: A1 (the Safest: Non
Combustible)
New European Classification System in compliance with the Directive 89/106/EC, according to the Fire
Behaviour of the Materials.
Classification (*)
1
A1
Non combustible
2
A2
Slightly combustible
3
B
““
4
The safest
Additional Classification
Less Safe
(in decreasing order)
C
Smoke Production (S)
Smoke Density
Combustible
Flaming
droplets/particles (D)
5
D
““
6
E
““
7
F
No performance
determined
-
(*) In accordance with EN 13501-1:2002
BEHAVIOUR IN THE EVENT OF FIRE
Smoke Opacity
Smoke Toxicity
Contained
Halogens
No Smoke
No Smoke
No Smoke
NO
COMBUSTIBLE / FIRE
RESISTANT
Reduced
Smoke Emission
Reduced
Opacity of Smoke
Smoke with Low
Toxic Particles Level
NO
COMBUSTIBLE / FLAME
PROPAGATOR
Dangerous
Smoke Emission
High
Opacity of Smoke
Smoke with
Toxic Particles Level
YES
MATERIALS
Directive 89/106/EC
Steel Trays
NON-COMBUSTIBLE
Halogen-free cables
P.V.C.
Smoke Emissions
The Rejiband and Pemsaband Metal Tray (A1) systems guarantee safety in that they do NOT emit toxic gases
or halogens, they do NOT emit opaque smoke (luminous transmittance), they do NOT emit corrosive gases and
they do NOT propagate fire.
MAXIMUM SERVICE TEMPERATURES OF CABLES AND TRAYS (*)
Conventional PVC Cables
70ºC
Halogen-free Cables
90ºC
PVC Trays
60ºC
Rejiband and Pemsaband Metal Trays
150ºC
(*) For cables and trays, data according to manufacturer catalogues.
Rejiband and Pemsaband Metal Trays do not limit the maximum service temperature of halogen-free cables.
121
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 14
Fire Resistance
rejiband
®
Safety is a growing concern within electrical
installations.
In the event of a fire the behaviour of electrical
equipment, when exposed to high temperatures,
determines whether the installation achieves a
certain safety level. rejiband® wire mesh cable
tray complies with these requirements with a number of features and properties as described in the
E90 Certification.
rejiband® wire mesh cable tray is manufactured in accordance with the requirements and tests
of the product standard IEC 61537 "Cable Tray and Cable Ladder Systems".
So far this standard has not yet covered the fire risks and
fire resistance.
DIN 4102-12
“Cable Tray and Cable Ladder Systems”
E30
E60
When studying the properties of rejiband® wire mesh cable tray against fire, Pemsa has used the
German Standard DIN 4102-12 which is the main reference in other European countries.
This standard tests the complete installations, in order to evaluate the structural integrity of the assembly
and how the components react when exposed to fire.
A 3m length of wire mesh tray, accessories and power cables are the subject of the test. According to
the final results, the certification may be issued at three different levels:
Table 1.
Standards.
STANDARDS
E30
E60
E90
Time
Temperature
30 min.
840 ºC
E660 min.0
950 ºC
E990 min.0
1000 ºC0
The purpose of this test is to validate the correct operation of the electrical system and to ensure that
critical services (fire suppression system, emergency lighting, ventilation and other basic installations)
remain functional for long enough to organise evacuation in the event of fire.
122
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 15
Fire Resistance
Test Set-up
Figure 1:
General View Of
The Assembly
The test set-up consisted of a 3m length of wire mesh
tray, including joints and accessories, supported on
brackets at intervals of 1.2m. The power cables, up to
1kV, should be fire resistant at the same or higher level
than halogen free, high safety cables. The wire mesh
tray was then loaded with chains to simulate the cable
weight and other standard conditions of the test.
During the test, a standardised temperature vs. time curve is imposed in
the test oven, obtaining the 3 levels of certification and their
corresponding times and temperatures as shown on table 1.
The results prove that the cables maintain electrical continuity during the
test, and therefore the operational integrity of the installation is
maintained.
As the test was progressing, both cables and trays
were damaged by the high temperatures as defined in
DIN 4102-12. Trays are deformed but maintain their
support function. The cable sheathing starts to burn
causing risk to the correct functioning of the system.
As shown in figure 3, rejiband® wire mesh cable tray
and its accessories neither collapsed nor were they
detached from the supports, ensuring enough
structural resistance within the system.
Figure 2:
Assembly
Before Test
rejiband®
Figure 3: Assembly After
Test
Conclusions
The wire mesh cable tray exceeded the fire
resistance test, qualifying for the highest level of
resistance proposed by this standard, the E90.
The tray with cables were tested for 90 minutes
at temperatures of 1,000ºC (in accordance with
the conditions of DIN 4102-12), maintaining
circuit integrity against fire.
The combined use of rejiband® wire mesh tray with high safety halogen-free electrical
cables improves substantially the safety of the installation. Since both components
provide a self extinguishing system, which does not produce toxic, corrosive or opaque
fumes (more typical for polymeric & halogen materials), this allows a period of time long
enough for evacuation and emergency works.
Investing in safety equipment and systems with high fire resistance must be
accompanied by a safe installation that ensures their correct functioning in the
most critical situations.
123
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 16
Fire test in the tunnels of El Padrún.
Asturias-Spain
Test objectives
In the tests at the El Padrún tunnels, it was especially taken into account that a fire might occur with the tunnel in
service (see bibliography).
It was deemed appropriate to perform a
fire test in a real environment, in the tunnel itself. Even though this kind of testing
could be performed in specialised laboratories, the extrapolation to a real scale
could be complicated, and, of course,
would have made it difficult to attain
some of the most important objectives,
which can be summarised
as follows:
- To maintain direct contact with the Civil
Protection and Fire Fighting services that
would have to intervene in the event of a
fire.
- To test materials that have been used
traditionally in other tunnels.
Fire test area, with a waterproofing layer and two cable tray models
installed.
- To study the movement of smoke in a
tunnel fire, to measure the temperatures
reached and to study the composition of
the gases emitted.
- To allow the fire to develop up to the maximum threshold and then have it extinguished by the Fire Department.
Materials tested and measurements taken
Cable Trays: Cable trays were fastened to the walls of the tunnel to house the energy cables (lighting, ventilation,
communications, etc.).
Two kinds of trays were tested: a PVC tray and a metal tray (Rejiband).
Chemical Analysis of the Combustion: Possible products from the combustion.
Toxic gases:
- Carbon monoxide: Produced by the incomplete combustion of carbon, caused by combustion with an oxygen
deficit. Highly toxic gas, which, added to the fact that it is
colourless and odourless, is very dangerous.
- Lack of oxygen: Produced by the needs of the combustion itself. In air, the concentration of oxygen is 21%
by volume (nitrogen, 78%; oxygen, 21%; carbon dioxide,
0.035%, etc.). When the oxygen level falls to 12%,
headaches and fatigue appear, and if it falls to 6%, death
occurs after about 5 to 8 minutes.
Tunnel in flames.
124
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 17
Fire test in the tunnels of El Padrún. Asturias-Spain
- Other gases:
From the combustion of the various materials used, the following can be produced: Carbon dioxide, CO2.
Hydrochloric acid, CIH. Phosgene, CI2CO. Hydrocyanic acid, CNH:
Smoke:
- Smoke is produced as a mixture of gases, droplets of liquids and solid particles that are given off in combustion and transported by air.
- Even though the previously stated gases are more worrisome from the point of view of their toxicity, in a
fire, smoke creates panic, and linked with a reduction in visibility, this almost always results in more victims than the
fire itself.
Results and conclusions
Temperatures reached
The maximum temperatures, in the section where the vehicles were
set on fire, varied between 40º and 190º C, recorded by the probe at
the keystone (straight above the fire).
On the side faces of the same section, the maximum temperatures
reached was 75º C.
In the area behind the fire, in the direction of the gas motion impelled
by the ventilation, the maximum temperatures measured were 60º at
the keystone and 37º on the side faces.
Smoke and gases produced
The test clearly showed the fundamental importance of smoke production in a tunnel fire, given that it cancels out visibility in a very
short period of time over long sections.
Frequently, the reactions that may be caused by panic must be
added to this difficulty.
Behaviour of the tested materials
Both the waterproofing layer as well as the PVC cable tray that were tested were rapidly sensitive to the effects of
the fire (the metal tray was not affected at all).
The PVC cable tray began to undergo a process of deformation due to the effect of heat, and continued to deform
(without burning), thereby reaching a point where, if the tray held cables (its real task), the cables would have fallen
or they would have held the tray.
Final notes
Reduction of visibility: After the fire, the area between the damaged vehicle and the smoke outlet filled completely
with smoke within a few minutes.
The solution to the problems that can occur in a tunnel in service have to be planned for, the material and human
resources have to be operational (trained personnel are required), and they must all be backed up by the various entities that could be involved.
125
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 18
Product Index by Description
Description
Adjustable bend Click
Adjustable medium duty cantilever RPLUS
Angle bracket
Angle tray
Angle tray fastener
Beam clamp hanging assembly
Bend 90º Click
Bend 90º Click cover
Bend cover 90º for Inducanal
Bend 90º for Inducanal
Bolt cutter
Box support for Rejitech
Ceiling bracket
Ceiling fastener for Rejitech
Central hanging plate
Central hanging plate 7
Central joiner
Clamp
Click central suspension
Click connector
Connector plate
Cover
Crossover Click
Crossover Click cover
Channel beam clamp
Channel floor boss
Channel nut
Data outlet
Divider plate
Double heavy duty pendant drop
Earth terminal
Fixing support for Rejiband
Floor foot
Floor foot adhesive
Gland bracket
Heavy duty cantilever RPLUS
Heavy duty channel 41x41
Heavy duty channel 41x21
Heavy duty pendant boss
Heavy duty pendant channel
Heavy duty pendant drop
Horizontal angle hanger
Identification label
Identification plate
Inducanal
Inducanal Cover
Inside riser Click
Inside riser cover Click
Joiner
Light duty channel 41x21
Light duty channel 41x41
Medium duty cantilever RPLUS
126
Page
72
36-84
106
14-48
48
42-90
74
74
100
100
17
54
40-88-103
54
17-40-103
100
68
106
40-103
22
17-28-72
28-70
76
76
106
106
104
28
28-68
48-96
24-50
26
50
50
28-50
36-84
104
104
48-96
48-96
48-96-103
42-88
28-68
26
98
100
78
78
68-100
104
104
36-84
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Description
Mesh channel
Mesh Click channel
Mini universal bracket
Nuts
Omega bracket
Omega ceiling bracket
Omega Click bracket
Omega Click ceiling bracket
Omega pendant bracket
Outside riser Click
Outside riser cover Click
Part clamp
Pemsaband System
Pemsaband SX
Pemsaband RX
Pemsaband LX
Protector for ends & edges
Reducer
Reinforced joint clamp
Rejiband
Rejiband box support
Rejifix
Rejitech
Riser/Dropper
Rod connector M8
Screws
Side entry Click
Side entry Click cover
Side joint-plate
Side support 60
Splice plate
Stand off bracket
Supports & structures
Threaded rod
Tee Click
Tee Click cover
Tee plate
Universal bracket
Universal bracket for Pemsaband
Variable ceiling rod bracket
Vertical angle hanger
Washers
Wire end cap
Zinc paint spray
Página 19
Page
42-90-103
42
32-103
107
34-82-103
46-83-94
34
46-103
46-83-94-103
78
78
17-24
56
60
65
67
70
70
17-22
14-50
26
26-72
14-52-54
70
40-88
107
76
76
22
32-40-106
17-24-106
32-68
102
40-88-100-103
74
74
106
28
72-100
40-88-103
42-88
107
22
24-72
127
PEMSA-219-109 AL FINAL-REV-
27/11/09
11:51
Página 20
Product Index
by Reference Number
Ref
Description
Finish
Quantity
EAN 13
Page
60.21
60.211.100
60.211.200
60.211.300
60.211.400
60.212.060
60.212.100
60.212.150
60.212.200
60.212.300
60.212.400
60.212.500
60.212.600
60.213.200
60.213.300
60.213.400
60.213.500
60.213.600
60.215.020
REJIBAND 35x100
REJIBAND 35x200
REJIBAND 35x300
REJIBAND 35x400
REJIBAND 60x 60
REJIBAND 60x100
REJIBAND 60x150
REJIBAND 60x200
REJIBAND 60x300
REJIBAND 60x400
REJIBAND 60x500
REJIBAND 60x600
REJIBAND 100x200
REJIBAND 100x300
REJIBAND 100x400
REJIBAND 100x500
REJIBAND 100x600
REJITECH 60x100
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
24
18
18
12
24
24
24
18
12
6
6
6
6
6
6
6
6
16
8431927012395
8431927012401
8431927012418
8431927015907
8431927012425
8431927012432
8431927012449
8431927012456
8431927012463
8431927012470
8431927012487
8431927012494
8431927012500
8431927012517
8431927012524
8431927012531
8431927012548
8431927012562
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14-54
ANGLE WIRE MESH TRAY
REJIBAND 35x100
REJIBAND 35x200
REJIBAND 35x300
REJIBAND 35x400
REJIBAND 60x 60
REJIBAND 60x100
REJIBAND 60x150
REJIBAND 60x200
REJIBAND 60x300
REJIBAND 60x400
REJIBAND 60x500
REJIBAND 60x600
REJIBAND 100x200
REJIBAND 100x300
REJIBAND 100x400
REJIBAND 100x500
REJIBAND 100x600
REJITECH 60x100
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
BYCRO
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
18
24
18
18
12
24
24
24
18
12
6
6
6
6
6
6
6
6
16
8431927006462
8431927006479
8431927006486
8431927006493
8431927015914
8431927006509
8431927006516
8431927006523
8431927006530
8431927006547
8431927006554
8431927006561
8431927006578
8431927006585
8431927006592
8431927006608
8431927006615
8431927006622
8431927006646
14-48
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14-54
ANGLE WIRE MESH TRAY
REJIBAND 35x100
REJIBAND 35x200
REJIBAND 35x300
REJIBAND 35x400
REJIBAND 60x 60
REJIBAND 60x100
REJIBAND 60x150
REJIBAND 60x200
REJIBAND 60x300
REJIBAND 60x400
REJIBAND 60x500
REJIBAND 60x600
REJIBAND 100x200
REJIBAND 100x300
REJIBAND 100x400
REJIBAND 100x500
REJIBAND 100x600
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
18
24
18
18
12
24
24
24
18
12
6
6
6
6
6
6
6
6
8431927006653
8431927006660
8431927006677
8431927006684
8431927015921
8431927006691
8431927006707
8431927006714
8431927006721
8431927006738
8431927006745
8431927006752
8431927006769
8431927006776
8431927006783
8431927006790
8431927006806
8431927006813
14-48
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
ANGLE WIRE MESH TRAY
REJIBAND 35x100
REJIBAND 35x200
REJIBAND 35x300
REJIBAND 35x400
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
m
m
m
m
m
18
24
18
18
12
8431927006820
8431927006837
8431927006844
8431927006851
8431927015938
14-48
14
14
14
14
60.22
60.220.000
60.221.100
60.221.200
60.221.300
60.221.400
60.222.060
60.222.100
60.222.150
60.222.200
60.222.300
60.222.400
60.222.500
60.222.600
60.223.200
60.223.300
60.223.400
60.223.500
60.223.600
60.225.020
60.23
60.230.000
60.231.100
60.231.200
60.231.300
60.231.400
60.232.060
60.232.100
60.232.150
60.232.200
60.232.300
60.232.400
60.232.500
60.232.600
60.233.200
60.233.300
60.233.400
60.233.500
60.233.600
60.25
60.250.000
60.251.100
60.251.200
60.251.300
60.251.400
128
PEMSA-219-109 AL FINAL-REV-
Ref
60.252.060
60.252.100
60.252.150
60.252.200
60.252.300
60.252.400
60.252.500
60.252.600
60.253.200
60.253.300
60.253.400
60.253.500
60.253.600
27/11/09
11:51
Página 21
Description
Finish
Quantity
EAN 13
Page
REJIBAND 60x 60
REJIBAND 60x100
REJIBAND 60x150
REJIBAND 60x200
REJIBAND 60x300
REJIBAND 60x400
REJIBAND 60x500
REJIBAND 60x600
REJIBAND 100x200
REJIBAND 100x300
REJIBAND 100x400
REJIBAND 100x500
REJIBAND 100x600
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
S.S.304
m
m
m
m
m
m
m
m
m
m
m
m
m
24
24
24
18
12
6
6
6
6
6
6
6
6
8431927006868
8431927006875
8431927006882
8431927006899
8431927006905
8431927006912
8431927006929
8431927006936
8431927006943
8431927006950
8431927006967
8431927006974
8431927006981
14
14
14
14
14
14
14
14
14
14
14
14
14
ANGLE WIRE MESH TRAY
REJIBAND 35x100
REJIBAND 35x200
REJIBAND 35x300
REJIBAND 35x400
REJIBAND 60x 60
REJIBAND 60x100
REJIBAND 60x150
REJIBAND 60x200
REJIBAND 60x300
REJIBAND 60x400
REJIBAND 60x500
REJIBAND 60x600
REJIBAND 100x200
REJIBAND 100x300
REJIBAND 100x400
REJIBAND 100x500
REJIBAND 100x600
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
18
24
18
18
12
24
24
24
18
12
6
6
6
6
6
6
6
6
8431927108458
8431927018465
8431927018472
8431927018489
8431927018496
8431927018502
8431927014726
8431927014733
8431927014740
8431927014757
8431927014764
8431927014771
8431927014788
8431927018519
8431927018526
8431927018533
8431927018540
8431927018557
14-48
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
SIDE SUPPORT 60
E.G.
u
25
8431927012579
32-40
SIDE SUPPORT 60
OMEGA BRACKET 100
OMEGA BRACKET 150
OMEGA BRACKET 200
SUPPORT/PENDANT OMEGA BRACKET 300
SUPPORT/PENDANT OMEGA BRACKET 400
OMEGA PENDANT BRACKET 500
OMEGA PENDANT BRACKET 600
OMEGA CEILING BRACKET 100
OMEGA CEILING BRACKET 150
OMEGA CEILING BRACKET 200
OMEGA CEILING BRACKET 300
OMEGA CEILING BRACKET 400
OMEGA CLICK BRACKET 100
OMEGA CLICK BRACKET 150
OMEGA CLICK BRACKET 200
OMEGA CLICK BRACKET 300
OMEGA CLICK BRACKET 400
MED DUTY CANTILEVER RPLUS 100
MED DUTY CANTILEVER RPLUS 150
MED DUTY CANTILEVER RPLUS 200
MED DUTY CANTILEVER RPLUS 300
MED DUTY CANTILEVER RPLUS 400
MED DUTY CANTILEVER RPLUS 500
MED DUTY CANTILEVER RPLUS 600
MINI UNIVERSAL BRACKET
UNIVERSAL BRACKET REJIBAND
OMEGA CLICK CEILING BRACKET 100
OMEGA CLICK CEILING BRACKET 150
OMEGA CLICK CEILING BRACKET 200
OMEGA CLICK CEILING BRACKET 300
OMEGA CLICK CEILING BRACKET 400
E.B.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
25
5
5
5
5
5
5
5
4
4
4
4
4
5
5
5
5
5
4
4
4
4
4
4
4
10
10
4
4
4
4
4
8431927006998
32-40
8431927017543
34-82
8431927017550
34-82
8431927017567
34-82
8431927017574 34-46-82-83-94
8431927017581 34-46-82-83-94
8431927017598
46-83-94
8431927017604
46-83-94
8431927017611
46-83-94
8431927017628
46-83-94
8431927017635
46-83-94
8431927017642
46-83-94
8431927017659
46-83-94
8431927017666
34
8431927017673
34
8431927017680
34
8431927017697
34
8431927017703
34
8431927039811
36-84
8431927039828
36-84
8431927039835
36-84
8431927039842
36-84
8431927039859
36-84
8431927039866
36-84
8431927039873
36-84
8431927007186
32
8431927007193
28
8431927017710
46
8431927017727
46
8431927017734
46
8431927017741
46
8431927017758
46
H.D.G.
H.D.G.
H.D.G.
u
u
u
25
5
5
8431927007247
8431927017765
8431927017772
60.26
60.260.000
60.261.100
60.261.200
60.261.300
60.261.400
60.262.060
60.262.100
60.262.150
60.262.200
60.262.300
60.262.400
60.262.500
60.262.600
60.263.200
60.263.300
60.263.400
60.263.500
60.263.600
62.01
62.011.060
62.02
62.021.060
62.021.103
62.021.153
62.021.203
62.021.303
62.021.403
62.021.503
62.021.603
62.022.103
62.022.153
62.022.203
62.022.303
62.022.403
62.023.103
62.023.153
62.023.203
62.023.303
62.023.403
62.025.103
62.025.153
62.025.203
62.025.303
62.025.403
62.025.503
62.025.603
62.026.010
62.026.011
62.029.103
62.029.153
62.029.203
62.029.303
62.029.403
62.03
62.031.060
62.031.103
62.031.153
SIDE SUPPORT 60
OMEGA BRACKET 100
OMEGA BRACKET 150
32-40
34-82
34-82
129
PEMSA-219-109 AL FINAL-REV-
Ref
62.031.203
62.031.303
62.031.403
62.031.503
62.031.603
62.032.103
62.032.153
62.032.203
62.032.303
62.032.403
62.033.103
62.033.153
62.033.203
62.033.303
62.033.403
62.035.103
62.035.153
62.035.203
62.035.303
62.035.403
62.035.503
62.035.603
62.036.010
62.036.011
62.037.103
62.037.153
62.037.203
62.037.303
62.037.403
62.037.503
62.037.603
62.039.103
62.039.153
62.039.203
62.039.303
62.039.403
27/11/09
11:51
Página 22
Description
Finish
Quantity
EAN 13
Page
OMEGA BRACKET 200
SUPPORT/PENDANT OMEGA BRACKET 300
SUPPORT/PENDANT OMEGA BRACKET 400
OMEGA PENDANT BRACKET 500
OMEGA PENDANT BRACKET 600
OMEGA CEILING BRACKET 100
OMEGA CEILING BRACKET 150
OMEGA CEILING BRACKET 200
OMEGA CEILING BRACKET 300
OMEGA CEILING BRACKET 400
OMEGA CLICK BRACKET 100
OMEGA CLICK BRACKET 150
OMEGA CLICK BRACKET 200
OMEGA CLICK BRACKET 300
OMEGA CLICK BRACKET 400
MED DUTY CANTILEVER RPLUS 100
MED DUTY CANTILEVER RPLUS 150
MED DUTY CANTILEVER RPLUS 200
MED DUTY CANTILEVER RPLUS 300
MED DUTY CANTILEVER RPLUS 400
MED DUTY CANTILEVER RPLUS 500
MED DUTY CANTILEVER RPLUS 600
MINI UNIVERSAL BRACKET
UNIVERSAL BRACKET REJIBAND
ADJUST HEAVY DUTY CANTILEVER RPLUS 100
ADJUST HEAVY DUTY CANTILEVER RPLUS 150
ADJUST HEAVY DUTY CANTILEVER RPLUS 200
ADJUST HEAVY DUTY CANTILEVER RPLUS 300
ADJUST HEAVY DUTY CANTILEVER RPLUS 400
ADJUST HEAVY DUTY CANTILEVER RPLUS 500
ADJUST HEAVY DUTY CANTILEVER RPLUS 600
OMEGA CLICK CEILING BRACKET 100
OMEGA CLICK CEILING BRACKET 150
OMEGA CLICK CEILING BRACKET 200
OMEGA CLICK CEILING BRACKET 300
OMEGA CLICK CEILING BRACKET 400
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
5
5
5
5
5
4
4
4
4
4
5
5
5
5
5
4
4
4
4
4
4
4
10
10
4
4
4
4
4
4
4
4
4
4
4
4
8431927017789
34-82
8431927017796 34-46-82-83-94
8431927017802 34-46-82-83-94
8431927017819
46-83-94
8431927017826
46-83-94
8431927017833
46-83-94
8431927017840
46-83-94
8431927017857
46-83-94
8431927017864
46-83-94
8431927017871
46-83-94
8431927017888
34
8431927017895
34
8431927017901
34
8431927017918
34
8431927017925
34
8431927039880
36-84
8431927039897
36-84
8431927039903
36-84
8431927039910
36-84
8431927039927
36-84
8431927039934
36-84
8431927039941
36-84
8431927007667
32
8431927007674
28
8431927039958
36-84
8431927039965
36-84
8431927039972
36-84
8431927039989
36-84
8431927039996
36-84
8431927040008
36-84
8431927040015
36-84
8431927017932
46
8431927017949
46
8431927017956
46
8431927017963
46
8431927017970
46
SIDE SUPPORT 60
OMEGA BRACKET 100
OMEGA BRACKET 150
OMEGA BRACKET 200
SUPPORT/PENDANT OMEGA BRACKET 300
SUPPORT/PENDANT OMEGA BRACKET 400
OMEGA PENDANT BRACKET 500
OMEGA PENDANT BRACKET 600
OMEGA CEILING BRACKET 100
OMEGA CEILING BRACKET 150
OMEGA CEILING BRACKET 200
OMEGA CEILING BRACKET 300
OMEGA CEILING BRACKET 400
MED DUTY CANTILEVER RPLUS 100
MED DUTY CANTILEVER RPLUS 150
MED DUTY CANTILEVER RPLUS 200
MED DUTY CANTILEVER RPLUS 300
MED DUTY CANTILEVER RPLUS 400
MED DUTY CANTILEVER RPLUS 500
MED DUTY CANTILEVER RPLUS 600
MINI UNIVERSAL BRACKET
UNIVERSAL BRACKET REJIBAND
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
25
5
5
5
5
5
5
5
4
4
4
4
4
4
4
4
4
4
4
4
10
10
8431927018564
8431927018571
8431927018588
8431927018595
8431927018601
8431927018618
8431927018625
8431927018632
8431927018649
8431927018656
8431927018663
8431927018670
8431927018687
8431927040022
8431927040039
8431927040046
8431927040053
8431927040060
8431927040077
8431927040084
8431927018762
8431927018779
32-40
34
34
34
34-46
34-46
46
46
46
46
46
46
46
36-84
36-84
36-84
36-84
36-84
36-84
36-84
32
28
MESH CLICK CHANNEL 200
MESH CLICK CHANNEL 300
MESH CLICK CHANNEL 400
MESH CLICK CHANNEL 500
MESH CLICK CHANNEL 600
MESH CHANNEL 200
MESH CHANNEL 300
MESH CHANNEL 400
MESH CHANNEL 500
MESH CHANNEL 600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
10
10
10
10
10
10
10
10
10
10
8431927018106
8431927018113
8431927018120
8431927018137
8431927018144
8431927018151
8431927018168
8431927018175
8431927018182
8431927018199
42
42
42
42
42
42-90
42-90
42-90
42-90
42-90
MESH CLICK CHANNEL 200
MESH CLICK CHANNEL 300
H.D.G.
H.D.G.
u
u
10
10
8431927018205
8431927018212
42
42
62.06
62.061.060
62.061.103
62.061.153
62.061.203
62.061.303
62.061.403
62.061.503
62.061.603
62.062.103
62.062.153
62.062.203
62.062.303
62.062.403
62.065.103
62.065.153
62.065.203
62.065.303
62.065.403
62.065.503
62.065.603
62.066.010
62.066.011
63.02
63.021.203
63.021.303
63.021.403
63.021.503
63.021.603
63.022.203
63.022.303
63.022.403
63.022.503
63.022.603
63.03
63.031.203
63.031.303
130
PEMSA-219-109 AL FINAL-REV-
Ref
63.031.403
63.031.503
63.031.603
63.032.203
63.032.303
63.032.403
63.032.503
63.032.603
63.033.303
63.033.403
63.033.503
63.033.603
27/11/09
11:51
Página 23
Description
MESH CLICK CHANNEL 400
MESH CLICK CHANNEL 500
MESH CLICK CHANNEL 600
MESH CHANNEL 200
MESH CHANNEL 300
MESH CHANNEL 400
MESH CHANNEL 500
MESH CHANNEL 600
HEAVY DUTY RPLUS CANTILEVER 300
HEAVY DUTY RPLUS CANTILEVER 400
HEAVY DUTY RPLUS CANTILEVER 500
HEAVY DUTY RPLUS CANTILEVER 600
Finish
Quantity
EAN 13
Page
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
u
u
u
u
u
u
u
10
10
10
10
10
10
10
10
4
4
4
4
8431927018229
8431927018236
8431927018243
8431927018250
8431927018267
8431927018274
8431927018281
8431927018298
8431927040091
8431927040107
8431927040114
8431927040121
42
42
42
42-90
42-90
42-90
42-90
42-90
36-84
36-84
36-84
36-84
CLICK CONNECTOR
SIDE JOINT PLATE
SERRATED HEXAGON FLANGE NUT M 6
PART CLAMP
REINFORCED JOINT PLATE
CONNECTOR PLATE
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
u
u
u
u
u
u
25
50
50
50
50
50
8431927012586
8431927012593
8431927008435
8431927012609
8431927012616
8431927012623
22
22
107
17-24
17-22
17-28-72
CLICK CONNECTOR
SIDE JOINT PLATE
SERRATED HEXAGON FLANGE NUT M 6
PART CLAMP
REINFORCED JOINT PLATE
CONNECTOR PLATE
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
u
u
u
u
u
u
25
50
50
50
50
50
8431927008442
8431927008459
8431927008466
8431927008473
8431927008480
8431927008497
22
22
107
17-24
17-22
17-28-72
SIDE JOINT PLATE
SERRATED HEXAGON FLANGE NUT M 6
PART CLAMP
REINFORCED JOINT PLATE
CONNECTOR PLATE
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
50
50
50
50
50
8431927008503
8431927008510
8431927008527
8431927008534
8431927008541
22
107
17-24
17-22
17-28-72
SIDE JOINT PLATE
SERRATED HEXAGON FLANGE NUT M6
PART CLAMP
REINFORCED JOINT PLATE
CONNECTOR PLATE
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
u
u
u
u
u
50
50
50
50
50
8431927018786
8431927018793
8431927014818
8431927014825
8431927014832
22
107
17-24
17-22
17-28
CONDUIT GLAND BRACKET
CLICK CENTRAL SUSPENSION M 8
CENTRAL HANGING PLATE 9
CEILING FASTENER FOR REJITECH
SPLICE PLATE
SOULDER SCREW C/DIN603 M 6x12
SOULDER SCREW C/DIN603 M 6x20
THREADED ROD M 6x500
THREADED ROD M 6x1000
CLICK CENTRAL SUSPENSION M 6
CENTRAL HANGING PLATE 7
CLICK CENTRAL SUSPENSION M10
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
E.G.
u
u
u
u
u
u
u
u
u
u
u
u
10
20
20
25
10
100
100
50
50
20
20
20
8431927012630
8431927015945
8431927012654
8431927015839
8431927012685
8431927008602
8431927008619
8431927008626
8431927008633
8431927015952
8431927008664
8431927015969
28
40
17-40
54
17-24
107
107
40-88-100
40-88-100
40
100
40
HEXAGONAL SET SCREW M10x60
WASHER M10
HEXAGONAL NUT M10
DATA OUTLET
CONDUIT GLAND BRACKET
BOX SUPPORT FOR REJITECH
CLICK CENTRAL SUSPENSION M 8
THREADED ROD M 8X500
THREADED ROD M 8x1000
CENTRAL HANGING PLATE 9
BEAM CLAMP HANGING ASS
ANGLY TRAY FASTENER
CEILING FASTENER FOR REJITECH
SPLICE PLATE
HEXAGONAL SET SCREW M 6x15
E.G.
E.B.
E.B.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
100
100
100
10
10
10
20
50
50
20
1
10
25
10
100
8431927008718
8431927008725
8431927008732
8431927008749
8431927008756
8431927008763
8431927015976
8431927008770
8431927008787
8431927008794
8431927014672
8431927008824
8431927008831
8431927008848
8431927008855
107
107
107
28
28
54
40
40-88
40-88
17-40
42-90
48
54
17-24
107
64.01
64.010.020
64.010.041
64.010.059
64.010.060
64.010.061
64.010.062
64.02
64.020.030
64.020.041
64.020.059
64.020.060
64.020.061
64.020.062
64.03
64.030.041
64.030.059
64.030.060
64.030.061
64.030.062
64.06
64.060.041
64.060.059
64.060.060
64.060.061
64.060.062
67.01
67.010.040
67.010.043
67.010.046
67.010.052
67.010.053
67.010.099
67.010.100
67.010.140
67.010.141
67.010.143
67.010.144
67.010.243
67.02
67.020.010
67.020.013
67.020.014
67.020.039
67.020.040
67.020.041
67.020.043
67.020.044
67.020.045
67.020.046
67.020.048
67.020.051
67.020.052
67.020.053
67.020.054
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.G.
131
PEMSA-219-109 AL FINAL-REV-
Ref
67.020.055
67.020.058
67.020.059
67.020.061
67.020.062
67.020.063
67.020.065
67.020.067
67.020.077
67.020.079
67.020.083
67.020.084
67.020.086
67.020.092
67.020.095
67.020.098
67.020.100
67.020.140
67.020.141
67.020.143
67.020.145
67.020.146
67.020.243
67.020.610
67.020.611
67.020.612
27/11/09
11:51
Página 24
Description
CHANNEL NUT M 6
CHANNEL NUT M10
HEXAGONAL SET SCREW M10x20
WASHER M10
HEXAGONAL NUT M 8
WASHER M 8
SOULDER SCREW C/ALLEN M10x20
ROD CONNECTOR M 8
HEXAGONAL SET SCREW M10x35
HEXAGONAL NUT M10
WASHER M 8
SERRATED WASHER M 8
SERRATED WASHER M10
HEXAGONAL SET SCREW M 8x65
HEXAGONAL NUT M 8
HEXAGONAL CONE POINT SCREW M10x20
SOULDER SCREW C/DIN603 M 6x20
THREADED ROD M 6x 500
THREADED ROD M 6x1000
CLICK CENTRAL SUSPENSION M 6
THREADED ROD M10x1000
CENTRAL HANGING PLATE 11
CLICK CENTRAL SUSPENSION M10
CLICK DIVIDER PLATE 25
CLICK DIVIDER PLATE 50
CLICK DIVIDER PLATE 80
Finish
Quantity
EAN 13
Page
E.G.
E.G.
E.G.
E.G.
E.B.
E.B.
E.G.
E.B.
E.G.
E.G.
E.G.
PASSIVATED
PASSIVATED
E.G.
E.G.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
E.B.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
m
m
m
100
100
100
100
100
100
50
50
100
100
100
100
100
100
100
10
100
50
50
20
50
20
20
60
48
36
8431927008862
8431927008879
8431927008886
8431927008893
8431927008909
8431927008916
8431927015181
8431927008923
8431927008930
8431927008947
8431927008954
8431927008961
8431927008978
8431927008985
8431927008992
8431927009012
8431927009029
8431927016065
8431927016072
8431927015983
8431927009036
8431927009043
8431927015990
8431927017024
8431927017031
8431927017048
104
104
107
107
107
107
107
40-88
107
107
107
107
107
107
107
107
107
40-88-100
40-88-100
40
40-88
17-40
40
28-68
28-68
28-68
CLICK CENTRAL SUSPENSION M 8
CENTRAL HANGING PLATE 9
SPLICE PLATE
HEAVY DUTY CHANNEL
HEAVY DUTY CHANNEL
HEAVY DUTY CHANNEL
HEAVY DUTY CHANNEL
CEILING BRACKET
VARIABLE CEILING ROD BRACKET
CHANNEL FLOR BOSS
LIGHT DUTY CHANNEL 41
LIGHT DUTY CHANNEL 21
SOULDER SCREW C/DIN603 M 6x12
SOULDER SCREW C/DIN603 M 6x20
CHANNEL BEAM CLAMP
CLICK CENTRAL SUSPENSION M 6
CENTRAL HANGING PLATE 11
ANGLE BRACKET Nº1
ANGLE BRACKET Nº2
TEE PLATE Nº4
TEE PLATE Nº5
SPICE PLATE Nº3
CLAMP 21
CLAMP 41
CLICK CENTRAL SUSPENSION M10
STAND OFF BRACKET 180
STAND OFF BRACKET 350
STAND OFF BRACKET 180
STAND OFF BRACKET 350
CLICK DIVIDER PLATE 25
CLICK DIVIDER PLATE 50
CLICK DIVIDER PLATE 80
HEAVY DUTY PENDANT BOX
HEAVY DUTY PENDANT CHANNEL 500
HEAVY DUTY PENDANT CHANNEL 1000
HEAVY DUTY PENDANT DROP 500
HEAVY DUTY PENDANT DROP 1000
DOUBLE HEAVY DUTY PENDANT DROP 500
DOUBLE HEAVY DUTY PENDANT DROP 1000
H.D.G.
H.D.G.
H.D.G.
P.G.
P.G.
H.D.G.
H.D.G.
P.G.
H.D.G.
H.D.G.
P.G.
P.G.
H.D.G.
H.D.G.
E.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
P.G.
P.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
P.G.
P.G.
P.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
m
m
m
m
u
u
u
m
m
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
m
m
m
u
u
u
u
u
u
u
20
20
10
3
3
3
3
10
1
1
3
3
100
100
1
20
20
1
1
1
1
1
1
1
20
10
10
10
10
60
48
36
1
1
1
1
1
1
1
8431927016003
8431927009050
8431927009067
8431927009074
8431927009081
8431927009098
8431927009104
8431927009128
8431927009135
8431927009142
8431927009159
8431927009166
8431927009210
8431927009227
8431927009234
8431927016010
8431927009241
8431927009258
8431927009265
8431927009272
8431927009289
8431927009296
8431927009302
8431927009319
8431927016027
8431927009326
8431927009333
8431927009340
8431927009357
8431927017055
8431927017062
8431927017079
8431927009401
8431927009418
8431927009425
8431927009432
8431927009449
8431927009456
8431927009463
40
17-40
17-24
104
104
104
104
40-88
40-88
106
104
104
107
107
106
40
17-40
106
106
106
106
106
106
106
40
32-68
32-68
32-68
32-68
28-68
28-68
28-68
48-96
48-96
48-96
48-96
48-96
48-96
48-96
HEXAGONAL NUT M10
CLICK CENTRAL SUSPENSION M 8
THREADED ROD M 8x 500
THREADED ROD M 8x1000
CENTRAL HANGING PLATE 9
SPLICE PLATE
HEAVY DUTY CHANNEL
HEAVY DUTY CHANNEL
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
u
u
u
u
u
u
u
u
100
20
50
50
20
10
3
3
8431927018809
8431927016034
8431927016089
8431927016096
8431927014849
8431927018816
8431927018823
8431927018830
107
40
40
40
17-40
17-24
104
104
67.03
67.030.043
67.030.046
67.030.047
67.030.052
67.030.053
67.030.055
67.030.057
67.030.060
67.030.061
67.030.064
67.030.074
67.030.075
67.030.099
67.030.100
67.030.101
67.030.143
67.030.146
67.030.201
67.030.202
67.030.203
67.030.204
67.030.205
67.030.206
67.030.207
67.030.243
67.030.539
67.030.540
67.030.541
67.030.542
67.030.610
67.030.611
67.030.612
67.030.645
67.030.646
67.030.647
67.030.660
67.030.661
67.030.662
67.030.663
67.06
67.060.014
67.060.043
67.060.044
67.060.045
67.060.046
67.060.053
67.060.055
67.060.057
132
PEMSA-219-109 AL FINAL-REV-
Ref
67.060.058
67.060.062
67.060.063
67.060.064
67.060.100
67.060.141
67.060.143
67.060.145
67.060.146
67.060.243
67.060.541
67.060.542
67.060.610
67.060.611
67.060.612
27/11/09
11:51
Página 25
Description
CHANNEL NUT M10
HEXAGONAL NUT M 8
WASHER M 8
WASHER M10
SOULDER SCREW C/DIN603 M 6x20
THREADED ROD M 6x1000
CLICK CENTRAL SUSPENSION M 6
THREADED ROD M10x1000
CENTRAL HANGING PLATE 11
CLICK CENTRAL SUSPENSION M10
STAND OFF BRACKET 180
STAND OFF BRACKET 360
CLICK DIVIDER PLATE 25
CLICK DIVIDER PLATE 50
CLICK DIVIDER PLATE 80
Finish
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
Quantity
EAN 13
Page
u
u
u
u
u
u
u
u
u
u
m
m
m
m
m
100
100
100
100
100
50
20
50
20
20
10
10
60
48
36
8431927018847
8431927018854
8431927018861
8431927018878
8431927018885
8431927016119
8431927016041
8431927016102
8431927014856
8431927016058
8431927018892
8431927018908
8431927017086
8431927017093
8431927017109
104
107
107
107
107
40
40
40
17-40
40
32
32
28
28
28
u
8431927015860
8431927017017
8431927016126
8431927017529
8431927009647
8431927009654
8431927009661
8431927014719
8431927009678
8431927009685
8431927009692
8431927009708
8431927009715
8431927009722
26
28-68
24-50
26
22
24-72
17
17
50
50
42-88
42-88
42-88
42-88
8431927037046
8431927037053
8431927037060
8431927037077
8431927037084
8431927037091
8431927037107
8431927037114
8431927037121
8431927037138
8431927037145
8431927037152
8431927037169
8431927037176
8431927037183
8431927037190
8431927037206
8431927037213
8431927037220
8431927037237
8431927037244
8431927037251
8431927037268
8431927037275
8431927037282
8431927037299
8431927037305
8431927037312
8431927037329
8431927037336
8431927037343
8431927037350
8431927037367
8431927037374
8431927037381
8431927037398
8431927037404
8431927037411
8431927037428
8431927037435
8431927037442
8431927037459
8431927037466
8431927037473
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
76
76
76
76
76
76
76
76
76
76
76
76
68.00
68.000.010
68.000.020
68.000.032
68.000.040
68.000.049
68.000.052
68.000.058
68.000.059
68.000.060
68.000.065
68.000.721
68.000.722
68.000.731
68.000.732
FIXING SUPPORT FOR REJIBAND
IDENTIFICATION LABEL
EARTH TERMINAL FOR REJIBAND
REJIBAND BOX SUPPORT
WIRE END CAP
ZINC PAINT SPRAY 400 ml
BOLT CUTTER
SPECIAL BOLT CUTTER
FLOOR FOOT
FLOOR FOOT ADHESIVE (A+B)
HORIZONTAL ANGLE HANGER 1,50 / 5
HORIZONTAL ANGLE HANGER 5,00 / 9
VERTICAL ANGLE HANGER 1,50 / 5
VERTICAL ANGLE HANGER 4,00 / 10
PASSIVATED
PASSIVATED
PASSIVATED
PASSIVATED
u
u
u
u
20
50
20
20
100
1
1
1
100
1
100
100
100
100
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
u
u
u
u
u
u
70.02
70.020.110
70.020.115
70.020.120
70.020.130
70.020.210
70.020.215
70.020.220
70.020.230
70.020.240
70.020.250
70.020.260
70.020.320
70.020.330
70.020.340
70.020.350
70.020.360
70.022.110
70.022.115
70.022.120
70.022.130
70.022.210
70.022.215
70.022.220
70.022.230
70.022.240
70.022.250
70.022.260
70.022.320
70.022.330
70.022.340
70.022.350
70.022.360
70.023.110
70.023.115
70.023.120
70.023.130
70.023.210
70.023.215
70.023.220
70.023.230
70.023.240
70.023.250
70.023.260
70.023.320
BEND 90º CLICK 35x100
BEND 90º CLICK 35x150
BEND 90º CLICK 35x200
BEND 90º CLICK 35x300
BEND 90º CLICK 60x100
BEND 90º CLICK 60x150
BEND 90º CLICK 60x200
BEND 90º CLICK 60x300
BEND 90º CLICK 60x400
BEND 90º CLICK 60x500
BEND 90º CLICK 60x600
BEND 90º CLICK 85x200
BEND 90º CLICK 85x300
BEND 90º CLICK 85x400
BEND 90º CLICK 85x500
BEND 90º CLICK 85x600
TEE CLICK 35x100
TEE CLICK 35x150
TEE CLICK 35x200
TEE CLICK 35x300
TEE CLICK 60x100
TEE CLICK 60x150
TEE CLICK 60x200
TEE CLICK 60x300
TEE CLICK 60x400
TEE CLICK 60x500
TEE CLICK 60x600
TEE CLICK 85x200
TEE CLICK 85x300
TEE CLICK 85x400
TEE CLICK 85x500
TEE CLICK 85x600
SIDE ENTRY CLICK 35x100
SIDE ENTRY CLICK 35x150
SIDE ENTRY CLICK 35x200
SIDE ENTRY CLICK 35x300
SIDE ENTRY CLICK 60x100
SIDE ENTRY CLICK 60x150
SIDE ENTRY CLICK 60x200
SIDE ENTRY CLICK 60x300
SIDE ENTRY CLICK 60x400
SIDE ENTRY CLICK 60x500
SIDE ENTRY CLICK 60x600
SIDE ENTRY CLICK 85x200
133
PEMSA-219-109 AL FINAL-REV-
Ref
70.023.330
70.023.340
70.023.350
70.023.360
70.024.110
70.024.115
70.024.120
70.024.130
70.024.210
70.024.215
70.024.220
70.024.230
70.024.240
70.024.250
70.024.260
70.024.320
70.024.330
70.024.340
70.024.350
70.024.360
70.025.110
70.025.115
70.025.120
70.025.130
70.025.210
70.025.215
70.025.220
70.025.230
70.025.240
70.025.250
70.025.260
70.025.320
70.025.330
70.025.340
70.025.350
70.025.360
70.026.110
70.026.115
70.026.120
70.026.130
70.026.210
70.026.215
70.026.220
70.026.230
70.026.240
70.026.250
70.026.260
70.026.320
70.026.330
70.026.340
70.026.350
70.026.360
70.028.110
70.028.115
70.028.120
70.028.130
70.028.210
70.028.215
70.028.220
70.028.230
27/11/09
11:51
Página 26
Description
SIDE ENTRY CLICK 85x300
SIDE ENTRY CLICK 85x400
SIDE ENTRY CLICK 85x500
SIDE ENTRY CLICK 85x600
CROSSOVER CLICK 35x100
CROSSOVER CLICK 35x150
CROSSOVER CLICK 35x200
CROSSOVER CLICK 35x300
CROSSOVER CLICK 60x100
CROSSOVER CLICK 60x150
CROSSOVER CLICK 60x200
CROSSOVER CLICK 60x300
CROSSOVER CLICK 60x400
CROSSOVER CLICK 60x500
CROSSOVER CLICK 60x600
CROSSOVER CLICK 85x200
CROSSOVER CLICK 85x300
CROSSOVER CLICK 85x400
CROSSOVER CLICK 85x500
CROSSOVER CLICK 85x600
INSIDE RISER CLICK 35x100
INSIDE RISER CLICK 35x150
INSIDE RISER CLICK 35x200
INSIDE RISER CLICK 35x300
INSIDE RISER CLICK 60x100
INSIDE RISER CLICK 60x150
INSIDE RISER CLICK 60x200
INSIDE RISER CLICK 60x300
INSIDE RISER CLICK 60x400
INSIDE RISER CLICK 60x500
INSIDE RISER CLICK 60x600
INSIDE RISER CLICK 85x200
INSIDE RISER CLICK 85x300
INSIDE RISER CLICK 85x400
INSIDE RISER CLICK 85x500
INSIDE RISER CLICK 85x600
OUTSIDE RISER CLICK 35x100
OUTSIDE RISER CLICK 35x150
OUTSIDE RISER CLICK 35x200
OUTSIDE RISER CLICK 35x300
OUTSIDE RISER CLICK 60x100
OUTSIDE RISER CLICK 60x150
OUTSIDE RISER CLICK 60x200
OUTSIDE RISER CLICK 60x300
OUTSIDE RISER CLICK 60x400
OUTSIDE RISER CLICK 60x500
OUTSIDE RISER CLICK 60x600
OUTSIDE RISER CLICK 85x200
OUTSIDE RISER CLICK 85x300
OUTSIDE RISER CLICK 85x400
OUTSIDE RISER CLICK 85x500
OUTSIDE RISER CLICK 85x600
ADJUSTABLE BEND CLICK 35x100
ADJUSTABLE BEND CLICK 35x150
ADJUSTABLE BEND CLICK 35x200
ADJUSTABLE BEND CLICK 35x300
ADJUSTABLE BEND CLICK 60x100
ADJUSTABLE BEND CLICK 60x150
ADJUSTABLE BEND CLICK 60x200
ADJUSTABLE BEND CLICK 60x300
Finish
Quantity
EAN 13
Page
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8431927037480
8431927037497
8431927037503
8431927037510
8431927037527
8431927037534
8431927037541
8431927037558
8431927037565
8431927037572
8431927037589
8431927037596
8431927037602
8431927037619
8431927037626
8431927037633
8431927037640
8431927037657
8431927037664
8431927037671
8431927037688
8431927037695
8431927037701
8431927037718
8431927037725
8431927037732
8431927037749
8431927037756
8431927037763
8431927037770
8431927037787
8431927037794
8431927037800
8431927037817
8431927037824
8431927037831
8431927037848
8431927037855
8431927037862
8431927037879
8431927037886
8431927037893
8431927037909
8431927037916
8431927037923
8431927037930
8431927037947
8431927037954
8431927037961
8431927037978
8431927037985
8431927037992
8431927043832
8431927043849
8431927043856
8431927043863
8431927043870
8431927043887
8431927043894
8431927043900
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
72
72
72
72
72
72
72
72
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8431927038005
8431927038012
8431927038029
8431927038036
8431927038043
8431927038050
8431927038067
8431927038074
8431927038081
8431927038098
8431927038104
8431927038111
8431927038128
8431927038135
8431927038142
8431927038159
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
70.03
70.030.110
70.030.115
70.030.120
70.030.130
70.030.210
70.030.215
70.030.220
70.030.230
70.030.240
70.030.250
70.030.260
70.030.320
70.030.330
70.030.340
70.030.350
70.030.360
134
90º BEND CLICK 35x100
90º BEND CLICK 35x150
90º BEND CLICK 35x200
90º BEND CLICK 35x300
90º BEND CLICK 60x300
90º BEND CLICK 60x150
90º BEND CLICK 60x200
90º BEND CLICK 60x300
90º BEND CLICK 60x400
90º BEND CLICK 60x500
90º BEND CLICK 60x600
90º BEND CLICK 85x200
90º BEND CLICK 85x300
90º BEND CLICK 85x400
90º BEND CLICK 85x500
90º BEND CLICK 85x600
PEMSA-219-109 AL FINAL-REV-
Ref
70.032.110
70.032.115
70.032.120
70.032.130
70.032.210
70.032.215
70.032.220
70.032.230
70.032.240
70.032.250
70.032.260
70.032.320
70.032.330
70.032.340
70.032.350
70.032.360
70.033.110
70.033.115
70.033.120
70.033.130
70.033.210
70.033.215
70.033.220
70.033.230
70.033.240
70.033.250
70.033.260
70.033.320
70.033.330
70.033.340
70.033.350
70.033.360
70.034.110
70.034.115
70.034.120
70.034.130
70.034.210
70.034.215
70.034.220
70.034.230
70.034.240
70.034.250
70.034.260
70.034.320
70.034.330
70.034.340
70.034.350
70.034.360
70.035.110
70.035.115
70.035.120
70.035.130
70.035.210
70.035.215
70.035.220
70.035.230
70.035.240
70.035.250
70.035.260
70.035.320
70.035.330
70.035.340
70.035.350
70.035.360
70.036.110
70.036.115
70.036.120
70.036.130
70.036.210
70.036.215
70.036.220
70.036.230
70.036.240
70.036.250
70.036.260
70.036.320
70.036.330
70.036.340
70.036.350
27/11/09
11:51
Página 27
Description
TEE CLICK 35x100
TEE CLICK 35x150
TEE CLICK 35x200
TEE CLICK 35x300
TEE CLICK 60x100
TEE CLICK 60x150
TEE CLICK 60x200
TEE CLICK 60x300
TEE CLICK 60x400
TEE CLICK 60x500
TEE CLICK 60x600
TEE CLICK 85x200
TEE CLICK 85x300
TEE CLICK 85x400
TEE CLICK 85x500
TEE CLICK 85x600
SIDE ENTRYCLICK 35x100
SIDE ENTRYCLICK 35x150
SIDE ENTRYCLICK 35x200
SIDE ENTRYCLICK 35x300
SIDE ENTRYCLICK 60x100
SIDE ENTRYCLICK 60x150
SIDE ENTRYCLICK 60x200
SIDE ENTRYCLICK 60x300
SIDE ENTRYCLICK 60x400
SIDE ENTRYCLICK 60x500
SIDE ENTRYCLICK 60x600
SIDE ENTRYCLICK 85x200
SIDE ENTRYCLICK 85x300
SIDE ENTRYCLICK 85x400
SIDE ENTRYCLICK 85x500
SIDE ENTRYCLICK 85x600
CROSSOVER CLICK 35x100
CROSSOVER CLICK 35x150
CROSSOVER CLICK 35x200
CROSSOVER CLICK 35x300
CROSSOVER CLICK 60x100
CROSSOVER CLICK 60x150
CROSSOVER CLICK 60x200
CROSSOVER CLICK 60x300
CROSSOVER CLICK 60x400
CROSSOVER CLICK 60x500
CROSSOVER CLICK 60x600
CROSSOVER CLICK 85x200
CROSSOVER CLICK 85x300
CROSSOVER CLICK 85x400
CROSSOVER CLICK 85x500
CROSSOVER CLICK 85x600
INSIDE RISER CLICK 35x100
INSIDE RISER CLICK 35x150
INSIDE RISER CLICK 35x200
INSIDE RISER CLICK 35x300
INSIDE RISER CLICK 60x100
INSIDE RISER CLICK 60x150
INSIDE RISER CLICK 60x200
INSIDE RISER CLICK 60x300
INSIDE RISER CLICK 60x400
INSIDE RISER CLICK 60x500
INSIDE RISER CLICK 60x600
INSIDE RISER CLICK 85x200
INSIDE RISER CLICK 85x300
INSIDE RISER CLICK 85x400
INSIDE RISER CLICK 85x500
INSIDE RISER CLICK 85x600
OUTSIDE RISER CLICK 35x100
OUTSIDE RISER CLICK 35x150
OUTSIDE RISER CLICK 35x200
OUTSIDE RISER CLICK 35x300
OUTSIDE RISER CLICK 60x100
OUTSIDE RISER CLICK 60x150
OUTSIDE RISER CLICK 60x200
OUTSIDE RISER CLICK 60x300
OUTSIDE RISER CLICK 60x400
OUTSIDE RISER CLICK 60x500
OUTSIDE RISER CLICK 60x600
OUTSIDE RISER CLICK 85x200
OUTSIDE RISER CLICK 85x300
OUTSIDE RISER CLICK 85x400
OUTSIDE RISER CLICK 85x500
Finish
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
Quantity
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
EAN 13
8431927038166
8431927038173
8431927038180
8431927038197
8431927038203
8431927038210
8431927038227
8431927038234
8431927038241
8431927038258
8431927038265
8431927038272
8431927038289
8431927038296
8431927038302
8431927038319
8431927038326
8431927038333
8431927038340
8431927038357
8431927038364
8431927038371
8431927038388
8431927038395
8431927038401
8431927038418
8431927038425
8431927038432
8431927038449
8431927038456
8431927038463
8431927038470
8431927038487
8431927038494
8431927038500
8431927038517
8431927038524
8431927038531
8431927038548
8431927038555
8431927038562
8431927038579
8431927038586
8431927038593
8431927038609
8431927038616
8431927038623
8431927038630
8431927038647
8431927038654
8431927038661
8431927038678
8431927038685
8431927038692
8431927038708
8431927038715
8431927038722
8431927038739
8431927038746
8431927038753
8431927038760
8431927038777
8431927038784
8431927038791
8431927038807
8431927038814
8431927038821
8431927038838
8431927038845
8431927038852
8431927038869
8431927038876
8431927038883
8431927038890
8431927038906
8431927038913
8431927038920
8431927038937
8431927038944
Page
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
135
PEMSA-219-109 AL FINAL-REV-
Ref
70.036.360
70.038.110
70.038.115
70.038.120
70.038.130
70.038.210
70.038.215
70.038.220
70.038.230
27/11/09
11:51
Página 28
Description
OUTSIDE RISER CLICK 85x600
ADJUSTABLE BEND CLICK 35x100
ADJUSTABLE BEND CLICK 35x150
ADJUSTABLE BEND CLICK 35x200
ADJUSTABLE BEND CLICK 35x300
ADJUSTABLE BEND CLICK 60x100
ADJUSTABLE BEND CLICK 60x150
ADJUSTABLE BEND CLICK 60x200
ADJUSTABLE BEND CLICK 60x300
Finish
Quantity
EAN 13
Page
H.D.G.
H.D.G.
H.D.G.
H.D.G
H.D.G
H.D.G
H.D.G
H.D.G
H.D.G
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
8431927038951
8431927043917
8431927043924
8431927043931
8431927043948
8431927043955
8431927043962
8431927043979
8431927043986
78
72
72
72
72
72
72
72
72
UNIVERSAL BRACKET PEMSABAND
P.G.
u
10
8431927009739
72-100
UNIVERSAL BRACKET PEMSABAND
H.D.G.
u
10
8431927009746
72-100
10
8431927009753
70
70.42
70.420.911
70.43
70.430.911
71.00
71.000.000
PROTECTOR FOR ENDS & EDGES
71.02
71.020.300
71.020.400
71.020.500
71.020.600
71.021.005
71.021.006
71.021.007
71.022.005
71.022.006
71.022.007
71.022.062
71.023.005
CENTRAL JOINER 300
CENTRAL JOINER 400
CENTRAL JOINER 500
CENTRAL JOINER 600
JOINER 35
RISER/DROPER 35
REDUCER PEMSABAND 35
JOINER 60
RISER/DROPER 60
REDUCER PEMSABAND 60
90º BEND INDUCANAL
JOINER 85
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
10
10
10
10
50
4
4
50
4
4
1
25
8431927009760
8431927009777
8431927009784
8431927009791
8431927009814
8431927009821
8431927009838
8431927010056
8431927010063
8431927010070
8431927010087
8431927013019
68
68
68
68
68
70
70
68-100
70
70
100
68
CENTRAL JOINER 300
CENTRAL JOINER 400
CENTRAL JOINER 500
CENTRAL JOINER 600
JOINER 35
RISER/DROPER 35
REDUCER PEMSABAND 35
JOINER 60
RISER/DROPER 60
REDUCER PEMSABAND 60
JOINER 85
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
u
u
u
u
u
u
10
10
10
10
50
4
4
50
4
4
25
8431927010414
8431927010421
8431927010438
8431927010445
8431927010469
8431927010476
8431927010483
8431927010704
8431927010711
8431927010728
8431927013026
68
68
68
68
68
70
70
68
70
70
68
90º BEND COVER INDUCANAL
P.G.
u
1
8431927011060
100
BEND COVER 90º CLICK 100
BEND COVER 90º CLICK 150
BEND COVER 90º CLICK 200
BEND COVER 90º CLICK 300
BEND COVER 90º CLICK 400
BEND COVER 90º CLICK 500
BEND COVER 90º CLICK 600
COVER 60x3 m
COVER 100x3 m
COVER 150x3 m
COVER 200x3 m
COVER 300x3 m
COVER 400x3 m
COVER 500x3 m
COVER 600x3 m
TEE COVER CLICK 100
TEE COVER CLICK 150
TEE COVER CLICK 200
TEE COVER CLICK 300
TEE COVER CLICK 400
TEE COVER CLICK 500
TEE COVER CLICK 600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
m
m
m
m
m
m
m
m
u
u
u
u
u
u
u
1
1
1
1
1
1
1
24
24
12
12
6
6
6
6
1
1
1
1
1
1
1
8431927038968
8431927038982
8431927038975
8431927038999
8431927039002
8431927039019
8431927039026
8431927016133
8431927016140
8431927016157
8431927016164
8431927016171
8431927016188
8431927016195
8431927016201
8431927039033
8431927039040
8431927039057
8431927039064
8431927039071
8431927039088
8431927039095
74
74
74
74
74
74
74
28-70-100
28-70
28-70
28-70
28-70
28-70
28-70
28-70
74
74
74
74
74
74
74
71.03
71.030.300
71.030.400
71.030.500
71.030.600
71.031.005
71.031.006
71.031.007
71.032.005
71.032.006
71.032.007
71.033.005
72.02
72.020.062
73.02
73.020.100
73.020.150
73.020.200
73.020.300
73.020.400
73.020.500
73.020.600
73.021.060
73.021.100
73.021.150
73.021.200
73.021.300
73.021.400
73.021.500
73.021.600
73.022.100
73.022.150
73.022.200
73.022.300
73.022.400
73.022.500
73.022.600
136
PEMSA-219-109 AL FINAL-REV-
Ref
73.023.100
73.023.150
73.023.200
73.023.300
73.023.400
73.023.500
73.023.600
73.024.100
73.024.150
73.024.200
73.024.300
73.024.400
73.024.500
73.024.600
73.025.100
73.025.150
73.025.200
73.025.300
73.025.400
73.025.500
73.025.600
73.026.100
73.026.150
73.026.200
73.026.300
73.026.400
73.026.500
73.026.600
27/11/09
11:51
Página 29
Description
Finish
Quantity
EAN 13
Page
SIDE ENTRY COVER CLICK 100
SIDE ENTRY COVER CLICK 150
SIDE ENTRY COVER CLICK 200
SIDE ENTRY COVER CLICK 300
SIDE ENTRY COVER CLICK 400
SIDE ENTRY COVER CLICK 500
SIDE ENTRY COVER CLICK 600
CROSSOVER CLICK COVER 100
CROSSOVER CLICK COVER 150
CROSSOVER CLICK COVER 200
CROSSOVER CLICK COVER 300
CROSSOVER CLICK COVER 400
CROSSOVER CLICK COVER 500
CROSSOVER CLICK COVER 600
INSIDE RISER COVER CLICK 100
INSIDE RISER COVER CLICK 150
INSIDE RISER COVER CLICK 200
INSIDE RISER COVER CLICK 300
INSIDE RISER COVER CLICK 400
INSIDE RISER COVER CLICK 500
INSIDE RISER COVER CLICK 600
OUTSIDE RISER COVER CLICK 100
OUTSIDE RISER COVER CLICK 150
OUTSIDE RISER COVER CLICK 200
OUTSIDE RISER COVER CLICK 300
OUTSIDE RISER COVER CLICK 400
OUTSIDE RISER COVER CLICK 500
OUTSIDE RISER COVER CLICK 600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8431927039101
8431927039118
8431927039125
8431927039132
8431927039149
8431927039156
8431927039163
8431927039170
8431927039187
8431927039194
8431927039200
8431927039217
8431927039224
8431927039231
8431927039248
8431927039255
8431927039262
8431927039279
8431927039286
8431927039293
8431927039309
8431927039316
8431927039323
8431927039330
8431927039347
8431927039354
8431927039361
8431927039378
76
76
76
76
76
76
76
76
76
76
76
76
76
76
78
78
78
78
78
78
78
78
78
78
78
78
78
78
BEND COVER 90º CLICK 100
BEND COVER 90º CLICK 150
BEND COVER 90º CLICK 200
BEND COVER 90º CLICK 300
BEND COVER 90º CLICK 400
BEND COVER 90º CLICK 500
BEND COVER 90º CLICK 600
COVER 60x3 m
COVER 100x3 m
COVER 150x3 m
COVER 200x3 m
COVER 300x3 m
COVER 400x3 m
COVER 500x3 m
COVER 600x3 m
TEE COVER CLICK 100
TEE COVER CLICK 150
TEE COVER CLICK 200
TEE COVER CLICK 300
TEE COVER CLICK 400
TEE COVER CLICK 500
TEE COVER CLICK 600
SIDE ENTRY COVER CLICK 100
SIDE ENTRY COVER CLICK 150
SIDE ENTRY COVER CLICK 200
SIDE ENTRY COVER CLICK 300
SIDE ENTRY COVER CLICK 400
SIDE ENTRY COVER CLICK 500
SIDE ENTRY COVER CLICK 600
CROSSOVER CLICK COVER 100
CROSSOVER CLICK COVER 150
CROSSOVER CLICK COVER 200
CROSSOVER CLICK COVER 300
CROSSOVER CLICK COVER 400
CROSSOVER CLICK COVER 500
CROSSOVER CLICK COVER 600
INSIDE RISER COVER CLICK 100
INSIDE RISER COVER CLICK 150
INSIDE RISER COVER CLICK 200
INSIDE RISER COVER CLICK 300
INSIDE RISER COVER CLICK 400
INSIDE RISER COVER CLICK 500
INSIDE RISER COVER CLICK 600
OUTSIDE RISER COVER CLICK 100
OUTSIDE RISER COVER CLICK 150
OUTSIDE RISER COVER CLICK 200
OUTSIDE RISER COVER CLICK 300
OUTSIDE RISER COVER CLICK 400
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
u
u
u
u
u
u
u
m
m
m
m
m
m
m
m
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
u
1
1
1
1
1
1
1
24
24
12
12
6
6
6
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8431927039385
8431927039392
8431927039408
8431927039415
8431927039422
8431927039439
8431927039446
8431927016218
8431927016225
8431927016232
8431927016249
8431927016256
8431927016263
8431927016270
8431927016287
8431927039453
8431927039460
8431927039477
8431927039484
8431927039491
8431927039507
8431927039514
8431927039521
8431927039538
8431927039545
8431927039552
8431927039569
8431927039576
8431927039583
8431927039590
8431927039606
8431927039613
8431927039620
8431927039637
8431927039644
8431927039651
8431927039668
8431927039675
8431927039682
8431927039699
8431927039705
8431927039712
8431927039729
8431927039736
8431927039743
8431927039750
8431927039767
8431927039774
74
74
74
74
74
74
74
28-70
28-70
28-70
28-70
28-70
28-70
28-70
28-70
74
74
74
74
74
74
74
76
76
76
76
76
76
76
76
76
76
76
76
76
76
78
78
78
78
78
78
78
78
78
78
78
78
73.03
73.030.100
73.030.150
73.030.200
73.030.300
73.030.400
73.030.500
73.030.600
73.031.060
73.031.100
73.031.150
73.031.200
73.031.300
73.031.400
73.031.500
73.031.600
73.032.100
73.032.150
73.032.200
73.032.300
73.032.400
73.032.500
73.032.600
73.033.100
73.033.150
73.033.200
73.033.300
73.033.400
73.033.500
73.033.600
73.034.100
73.034.150
73.034.200
73.034.300
73.034.400
73.034.500
73.034.600
73.035.100
73.035.150
73.035.200
73.035.300
73.035.400
73.035.500
73.035.600
73.036.100
73.036.150
73.036.200
73.036.300
73.036.400
137
PEMSA-219-109 AL FINAL-REV-
Ref
73.036.500
73.036.600
27/11/09
11:51
Página 30
Description
Finish
Quantity
EAN 13
Page
OUTSIDE RISER COVER CLICK 500
OUTSIDE RISER COVER CLICK 600
H.D.G.
H.D.G.
u
u
1
1
8431927039781
8431927039798
78
78
COVER 60x3 m
COVER 100x3 m
COVER 150x3 m
COVER 200x3 m
COVER 300x3 m
COVER 400x3 m
COVER 500x3 m
COVER 600x3 m
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
S.S.316
m
m
m
m
m
m
m
m
24
24
12
12
6
6
6
6
8431927016294
8431927016300
8431927016317
8431927016324
8431927016331
8431927016348
8431927016355
8431927016362
28
28
28
28
28
28
28
28
PEMSABAND INDUCANAL
P.G.
m
24
8431927011862
99
PEMSABAND SX PERFORATED 85x200
PEMSABAND SX PERFORATED 85x300
PEMSABAND SX PERFORATED 85x400
PEMSABAND SX PERFORATED 85x500
PEMSABAND SX PERFORATED 85x600
PEMSABAND SX PERFORATED 100x200
PEMSABAND SX PERFORATED 100x300
PEMSABAND SX PERFORATED 100x400
PEMSABAND SX PERFORATED 100x500
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
6
6
6
6
6
6
6
6
6
8431927012708
8431927012715
8431927012722
8431927012739
8431927012746
8431927036995
8431927043696
8431927037008
8431927043702
60
60
60
60
60
60
60
60
60
PEMSABAND SX PERFORATED 35x100
PEMSABAND SX PERFORATED 35x150
PEMSABAND SX PERFORATED 35x200
PEMSABAND SX PERFORATED 35x300
PEMSABAND SX PERFORATED 35x400
PEMSABAND SX PERFORATED 35x500
PEMSABAND SX PERFORATED 35x600
PEMSABAND SX PERFORATED 60x100
PEMSABAND SX PERFORATED 60x150
PEMSABAND SX PERFORATED 60x200
PEMSABAND SX PERFORATED 60x300
PEMSABAND SX PERFORATED 60x400
PEMSABAND SX PERFORATED 60x500
PEMSABAND SX PERFORATED 60x600
PEMSABAND SX PERFORATED 85x200
PEMSABAND SX PERFORATED 85x300
PEMSABAND SX PERFORATED 85x400
PEMSABAND SX PERFORATED 85x500
PEMSABAND SX PERFORATED 85x600
PEMSABAND SX PERFORATED 100x200
PEMSABAND SX PERFORATED 100x300
PEMSABAND SX PERFORATED 100x400
PEMSABAND SX PERFORATED 100x500
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
24
12
12
12
6
6
6
24
12
12
6
6
6
6
6
6
6
6
6
6
6
6
6
8431927011985
8431927011992
8431927012005
8431927012012
8431927041555
8431927041562
8431927041579
8431927012029
8431927012036
8431927012043
8431927012050
8431927012067
8431927012074
8431927012081
8431927012753
8431927012760
8431927012777
8431927012784
8431927012791
8431927043719
8431927043726
8431927043733
8431927043740
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
PEMSABAND SX SOLID 85x200
PEMSABAND SX SOLID 85x300
PEMSABAND SX SOLID 85x400
PEMSABAND SX SOLID 85x500
PEMSABAND SX SOLID 85x600
PEMSABAND SX SOLID 100x200
PEMSABAND SX SOLID 100x300
PEMSABAND SX SOLID 100x400
PEMSABAND SX SOLID 100x500
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
6
6
6
6
6
6
6
6
6
8431927012807
8431927012814
8431927012821
8431927012838
8431927012845
8431927043757
8431927043764
8431927043771
8431927043788
63
63
63
63
63
63
63
63
63
PEMSABAND SX SOLID 35x100
PEMSABAND SX SOLID 35x150
PEMSABAND SX SOLID 35x200
PEMSABAND SX SOLID 35x300
PEMSABAND SX SOLID 35x400
PEMSABAND SX SOLID 35x500
PEMSABAND SX SOLID 35x600
PEMSABAND SX SOLID 60x100
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
24
12
12
12
6
6
6
24
8431927012852
8431927012869
8431927012876
8431927012883
8431927041586
8431927041593
8431927041609
8431927012890
64
64
64
64
64
64
64
64
73.06
73.061.060
73.061.100
73.061.150
73.061.200
73.061.300
73.061.400
73.061.500
73.061.600
75.12
75.122.060
75.22
75.223.200
75.223.300
75.223.400
75.223.500
75.223.600
75.224.200
75.224.300
75.224.400
75.224.500
75.23
75.231.100
75.231.150
75.231.200
75.231.300
75.231.400
75.231.500
75.231.600
75.232.100
75.232.150
75.232.200
75.232.300
75.232.400
75.232.500
75.232.600
75.233.200
75.233.300
75.233.400
75.233.500
75.233.600
75.234.200
75.234.300
75.234.400
75.234.500
75.42
75.423.200
75.423.300
75.423.400
75.423.500
75.423.600
75.424.200
75.424.300
75.424.400
75.424.500
75.43
75.431.100
75.431.150
75.431.200
75.431.300
75.431.400
75.431.500
75.431.600
75.432.100
138
PEMSA-219-109 AL FINAL-REV-
Ref
75.432.150
75.432.200
75.432.300
75.432.400
75.432.500
75.432.600
75.433.200
75.433.300
75.433.400
75.433.500
75.433.600
75.434.200
75.434.300
75.434.400
75.434.500
27/11/09
11:51
Página 31
Description
PEMSABAND SX SOLID 60x150
PEMSABAND SX SOLID 60x200
PEMSABAND SX SOLID 60x300
PEMSABAND SX SOLID 60x400
PEMSABAND SX SOLID 60x500
PEMSABAND SX SOLID 60x600
PEMSABAND SX SOLID 85x200
PEMSABAND SX SOLID 85x300
PEMSABAND SX SOLID 85x400
PEMSABAND SX SOLID 85x500
PEMSABAND SX SOLID 85x600
PEMSABAND SX SOLID 100x200
PEMSABAND SX SOLID 100x300
PEMSABAND SX SOLID 100x400
PEMSABAND SX SOLID 100x500
Finish
Quantity
EAN 13
Page
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
12
12
6
6
6
6
6
6
6
6
6
6
6
6
6
8431927012906
8431927012913
8431927012920
8431927012937
8431927012944
8431927012951
8431927012968
8431927012975
8431927012982
8431927012999
8431927013002
8431927043795
8431927043801
8431927043818
8431927043825
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
PEMSABAND SX CLICK PERFORATED 35x100
PEMSABAND SX CLICK PERFORATED 35x150
PEMSABAND SX CLICK PERFORATED 35x200
PEMSABAND SX CLICK PERFORATED 35x200
PEMSABAND SX CLICK PERFORATED 35x400
PEMSABAND SX CLICK PERFORATED 35x500
PEMSABAND SX CLICK PERFORATED 35x600
PEMSABAND SX CLICK PERFORATED 60x100
PEMSABAND SX CLICK PERFORATED 60x150
PEMSABAND SX CLICK PERFORATED 60x200
PEMSABAND SX CLICK PERFORATED 60x200
PEMSABAND SX CLICK PERFORATED 60x400
PEMSABAND SX CLICK PERFORATED 60x500
PEMSABAND SX CLICK PERFORATED 60x600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
24
12
12
12
6
6
6
24
12
12
6
6
6
6
8431927034922
8431927034939
8431927034946
8431927034953
8431927041616
8431927041623
8431927041630
8431927016416
8431927016423
8431927016430
8431927034960
8431927041647
8431927041654
8431927041661
60
60
60
60
60
60
60
60
60
60
60
60
60
60
PEMSABAND SX CLICK SOLID 35x100
PEMSABAND SX CLICK SOLID 35x150
PEMSABAND SX CLICK SOLID 35x200
PEMSABAND SX CLICK SOLID 35x300
PEMSABAND SX CLICK SOLID 35x400
PEMSABAND SX CLICK SOLID 35x500
PEMSABAND SX CLICK SOLID 35x600
PEMSABAND SX CLICK SOLID 60x100
PEMSABAND SX CLICK SOLID 60x150
PEMSABAND SX CLICK SOLID 60x200
PEMSABAND SX CLICK SOLID 60x300
PEMSABAND SX CLICK SOLID 60x400
PEMSABAND SX CLICK SOLID 60x500
PEMSABAND SX CLICK SOLID 60x600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
24
12
12
12
6
6
6
24
12
12
6
6
6
6
8431927034977
8431927034984
8431927034991
8431927035004
8431927041678
8431927041685
8431927041692
8431927016737
8431927016744
8431927016751
8431927035011
8431927041708
8431927041715
8431927041722
63
63
63
63
63
63
63
63
63
63
63
63
63
63
PEMSABAND LX CLICK PERFORATED 35x100
PEMSABAND LX CLICK PERFORATED 35x150
PEMSABAND LX CLICK PERFORATED 35x200
PEMSABAND LX CLICK PERFORATED 35x300
PEMSABAND LX CLICK PERFORATED 35x400
PEMSABAND LX CLICK PERFORATED 35x500
PEMSABAND LX CLICK PERFORATED 35x600
PEMSABAND LX CLICK PERFORATED 60x100
PEMSABAND LX CLICK PERFORATED 60x150
PEMSABAND LX CLICK PERFORATED 60x200
PEMSABAND LX CLICK PERFORATED 60x300
PEMSABAND LX CLICK PERFORATED 60x400
PEMSABAND LX CLICK PERFORATED 60x500
PEMSABAND LX CLICK PERFORATED 60x600
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
840
504
420
252
288
240
138
720
492
360
204
180
156
72
8431927040541
8431927040558
8431927040565
8431927040572
8431927040589
8431927040596
8431927040602
8431927040619
8431927040626
8431927040633
8431927040640
8431927040657
8431927040664
8431927040671
67
67
67
67
67
67
67
67
67
67
67
67
67
67
PEMSABAND RX PERFORATED 60x100
PEMSABAND RX PERFORATED 60x200
PEMSABAND RX PERFORATED 60x300
PEMSABAND RX PERFORATED 60x400
PEMSABAND RX PERFORATED 60x500
PEMSABAND RX PERFORATED 60x600
PEMSABAND RX PERFORATED 85x200
PEMSABAND RX PERFORATED 85x300
PEMSABAND RX PERFORATED 85x400
PEMSABAND RX PERFORATED 85x500
PEMSABAND RX PERFORATED 85x600
PEMSABAND RX PERFORATED 100x200
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
m
m
m
24
12
6
6
6
6
6
6
6
6
6
6
TO CONSULT
8431927043023
8431927043030
8431927043047
8431927043054
8431927043061
8431927043078
8431927043085
8431927043092
8431927043108
8431927043115
8431927043122
65
65
65
65
65
65
65
65
65
65
65
65
75.52
75.521.100
75.521.150
75.521.200
75.521.300
75.521.400
75.521.500
75.521.600
75.522.100
75.522.150
75.522.200
75.522.300
75.522.400
75.522.500
75.522.600
75.62
75.621.100
75.621.150
75.621.200
75.621.300
75.621.400
75.621.500
75.621.600
75.622.100
75.622.150
75.622.200
75.622.300
75.622.400
75.622.500
75.622.600
75.82
75.821.100
75.821.150
75.821.200
75.821.300
75.821.400
75.821.500
75.821.600
75.822.100
75.822.150
75.822.200
75.822.300
75.822.400
75.822.500
75.822.600
76.12
76.122.100
76.122.200
76.122.300
76.122.400
76.122.500
76.122.600
76.123.200
76.123.300
76.123.400
76.123.500
76.123.600
76.124.200
139
PEMSA-219-109 AL FINAL-REV-
Ref
76.124.300
76.124.400
76.124.500
27/11/09
11:51
Página 32
Description
Finish
Quantity
EAN 13
Page
PEMSABAND RX PERFORATED 100x300
PEMSABAND RX PERFORATED 100x400
PEMSABAND RX PERFORATED 100x500
P.G.
P.G.
P.G.
m
m
m
6
6
6
8431927043139
8431927043146
8431927043153
65
65
65
PEMSABAND RX PERFORATED 60x100
PEMSABAND RX PERFORATED 60x200
PEMSABAND RX PERFORATED 60x300
PEMSABAND RX PERFORATED 60x400
PEMSABAND RX PERFORATED 60x500
PEMSABAND RX PERFORATED 60x600
PEMSABAND RX PERFORATED 85x200
PEMSABAND RX PERFORATED 85x300
PEMSABAND RX PERFORATED 85x400
PEMSABAND RX PERFORATED 85x500
PEMSABAND RX PERFORATED 85x600
PEMSABAND RX PERFORATED 100x200
PEMSABAND RX PERFORATED 100x300
PEMSABAND RX PERFORATED 100x400
PEMSABAND RX PERFORATED 100x500
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
24
12
6
6
6
6
6
6
6
6
6
6
6
6
6
TO CONSULT
8431927043160
8431927043177
8431927043184
8431927043191
8431927043207
8431927043214
8431927043221
8431927043238
8431927043245
8431927043252
8431927043269
8431927043276
8431927043283
8431927043290
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
PEMSABAND RX SOLID 60x200
PEMSABAND RX SOLID 60x300
PEMSABAND RX SOLID 60x400
PEMSABAND RX SOLID 60x500
PEMSABAND RX SOLID 60x600
PEMSABAND RX SOLID 100x200
PEMSABAND RX SOLID 100x300
PEMSABAND RX SOLID 100x400
PEMSABAND RX SOLID 100x500
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
P.G.
m
m
m
m
m
m
m
m
m
6
6
6
6
6
6
6
6
6
8431927043481
8431927043498
8431927043504
8431927043511
8431927043528
8431927043535
8431927043542
8431927043559
8431927043566
66
66
66
66
66
66
66
66
66
PEMSABAND RX SOLID 60x200
PEMSABAND RX SOLID 60x300
PEMSABAND RX SOLID 60x400
PEMSABAND RX SOLID 60x500
PEMSABAND RX SOLID 60x600
PEMSABAND RX SOLID 100x200
PEMSABAND RX SOLID 100x300
PEMSABAND RX SOLID 100x400
PEMSABAND RX SOLID 100x500
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
H.D.G.
m
m
m
m
m
m
m
m
m
6
6
6
6
6
6
6
6
6
8431927043573
8431927043580
8431927043597
8431927043603
8431927043610
8431927043627
8431927043634
8431927043641
8431927043658
66
66
66
66
66
66
66
66
66
8431927012203
8431927014689
26
26-72
76.13
76.132.100
76.132.200
76.132.300
76.132.400
76.132.500
76.132.600
76.133.200
76.133.300
76.133.400
76.133.500
76.133.600
76.134.200
76.134.300
76.134.400
76.134.500
76.32
76.323.200
76.323.300
76.323.400
76.323.500
76.323.600
76.324.200
76.324.300
76.324.400
76.324.500
76.33
76.333.200
76.333.300
76.333.400
76.333.500
76.333.600
76.334.200
76.334.300
76.334.400
76.334.500
89.01
89.010.000
89.011.000
140
IDENTIFICATION PLATE
REJIFIX BLACK
u
50
ROLL 1
General
Catalogue
Origin, development and current position
Pemsa was founded in Madrid in 1969, and today it is a company engaged in
the manufacture of metal tray and channel systems for the support and
management of medium and low voltage electric cables, as well as the
manufacture of flexible tubing, connectors, compression glands and accessories.
Pemsa heads the ranking of Spanish manufacturers of metal cable trays and
is second at the European level as manufacturer of wire mesh cable trays of
electrically welded steel. Moreover, Pemsa is one of the top 10 leading European
manufacturers.
New facilities
At the end of 2002, the company
inaugurated its new facilities at Alcalá
de Henares, (Madrid). The current
surface area exceeds 45,000 m2, of
which 10,500 m2 consists of building
space, including 1500 m2 assigned
to offices and administrative
departments.The new factory is
equipped with the most modern
technology available in the world today. This technology also extends to the
warehouse and central offices, which include the various commercial and
marketing departments, the Technical Office, Production, Quality, Exports,
Logistics and Customer Service. The capacity of these new facilities may be
doubled in the future.
Metal tray and channel system for
cod. CYNW. E305934
F o r f u r t h e r i n f o r m a t i o n re g a rd i n g t h e s e c e r t i f i c a t e s p l e a s e c h e c k w i t h i n t h e d o c u m e n t .
Catalogue Nº 219
SUBSIDIARIES:
PEMSA UK:
Unit 2. Hunslet Trading Estate
Severn Road, LEEDS LS10 1BL
Tel.: 0113 277 9090
Fax.: 0113 277 5939
sales@pemsa.co.uk
Metal tray and channel system for cable support and management
PEMSA PORTUGAL:
Estrada de Polima. Centro Industrial de
Abóboda Edificio Fase 2. 2ºK
2785-543 São Domingos de Rana
Tel: +351 21 444 5725
Fax: +351 21 444 5727
pemsa.portugal@pemsa-rejiband.com
PEMSA FRANCE:
ZI Le clos aux pois. 12 Rue de la Closerie,
91090 LISSES
Tél.: 01 60 86 75 65
Telécopie: 01 60 87 11 83
service-client@pemsa.fr
www.pemsa.fr
HEADQUARTERS:
PEMSA SPAIN:
Galileo Galilei, 22-24. P.E. La Garena
28806 Alcalá de Henares. Madrid
Tel: +34 91 802 34 88
Fax: +34 91 802 33 81
info@pemsa-rejiband.com
Cable Management System
Metal tray and channel system
for cable support and management
www.pemsa-rejiband.com
cod. CYNW. E305934
F o r f u r t h e r i n f o r m a t i o n re g a rd i n g t h e s e c e r t i f i c a t e s p l e a s e c h e c k w i t h i n t h e d o c u m e n t .
Depósito Legal: M-12392-2008
Catalogue Nº 219
E-mail: info@pemsa-rejiband.com
General Catalogue

Similar documents

NEW - Aste

NEW - Aste Its design prevents the accumulation of dust and dirt. It provides maximum cleanliness and faster and easier handling. The reduction in installation time exceeds 55%, given that it has been designe...

More information

pemsaband® Sheet steel trays - Pemsa Cable Management Systems

pemsaband® Sheet steel trays - Pemsa Cable Management Systems (*) T he hot dip galvanized finish is NOT AN ACCURATE AESTHETIC FINISH. It is a very effective corrosion protection. COLOUR DIFFERENCES CAN OCCUR (shades of grey), brightness and surface finish

More information