Standard Specifications For Private Sewer Laterals
Transcription
Standard Specifications For Private Sewer Laterals
BUILDING SERVICES DEPARTMENT 250 Frank H. Ogawa Plaza, 2nd Floor, Oakland, CA 94612 Inspection Services: 510.238.3443 FAX: 510.238.2263 Standard Specifications For Private Sewer Laterals APPROVED MATERIALS LIST City of Oakland 2012 Table of Contents • • • • • • • • • • • • • • • • • • • Approved materials Inspections House sewer 4”-6” Couplings Bedding and Backfill Guidelines for CSLM for VC pipe ASTM C 12 Installing VC ASTM D 2321 Installation of underground thermoplastic pipe Main Sewer Taps Standard cover for upper and lower laterals GeoTexti1e Fabric Reinforced Concrete utility boxes Concrete Curing Compounds Ready mix designs j Main sewer Taps Water and Sewer Separation Sewer Overflow Devices and Backwater vavles Cleanouts Legislation for protected trees and Overflow prevention devices 1). APPROVED Extra strength Vitrified Clay Standards ASTM-C700 with ASTM-C425 Bell and spigot polyurethane joints Plain end ASTM-C700 with 4 band shear ring coupling (type Z) approved on private property Local Manufacturer-Mission Clay 2) APPROVED Cast Iron Soil Pipe Standards -ASTM A 74 for Hub and Spigot Cast Iron Soil pipe and ASTM A746 for fittings. NSF marking ensures compliance with t relevant standards. No-Hub ~ ASTM 888 CISPI 301. NSF marking ensures compliance with relevant standards. 4 band shear coupling for underground installations. Above ground may be 2 banded shear coupling (CISPI 310 and NSF) MANUFACTURES- AB&I, Charlotte foundry, Tyler Pipe Couplings - Anaco and Ideal 3) APPROVED PVC SDR 26 IPS ASTM D3034 ASTM F477 bell and spigot joints Schedule 40 ASTM Dl785 & ASTM D2655 (NO cellular core pipe is permitted) Solvent welded on private property only. Not permitted in public right of way or sewer easement. 4) APPROVED HDPE SDR 17 DIPS with fused joints ASTM D3035 F714 HDPE SHALL ONLY BE USED WHEN PIPE BURSTING AND TRENCHLESS SEWERS 5) APPROVED DUCTILE IRON PIPE Class 52 thickness class-350 psi pressure class Cement or Ceramic epoxy lined (US PIPE PROTECTO 401) AWWA C 151 and AWWA C200 Joints shall conform to AWWA C 111 for push on and Mechanical joints and AWWA C110 for flanged joints Local Manufacture-US Pipe and Foundry 6) APRROVED ABS PIPE Schedule 40 ABS shall meet ASTM D2661 standards for solid core pipe and fittings. Solvent cement shall meet ASTM 2235. (NO cellular core pipe is permitted) Solvent welded on private property only. Not permitted on sewer in public right of way. The use of cellular core ABS or PVC pipe shall be rejected. Inspections: All piping shall be bedded and haunched to the spring line of the pipe for inspection. All markings and ASTM makings shall be visible on top of pipe to verify correct standards. HOUSE SEWERS 4”-6” Material Types: pipe 1) Cast Iron Service weight Bell and Spigot or No Hub CI installed with 4 band shear couplings below ground. Above ground installation of NO HUB CI may be made with approved 2 band shear couplings. All CI shall be Poly encased in Public Right of Way or sewer easement. 2) PVC SDR 26 IPS bell and spigot solid wall and Schedule 40 PVC, solvent weld (on private property only). The use of ABS to PVC transition GLUE prohibited. Use approved 4 band shear coupling . 3) VCP Extra Heavy with Bell and Spigot or plain end with shear ring couplings. 4) DIP class 52 thickness, 350 psi class. Bell and Spigot, mechanical or flanged joints. Poly encased in Public Right of way or sewer easement. 5) HDPE SDR 17 DIPS with fused joints (allowed for trenchless only). 6) ABS Schedule 40 ABS, solvent weld (on private property only). The use of ABS to PVC transition GLUE is Prohibited. Use approved 4 band shear coupling. ALL piping shall be installed without stress and to approved standards. COUPLINGS All underground transitions to dissimilar materials shall be made with 4 band u shear couplings. Above ground transitions may be made with approved 2 band shear couplings. Approved Couplings for Transitions to dissimilar materials & underground NO HUB installations: Husky 4 clamp shielded coupling (80 in-lb) Anaco No-Hub 4 clamp shielded coupling (60 in-lb) Fernco No-Hub 4 clamp shielded coupling, Silver (60 in-lb), Yellow and Green (80 inlb) Fernco 4 clamp shielded coupling Strong back RC Couplings, (60 in-lb) Fernco 50004 clamp shielded coupling Series RC Coupling, (60 in-lb) Mission adjustable 4 clamp shielded repair coupling coupling. APPROVED ABOVE GROUND (60 in-lb) NO-HUB TO NO-HUB COUPLINGS: Ideal 2 banded shielded coupling, CISPI 310 and NSF Anaco 2 banded shielded coupling, CISPI 310 and NSF (shown below) 6 Couplings Material Type(s): Banded Rubber Couplings Description: For repairs, alterations and house sewers with connections of dissimilar materials. Banded rubber couplings shall have four (4) clamps and metal shear bands. Manufacturer: Manufacturers included but are not limited to: 1. 2. 3. 4. Note: Fernco® Mission® Husky® Anaco® Check with Inspector prior to purchase of material to insure proper coupling is selected for the different pipe types encountered. Mission® Band Seal Fernco® Proflex Coupling Joints® Calder Coupling Anaco 2-Banded (60 in-lb) 7 Husky® 4 Clamp Coupling (80 in-lb) Fernco® Strong Back RC Couplings Fernco® No-Hub Couplings Silver (60 in-lb) Yellow & Green (80 in-lb) Fernco® Stainless Steel Shear Rings (60 in-lb) Fernco® 5000 Series RC Couplings Mission® Adjustable Repair Coupling Anaco No Hub (60 in-lb) 8 Approved High Density Polyethylene Couplings Friatec® Frialen Electrofusion Coupling 9 Standard cover requirements for upper and lower laterals Upper laterals are collection to the building drain at the structure and do not cross into the Public right of way or sewer easements’. The lower lateral is the portion of the sewer that is installed in the Public right of way. Only contractors with a C 42 sewer license or A contractor is permitted to work in the right of way. Pipe cover limitation tables First table is for upper laterals on private property without loading. Plain end VC is approved with shear ring couplings on upper laterals. For upper laterals under driveway, use Lower lateral table Size 4”– 6” 4”– 6” 4”– 6” 4”– 6” 4”– 6” 4”– 6” 4”– 6” Size 4”– 6” 4”– 6” 4”– 6” 4”– 6” 4”– 6” UPPER LATERAL TABLE Min. Material depth ABS Schedule 40 Solid Core 2.5 VC C700 Sewer pipe 2.5 CI SVandNohub 1.5 DI Class 52 1 PVC SDR26 IPS 2.5 HPDE SDR 17 DIPS 2.5 PVC Schedule 40 Solid Core 2.5 LOWER LATERAL TABLE Min. Material depth VC C700 Bell and spigot only 5 CI* Service weight and No Hub 4 DI* Class 52 1 PVC SDR26 IPS 5 HDPE SDR 17 DIPS 5 Max. depth 24 30 30 30 24 24 24 Max. depth 30 30 30 24 24 * ALL DIP AND CI SHALL BE POLY ENCASED IN PUBLIC EASEMENT Standard enclosed All NO HUB Underground Couplings shall be Heavy Duty shear with 4 bands. Reinforced Concrete Utility Boxes Material Type(s): Traffic Area Non-Traffic Area Utility boxes for traffic and non-traffic areas ITEM DESCRIPTION 12" x 12" Drain Box 10-3/8" I.D. x 12" Valve Box Cast Iron Grate (3/8" Max Spacing) H/20 Loading 8" I.D. x 12" Valve Box 8-1/2" I.D. x 11-3/4" Drain Box 10-5/8" I.D. x 17-1/4" Drain Box PRODUCT Christy® V12 Box Christy® or Jensen® G5 Traffic Valve Christy® V12-71W Welded Grate Christy® or Jensen® F8 Box Christy® V1 Drain Box Christy® V9 Drain Box Christy® V1-71C Grate Cast Iron Grate 3/4" Max Spacing and V9-71C Grate Christy® V12 Box Christy® V12-71W Welded Grate Christy® G5 Box Christy® K-6004 Grate (Special Order) Christy® F8 Box Christy® V1-71C Grate 17 TAPS Material types: Taps The portion of the lower lateral in the right-of-way or public easement shall be installed at a 90-degree angle to the sewer main with a wye-connection oriented in the direction of flow in the main. The wye-connection shall be installed a minimum of 3 feet from a manhole, and 5 feet from a lamp-hole (sewer main clean-out). The minimum horizontal distances between adjacent sewer lateral connections shall be: a) Laterals on the same side of the street/sewer 10(ten) feet b) Laterals on the opposiste side of the street/sewer 5 (five) feet Tap materials for the corresponding main sewer ACP RCP CIP, DIP HDPE VCP Fowler saddle Insert a wye Fowler saddle Sealtite type “S” saddle with 4 band coupling Insert a wye Insert a wye All other taps shall be performed by Tap-tite or Roto rooter. Where possible, taps shall be installed above the springline of pipe at an angle not to exceed 45 degrees from the horizontal. Effort shall be made to install tap fitting and saddles with a 45 degree (wye) configuration to facilitate continuous flow velocities into the main. Straight taps can cause hydraulic jump which can cause solids to drop off and accumulate in the main. TRANSVERSE SECTION 45˚ min. Lower lateral 45˚ max. 8 in. main 1/8 bend Coupling Min. slope 2% without special approval Saddle Sewer main SADDLE CONNECTION DETAIL Radial connection CONNECTION AT MAIN Notes: 1. When a lateral sewer is installed in advance of the building sewer, it shall be terminated with a cap or plug 5’ past the property line, easement line or last improvement and the Contractor shall mark the location of the capped/plugged end with a 2x4 pressure treated stake painted green. 2. Refer to section 15.02205 for bedding and backfill requirements. 3. See note 2 on DWG-25 for cover requirements Criteria For The Separation Of Water Main & Gravity Sanitary Sewers DOHS Memo # 2003-201 Special permission 2 Parallel Construction Special pipe Plan View 1 Water Main B A P 6 ft. 3 ft. 1 ft. Grade Grade Special pipe Crossing SIDE View C No joints P 6 in. 5 ft. 4 ft. 4 ft. 5 ft. 6 in. 1 ft. P D ZONE “A”: Sewer lines not permitted without approval of AHJ (Authority Having Jurisdiction) ZONE “B”: Permitted Materials: • VC pipe with compression joints • PVC pipe with rubber ring joints (ASTM 3034) • C1 or 01 pipe with compo joints • Rc pressure pipe with compo joints • HDPE pipe with fusion welded Joints (AWWA C906-99) • Spirally-reinforced HDPE pipe with gasketed joints (ASTM F-984) ZONE “C”: Permitted Materials: • DI Pipe with hot dip bituminous coating • C-900 PVC (DR 14). Continuous section centered over pipe being crossed • RC pressure pipe. Continuous section centered over pipe being crossed • Any sewer pipe within a continuous sleeve • HDPE pipe with fusion welded joints (AWWA C906-99) ZONE “D”: Permitted Materials: • DI pipe with hot dip bituminous coating & mechanical joints • HDPE pipe with fusion-welded joints (AWWA C906-99) • C-900 PVC (DR 14) continuous section centered over pipe being crossed • RC pressure pipe continuous section centered over pipe being crossed • Any sewer pipe within a continuous sleeve ZONE “P”: NOT PERMITTED EBMUD Private Sewer Lateral Ordinance How to Prevent Backup from City Main & Protect Your Home Backwater Device Drainage piping serving fixtures on a floor, where the floor level is located BELOW the elevation of the next upstream manhole cover of the public/private sewer system, shall be protected from the backflow of sewage by installing anapproved Backwater Valve. Section 710.1 UPC ☑ NOTE: Fixtures located on a floor, where the floor level is located ABOVE the next uphill manhole cover elevation shall not discharge through a Backwater Valve. Cleanout Finish grade 2nd floor ABOVE manhole 1st floor BELOW manhole Manhole cover Backwater device Second floor drain bypasses backwater valve Box & cover containing backwater valve Building sewer Public sewer To public sewer No water in building sewer, flap opens by gravity, rests against ledge BUILDING SERVICES DEPARTMENT 250 Frank H. Ogawa Plaza, 2nd Floor, Oakland, CA 94612 Inspection Services: 510.238.3443 FAX: 510.238.2263 Discharge from building into building sewer, flaw swings upward, letting discharge flow through To building Sewage backflow into building sewer, is stopped by flap directing sewage flow into device, building is protected Illustrations ©2012 Code Check EBMUD Private Sewer Lateral Ordinance How to Prevent Backup from City Main & Protect Your Home Things to Consider when Replacing Sewer Laterals in Multistory Dwellings When owners of a multistory dwelling are required to replace their private sewer lateral, it may be determined that the lowest floor is below the upstream manhole cover. This condition can cause flooding of the building if the sewer main has a blockage. 1 2 Current code requires that only fixtures below the manhole cover drain through the backwater valve. This prevents occupants on upper floors from flooding the lower floor accidently. Since this would require an expensive re-plumbing of existing buildings, the city will require the use of a sewer overflow device in addition to a backwater valve to prevent both a backup from the main City sewer and the accidental flooding of the lower floor by owners unaware that there is a blockage in the sewer. It will also protect the building in case of blockages in their own private sewer lateral 1 Sewer overflow device 3 2 Backwater valve BUILDING SERVICES DEPARTMENT 250 Frank H. Ogawa Plaza, 2nd Floor, Oakland, CA 94612 Inspection Services: 510.238.3443 FAX: 510.238.2263 6 in. min. Finish grade 2 3 in. min. Standard cleanout 4 in. min. Backwater valve Flap prevents water entry Lowest floor in structure 1 Sewer overflow device Finish grade 6 in. min. 3 2 ft. max. to bldg. 6 in. min. 3 in. min. 4 in. min. Cast in place concrete Water pressure raises ball, water escapes through bell 2 ft. max. to bldg. Remove standard cleanout plug 4 in. min. Ball seated Lowest floor in structure Pop-up ball to elimate emission of odors & access of rodents see lower left drawing A sewer overflow device per the approved materials list is required on ALL side sewer connections and repairs and/or alternations on existing side sewers. The specific location of the sewer overflow device shall be determined by the contractor and the property owner such that the top location of the overflow device is a minimum of 6 inches below the lowest finished floor elevation of the connected building. 3 6 in. min. (typical) Standard cleanout 4 in. min. Illustrations ©2012 Code Check Overflow Protection Devices Material Type(s): Overflow Protection Devices (OPD) Description: Overflow protection devices prevent sewage from entering homes and businesses and reroute the spill outside the building. Manufacturer: MANUFACTURER Extendable Backwater Valve Mainline Backflow PRODUCT NAME Products Rector Seal Adapt-a-valve Inspection Chamber with Test-Eze Gate Feature Clean Check Backwater Valve Kelly Backwater Device (No-Hub & IPS) Sewer Popper™ Model S62-304 "Mushroom" Genplex Sewer Popper™ Stephens Corp Relief Cap Unlimited Home Solutions LLC (www.unlimitedhomesolutions.com) Sewer Relief Cap Extendable Backwater Valves ABS PVC Sewer Popper™ OPD “Mushroom” OPD Sewer Relief Cap 11