Safety Bus System AS-Interface Safety at Work

Transcription

Safety Bus System AS-Interface Safety at Work
Safety Bus System
AS-Interface Safety at Work
R
S
C
OR
AS-Interface Safety at Work ®
AS-Interface SaW
Easy, safe and reliab
2
AS-Interface Safety at Work
(SaW) is the first safety bus
system based upon the open
standard of AS-International.
Safety components such as
Emergency Stop command
devices, safety switches, solenoid interlocks or safety light
curtains are simply connected
to the yellow AS-Interface cable.
For the evaluation of the safety
signals a “Safety Monitor” is
merely added to the AS-Interface system.
Safe transmission mechanism
The communication protocol for
safety relevant applications is
based on the unchanged ASInterface Standard transmission.
With each AS-Interface master
call each safety device answers
in return with a preset data telegram. This information is analysed and in case of a deviation
from the pre-set values the
enabling paths are opened. The
maximum response time for a
safe shutdown is 40 ms.
AS-Interface Standard in
accordance with EN 50295
With the integration of AS-Interface SaW the AS-Interface network will continue to operate
unchanged. The well known
components, like the standard
AS-Interface master, the standard power supply as well as the
AS-Interface yellow cable will
still form the basis of all ASInterface installations. Therefore
an existing machine can easily
be equipped with additional
AS-i SaW components.
Cost reduction with
AS-Interface Safety at Work
Reduce cost and installation
time – A never ending story.
During installation and machine
commissioning as well as during
maintenance, AS-Interface SaW
supports the user with integrated system diagnosis. It provides detailed information about
the cause and place of the failure, and enables the user to
quickly find and analyse a malfunction and therefore minimise
machine downtime. With ASInterface Safety at Work you
can directly reduce your cost.
The heart of safety
The safety monitor analyses all
transmitted information from
each safety device on the ASInterface network and, in case of
a safety device being activated
or in case of a fault in one of the
safety devices, the safety monitor immediately shuts down to
create a safe condition. The
safety monitor is equipped with
one or two redundant pairs of
enabling paths for applications
up to Control Category 4 according to EN 954-1.
Each safety function of the monitor can be set with a simple drag
& drop software. Afterwards the
configuration is downloaded into
the safety monitor and protected
with a password.
More flexibility with
AS-Interface Safety at Work
For the realisation of individual
safety solutions, SCHMERSAL
offers the maximum amount of
flexibility with its diverse range
of safety devices. Depending on
the application the user can
choose the optimal solution out
of an extensive product basket.
As AS-Interface SaW is an open
system, the user has also the
possibility to include additional
Safety components from other
suppliers. AS-Interface Safety
at Work fulfils the safety requirements to the highest standards.
R
S
C
OR
ble
No further settings are required
at each of the safety devices,
the bulky parallel wire cables
between the safety devices in
the field and the switching cabinet
are reduced and wiring time is
decreased. The power supply
for all safety sensors is supplied
over the single yellow AS-Interface cable.
Less installation time with
AS-Interface Safety at Work
Easier and quicker with ASInterface SaW: Choose a Safety
device – Connect it to the yellow
AS-Interface cable – Configure
the safety function in the safety
monitor. – That’s it.
AS-Interface Safety at Work overview
Controller
AS-i
Power
Safety
guard
monitoring
AS-i
Master
Safety
monitor
Position
switch
E-Stop
Command
Two-Hand
Control
AS-Interface SaW
System Features
• Up to 31 standard and
safety slaves on the
AS-Interface system
• No Safety PLC
necessary
• Safety-relevant signals
can be allocated into
groups and multiple
Safety monitors may
be connected
• Response time is
max. 40 ms
• Safety-relevant signals
can be integrated into
plant diagnostics
• Certified up to Control
Category 4 in accordance
with EN 954-1
• Certified by the TÜV
(German Technical
Inspectorate)
Safety
light curtain
Standard AS-Interface Module
3
AS-Interface Safety at Work ®
AS-Interface SaW
AS-i Safety at Work
4
STIHL AG & Co., Waiblingen
Hydro Aluminium, Raufoss
Production line with global
safety concept
Fast configuring,
higher transparency
For its new chain guide production unit at the Waiblingen plant,
STIHL, world leader in the production of chain saws, chose an
innovative safety concept. All
stations of the production line –
both the “in-house” manufactured and the nine third-party
machines – should have a
uniform safety standard and
communicate through AS-i SaW.
The Raufoss plant of the Norwegian Hydro concern produces
every year thousands of aluminium shock absorbers for the
automobile industry. As production is regarded, the company
considers safety of paramount
importance as well: all safety
components at the machines
and plants are equipped with
AS-Interface Safety at Work
(AS-i SaW).
This concept was successfully
implemented. STIHL requested
its suppliers to use the AS-i SaW
switchgear from Schmersal.
More than 110 safety switching
appliances were installed: 68 by
Stihl, 45 by the suppliers.
Basically two types are used:
the AZM 161 AS solenoid interlock and the BNS 33 AS safety
sensor with integrated ASi SaW
interface.
Paul Giesinger, Electrical Construction Manager of the „Machine and Device Centre“ from
STIHL AG & Co: „The ASi SaW
components only require a minimum of wiring compared to the
traditional safety switching
appliances. The comfortable
software moreover allows for a
smooth parametrering of the
safety functions.“
With AS-i SaW, Hydro Aluminium
could save a lot of money as the
wiring costs were regarded.
Another important issue was the
simplified configuration of the
safety appliances through PC.
The safety functions simply can
be chosen and configured by
Drag & Drop and then can be
copied to multiple safety switching appliances if required.
Ola Överstad, project manager
of the New Process & Production Equipment Division at the
Raufoss plant: „The increased
transparency was one of the
main reasons why we chose the
AS-i solution. At all times, the
asimon software keeps me informed about newly installed safety
components. This is particularly
advantageous when transferring
the safety systems from one
shift to another. In this way, the
safety engineers always have
100% control over the system.“
R
S
C
OR
applications
Benz & Hilgers GmbH, Neuss
Installation costs reduced
by 30%
Benz & Hilgers (Benhil) at Neuss
is specialised in packaging machines for pasteurised products.
For the new series of wrapping
machines, e.g. for butter, Benhil
has decided to use the safety-related communication technology.
During a thorough analysis of
the different systems available,
AS-i SaW revealed itself as a
highly economical solution, as
the safety signals are transmitted
through the same cable as the
conventional sensor-actor signals. This decision furthermore
was facilitated as Schmersal,
Benhil’s usual partner for safety
components, offered a comprehensive program of safety
switchgear with integrated
AS-i SaW interface.
Dipl.-Ing Ralph Bellin, Electrical
Site Manager at Benhil’s: „We
essentially chose AS-i SaW because of the simplified mounting
possibilities. As the burden of
the costs is enormous in our
field, we must save money
wherever we can, including on
the installation costs. Safetyrelated bus systems are valuable
in this regard: with AS-i SaW,
the installation costs were reduced by 30%. For the future
generations of our machines,
we will use AS-i SaW as well.“
Magurit Gefrierschneider
GmbH, Remscheid
Optimal signal transmission
between control cabinet and
machine
The company Magurit Gefrierschneider GmbH produces
slicers, mincers and shredders
for food industry. As these highcapacity machines are equipped
with extremely sharp and powerful cutting devices to cut up
fresh and frozen products, the
risk of injury is very high.
Furthermore, in food industry,
high hygienic standards have to
be maintained and simplicity of
cleaning must be provided.
Therefore, the different machine
compartments are equipped
with flaps and large sliding
guards, whose position is monitored by concealed-mounted
safety sensors.
When it became necessary to
install the control cabinet at
approximately 60 meters from
the machine, Magurit decided to
use safety switching appliances
with AS-i SaW interface. Nine
different types of safety switching
appliances were installed and
connected to the bus cable. The
safety-monitoring module is
installed in the control cabinet.
Dipl.-Ing. Dino Vieth, Electrical
Site Manager of Magurit: „The
reduction of the wiring costs is
not the sole advantage of the
safety bus. It also provides the
user with improved diagnostic
possibilities, considering that
many operational conditions can
be documented and inquired.“
5
AS-Interface Safety at Work
R
S
ASM
C
OR
Technical data
Standards:
Control category:
Enclosure:
Mounting:
Screw terminals:
Protection class:
• Safety monitor
• Control Category 4 to EN 954-1
• Monitor for AS-i SaW compatible safety device, i.e. safety switches, solenoid interlocks,
Emergency-Stop buttons,
2-Hand control, light grid and light curtains
• AS-i connection
• One or two redundant pairs
of enabling paths
• Additional outputs (transistor,
short-circuit proof)
• Configurable functions: AND logical
element, OR logical element,
Start devices, Start-up test
• Edge-sensitive start push button
• Feedback circuit to monitor
external contactors
• LED status display
EN 50295, EN 61496-1 (1997), IEC/EN 60204-1, EN 954-1, IEC 61508
4
Polyamide PA 66, black
snaps onto standard DIN rail to EN 50022
max. 2.5 mm2 (incl. conductor ferrules)
terminals IP 20
enclosure IP 20
Ub:
24 VDC ± 15 %
Residual ripple:
< 15%
Ib:
ASM E1-R2: 0,15 A
ASM E2-R2/R2: 0,2 A
Switch-on peak current:
600 mA
AS-Interface operating voltage:
18.5 ... 31.6 V
AS-Interface operating current:
< 45 mA
AS-Interface specification:
Profile - Monitor 7.F
Configuration interface:
RS232: 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits
Inputs:
1.Y1,1.Y2
Input signal:
„Y1, Y2“: le < 10 mA at 24 VDC (opto coupler, high-active)
Outputs:
ASM E1-R2: 1.13/14,1.23/24, 1 enabling path (redundant);
ASM E2-R2/R2: 1.13/14,1.23/24, 2.13/14, 2.23/24,
2 enabling paths (redundant)
Utilisation category:
AC-15, DC-13
Ie/Ue:
3 A / 230 VAC
1 A / 24 VDC
Switching voltage:
max. 230 VAC
Ithe:
3 A per output circuit
Max. fuse rating:
4 A (slow blow), external
Additional outputs:
transistor outputs, 200 mA total,
short-circuit proof-type, positive-switching
Switch-on time:
< 10 s
Response time:
< 40 ms
Indications:
AS-Interface: voltage LED green,
communication LED red;
Enabling paths: LED green, yellow, red
EMC rating:
conforming to EMC Directive
Overvoltage category:
III to DIN VDE 0110
Resistance to vibration:
5 ... 500 Hz
(5 … 26 Hz, 0.75 mm amplitude;
26 … 500 Hz, 2g)
Resistance to shock:
15 g / 11 ms
Ambient temperature:
– 20 °C … + 60 ºC
Storage and transport temperature:
– 30 °C … + 70 ºC
Weight:
ASM E1-R2: approx. 350 g;
ASM E2-R2/R2: approx. 450 g
Abmessungen:
45 x 105 x 120 mm
Inductive loads (e.g. contactors, relays, etc.) are
Note:
to be suppressed by means of a suitable circuit.
Approvals
F
C
Ordering details
ASM E ➀
No.
Replace
Description
➀
1-R2
1 enabling field
(redundant)
2 enabling fields
(redundant)
2-R2/R2
6
Note
The safety monitors ASM E1-R2 and ASM E2-R2/R2 evaluate all transmitted information from
each safety device on the AS-Interface network. For the safe guarding of different applications
various AS-Interface Safety at Work compatible safety devices are needed, i.e. safety switches,
solenoid interlocks, safety sensors, E-stop buttons as well as safe input modules.
The AS-Interface Safety at Work can be used in applications up to control category 4 according
to EN 954-1 with the appropriate safety devices and systems.
AS-Interface Safety at Work
R
S
• The installation of different safety areas is
possible with numerous safety monitors
working alongside each other. The maximum
number of safety devices including the safety
monitors may not exceed 31 participants.
• The allocation of the safety devices to one or
more safety monitors is achieved with the
help of the configuration software ”asimon“.
• The wiring diagram shows the safety monitor
ASM E2-R2/R2 with start-pushbuttons and
feedback loops.
• No safety devices are displayed, because
they are installed in the field i.e. on the safety
guards itself. The data connection between
the safety monitor and the decentralised
safety slaves is established via the ASInterface network.
• For the operation of AS-Interface Safety at
Work system, a standard controller, an ASInterface Master and AS-Interface power
supply, must always be used in the
application.
• With the RJ 45 connector the safety monitor
is configured and started up.
OR
Wiring diagram
+ 24 VDC
+ 24 VDC
0V
L1
S2
S1
AS-iAS-i+
M1
AS-i+ AS-i-
1Y1
ASInterface
1Y2
2Y1
1.32
2Y2
M2
2.32
1.13
1.23
2.13
2.23
1.14
1.24
2.14
2.24
K1
K3
RJ 45
Note
C
RS
232
K2
K4
24 V
L+
M
FE
2.14
2.24
L1 L2 L3
K5
+ 24 VDC
K6
0V
L1 L2 L3
K7
K5
K7
K8
K6
K8
N
M
3
N
M
3
• Start push button H
A start push button (NO) can optionally be
connected to the ASM. With the guard
door(s) closed, the enabling paths are then
not closed until the start push button has
been operated. If neither start button nor
feedback circuit are required, then no
connections are required to the terminals
(1Y1/2, 2Y1/2).
• Output expander module
For additional contacts by means of more
enabling paths and potential-free indication
contacts an output expander module is
connected to the safety monitor, i.e. to the
internal ASM enabling path. For the control
of the additional outputs the ASM feedback
loop is utilised.
Note
Further information and details of the safety
monitor ASM are available on the asimonCD-ROM.
Note
The AS-i system limitations according to EN 50295 have to be concidered during the planning,
development and design phase of the AS-i network, especially the max. number of AS-i slaves
and the total „yellow“ cable length (< 100 m without repeater).
7
AS-Interface Safety at Work
R
S
asimon
C
OR
System components
Following the successful configuration and
download, the safety monitor and the safety
devices can be tested and monitored with
asimon.
The asimon software is a tool for the
configuration and commissioning of the
AS-Interface safety monitor.
The configuration of the safety monitor and its
safety devices, i.e. E-Stop buttons, solenoid
interlocks, safety switches, 2-Hand controls,
light curtains etc. is performed by an easyto-use graphical interface. Thus providing
safeguarding of hazardous areas present by
power-driven machinery.
The following functions are available with
the asimon software:
• Configuration of different safety devices
• Configuration of start-modules
• Configuration logical combinations
(AND, OR, RS Flip-Flops)
• Configuration of the feedback loops
• Configuration of the operating methods
• Configuration of the system-modules
• Print out of Configuration protocol
Download cable ASM-DC1
Asimon can be used offline as well as online
during development and project planning.
The configuration files can be saved and
loaded as desired.
The software is compatibable with the
Microsoft® operating system
Windows 95/98/ME/NT/2000/XP.
Configuration cable ASM-KC1
The asimon offers the user a library of icons
representing different safety devices and other
functional devices, i.e. one or two independent
enabling paths, automatic or monitored start,
stop category 0 or 1 etc. For the implementation of a new safety application the required
safety devices are selected from the icon
library, configured and assigned to the
respective enabling path.
Approvals
F
C
Ordering details
Note
ASM-startup-package:
SET ASM-SWP
Configuration and diagnostic
software package with
online documentation on
CD-ROM, a configurationand downloadcable
asimon software package:
Configuration and diagnostic
software package with online
documentation on CD-ROM
ASM-CD
Hardware requirements:
• 200 MHz INTEL Pentium® or
AMD® Processor or quicker
• Min. 8 Mbyte free main memory (RAM)
• Min. 8 Mbyte free hard disk memory
• A CD-ROM drive (or 3 1/2 “ disc drive)
for the installation
• A mouse
• A free serial interface with
9 SubD-connection
Software requirements:
• Microsoft Windows ® 95/98/ME/NT/2000/XP
8
Ordering details
Download cable:
Interface cable with
two RJ 45 connectors,
Length: 0.10 m
ASM-DC1
Configuration cable:
Interface cable with one RJ 45
and SUBD 9 connector,
Length: 1.2 m
ASM-KC1
AS-Interface Safety at Work
R
S
T.. 235-AS
Design:
Enclosure:
Switching system:
10
3,5
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
25
4,3
6
12
8,5
OR
Technical data
Standards:
63,5
C
20
20
20
22
22
13,5
30
30
• Position switch
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector, adjustable
• Metal enclosure
• Wide range of alternative actuators
• Actuator heads can be repositioned
by 4 x 90°
• Angle of roller lever adjustable in 10° steps
• Good resistance to oil and petroleum spirit
• Protection class IP 67
EN 50295
EN 60947-5-1
EN 954-1
BG-GS-ET-15
fixings to EN 50047
zinc die-cast, enamelled
slow action,
positive break
NC contacts A
connector M12 x 1
IP 67 to EN 60529
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
AS electronics: 50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
0xE
ID-Code2:
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 ... A3 not used
Parameter bits:
P0 ... P3 not used
Input module address:
Default on address 0
Indications: AS-interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
> 1 million operations
Mechanical life:
Switching frequency:
max. 5000/h
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
temperature:
– 25 °C … + 85 ºC
≤
Approvals
F
C
Ordering details
T➀ 235-AS-ST
No.
➀
Replace
Description
For the appropriate actuator see
Main catalogue „Safety technology“
Note
A separate address jack is not available as an
option. The addressing must take place via the
M12 connector.
1
2
4
3
5
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
5: FE (shield)
9
AS-Interface Safety at Work
R
S
AZM 161 AS
Technical data
Standards:
Enclosure:
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
40
6
18
29
b
90
a
7
6
6
5,5
M12
130
56
M12
30
• Solenoid interlock
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Magnetic drive through AS-Interface output
• Solenoid power supply via the
AS-Interface network or via an external
24 VDC power supply (p version)
• Address jack (optional)
• Thermoplastic enclosure
• Manual release, emergency exit
or emergency release
• High holding force 2000 N
• 30 N latching force (optional)
• Power to unlock / power to lock principle
• Actuating play 5.5 mm in direction
of actuation
• Protection class IP 67
Approvals
F
*
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic,
self-extinguishing
connector M12 x 1
IP 67
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
≤
Total: 500 mA
AS electronics: 50 mA
AS-Interface specification:
(V 2.1)
Profile
S-7.B
IO-Code
0x7
ID-Code
0xB
ID-Code1:
0xF
ID-Code2
0xE
Inputs:
Status
Data bits
Contact
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Solenoid control
A1 … A3 not used
Parameter bits: P0 Actuator / interlock status
P1 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications:
AS-Interface:
voltage LED green,
communication LED red
Enabling status:
LED yellow
Mechanical life:
> 1 million operations
Fmax:
2000 N
EMC rating:
conforming to EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
≤
➀
➁
➂
Description
B
Z
ST1
ST2
Actuator monitored
Guard locking monitored
Connector (middle)
Connector (right)
No latching
Latching 30 N
Power to unlock
Power to lock
No address jack
Address jack
➃
r
➄
a
b
10
Output A0 is used to lock or unlock the
solenoid of the solenoid interlock. Parameter
bit P0 gives the control system feedback about
the status of the actuator or solenoid interlock.
Parameter bit:
The status of the actuator or the locking bolt
can be monitored by the parameter bit P0
depending on the device:
Device
AZM 161 B
AZM 161 B
AZM 161 Z
AZM 161 Z
Parameter
bit P0
0
1
0
1
Safety guard
status
Guard locked
Guard unlocked
Guard closed
Guard open
Note
AZM 161➀➁ -AS➂➃➄➅➆
Replace
The AZM 161 Z version must be selected for
applications where safety guard locking is
required. The AZM 161 B version has a safetymonitored actuator with supplementary guard
locking function.
* UL / CSA approvals
only without address jack
C
Ordering details
No.
OR
Note
AS-Interface
operating current:
78
72
8
6
C
No.
Replace
➅
➆
p
N
T
Description
A separate address jack is not available as an
option. The addressing must take place via the
M12 connector.
Integrated solenoid supply
External solenoid supply
Manual release
Emergency release
Emergency exit
1
2
4
3
1: AS-i +
2: Aux – (p)
3: AS-i –
4: Aux + (p)
AS-Interface Safety at Work
R
S
Contact variants
Contact variants
Integrated power supply
External power supply
Power to unlock
Guard locking monitored
Power to unlock
Guard locking monitored
C
OR
Note
Integrated power supply:
The solenoid interlock AZM 161 AS is powered
by the AS-Interface. Connection to the ASInterface is made via the M12 connector.
The required supply voltage for the solenoid
is also supplied by the AS network.
P0
AS-i
+
-
D0-D3
A0
Actuator monitored
D0-D3
AS-i
+
-
P0
D0-D3
A0
Actuator monitored
D0-D3
AS-i
P0
A0
+
-
+ 24 VDC
-
Actuator monitored
D0-D3 A0 P0
A0
+
-
A0 D0-D3
+
-
P0
Power to lock
Guard locking monitored
AS-i
P0
AS-i
AS-i
+
-
+
- 24 VDC
Power to lock
Guard locking monitored
P0
AS-i
A0 D0-D3
+
-
D0-D3 A0
+
-
To lock or unlock the guard door, the network
must supply a maximum current of 0.5 A per
solenoid interlock.
External power supply:
The solenoid interlock AZM 161 AS ...p is
monitored by the AS-Interface. The locking
solenoid is powered by an external power
supply. Connection to the AS-Interface and
the auxiliary power is made via a single
M12 connector.
+ 24 VDC
-
Actuator monitored
AS-i
The maximum number of interlocks with
integrated power supply and power to lock
principle (a) depends solely on the employed
AS-Interface power supply and its electric
current output.
The passive connection module (see page 29)
links up the external solenoid power supply
(auxiliary power supply, black cable) and the
AS-i network connection (yellow cable) to a
single M12 connector. A 4-wired cable makes
the connection to the solenoid interlock.
P0
+ 24 VDC
-
Solenoid control:
An internal output controls the solenoid
operation. Depending on the device version,
the output bit A0 locks or releases the actuator.
The output bit A0 has the same address as the
safety inputs.
Legend
D0 – D3
P0
A0
Coded data for the evaluation
of the safety monitor (4 Bit)
Status signal (1 Bit)
Output for switching the
solenoid (1 Bit)
11
AS-Interface Safety at Work
R
S
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic,
self-extinguishing
Enclosure:
40
ø 5,5
connector M12 x 1
IP 67
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
50 mA
AS-Interface specification:
(V 2.1)
Profile
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
on
D0/D1 = dynamic code
1
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications:
AS-Interface:
voltage LED green,
communication LED red
Enabling status:
LED yellow
> 1 million operations
Mechanical life:
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
27
Straight actuator AZ 15/16-B1
a
R min. 45
16
5
11
56
40
ø 5,5
27,3
a
27
Flexible actuator AZ 15/16-B2
16
R min. 38
56
40
R min. 25
ø 5,5
11
• Safety switch with separate actuator
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Address jack (optional)
• Thermoplastic enclosure
• Coded actuator
• Long life
• Protection class IP 67
0
7
30
R min. 15
27,3
90
15,5 7
5,5
M 12 52
9
13
M 12
16
≤
29
18
8
0
7
14
8
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
R min. 15
56
40
10
Standards:
System components
5
Technical data
OR
28,3
AZ 16 AS
C
27
Flexible actuator AZ 15/16-B6
Approvals
F
C
Ordering details
AZ 16➀ -AS➁➂
No.
➀
➁
➂
Replace
Description
ST1
ST2
ST3
Connector (middle)
Connector (right)
Connector (left)
No latching
Latching 30 N
Latching 5 N
No address jack
Address jack
r
r-2254
b
Note
Ordering details
A separate address jack is not available as an
option. The addressing must take place via the
M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
Straight actuator
Flexible actuator
Flexible actuator
AZ 15/16-B1
AZ 15/16-B2
AZ 15/16-B6
Further actuators can be found in the chapter
„Safety switches with separate actuator“,
see page 1-8.
Actuators must be ordered separately.
AS-Interface Safety at Work
R
S
Technical data
Standards:
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
39
52
26
37
90
M20 x 1,5 7
15
M20 x 1,5
M 12
40
17
20
60
40
¤ 5,5
connector M12 x 1
IP 67
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
100 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
on
D0/D1 = dynamic code
1
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
Default on address 0
Indications:
AS-Interface:
voltage LED green,
communication LED red
Enabling status:
LED yellow
Mode of operation:
magnetic
Sao:
8 mm
Sar:
18 mm
R ≤ 0,1 x Sao
Repeat accuracy:
Switching frequency f:
< 1 Hz
Actuating magnet:
BPS 16, coded
EMC rating:
conforming to
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
Actuating magnet BPS 16
≤
9
M 12
System components
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic,
self-extinguishing
Enclosure:
OR
11
BNS 16 AS
C
• Safety sensor
• Integrated AS-Interface
• AS-Interface LED status display
• Available with M12 plug-in connetor
and pre-wired cable
• Thermoplastic enclosure
• Coded actuator
• Long life, no mechanical wear
• Insensitive to transverse misalignment
• Concealed mounting possible
• Insensitive to soiling
• Protection class IP 67
Actuating planes
Approvals
F
C
Ordering details
BNS 16➀ -AS➁
No.
➀
➁
Replace
Description
ST1
ST2
ST3
Connector (middle)
Connector (right)
Connector (left)
Actuating planes:
front side
cover-side
V
D
Note
Ordering details
A separate address jack is not available as an
option. The addressing must take place via the
M12 connector.
1
2
4
3
Actuating magnet
BPS 16
Actuators must be ordered separately.
1: AS-i +
2: spare
3: AS-i –
4: spare
13
AS-Interface Safety at Work
R
S
AS-Interface
connection type:
Cable section:
Protection class:
AS-Interface
operating voltage:
7,5
LED
• Safety sensor
• Integrated AS-Interface
• AS-Interface LED status display
• Available with M12 plug-in connetor
and pre-wired cable
• Thermoplastic enclosure
• Coded actuator
• Long life, no mechanical wear
• Insensitive to transverse misalignment
• Concealed mounting possible
• Insensitive to soiling
• Protection class IP 67
ø5
3
13
Actuating magnet BPS 33
13
8,5
ø5
3,5
6,5
18,5
3,5
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Mode of operation:
magnetic
Sao:
5 mm
15 mm
Sar:
Repeat accuracy:
R ≤ 0,1 x Sao
Switching frequency f:
< 1 Hz
Actuating magnet:
BPS 33, coded
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 70 ºC
Storage and transport
temperature:
– 25 °C … + 85 ºC
7
7
2000
4,5
25
cable LSYY (black)
2 x 0.24 mm2
IP 67 to EN 60529
≤
88
78
ø5
4,5
10
Enclosure:
88
78
18,5
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic
18,5
25
Standards:
System components
3,5
Technical data
OR
25
7
BNS 33 AS
C
78
88
Spacer BN 31/33
Approvals
F
C
Ordering details
BNS 33➀ -AS
No.
Replace
➀
STG
STW
14
Note
Ordering details
Description
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
2 m cable
2 m cable with
straight plug M12
2 m cable with
angled plug M12
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
Actuating magnet
Spacer
BPS 33
BN 31/33
The actuators for the safety sensors must be
ordered separately.
AS-Interface Safety at Work
R
S
Technical data
Standards:
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic
Enclosure:
36
LED
22
¤ 4,5
26
19
4
• Safety sensor
• Integrated AS-Interface
• AS-Interface LED status display
• Available with M12 plug-in connetor
and pre-wired cable
• Thermoplastic enclosure
• Coded actuator
• Long life, no mechanical wear
• Insensitive to transverse misalignment
• Concealed mounting possible
• Insensitive to soiling
• Protection class IP 67
Approvals
F
BNS 260➀ -AS-➁
Replace
➀
STG
STW
➁
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications:
AS-Interface:
voltage LED green
communication LED amber
Mode of operation:
magnetic
Sao:
5 mm
15 mm
Sar:
Repeat accuracy:
R ≤ 0,1 x Sao
Switching frequency f:
< 1 Hz
Wiederholgenauigkeit:
R ≤ 0,1 x Sao
Schaltfrequenz f:
< 1 Hz
BPS 260, coded
Actuating magnet:
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 70 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
Left hand door
≤
Right hand door
19
13
6
¤4,5
26
BPS 260
C
Ordering details
No.
cable LSYY (black)
2 x 0.24 mm2
IP 67 to EN 60529
36
6
13
AS-Interface
connection type:
Cable section:
Protection class:
AS-Interface
operating voltage:
1000
OR
System components
22
BNS 260 AS
C
L
R
Description
2 m cable
2 m cable with
straight plug M12
2 m cable with
angled plug M12
Left hand door
Right hand door
Note
Ordering details
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
Left hand door
Right hand door
ordering suffix -L
ordering suffix -R
Actuating magnet
Actuator and sensor mounted
on same fixing plane
Actuator for 90° fixing
BPS 260-1
BPS 260-2
The actuators for the safety sensors must be
ordered separately.
15
AS-Interface Safety at Work
R
S
BNS-B20-AS
Technical data
Standards:
Enclosure:
43,3
32,4
Protection class:
AS-Interface
connection type:
AS-Interface
operating voltage:
8,5
40
108
119,5
17
140
82
120
99
62
10 LED
5
20
• Safety sensor
• Integrated AS-Interface
• AS-Interface LED status display
• Substitutes door-handle and safety switch,
no further door fittings required
• Latching force of approx. 100 N
• M12 plug-in connetor
• Tamper-proof because of integral
coded safety sensor
• LED indication
• Ergonomic operation
• Suitable for hinged and sliding guards
• Protection class IP 67
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
thermoplastic
IP 67 to EN 60529
connector M12
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
≤ 50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
off
D0/D1 = static code “00”
1
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Mode of operation:
magnetic
sao:
0 mm
sar:
22 mm
Ambient temperature:
– 25 °C … + 70 ºC
Storage and transport
temperature:
– 25 °C … + 70 ºC
Switching frequency f:
< 1 Hz
Resistance to shock:
30 g / 11 ms
Resistance to vibration:
10 … 55 Hz,
amplitude 1 mm
Max. door weight:
hinged guard: 5 kg
sliding guard: 3 kg
Approvals
F
C
Ordering details
BNS-B20-AS-ST-➀ Sensor
BNS-B20-B01
Actuator
No.
➀
Replace
Description
L
R
Left hand door
Right hand door
The actuators for the safety sensors must be
ordered separately.
16
Note
A separate address jack is not available as an
option. The addressing must take place via the
M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
C
OR
AS-Interface Safety at Work
R
S
NAS 311 AS
C
OR
Technical data
Standards: EN 50295, EN 60947-5-1, EN 954-1
Enclosure:
glass-fibre reinforced
polyamide nylon,
self-extinguishing
Emergency-Stop button:
thermoplastic
or aluminium
AS-Interface
connection type:
connector M12 x 1
Protection class:
IP 65
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
50 mA
AS-Interface
specification:
Profile
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
on
D0/D1 = dynamic code
1
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
temperature:
– 25 °C … + 85 ºC
≤
85
¤ 29
¤ 40
85
M 12
97,8
M 12
37,8
• E-STOP station
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Pull to reset
• Resistant to chemicals
• Protection class IP 65
Approvals
F
C
Ordering details
NAS 311 ➀ -AS ➁
Note
No.
Replace
Description
➀
➁
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
ST1
Connector
Thermoplastic enclosure
Metal housing
Metal housing and
push button with
protection collar
1
2
M
MH
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
17
AS-Interface Safety at Work
R
C
S
AST ... ST-AS
AST ... L-AS
Technical data
Vorschriften:
Enclosure:
EN 50295, EN 60947-5-1,
EN 954-1
glass-fibre reinforced
thermoplastic, self-extinguishing
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
16,5
70
66
ca. 2000
ca. 2000
70
66
2
ca. 2000
2
25
M30x1,5
¤28
M30x1,5
¤28
25
• Input module with M12 connector (AS-i)
• 2 safe inputs for mechanical contacts
• Connection of NC/NC contact
or NC/NO contact combination
• Cross-wire monitoring
• Magnetic drive through
AS-Interface output
• Solenoid power supply via via
an external 24 VDC (max. 0.5 A)
power supply
• AS-Interface LED status display
• AS-Interface M12 connector
• Thermoplastic enclosure
• Long life
• Protection class IP 67
OR
• Input module with connecting cable
(AS-i), length 2 m
(see ordering data)
IP 67 to EN 60529
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
≤ 50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-7.B
IO-Code:
0x7
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
on
D2/D3 = dynamic code
2
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Solenoid control(AST ... 6)
(24 VDC, max. 500 mA)
A1... A3 not used
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red,
blinking = cross-wire short
Enabling status: LED1/contact1,
yellow/contact2
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 55 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
Approvals
F
C
Ordering details
Note
AST ➀➁ -AS➂➃
No.
➀
➁
Replace
Description
02
11
1 NC/1 NC
1 NO/1 NC
AS-i connection:
M12 connector
Cable (2m)
ST
L
No.
Replace
➂
2
4
6
➃
ST
18
Description
Sensor connection:
2 x 2-single conductors
(2 safety inputs)
1 x 4-single conductors
(2 safety inputs)
1 x 6-single conductors
(2 safety inputs and
1 semiconductor output)
Sensor connection:
M12 connector with
2m cable
2 x 2 and 1 x 4 (option)
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: Aux – (6) (AST...6)
3: AS-i –
4: Aux + (6) (AST...6)
AS-Interface Safety at Work
R
S
Note
C
OR
Wiring diagram
• The wiring diagram is shown with guard
doors closed and in de-energised condition.
• The AST module can on be used for the
connection of potential-free contacts.
Additional LED’s on the connecting wire
are not acceptable.
• Monitoring a sliding guard door using two
position switches with safety function.
The NC contact must have positive break
when the guard door is opened.
BU BU
BN BN
Sensor connection
AST 02
ST 2
AS-i connection
AZM 170-11z
• The module AST...AS is monitored by the
AS-Interface. The locking solenoid is
powered by an external power supply.
Connection to the AS-Interface and the
auxiliary power is made via a single M12
connector or via a 4-pole connecting cable.
A1 A2
13 14 21 22
BN BU WH BK
RD GY
• The passive connection module (see page 29)
links up the external solenoid power supply
(auxiliary power supply, black cable) and the
AS-i network connection (yellow cable) to a
single M12 connector. A 4-wired cable makes
the connection to the AST…ST6 module.
Sensor connection
• An internal output controls the solenoid
operation. Depending on the interlocking
device, output bit A0 locks or unlocks the
actuator. Output bit A0 has the same
address as the safety inputs.
AST 11
ST 6
AS-i connection
19
AS-Interface Safety at Work
R
S
AST LC ST-AS
Technical data
Standards:
Enclosure:
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
16,5
70
66
ca. 2000
ca. 500
25
2
M30x1,5
¤28
ST1
ST2
• Input module for 2 monitored PNP
semiconductor outputs for light
curtains and light grids
• AS-Interface LED status display
• AS-Interface M12 connector
• Thermoplastic enclosure
• Long life
• Protection class IP 67
EN 50295, EN 60947-5-1,
EN 954-1, EN 61496-1
glass-fibre reinforced
thermoplastic,
self-extinguishing
AST LC ST-AS
20
Connector ST
(male)
1
2
1:
2:
3:
4:
4
3
AS-i +
spare
AS-i –
spare
connector M12
IP 67 to EN 60529
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
≤ 50 mA
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
off
D0/D1 = static code “00”
1
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 ... A3 not used
Parameter bits:
P0 .. P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red,
OSSD1/2;
Enabling status:
LED yellow
Power supply
PELV power supply
for AOPD:
to IEC 364-4-41
Reaction time:
≤ 20 ms
EMC rating:
conforming to
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
C
Ordering details
OR
Note
Approvals
F
C
Note
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
Connector ST1
(male)
1
2
1:
2:
3:
4:
5:
4
3
5
Connector ST2
3
4
2
1
5
+ 24 VDC
OSSD 1
GND
OSSD 2
FE (function earth)
(female)
1:
2:
3:
4:
5:
+ 24 VDC
spare
GND
spare
FE (function earth)
AS-Interface Safety at Work
R
S
Note
C
OR
Wiring diagram
• The wiring diagram shows an active optoelectronic device (AOPD) (type SLC/SLG)
with a safety input module AST LC ST-AS
(Opto-Tube) connected to the AS-i Safety
at Work system.
Emitter module
• The Opto-Tube is directly connected to the
receiver module (ST2). The AOPD receives
its 24 VDC power supply via the second
M12-cable connection (ST1).
Receiver module
• The Opto-Tube itself is connected via the
M12 connector (ST) to the AS-i network.
Before hand the module has to be programmed with an individual adress (1 - 31).
ST2
see note
• The emitter module has be wired up
separately as described in its mounting
and wiring instruction.
24 VDC (ST1)
AS-i (ST)
21
AS-Interface Safety at Work
R
S
ASU command devices
Technical data
Standards:
AS-Interface
connection type:
Protection class:
(see ordering data)
IP 65 (front)
IP 20 (rear of the front plate)
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
AS-Interface
specification:
≤ 50 mA
Profile
IO-Code
ID-Code
ID-Code1:
ID-Code2
22
71
max. 6
29
Ø 38,5
23,5
75
38
• Emergency-Stop button
• Compact embeddable command
devices with ASU adapter box
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector,
IDC connector
• Miscellanous positioning parts
(metal, plastic)
• Mounting hole 22.3 mm
(to EN 50 007)
• Protection class IP 65 (from front)
Inputs:
Contact
1
OR
Technical data
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced
polyamide nylon,
self-extinguishing
Enclosure:
C
Actuating elements
Al-metal actuating element:
Resistance to shock:
max. 15 g / 22 ms*
(temporary data)
Resistance to vibration:
max. 0.35 mm,
0 … 150 Hz
Plastic actuating element:
Resistance to shock:
max. 15 g / 22 ms*
(temporary data)
Resistance to vibration:
max. 0.35 mm,
0 … 150 Hz
* preliminary data
S-7.B
0x7
0xB
0xF
0xE
Status
on
Data bits
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Resistance to shock: 110 g/4 ms…30 g/18 ms,
no bouncing
(for actuating heads with
higher respectively lower weight)
Resistance to vibration:
20 g / 10 …200 Hz
(for actuating heads with
higher respectively lower weight)
conforming to
EMC rating:
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
≥
Approvals
F
C
Ordering details
EFP ➀ -AS 110
➁DRZ 40 RT
No.
➀
➁
22
Replace
ST
DT
ME
E
K
Contact block
Actuating element
Note
Note
Addressing through flat cable connection
or through M12 connector.
Description
M12 connector
Flat cable connection (DC)
optional: 2 m cable,
cable gland, flying lead
Metal actuating element
Plastic actuating element
1
1
2
4
3
The positioning parts are not included
in delivery.
2
M12 connector:
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
Mounting
One-hole fixation 22.3 mm + 0.4 mm to
EN 50 007 (a tail cut-out as displacement
protection is not required for Elan devices)
Flat cable connection:
1: AS-i +
2: AS-i –
AS-Interface Safety at Work
R
S
ASU command devices
C
OR
Technical data
Standards:
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced polyamide
nylon, self-extinguishing
Enclosure:
AS-Interface
connection type:
Protection class:
(see ordering data)
IP 65 (front)
IP 20 (rear of the front plate)
AS-Interface
operating voltage:
≤
22
71
max. 6
14
Ø 29,5 (29,8)
Ø 22 (25)
23,5
75
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA
AS-Interface
specification:
Profile
S-7.B
IO-Code
0x7
ID-Code
0xB
ID-Code1:
0xF
ID-Code2
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Resistance to shock: 110 g/4 ms…30 g/18 ms,
no bouncing
(for actuating heads with
higher respectively lower weight)
Resistance to vibration:
20 g / 10 …200 Hz
(for actuating heads with
higher respectively lower weight)
conforming to
EMC rating:
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
38
• Push button
• Compact embeddable command
devices with ASU adapter box
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector,
IDC connector
• Miscellanous positioning parts
(metal, plastic)
• Mounting hole 22.3 mm
(to EN 50 007)
• Protection class IP 65 (from front)
≥
Approvals
F
C
Ordering details
EFP ➀ -AS 033
➁ DT ➂
No.
➀
➁
➂
Replace
ST
DT
ME
E
K
GN*
SW*
BL*
Contact block
Actuating element
Note
Note
Addressing through flat cable connection
or through M12 connector.
Description
M12 connector
Flat cable connection (DC)
optional: 2 m cable,
cable gland, flying lead
Metal actuating element
Plastic actuating element
Green push-button
Black push-button
Blue push-button
Other colours on request
1
1
2
4
3
Mounting
One-hole fixation 22.3 mm + 0.4 mm to
EN 50 007 (a tail cut-out as displacement
protection is not required for Elan devices)
The positioning parts are not included
in delivery.
2
M12 connector:
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
Flat cable connection:
1: AS-i +
2: AS-i –
* Push-buttons in different colours available
on request.
23
AS-Interface Safety at Work
R
S
ASU command devices
C
OR
Technical data
Standards:
EN 50295, EN 60947-5-1
EN 954-1
glass-fibre reinforced polyamide
nylon, self-extinguishing
Enclosure:
AS-Interface
connection type:
Protection class:
(see ordering data)
IP 65 (front)
IP 20 (rear of the front plate)
AS-Interface
operating voltage:
≤
≤
22
71
max. 6
14
Ø 29,5 (29,8)
Ø 22 (25)
23,5
75
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA,
with illuminated
pushbutton 70 mA
AS-Interface
specification :
Profile
S-7.B
IO-Code
0x7
ID-Code
0xB
ID-Code1:
0xF
ID-Code2
0xE
Inputs:
Contact
Status
Data bits
on
D0/D1 = dynamic code
1
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Indicator lamp
A1 ... A3 not used
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
LED yellow
Enabling status:
Resistance to shock: 110 g/4 ms…30 g/18 ms,
no bouncing
(for actuating heads with
higher respectively lower weight)
Resistance to vibration:
20 g / 10 …200 Hz
(for actuating heads with
higher respectively lower weight)
EMC rating:
conforming to
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport temp.: – 25 °C … + 85 ºC
38
• Illuminated push-button
• Compact embeddable command
devices with ASU adapter box
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector,
IDC connector
• Miscellanous positioning parts
(metal, plastic)
• Mounting hole 22.3 mm
(to EN 50 007)
• Protection class IP 65 (from front)
≥
Approvals
F
C
Ordering details
EFP ➀ -AS 03L
➁ DL ➂
No.
➀
➁
➂
Replace
ST
DT
ME
E
K
GN*
SW*
24
Contact block
Actuating element
Note
Note
Addressing through flat cable connection
or through M12 connector.
Description
M12 connector
Flat cable connection (DC)
optional: 2 m cable,
cable gland, flying lead
Metal actuating element
Plastic actuating element
Green illuminated
push-button
Black illuminated
push-button
Other colours on request
1
1
2
4
3
Mounting
One-hole fixation 22.3 mm + 0.4 mm to
EN 50 007 (a tail cut-out as displacement
protection is not required for Elan devices)
The positioning parts are not included
in delivery.
2
M12 connector:
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
Flat cable connection:
1: AS-i +
2: AS-i –
* Push-buttons in different colours available
on request.
AS-Interface Safety at Work
R
S
ASU command devices
C
OR
Technical data
Standards:
EN 50295
EN 60947-5-1
EN 954-1
glass-fibre reinforced polyamide
nylon, self-extinguishing
Enclosure:
AS-Interface
connection type:
Protection class:
(see ordering data)
IP 65 (front)
IP 20 (rear of the front plate)
AS-Interface
operating voltage:
• Other ASU command devices on request
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA
AS-Interface
specification :
Profile
S-7.B
IO-Code
0x7
ID-Code
0xB
ID-Code1:
0xF
ID-Code2
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Switching frequency:
3600/h
Resistance to shock: 30 g/18 ms, no bouncing
(for actuating heads with
higher respectively lower weight)
Resistance to vibration:
15 g / 10 ... 200 Hz
(for actuating heads with
higher respectively lower weight)
conforming to
EMC rating:
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport temp.: – 25 °C … + 85 ºC
≤
≥
Approvals
F
C
Ordering details
on request
Note
Addressing through flat cable connection
or through M12 connector.
1
1
2
4
3
2
M12 connector:
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
Flat cable connection:
1: AS-i +
2: AS-i –
25
AS-Interface Safety at Work
R
S
ZS 71 AS
Technical data
ø 10
40
30
10
53,5
6
≤
≤
8
18
12
56
22
105
24
33
15
17,5
M 12
52
M 12
42
• Pull-wire Emergency-Stop switch
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Metal enclosure
• Various spring force variants
(actuating forces)
• Adjustable actuating force
• Wire up to 20 m long
• Reset by push button or key possible
• Protection class IP 65 (with push button
and external watertight collar)
Approvals
F
C
Ordering details
ZS 71➀ -AS ➁➂ -➃ -➄ / ➅
No.
Replace
Description
➀
➁
ST1
Connector
Without watertight collar
With watertight collar
Without safety function
Push button reset
Key reset
Without position indicator
With position indicator
Without indicator lamp
With indicator lamp
Pre-tensioning force:
For wire length 0 - 5 m
For wire length 5 - 20 m
➂
➃
W
VD
VS
➄
A
➅
G
55 N
200 N
26
Standards: EN 50295, EN 60947-5-1, EN 954-1
Enclosure:
cast aluminium, enamelled
Cover:
thermoplastic ultramid
AS-Interface
connection type:
connector M12 x 1
Protection class:
IP 54
IP 65 for version with
push button reset
and watertight collar
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
50 mA,
with indicator lamp 130 mA
AS-Interface
specification:
Profile
S-7.B
IO-Code:
0x7
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Status
Data bits
Contact
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Indicator lamp (optional)
A1 … A3 not used
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Mechanical life:
> 1 million operations
Maximum cable length:
20 m
Features:
wire pull and
breakage detection
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
Note
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
A wide range of accessories is available.
For selection, see Main catalogue
„Safety technology“.
C
OR
AS-Interface Safety at Work
R
S
ZS 73 AS
6,5
75
105
48
30
5
15
M 12
M 12 70
28
98
56
• Pull-wire Emergency-Stop switch
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Metal enclosure
• 4 various spring force variants
(actuating forces)
• Adjustable actuating force
• Wire up to 50 m long
• Reset by push button or key possible
• Protection class IP 65 (with push button
and external watertight collar)
Approvals
F
ZS 73➀ -AS ➁➂ -➃ / ➄
No.
Replace
Description
➀
➁
ST1
Connector
Without watertight collar
With watertight collar
Without safety function
Push button reset
Key reset
Without indicator lamp
With indicator lamp
Pre-tensioning force:
For wire length 0-10 m
For wire length 10-20 m
For wire length 20-30 m
For wire length 30-50 m
➃
➄
Standards: EN 50295, EN 60947-5-1, EN 954-1
Enclosure:
cast aluminium, enamelled
Cover:
thermoplastic ultramid
AS-Interface
connection type:
connector M12 x 1
Protection class:
IP 54
IP 65 for version with
push button reset
and watertight collar
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
50 mA,
with indicator lamp 130 mA
AS-Interface
specification:
Profile
S-7.B
IO-Code:
0x7
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Status
Data bits
Contact
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Indicator lamp (optional)
A1 … A3 not used
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Mechanical life:
> 1 million operations
Maximum cable length:
50 m
Features:
wire pull and
breakage detection
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
≤
≤
C
Ordering details
➂
OR
Technical data
170
25
C
W
VD
VS
G
80-100N
120-180N
195-275N
295-390N
Note
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
A wide range of accessories is available.
For selection, see Main catalogue
„Safety technology“.
27
AS-Interface Safety at Work
R
S
ZS 75 AS
Technical data
69
54
23
52
66
160
33
19,5
76
71
80
6,5
154
14
12
27
M 12
M 12 70
100
• Pull-wire Emergency-Stop switch
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Metal enclosure
• 4 various spring force variants
(actuating forces)
• Adjustable actuating force
• Wire up to 50 m long
• Reset by push button or key possible
• Protection class IP 65 (with push button
and external watertight collar)
Approvals
F
ZS 75➀ -AS ➁➂ -➃ / ➄
No.
Replace
Description
➀
➁
ST1
Connector
Without watertight collar
With watertight collar
Without safety function
Push button reset
Key reset
Without indicator lamp
With indicator lamp
Pre-tensioning force:
For wire length 0-10 m
For wire length 10-20 m
For wire length 20-30 m
For wire length 30-50 m
➃
➄
W
VD
VS
G
80-100N
120-180N
195-275N
295-390N
28
≤
≤
C
Ordering details
➂
Standards: EN 50295, EN 60947-5-1, EN 954-1
Enclosure:
cast aluminium, enamelled
Cover:
cast aluminium, enamel finish
AS-Interface
connection type:
connector M12 x 1
Protection class:
IP 54
IP 65 for version with
push button reset
and watertight collar
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface
operating current:
50 mA,
with indicator lamp 130 mA
AS-Interface
specification:
Profile
S-7.B
IO-Code:
0x7
ID-Code:
0xB
ID-Code1:
0xF
ID-Code2:
0xE
Inputs:
Status
Data bits
Contact
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Outputs:
A0 Indicator lamp (optional)
A1 … A3 not used
Parameter bits:
P0 … P3 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Enabling status:
LED yellow
Mechanical life:
> 1 million operations
Maximum cable length:
50 m
Features:
wire pull and
breakage detection
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
– 25 °C … + 85 ºC
temperature:
Note
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
A wide range of accessories is available.
For selection, see Main catalogue
„Safety technology“.
C
OR
AS-Interface Safety at Work
R
S
OR
System components
System components
System components
IDC connector M
Passive connection module
Terminal mounting
+
+
Aux
-
50
-
Aux
M5
21
9
AS-i
Ø 30
AS-i
C
5
free
2
Aux
-
4
Aux
+
3
AS-i
1
-
AS-i
+
34
50
64
Rundsteckverbinder
M12
IDC connector K
Passive connection module
Terminal mounting
Ordering details
Ordering details
Ordering details
IDC connector M
Connection from the AS-i flat cable (yellow) to
M12 connector
Passive connection module 0911 ANC 101
Passive connection module (IDC) for the yellow
and black flat cable to a M12 connector plug
Terminal mounting H 30
Mounting brackets for all AS-i Tube modules
with M30 housing
IDC connector K
Connection from the AS-i flat cable (yellow) to
a circular cable
29
AS-Interface Safety at Work
R
S
ASF 2 CC
Technical data
Standards:
Enclosure:
AS-Interface
connection type:
31
80
51
102
• Input module
• 2 safe inputs for
mechanical contacts
• Cross-wire monitoring
• Cage clamp terminals for
safety device connection
• LED function display
• IDC technology for
AS-Interface flat cable
• Protection class IP 67
OR
Wiring diagram
EN 50295, EN 954-1
black
IDC to the flat
cable AS-Interface
Cage clamp terminals:
max. 2,5 mm2
(incl. conductor ferrules)
AS-Interface
operating voltage:
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
Protection class:
IP 67
AS-Interface operating current:
< 70 mA
Inputs:
2 safe inputs for
mechanical contacts,
monitored for cross-wired
circuit, cable length < 30 m
Input signal:
„S+1, S+2“:
le < 10 mA, pulsed
AS-Interface specification:
(V 2.1)
Profile:
S-0.B
IO-Code:
0x0
ID-Code:
0xB
0xF
ID-Code1:
ID-Code2:
0xE
Inputs:
Contact
Status
Data bits
1
on
D0/D1 = dynamic code
transmission
1
off
D0/D1 = static code “00”
2
on
D2/D3 = dynamic code
transmission
2
off
D2/D3 = static code “00”
Parameter bits:
P0 … P1 not used
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green,
communication LED red
Switching condition: LED yellow
EMC rating:
conforming to
EMC Directive
– 25 °C … + 60 ºC
Ambient temperature:
Storage and transport
– 25 °C … + 85 ºC
temperature:
S+1 RES S-1 S-2 RES S+2
FAULT
POWER
45
66
C
S
Inputs
2 1
S+1 RES S-1 S-2 RES S+2
FAULT
POWER
Inputs
2 1
Approvals
F
C
Ordering details
ASF 2 CC
The base module ASF KM1 is the electromechanical link between the AS-Interface
flat cable and the user module (ASF 2CC).
30
Note
Note
The safe AS-Interface input module offers two
universal safety relevant inputs for mechanical
contacts. The safe switches are connected to
cage-clamp terminals inside the module housing. The signal voltage is supplied by the module itself.
The wiring diagram is shown with guard doors
closed and in de-energised condition.
The two safe input channels are cross-wire
monitored.
Monitoring a sliding guard door using two
position switches with safety function.
The NC contact must have positive break
when the guard door is opened.
Please note that for the correct use of the input
module there must be two jumpers present
(1+2 and 5+6, see electrical connection).
AS-Interface Safety at Work
R
S
ASF KM1
C
OR
Technical data
Standards:
Ue:
80
¤ 9,6
26
18,5
45
18,5
36
36
EN 50295
26,5 … 31,6 V
(according to AS-Interface specification)
max. 2 A
Ie:
AS-Interface specification:
EMS
AS-Interface
connection type:
2 flat cables
AS-Interface (IDC)
Protection class:
IP 67 to EN60529
(only in combination
with ASF 2 CC)
Ambient temperature:
– 25 °C … + 60 ºC
Storage and transport
temperature:
– 25 °C … + 85 ºC
Special features:
2 parallel cable channels
for various T- and
Cross-junctions
Mounting:
top hat section rail
or screw mounting
26
¤ 5,8
• Base module
• Base module without address jack
• AS-Interface interface for user module
• Connection of AS-Interface flat cable
• Top hat section rail or screw mounting
Approvals
Ordering details
ASF KM 1
Note
The base module is the electro-mechanical
link between the AS-Interface flat cable and
the user module (i.e. ASF 2CC).
Note
AS-i
AS-i
+
+
-
+Contacts
to module
31
AS-Interface Safety at Work
R
S
ASF PM
Technical data
Interface:
Operating device:
Operating duration:
Power supply:
Display:
Keyboard:
↑
↓
Protection class:
Ambient temperature:
Storage and transport
temperature:
Dimensions:
C
OR
Note
AS-Interface,
short-circuit- and
overload-proof
230 VAC,
plug-in charging unit,
included in the
delivery package
8 h or > 250 read/write
cycles with fully
charged batteries
battery mode,
charging time before
use about 14 h
LC-display
5 keys,
membrane keys
IP 20
0 °C … + 55 ºC
– 20 °C … + 55 ºC
80 x 34 x 214 mm
• Hand-held programming device
• Addressing and Programming up to
a maximum of 62 Slaves (A/B-Slaves)
• Read/write operation of slave data
• Displaying the IO-code
• Read/write operation of parameter data
• Displaying the address mode / ID-code
• Displaying the peripheral fault flags
• Determining the slave address
• Re-addressing with checking
• Slave connection is short-circuit
and overload proof
• Mech. connection with the help
of the universal adapter
• Battery charger included with delivery
The LCD displays the address, the operating
mode or an error code. The AS-Interface hand
held programming device will be switched on
by pressing the button “ADR”. It shuts down
independently after about one minute when
not in use.
• Pressing the “ADR” button causes the
current slave address to be displayed
• The two keys “ ↑ “ and “ ↓ “ can be used to
select the programmable address from the
address ring (i.e. 0 ...31, 0 ...31A, 0 ...31B)
• A short key stroke causes the page to turn
stepwise, whereas holding down the key
causes the pages to scroll continuously
(0.5s per address)
• Pressing the “PRG”-key causes the new
address to be loaded into the slave
• The correct programmed address is
automatically displayed after about 0.5s
• Holding down “ADR” and “PRG” simultaneously will automatically set back the
slave address to zero
• Other key combinations do not trigger
any further action
Approvals
C
Ordering details
ASF PM
Note
The LCD displays the address, the operating
mode or an error code.
„ ↑ “ button
= increments
slave address
„MODE“ button = changes the
working mode
= decrements
„ ↓ “ button
slave address
„PRG“ button
= programming of the
new slave address
„ADR“ button
= reading a slave address /
switches on the device
Error messages
F1: AS-Interface overload
F2: Slave not found
F3: Programming error
F4: Destination address busy
F5: Zero address already occupied
F6: Standard slave found instead
of an extended slave
F7: Extended slave found instead
of a standard slave
F8: Reception error
LOBAT = Recharge batteries !
After the first indication approx. 30
read/write operation are still possible.
Load the accumulator only with the
charger included within this delivery.
AS-Interface Safety at Work
R
S
TG...-A
C
OR
Technical data
Standards:
EN 50295
EN 60947-5-1
EN 954-1
PA + POM
Enclosure:
AS-Interface
connection type:
Protection class:
AS-Interface
operating voltage:
connector M12 x 1
IP 65
26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current:
50 mA
AS-Interface
specification :
Profile
S-B.A
IO-Code
0xB
ID-Code
0xA
ID-Code2
0xE
Outputs:
Data bits
Function
D0
LED 1 (G)
D1
LED 2 (R)
Inputs:
Data bits
Function
D2
NO contact 1
D3
NO contact 2
(optional)
Input module address:
default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface: voltage LED green
communication LED red
EMC rating:
conforming to
EMC Directive
Ambient temperature:
– 20 °C … + 60 ºC
Storage and transport
temperature:
– 25 °C … + 85 ºC
≤
10
M12 x 1
60
80
4
8,5
200
• Door handle switch
• Integrated AS-Interface
• AS-Interface LED status display
• AS-Interface M12 connector
• Enabling button
• Coloured signal LEDs (optional)
• Protection class IP 65
48
30
150
Approvals
C
Ordering details
TG-S GR xx-A
Further devices on request.
Note
A separate address jack is not available as an
option. The addressing must take place via the
cable end or the M12 connector.
1
2
4
3
1: AS-i +
2: spare
3: AS-i –
4: spare
33
German
agencies
International
agencies
01
02
03
04
19
12
05
16
09
08
Argentina - Argentinien
Condelectric S. A.
Hipólito Yrigoyen 2591
1640 Martinez
Pcia. de Buenos Aires
Telefon: +54 (11) 47 97 58 87
Telefax: +54 (11) 47 97 58 87
E-Mail: info@condelectric.com.ar
Internet: www.condelectric.com.ar
11
10/15
Stammhaus
K.A. Schmersal GmbH
Industrielle Sicherheitsschaltsysteme
Postfach 24 02 63, 42232 Wuppertal
Möddinghofe 30
42279 Wuppertal
Telefon: +49-(0) 2 02-64 74-0
Telefax: +49-(0) 2 02-64 74-1 00
E-Mail: info@schmersal.de
Internet: www.schmersal.com
01
02
03
04
05
14
Hamburg
K.A. Schmersal GmbH
Geschäftsstelle Hamburg
Zunftstraße 8
21244 Buchholz i.d.N.
Telefon: +49-(0) 41 81-9 22 0-0
Telefax: +49-(0) 41 81-9 22 0-20
E-Mail: gshamburg@schmersal.de
Berlin
KSA Komponenten der Steuerungsund Automatisierungstechnik GmbH
Buchholzer Str. 62-65
13156 Berlin
Telefon: +49-(0) 30-47 48 24 00
Telefax: +49-(0) 30-47 48 24 05
E-Mail: info@ksa-gmbh.de
Internet: www.ksa-gmbh.de
Hannover
ELTOP GmbH
Robert-Bosch-Str. 8
30989 Gehrden
Telefon: +49-(0) 51 08-92 73 20
Telefax: +49-(0) 51 08-92 73 21
E-Mail: eltop@eltop.de
Internet: www.eltop.de
Münster
K.A. Schmersal GmbH
Geschäftsstelle Münster
Am Vechte Ufer 22
48629 Metelen
Telefon: +49-(0) 25 56-9 38 30
Telefax: +49-(0) 25 56-93 83 73
E-Mail: gsmuenster@schmersal.de
Köln
Stollenwerk
Technisches Büro GmbH
Scheuermühlenstr. 40
51147 Köln
Telefon: +49-(0) 22 03-9 66 20-0
Telefax: +49-(0) 22 03-9 66 20-30
E-Mail: info@stollenwerk.de
Ruhrgebiet
K W S Elektronik Schumacher
Saarstr. 19a
53919 Weilerswist
Telefon: +49-(0) 22 54-33 80
Telefax: +49-(0) 22 54-18 58
E-Mail: k-w-s-@t-online.de
34
12
16
08
19
Siegen
Siegfried Klein
Elektro-Industrie-Vertretungen
Schloßblick 38
57074 Siegen
Telefon: +49-(0) 2 71-67 78
Telefax: +49-(0) 2 71-67 70
E-Mail: info@sk-elektrotechnik.de
Frankfurt
K.A. Schmersal GmbH
Geschäftsstelle Frankfurt
Kilianstädter Straße 38
61137 Schöneck
Telefon: +49-(0) 61 87-9 09 56-0
Telefax: +49-(0) 61 87-9 09 56-6
E-Mail: gsfrankfurt@schmersal.de
Saarland
Herbert Neundörfer
Werksvertretungen
Saargemünder Str. 68a
66130 Güdingen
Telefon: +49-(0) 6 81-87 54 54
Telefax: +49-(0) 6 81-87 54 53
E-Mail: info@herbert-neundoerfer.de
Internet: www.herbert-neundoerfer.de
Leipzig
K.A. Schmersal GmbH
Geschäftsstelle Leipzig
Nonnenstraße 11c
04229 Leipzig
Telefon: +49-(0) 3 41-4 87 34 50
Telefax: +49-(0) 3 41-4 87 34 51
E-Mail: gsleipzig@schmersal.de
Australia - Australien
NHP Electrical Engineering
Products Pty. Ltd.
43 - 67 River Street, PO Box 199
Richmond 3121
Melbourne, Victoria
Telefon: +61-(0) 3-94 29 29 99
Telefax: +61-(0) 3-94 29 10 75
E-Mail: products@nhp.com.au
Internet: www.nhp.com.au
Austria - Österreich
AVS-Schmersal Vertriebs Ges. m.b.H.
Biróstraße 17
1232 Wien
Telefon: +43-(0) 1-6 10 28
Telefax: +43-(0) 1-6 10 28-1 30
infoservice@avs-schmersal.co.at
Internet: www.avs-schmersal.co.at
Belgium - Belgien
Schmersal Belgium NV/SA
Nieuwlandlaan 16B
Industriezone B413
3200 Aarschot
Telefon: +32-(0) 16-57 16 18
Telefax: +32-(0) 16-57 16 20
E-Mail: info@schmersal.be
Internet: www.schmersal.be
Brazil - Brasilien
ACE Schmersal
Eletroeletrônica Industrial Ltda.
Rodovia Boituva-Porto Feliz, Km 12
Vila Esplanada – CEP: 18550-000
Boituva – SP
Telefon: +55-(0) 15-32 63-98 66
Telefax: +55-(0) 15-32 63-98 90
E-Mail: export@aceschmersal.com.br
Internet: www.aceschmersal.com.br
09
Bayern Nord
K.A. Schmersal GmbH
Geschäftsstelle Nürnberg
Beethovenstr. 14
91074 Herzogenaurach
Telefon: +49-(0) 91 32-73 70 00
Telefax: +49-(0) 91 32-73 48 44
E-Mail: gsnuernberg@schmersal.de
Bolivia - Bolivien
International Fil-Parts
Import/Export S.R.L
3er. Anillo, 1040, Frente al Zoo
Santa Cruz de la Sierra
Telefon: +591 (3) 3 42 99 00
Telefax: +591 (3) 3 42 36 37
E-Mail: presidente@filparts.com.bo
Internet: www.filparts.com.bo
10/
15
Bayern Süd
Ing. Adolf Müller GmbH
Industrievertretungen
Elly-Staegmeyr-Str. 15
80999 München
Telefon: +49-(0) 89-8 12 60 44
Telefax: +49-(0) 89-8 12 69 25
E-Mail: info@ingam.de
Canada - Kanada
Schmersal Canada LTD.
10 Riverside Drive
Orangeville / Ontario L9V1A5
Telefon: (905) 495-7540
Telefax: (905) 495-7543
E-Mail: info@schmersalusa.com
Internet: www.schmersalusa.com
11
Stuttgart
Labor-Schütz GmbH
Industrievertretungen
Eichwiesenring 6
70567 Stuttgart
Telefon: +49-(0) 7 11-7 15 46-0
Telefax: +49-(0) 7 11-7 15 46-18
E-Mail: hv@schuetzinger.de
Internet: www.schuetzinger.de
Chile - Chile
Vitel S.A.
Chiloé 1189
Casilla 440-3
Santiago
Telefon: +56 (2) 5 56 26 46
Telefax: +56 (2) 5 55 57 90
E-Mail: francisco@vitel.cl
Internet: www.vitel.cl
Colombia - Kolumbien
Cimpex Ltda.
Calle 53 No. 45-112 - Of. 1401
Apartado Aereo 2429
Medellin
Telefon: +57-4-2 51-59 72
Telefon: +57-4-2 51-59 87
Telefax: +57-4-2 51-46 08
E-Mail: cimpex@epm.net.co
Costa Rica - Costa Rica
Euro-Tec, S.A.
Apartado Postal 477
1250 Escazú
San José
Telefon: +5 06-2 84 78 69
Telefax: +5 06-2 96 15 42
E-Mail: eurotec@amnet.co.cr
PR China - VR China
Schmersal Industrial Switchgear Co. Ltd.
Central Plaza 1001
Huang Pi Bei Road 227
200003 Shanghai
Telefon: +86-21-63 75 82 87
Telefax: +86-21-63 75 82 97
E-Mail: sales@schmersal.com.cn
Internet: www.schmersal.com.cn
Czech Republic Tschechische Republik
Mercom Componenta spol. s.r.o.
Ruská 67
100 00 Praha 10
Telefon: +4 20-(0) 2-67 31 46 40
Telefax: +4 20-(0) 2-71 73 32 11
E-Mail: mercom@mercom.cz
Denmark - Dänemark
Schmersal Danmark A/S
Lindegårdsvej 17A
2920 Charlottenlund
Telefon: +45-70 20 90 27
Telefax: +45-70 20 90 37
E-Mail: info@schmersal.dk
Internet: www.schmersal.dk
Finland - Finnland
Advancetec Oy
Malminkaari 10B
PO Box 149
00701 Helsinki
Telefon: +3 58-(0) 9-3 50 52 60
Telefax: +3 58-(0) 9-35 05 26 60
E-Mail: advancetec@advancetec.fi
Internet: www.advancetec.fi
France - Frankreich
Schmersal France SAS
8, rue Raoul Follereau
BP 18
38180 Seyssins
Telefon: +33-4 76 84 23 20
Telefax: +33-4 76 48 34 22
E-Mail: info@automatisme-etcontrole.fr
Internet: www.automatisme-et-controle.fr
Greece - Griechenland
Kalamarakis Sapounas S.A.
Ionias & Neromilou
PO Box 46566
13671 Chamomilos Acharnes
Athens
Telefon: +30-(0) 210-2 40 60 00-6
Telefax: +30-(0) 210-2 40 60 07
E-Mail: ksa@ksa.gr
Honduras - Honduras
Lusitana International
Apdo. Postal #783
21105 San Pedro Sula
Tegucigalpa
Telefon: +5 (04) 3 93-16 40
Telefax: +5 (04) 5 50-22 52
E-Mail: jaimefernandes2002@yahoo.com
Hungary - Ungarn
NTK Ipari-Elektronikai és
Kereskedelmi Kft
Mészáros L. u. 5.
9023 Györ
Telefon: +36-(0) 96-52 32 68
Telefax: +36-(0) 96-43 00 11
E-Mail: info@ntk-kft.hu
Internet: www.ntk-kft.hu
India - Indien
Arihant Electricals
24/4866, Ansari Road
Darya Ganj, Sheel Tara House
102222 New Delhi
Telefon: +91-11-23 26 21 76
Telefax: +91-11-23 27 35 54
E-Mail: info@arihantelectricals.com
Indonesia - Indonesien
P.T. Wiguna Sumber Sejahtera
JI. Kesehatan Raya No. 36
Jakarta 10160
Telefon: +62-(0) 21-34 83 42 30
Telefax: +62-(0) 21-34 83 42 31
E-Mail: email@ptwiguna.com
Internet: www.ptwiguna.com
Israel - Israel
A.U. Shay Ltd.
23 Imber St. Kiriat. Arieh.
P.O. Box 10049
Petach Tikva
Telefon: +9 72-3-9 23 36 01
Telefax: +9 72-3-9 23 46 01
E-Mail: shay@uriel-shay.com
Italy - Italien
Schmersal Italia s.r.l.
Via Molino Vecchio, 206
25010 Borgosatollo, Brescia
Telefon: +39-0 30-2 50 74 11
Telefax: +39-0 30-2 50 74 31
E-Mail: info@schmersal.it
Internet: www.schmersal.it
Japan - Japan
Elan-Schmersal Japan Branch Office
3-39-8 Shoan, Suginami-ku,
Tokyo 167-0054
Telefon: +81-(03)-3247-0519
Telefax: +81-(03)-3247-0537
E-Mail: safety@elanjp.com
Korea - Korea
MEC Manhani Electric Co. Ltd.
576-8, Bisan-2dong
Dongan-Ku
Anyang-City
Kyungi-Do 431-821
Telefon: +82-(0) 31-4 63-33 00
Telefax: +82-(0) 31-4 63-33 98
Telefax: +82-(0) 31-4 63-33 99
E-Mail: andy@hanmec.co.kr
Malaysia - Malaysien
Ingermark (M) SDN.BHD
No. 29, Jalan KPK 1/8
Kawasan Perindustrian Kundang
48020 Rawang, Selangor Darul Ehsan
Telefon: +6 03-60-34 27 88
Telefax: +6 03-60-34 21 88
E-Mail: ingmal@tm.net.my
Mexico - Mexiko
ISEL SA de CV
Via Lopes Mateos 128. Col Jacarandas
54050 Tlalnepantla Edo. de Mexico
Telefon: +52 (55) 53 98 80 88
Telefax: +52 (55) 53 79 39 85
E-Mail: isel@prodigy.net.mx
Internet: www.isel.com.mx
Hatenboer Elektro BV
Postbus 200
2170 AE Sassenheim
Telefon: +31-(0) 2 52-21 90 12
Telefax: +31-(0) 2 52-23 29 38
E-Mail: info@hatenboer.com
Internet: www.hatenboer.com
Mercom Componenta spol. s.r.o.
Ruská 67
100 00 Praha 10
Czech Republic
Telefon: +4 20-(0) 2-67 31 46 40
Telefax: +4 20-(0) 2-71 73 32 11
E-Mail: mercom@bohem-net.cz
Norway - Norwegen
Schmersal Nordiske
Hoffsveien 92
0377 Oslo
Telefon: +47-22 06 00 70
Telefax: +47-22 06 00 80
E-Mail: info@schmersal.no
Internet: www.schmersal.se
Slovenia - Slowenien
Tipteh d.o.o.
Ulica Ivana Roba 21
1000 Ljubljana
Telefon: +386-1-2 00 51 50
Telefax: +386-1-2 00 51 51
E-Mail: info@tipteh.si
Paraguay - Paraguay
All-Med
Importación - Exportación Representaciones
Tacuary No. 1318e / 1 ra. Y 2da.
Asunción
Telefon: +595 (21) 37 04 40
Telefax: +595 (21) 37 16 87
E-Mail: allmed@telesurf.com.py
Spain - Spanien
Schmersal Ibérica, S.L.
Pol. Ind. La Masia
Camí de les Cabòries, Nave 4
08798 Sant Cugat Sesgarrigues
Telefon: +34 - 93 897 09 06
Telefax: +34 - 93 396 97 50
E-Mail: info@schmersal.es
Internet: www.schmersal.es
Poland - Polen
Schmersal - Polska Sp.j.
ul. Kremowa 65A
02-969 Warszawa
Telefon: +48-(0) 22-8 16 85 78
Telefon: +48-(0) 22-8 16 85 79
Telefax: +48-(0) 22-8 16 85 34
E-Mail: office@schmersal.pl
South Africa - Südafrika
A+A Dynamic Distributors (Pty) Ltd.
3 Ruarch Street
Park Central Johannesburg
PO Box 38247
2016 Booysens
Telefon: +27-11-4 93 50 22
Telefax: +27-11-4 93 07 60
E-Mail: awkayser@iafrica.com
Portugal - Portugal
Schmersal Ibérica, S.L.
Apartado 30
2626-909 Póvoa de Sta. Iria
Telefon: +351 - 21 959 38 35
Telefax: +351 - 21 959 42 83
E-Mail: info@schmersal.pt
Internet: www.schmersal.pt
Sweden - Schweden
Schmersal Nordiska AB
Klockarns Väg 1
43533 Mölnlycke
Telefon: +46-(0) 31-3 38 35 00
Telefax: +46-(0) 31-3 38 35 35
E-Mail: info@schmersal.se
Internet: www.schmersal.se
Russia - Russland
AT electronics Moskau
ul. Avtosavodskaya 16-2
109280 Moskau
Telefon: +7- (0) 95 -1 01 44 25
Telefax: +7- (0) 95-2 34 44 89
E-Mail: info@at-e.ru
Internet: www.at-e-ru
Switzerland - Schweiz
Schmersal Schweiz AG
Freilagerstr. 25
8047 Zürich
Telefon: +41-(0) 43-3 11 22 33
Telefax: +41-(0) 43-3 11 22 44
E-Mail: info@schmersal.ch
AT Petersburg
Polytechnicheskaya str, d.9,B
194021 St. Petersburg
Telefon: +7-(0) 81 27 03-08-17
Telefax: +7-(0) 81 27 03-08-34
E-Mail: spb@at-e.ru
Serbia/Montenegro - Serbien
Tipteh d.o.o. Beograd
Bulevar AVNOJ-a45D, lokal 18
11070 Novi Beograd
Telefon: +3 81-11-3 13 10 57
Telefax: +3 81-11-3 01 83 26
E-mail: vecerka@ptt.yu
Internet: www.tipteh.co.yu
Singapore - Singapur
Tong Sim Marine & Electric Co.
46 Kaki Bukit Crescent
Kaki Bukit Techpark 1
Singapore 416269
Telefon: +65-67 43 31 77
Telefax: +65-67 45 37 00
E-Mail: tongsim@singnet.com.sg
Internet: www.tongsim.com
Slovakia - Slowakei
Schmersal Ltd.
Sparrowhawk Close
Unit 1, Beauchamp Business Centre
Enigma Park
Worcs WR14 1GL, Malvern
Telefon: +44-(0) 16 84-57 19 80
Telefax: +44-(0) 16 84-56 02 73
E-Mail: support@schmersal.co.uk
Internet: www.schmersal.co.uk
Ukraine - Ukraine
AT Electronics Kiev
Zlatoustovskaya str. 32
01135 Kiev
Telefon: +38- (0) 44-4 82 22 19
+38- (0) 44-4 86 91 25
Telefax: +38- (0) 44-2 19 22 19
E-Mail: info@at-e.com.ua
Internet: www.at-e.com.ua
Uruguay - Uruguay
Gliston S.A.
Pedernal 1896 – Of. 203
CP 11800 Montevideo
Telefon: +598 (2) 2 00 07 91
Telefax: +598 (2) 2 00 07 91
E-Mail: colmedo@gliston.com.uy
Internet: www.gliston.com.uy
USA - USA
Schmersal Inc.
660 White Plains Road
Suite 160
Tarrytown, NY 10591
Telefon: +1-(0) 9 14-3 47-47 75
Telefax: +1-(0) 9 14-3 47-15 67
E-Mail: info@schmersalusa.com
Internet: www.schmersalusa.com
Venezuela - Venezuela
EMI Equipos y Sistemas C.A.
Calle 10, Edf. Centro Industrial
Martinisi, Piso 3, La Urbina
Caracas
Telefon: +58 (212) 2 43 50 72
Telefax: +58 (212) 2 43 50 72
E-Mail: jpereira@emi-ve.com
Taiwan - Taiwan
Leader Camel Enterprise Co., Ltd.
No. 453-7, Pei Tun Rd.
Taichung, Taiwan
Telefon: +886-4-22 41 32 92
Telefax: +886-4-22 41 29 23
E-Mail: camel88@ms46.hinet.net
Internet: www.leadercamel.com.tw
Thailand - Thailand
M. F. P. Engineering Co. Ltd.
64-66 Buranasart Road
Sanchaoporsva
Bangkok 10200
Telefon: +66-2-2 26 44 00
Telefax: +66-2-2 25 67 68
E-Mail: raty@ksc.th.com
Turkey - Türkei
BETA Elektrik Sanayi Ve Ticaret
Dogan Bektas
Okçumusa Caddesi
Anthem Han No. 44
34420 Karaköy / Istanbul
Telefon: +90-212-235 99 14
Telefax: +90-212-253 54 56
E-Mail: info@betaelektrik.com
Internet: www.betaelektrik.com
UK - Großbritannien
Netherlands - Niederlande
35
Möddinghofe 30
D-42279 Wuppertal
Postfach 24 02 63
D-42232 Wuppertal
Telefon +49 - (0)2 02 - 64 74 - 0
Telefax +49 - (0)2 02 - 64 74 - 1 00
E-Mail info@schmersal.de
Internet http://www.schmersal.com
3.000 / L.D. / 04.2006 / Teile-Nr. 1171696 / Ausgabe 03
K.A. Schmersal GmbH
Industrielle Sicherheitsschaltsysteme