Safety Bus System AS-Interface Safety at Work
Transcription
Safety Bus System AS-Interface Safety at Work
Safety Bus System AS-Interface Safety at Work R S C OR AS-Interface Safety at Work ® AS-Interface SaW Easy, safe and reliab 2 AS-Interface Safety at Work (SaW) is the first safety bus system based upon the open standard of AS-International. Safety components such as Emergency Stop command devices, safety switches, solenoid interlocks or safety light curtains are simply connected to the yellow AS-Interface cable. For the evaluation of the safety signals a “Safety Monitor” is merely added to the AS-Interface system. Safe transmission mechanism The communication protocol for safety relevant applications is based on the unchanged ASInterface Standard transmission. With each AS-Interface master call each safety device answers in return with a preset data telegram. This information is analysed and in case of a deviation from the pre-set values the enabling paths are opened. The maximum response time for a safe shutdown is 40 ms. AS-Interface Standard in accordance with EN 50295 With the integration of AS-Interface SaW the AS-Interface network will continue to operate unchanged. The well known components, like the standard AS-Interface master, the standard power supply as well as the AS-Interface yellow cable will still form the basis of all ASInterface installations. Therefore an existing machine can easily be equipped with additional AS-i SaW components. Cost reduction with AS-Interface Safety at Work Reduce cost and installation time – A never ending story. During installation and machine commissioning as well as during maintenance, AS-Interface SaW supports the user with integrated system diagnosis. It provides detailed information about the cause and place of the failure, and enables the user to quickly find and analyse a malfunction and therefore minimise machine downtime. With ASInterface Safety at Work you can directly reduce your cost. The heart of safety The safety monitor analyses all transmitted information from each safety device on the ASInterface network and, in case of a safety device being activated or in case of a fault in one of the safety devices, the safety monitor immediately shuts down to create a safe condition. The safety monitor is equipped with one or two redundant pairs of enabling paths for applications up to Control Category 4 according to EN 954-1. Each safety function of the monitor can be set with a simple drag & drop software. Afterwards the configuration is downloaded into the safety monitor and protected with a password. More flexibility with AS-Interface Safety at Work For the realisation of individual safety solutions, SCHMERSAL offers the maximum amount of flexibility with its diverse range of safety devices. Depending on the application the user can choose the optimal solution out of an extensive product basket. As AS-Interface SaW is an open system, the user has also the possibility to include additional Safety components from other suppliers. AS-Interface Safety at Work fulfils the safety requirements to the highest standards. R S C OR ble No further settings are required at each of the safety devices, the bulky parallel wire cables between the safety devices in the field and the switching cabinet are reduced and wiring time is decreased. The power supply for all safety sensors is supplied over the single yellow AS-Interface cable. Less installation time with AS-Interface Safety at Work Easier and quicker with ASInterface SaW: Choose a Safety device – Connect it to the yellow AS-Interface cable – Configure the safety function in the safety monitor. – That’s it. AS-Interface Safety at Work overview Controller AS-i Power Safety guard monitoring AS-i Master Safety monitor Position switch E-Stop Command Two-Hand Control AS-Interface SaW System Features • Up to 31 standard and safety slaves on the AS-Interface system • No Safety PLC necessary • Safety-relevant signals can be allocated into groups and multiple Safety monitors may be connected • Response time is max. 40 ms • Safety-relevant signals can be integrated into plant diagnostics • Certified up to Control Category 4 in accordance with EN 954-1 • Certified by the TÜV (German Technical Inspectorate) Safety light curtain Standard AS-Interface Module 3 AS-Interface Safety at Work ® AS-Interface SaW AS-i Safety at Work 4 STIHL AG & Co., Waiblingen Hydro Aluminium, Raufoss Production line with global safety concept Fast configuring, higher transparency For its new chain guide production unit at the Waiblingen plant, STIHL, world leader in the production of chain saws, chose an innovative safety concept. All stations of the production line – both the “in-house” manufactured and the nine third-party machines – should have a uniform safety standard and communicate through AS-i SaW. The Raufoss plant of the Norwegian Hydro concern produces every year thousands of aluminium shock absorbers for the automobile industry. As production is regarded, the company considers safety of paramount importance as well: all safety components at the machines and plants are equipped with AS-Interface Safety at Work (AS-i SaW). This concept was successfully implemented. STIHL requested its suppliers to use the AS-i SaW switchgear from Schmersal. More than 110 safety switching appliances were installed: 68 by Stihl, 45 by the suppliers. Basically two types are used: the AZM 161 AS solenoid interlock and the BNS 33 AS safety sensor with integrated ASi SaW interface. Paul Giesinger, Electrical Construction Manager of the „Machine and Device Centre“ from STIHL AG & Co: „The ASi SaW components only require a minimum of wiring compared to the traditional safety switching appliances. The comfortable software moreover allows for a smooth parametrering of the safety functions.“ With AS-i SaW, Hydro Aluminium could save a lot of money as the wiring costs were regarded. Another important issue was the simplified configuration of the safety appliances through PC. The safety functions simply can be chosen and configured by Drag & Drop and then can be copied to multiple safety switching appliances if required. Ola Överstad, project manager of the New Process & Production Equipment Division at the Raufoss plant: „The increased transparency was one of the main reasons why we chose the AS-i solution. At all times, the asimon software keeps me informed about newly installed safety components. This is particularly advantageous when transferring the safety systems from one shift to another. In this way, the safety engineers always have 100% control over the system.“ R S C OR applications Benz & Hilgers GmbH, Neuss Installation costs reduced by 30% Benz & Hilgers (Benhil) at Neuss is specialised in packaging machines for pasteurised products. For the new series of wrapping machines, e.g. for butter, Benhil has decided to use the safety-related communication technology. During a thorough analysis of the different systems available, AS-i SaW revealed itself as a highly economical solution, as the safety signals are transmitted through the same cable as the conventional sensor-actor signals. This decision furthermore was facilitated as Schmersal, Benhil’s usual partner for safety components, offered a comprehensive program of safety switchgear with integrated AS-i SaW interface. Dipl.-Ing Ralph Bellin, Electrical Site Manager at Benhil’s: „We essentially chose AS-i SaW because of the simplified mounting possibilities. As the burden of the costs is enormous in our field, we must save money wherever we can, including on the installation costs. Safetyrelated bus systems are valuable in this regard: with AS-i SaW, the installation costs were reduced by 30%. For the future generations of our machines, we will use AS-i SaW as well.“ Magurit Gefrierschneider GmbH, Remscheid Optimal signal transmission between control cabinet and machine The company Magurit Gefrierschneider GmbH produces slicers, mincers and shredders for food industry. As these highcapacity machines are equipped with extremely sharp and powerful cutting devices to cut up fresh and frozen products, the risk of injury is very high. Furthermore, in food industry, high hygienic standards have to be maintained and simplicity of cleaning must be provided. Therefore, the different machine compartments are equipped with flaps and large sliding guards, whose position is monitored by concealed-mounted safety sensors. When it became necessary to install the control cabinet at approximately 60 meters from the machine, Magurit decided to use safety switching appliances with AS-i SaW interface. Nine different types of safety switching appliances were installed and connected to the bus cable. The safety-monitoring module is installed in the control cabinet. Dipl.-Ing. Dino Vieth, Electrical Site Manager of Magurit: „The reduction of the wiring costs is not the sole advantage of the safety bus. It also provides the user with improved diagnostic possibilities, considering that many operational conditions can be documented and inquired.“ 5 AS-Interface Safety at Work R S ASM C OR Technical data Standards: Control category: Enclosure: Mounting: Screw terminals: Protection class: • Safety monitor • Control Category 4 to EN 954-1 • Monitor for AS-i SaW compatible safety device, i.e. safety switches, solenoid interlocks, Emergency-Stop buttons, 2-Hand control, light grid and light curtains • AS-i connection • One or two redundant pairs of enabling paths • Additional outputs (transistor, short-circuit proof) • Configurable functions: AND logical element, OR logical element, Start devices, Start-up test • Edge-sensitive start push button • Feedback circuit to monitor external contactors • LED status display EN 50295, EN 61496-1 (1997), IEC/EN 60204-1, EN 954-1, IEC 61508 4 Polyamide PA 66, black snaps onto standard DIN rail to EN 50022 max. 2.5 mm2 (incl. conductor ferrules) terminals IP 20 enclosure IP 20 Ub: 24 VDC ± 15 % Residual ripple: < 15% Ib: ASM E1-R2: 0,15 A ASM E2-R2/R2: 0,2 A Switch-on peak current: 600 mA AS-Interface operating voltage: 18.5 ... 31.6 V AS-Interface operating current: < 45 mA AS-Interface specification: Profile - Monitor 7.F Configuration interface: RS232: 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits Inputs: 1.Y1,1.Y2 Input signal: „Y1, Y2“: le < 10 mA at 24 VDC (opto coupler, high-active) Outputs: ASM E1-R2: 1.13/14,1.23/24, 1 enabling path (redundant); ASM E2-R2/R2: 1.13/14,1.23/24, 2.13/14, 2.23/24, 2 enabling paths (redundant) Utilisation category: AC-15, DC-13 Ie/Ue: 3 A / 230 VAC 1 A / 24 VDC Switching voltage: max. 230 VAC Ithe: 3 A per output circuit Max. fuse rating: 4 A (slow blow), external Additional outputs: transistor outputs, 200 mA total, short-circuit proof-type, positive-switching Switch-on time: < 10 s Response time: < 40 ms Indications: AS-Interface: voltage LED green, communication LED red; Enabling paths: LED green, yellow, red EMC rating: conforming to EMC Directive Overvoltage category: III to DIN VDE 0110 Resistance to vibration: 5 ... 500 Hz (5 … 26 Hz, 0.75 mm amplitude; 26 … 500 Hz, 2g) Resistance to shock: 15 g / 11 ms Ambient temperature: – 20 °C … + 60 ºC Storage and transport temperature: – 30 °C … + 70 ºC Weight: ASM E1-R2: approx. 350 g; ASM E2-R2/R2: approx. 450 g Abmessungen: 45 x 105 x 120 mm Inductive loads (e.g. contactors, relays, etc.) are Note: to be suppressed by means of a suitable circuit. Approvals F C Ordering details ASM E ➀ No. Replace Description ➀ 1-R2 1 enabling field (redundant) 2 enabling fields (redundant) 2-R2/R2 6 Note The safety monitors ASM E1-R2 and ASM E2-R2/R2 evaluate all transmitted information from each safety device on the AS-Interface network. For the safe guarding of different applications various AS-Interface Safety at Work compatible safety devices are needed, i.e. safety switches, solenoid interlocks, safety sensors, E-stop buttons as well as safe input modules. The AS-Interface Safety at Work can be used in applications up to control category 4 according to EN 954-1 with the appropriate safety devices and systems. AS-Interface Safety at Work R S • The installation of different safety areas is possible with numerous safety monitors working alongside each other. The maximum number of safety devices including the safety monitors may not exceed 31 participants. • The allocation of the safety devices to one or more safety monitors is achieved with the help of the configuration software ”asimon“. • The wiring diagram shows the safety monitor ASM E2-R2/R2 with start-pushbuttons and feedback loops. • No safety devices are displayed, because they are installed in the field i.e. on the safety guards itself. The data connection between the safety monitor and the decentralised safety slaves is established via the ASInterface network. • For the operation of AS-Interface Safety at Work system, a standard controller, an ASInterface Master and AS-Interface power supply, must always be used in the application. • With the RJ 45 connector the safety monitor is configured and started up. OR Wiring diagram + 24 VDC + 24 VDC 0V L1 S2 S1 AS-iAS-i+ M1 AS-i+ AS-i- 1Y1 ASInterface 1Y2 2Y1 1.32 2Y2 M2 2.32 1.13 1.23 2.13 2.23 1.14 1.24 2.14 2.24 K1 K3 RJ 45 Note C RS 232 K2 K4 24 V L+ M FE 2.14 2.24 L1 L2 L3 K5 + 24 VDC K6 0V L1 L2 L3 K7 K5 K7 K8 K6 K8 N M 3 N M 3 • Start push button H A start push button (NO) can optionally be connected to the ASM. With the guard door(s) closed, the enabling paths are then not closed until the start push button has been operated. If neither start button nor feedback circuit are required, then no connections are required to the terminals (1Y1/2, 2Y1/2). • Output expander module For additional contacts by means of more enabling paths and potential-free indication contacts an output expander module is connected to the safety monitor, i.e. to the internal ASM enabling path. For the control of the additional outputs the ASM feedback loop is utilised. Note Further information and details of the safety monitor ASM are available on the asimonCD-ROM. Note The AS-i system limitations according to EN 50295 have to be concidered during the planning, development and design phase of the AS-i network, especially the max. number of AS-i slaves and the total „yellow“ cable length (< 100 m without repeater). 7 AS-Interface Safety at Work R S asimon C OR System components Following the successful configuration and download, the safety monitor and the safety devices can be tested and monitored with asimon. The asimon software is a tool for the configuration and commissioning of the AS-Interface safety monitor. The configuration of the safety monitor and its safety devices, i.e. E-Stop buttons, solenoid interlocks, safety switches, 2-Hand controls, light curtains etc. is performed by an easyto-use graphical interface. Thus providing safeguarding of hazardous areas present by power-driven machinery. The following functions are available with the asimon software: • Configuration of different safety devices • Configuration of start-modules • Configuration logical combinations (AND, OR, RS Flip-Flops) • Configuration of the feedback loops • Configuration of the operating methods • Configuration of the system-modules • Print out of Configuration protocol Download cable ASM-DC1 Asimon can be used offline as well as online during development and project planning. The configuration files can be saved and loaded as desired. The software is compatibable with the Microsoft® operating system Windows 95/98/ME/NT/2000/XP. Configuration cable ASM-KC1 The asimon offers the user a library of icons representing different safety devices and other functional devices, i.e. one or two independent enabling paths, automatic or monitored start, stop category 0 or 1 etc. For the implementation of a new safety application the required safety devices are selected from the icon library, configured and assigned to the respective enabling path. Approvals F C Ordering details Note ASM-startup-package: SET ASM-SWP Configuration and diagnostic software package with online documentation on CD-ROM, a configurationand downloadcable asimon software package: Configuration and diagnostic software package with online documentation on CD-ROM ASM-CD Hardware requirements: • 200 MHz INTEL Pentium® or AMD® Processor or quicker • Min. 8 Mbyte free main memory (RAM) • Min. 8 Mbyte free hard disk memory • A CD-ROM drive (or 3 1/2 “ disc drive) for the installation • A mouse • A free serial interface with 9 SubD-connection Software requirements: • Microsoft Windows ® 95/98/ME/NT/2000/XP 8 Ordering details Download cable: Interface cable with two RJ 45 connectors, Length: 0.10 m ASM-DC1 Configuration cable: Interface cable with one RJ 45 and SUBD 9 connector, Length: 1.2 m ASM-KC1 AS-Interface Safety at Work R S T.. 235-AS Design: Enclosure: Switching system: 10 3,5 AS-Interface connection type: Protection class: AS-Interface operating voltage: 25 4,3 6 12 8,5 OR Technical data Standards: 63,5 C 20 20 20 22 22 13,5 30 30 • Position switch • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector, adjustable • Metal enclosure • Wide range of alternative actuators • Actuator heads can be repositioned by 4 x 90° • Angle of roller lever adjustable in 10° steps • Good resistance to oil and petroleum spirit • Protection class IP 67 EN 50295 EN 60947-5-1 EN 954-1 BG-GS-ET-15 fixings to EN 50047 zinc die-cast, enamelled slow action, positive break NC contacts A connector M12 x 1 IP 67 to EN 60529 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: AS electronics: 50 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF 0xE ID-Code2: Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 ... A3 not used Parameter bits: P0 ... P3 not used Input module address: Default on address 0 Indications: AS-interface: voltage LED green, communication LED red Enabling status: LED yellow > 1 million operations Mechanical life: Switching frequency: max. 5000/h EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport temperature: – 25 °C … + 85 ºC ≤ Approvals F C Ordering details T➀ 235-AS-ST No. ➀ Replace Description For the appropriate actuator see Main catalogue „Safety technology“ Note A separate address jack is not available as an option. The addressing must take place via the M12 connector. 1 2 4 3 5 1: AS-Interface + 2: spare 3: AS-Interface – 4: spare 5: FE (shield) 9 AS-Interface Safety at Work R S AZM 161 AS Technical data Standards: Enclosure: AS-Interface connection type: Protection class: AS-Interface operating voltage: 40 6 18 29 b 90 a 7 6 6 5,5 M12 130 56 M12 30 • Solenoid interlock • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Magnetic drive through AS-Interface output • Solenoid power supply via the AS-Interface network or via an external 24 VDC power supply (p version) • Address jack (optional) • Thermoplastic enclosure • Manual release, emergency exit or emergency release • High holding force 2000 N • 30 N latching force (optional) • Power to unlock / power to lock principle • Actuating play 5.5 mm in direction of actuation • Protection class IP 67 Approvals F * EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic, self-extinguishing connector M12 x 1 IP 67 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof ≤ Total: 500 mA AS electronics: 50 mA AS-Interface specification: (V 2.1) Profile S-7.B IO-Code 0x7 ID-Code 0xB ID-Code1: 0xF ID-Code2 0xE Inputs: Status Data bits Contact 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 Solenoid control A1 … A3 not used Parameter bits: P0 Actuator / interlock status P1 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mechanical life: > 1 million operations Fmax: 2000 N EMC rating: conforming to EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: ≤ ➀ ➁ ➂ Description B Z ST1 ST2 Actuator monitored Guard locking monitored Connector (middle) Connector (right) No latching Latching 30 N Power to unlock Power to lock No address jack Address jack ➃ r ➄ a b 10 Output A0 is used to lock or unlock the solenoid of the solenoid interlock. Parameter bit P0 gives the control system feedback about the status of the actuator or solenoid interlock. Parameter bit: The status of the actuator or the locking bolt can be monitored by the parameter bit P0 depending on the device: Device AZM 161 B AZM 161 B AZM 161 Z AZM 161 Z Parameter bit P0 0 1 0 1 Safety guard status Guard locked Guard unlocked Guard closed Guard open Note AZM 161➀➁ -AS➂➃➄➅➆ Replace The AZM 161 Z version must be selected for applications where safety guard locking is required. The AZM 161 B version has a safetymonitored actuator with supplementary guard locking function. * UL / CSA approvals only without address jack C Ordering details No. OR Note AS-Interface operating current: 78 72 8 6 C No. Replace ➅ ➆ p N T Description A separate address jack is not available as an option. The addressing must take place via the M12 connector. Integrated solenoid supply External solenoid supply Manual release Emergency release Emergency exit 1 2 4 3 1: AS-i + 2: Aux – (p) 3: AS-i – 4: Aux + (p) AS-Interface Safety at Work R S Contact variants Contact variants Integrated power supply External power supply Power to unlock Guard locking monitored Power to unlock Guard locking monitored C OR Note Integrated power supply: The solenoid interlock AZM 161 AS is powered by the AS-Interface. Connection to the ASInterface is made via the M12 connector. The required supply voltage for the solenoid is also supplied by the AS network. P0 AS-i + - D0-D3 A0 Actuator monitored D0-D3 AS-i + - P0 D0-D3 A0 Actuator monitored D0-D3 AS-i P0 A0 + - + 24 VDC - Actuator monitored D0-D3 A0 P0 A0 + - A0 D0-D3 + - P0 Power to lock Guard locking monitored AS-i P0 AS-i AS-i + - + - 24 VDC Power to lock Guard locking monitored P0 AS-i A0 D0-D3 + - D0-D3 A0 + - To lock or unlock the guard door, the network must supply a maximum current of 0.5 A per solenoid interlock. External power supply: The solenoid interlock AZM 161 AS ...p is monitored by the AS-Interface. The locking solenoid is powered by an external power supply. Connection to the AS-Interface and the auxiliary power is made via a single M12 connector. + 24 VDC - Actuator monitored AS-i The maximum number of interlocks with integrated power supply and power to lock principle (a) depends solely on the employed AS-Interface power supply and its electric current output. The passive connection module (see page 29) links up the external solenoid power supply (auxiliary power supply, black cable) and the AS-i network connection (yellow cable) to a single M12 connector. A 4-wired cable makes the connection to the solenoid interlock. P0 + 24 VDC - Solenoid control: An internal output controls the solenoid operation. Depending on the device version, the output bit A0 locks or releases the actuator. The output bit A0 has the same address as the safety inputs. Legend D0 – D3 P0 A0 Coded data for the evaluation of the safety monitor (4 Bit) Status signal (1 Bit) Output for switching the solenoid (1 Bit) 11 AS-Interface Safety at Work R S EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic, self-extinguishing Enclosure: 40 ø 5,5 connector M12 x 1 IP 67 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification: (V 2.1) Profile S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits on D0/D1 = dynamic code 1 transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow > 1 million operations Mechanical life: EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport – 25 °C … + 85 ºC temperature: 27 Straight actuator AZ 15/16-B1 a R min. 45 16 5 11 56 40 ø 5,5 27,3 a 27 Flexible actuator AZ 15/16-B2 16 R min. 38 56 40 R min. 25 ø 5,5 11 • Safety switch with separate actuator • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Address jack (optional) • Thermoplastic enclosure • Coded actuator • Long life • Protection class IP 67 0 7 30 R min. 15 27,3 90 15,5 7 5,5 M 12 52 9 13 M 12 16 ≤ 29 18 8 0 7 14 8 AS-Interface connection type: Protection class: AS-Interface operating voltage: R min. 15 56 40 10 Standards: System components 5 Technical data OR 28,3 AZ 16 AS C 27 Flexible actuator AZ 15/16-B6 Approvals F C Ordering details AZ 16➀ -AS➁➂ No. ➀ ➁ ➂ Replace Description ST1 ST2 ST3 Connector (middle) Connector (right) Connector (left) No latching Latching 30 N Latching 5 N No address jack Address jack r r-2254 b Note Ordering details A separate address jack is not available as an option. The addressing must take place via the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare Straight actuator Flexible actuator Flexible actuator AZ 15/16-B1 AZ 15/16-B2 AZ 15/16-B6 Further actuators can be found in the chapter „Safety switches with separate actuator“, see page 1-8. Actuators must be ordered separately. AS-Interface Safety at Work R S Technical data Standards: AS-Interface connection type: Protection class: AS-Interface operating voltage: 39 52 26 37 90 M20 x 1,5 7 15 M20 x 1,5 M 12 40 17 20 60 40 ¤ 5,5 connector M12 x 1 IP 67 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 100 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits on D0/D1 = dynamic code 1 transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: Default on address 0 Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mode of operation: magnetic Sao: 8 mm Sar: 18 mm R ≤ 0,1 x Sao Repeat accuracy: Switching frequency f: < 1 Hz Actuating magnet: BPS 16, coded EMC rating: conforming to EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: Actuating magnet BPS 16 ≤ 9 M 12 System components EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic, self-extinguishing Enclosure: OR 11 BNS 16 AS C • Safety sensor • Integrated AS-Interface • AS-Interface LED status display • Available with M12 plug-in connetor and pre-wired cable • Thermoplastic enclosure • Coded actuator • Long life, no mechanical wear • Insensitive to transverse misalignment • Concealed mounting possible • Insensitive to soiling • Protection class IP 67 Actuating planes Approvals F C Ordering details BNS 16➀ -AS➁ No. ➀ ➁ Replace Description ST1 ST2 ST3 Connector (middle) Connector (right) Connector (left) Actuating planes: front side cover-side V D Note Ordering details A separate address jack is not available as an option. The addressing must take place via the M12 connector. 1 2 4 3 Actuating magnet BPS 16 Actuators must be ordered separately. 1: AS-i + 2: spare 3: AS-i – 4: spare 13 AS-Interface Safety at Work R S AS-Interface connection type: Cable section: Protection class: AS-Interface operating voltage: 7,5 LED • Safety sensor • Integrated AS-Interface • AS-Interface LED status display • Available with M12 plug-in connetor and pre-wired cable • Thermoplastic enclosure • Coded actuator • Long life, no mechanical wear • Insensitive to transverse misalignment • Concealed mounting possible • Insensitive to soiling • Protection class IP 67 ø5 3 13 Actuating magnet BPS 33 13 8,5 ø5 3,5 6,5 18,5 3,5 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mode of operation: magnetic Sao: 5 mm 15 mm Sar: Repeat accuracy: R ≤ 0,1 x Sao Switching frequency f: < 1 Hz Actuating magnet: BPS 33, coded EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 70 ºC Storage and transport temperature: – 25 °C … + 85 ºC 7 7 2000 4,5 25 cable LSYY (black) 2 x 0.24 mm2 IP 67 to EN 60529 ≤ 88 78 ø5 4,5 10 Enclosure: 88 78 18,5 EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic 18,5 25 Standards: System components 3,5 Technical data OR 25 7 BNS 33 AS C 78 88 Spacer BN 31/33 Approvals F C Ordering details BNS 33➀ -AS No. Replace ➀ STG STW 14 Note Ordering details Description A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 2 m cable 2 m cable with straight plug M12 2 m cable with angled plug M12 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare Actuating magnet Spacer BPS 33 BN 31/33 The actuators for the safety sensors must be ordered separately. AS-Interface Safety at Work R S Technical data Standards: EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic Enclosure: 36 LED 22 ¤ 4,5 26 19 4 • Safety sensor • Integrated AS-Interface • AS-Interface LED status display • Available with M12 plug-in connetor and pre-wired cable • Thermoplastic enclosure • Coded actuator • Long life, no mechanical wear • Insensitive to transverse misalignment • Concealed mounting possible • Insensitive to soiling • Protection class IP 67 Approvals F BNS 260➀ -AS-➁ Replace ➀ STG STW ➁ 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green communication LED amber Mode of operation: magnetic Sao: 5 mm 15 mm Sar: Repeat accuracy: R ≤ 0,1 x Sao Switching frequency f: < 1 Hz Wiederholgenauigkeit: R ≤ 0,1 x Sao Schaltfrequenz f: < 1 Hz BPS 260, coded Actuating magnet: EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 70 ºC Storage and transport – 25 °C … + 85 ºC temperature: Left hand door ≤ Right hand door 19 13 6 ¤4,5 26 BPS 260 C Ordering details No. cable LSYY (black) 2 x 0.24 mm2 IP 67 to EN 60529 36 6 13 AS-Interface connection type: Cable section: Protection class: AS-Interface operating voltage: 1000 OR System components 22 BNS 260 AS C L R Description 2 m cable 2 m cable with straight plug M12 2 m cable with angled plug M12 Left hand door Right hand door Note Ordering details A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare Left hand door Right hand door ordering suffix -L ordering suffix -R Actuating magnet Actuator and sensor mounted on same fixing plane Actuator for 90° fixing BPS 260-1 BPS 260-2 The actuators for the safety sensors must be ordered separately. 15 AS-Interface Safety at Work R S BNS-B20-AS Technical data Standards: Enclosure: 43,3 32,4 Protection class: AS-Interface connection type: AS-Interface operating voltage: 8,5 40 108 119,5 17 140 82 120 99 62 10 LED 5 20 • Safety sensor • Integrated AS-Interface • AS-Interface LED status display • Substitutes door-handle and safety switch, no further door fittings required • Latching force of approx. 100 N • M12 plug-in connetor • Tamper-proof because of integral coded safety sensor • LED indication • Ergonomic operation • Suitable for hinged and sliding guards • Protection class IP 67 EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced thermoplastic IP 67 to EN 60529 connector M12 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: ≤ 50 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission off D0/D1 = static code “00” 1 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mode of operation: magnetic sao: 0 mm sar: 22 mm Ambient temperature: – 25 °C … + 70 ºC Storage and transport temperature: – 25 °C … + 70 ºC Switching frequency f: < 1 Hz Resistance to shock: 30 g / 11 ms Resistance to vibration: 10 … 55 Hz, amplitude 1 mm Max. door weight: hinged guard: 5 kg sliding guard: 3 kg Approvals F C Ordering details BNS-B20-AS-ST-➀ Sensor BNS-B20-B01 Actuator No. ➀ Replace Description L R Left hand door Right hand door The actuators for the safety sensors must be ordered separately. 16 Note A separate address jack is not available as an option. The addressing must take place via the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare C OR AS-Interface Safety at Work R S NAS 311 AS C OR Technical data Standards: EN 50295, EN 60947-5-1, EN 954-1 Enclosure: glass-fibre reinforced polyamide nylon, self-extinguishing Emergency-Stop button: thermoplastic or aluminium AS-Interface connection type: connector M12 x 1 Protection class: IP 65 AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification: Profile S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits on D0/D1 = dynamic code 1 transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport temperature: – 25 °C … + 85 ºC ≤ 85 ¤ 29 ¤ 40 85 M 12 97,8 M 12 37,8 • E-STOP station • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Pull to reset • Resistant to chemicals • Protection class IP 65 Approvals F C Ordering details NAS 311 ➀ -AS ➁ Note No. Replace Description ➀ ➁ A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. ST1 Connector Thermoplastic enclosure Metal housing Metal housing and push button with protection collar 1 2 M MH 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare 17 AS-Interface Safety at Work R C S AST ... ST-AS AST ... L-AS Technical data Vorschriften: Enclosure: EN 50295, EN 60947-5-1, EN 954-1 glass-fibre reinforced thermoplastic, self-extinguishing AS-Interface connection type: Protection class: AS-Interface operating voltage: 16,5 70 66 ca. 2000 ca. 2000 70 66 2 ca. 2000 2 25 M30x1,5 ¤28 M30x1,5 ¤28 25 • Input module with M12 connector (AS-i) • 2 safe inputs for mechanical contacts • Connection of NC/NC contact or NC/NO contact combination • Cross-wire monitoring • Magnetic drive through AS-Interface output • Solenoid power supply via via an external 24 VDC (max. 0.5 A) power supply • AS-Interface LED status display • AS-Interface M12 connector • Thermoplastic enclosure • Long life • Protection class IP 67 OR • Input module with connecting cable (AS-i), length 2 m (see ordering data) IP 67 to EN 60529 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: ≤ 50 mA AS-Interface specification: (V 2.1) Profile: S-7.B IO-Code: 0x7 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” on D2/D3 = dynamic code 2 transmission 2 off D2/D3 = static code “00” Outputs: A0 Solenoid control(AST ... 6) (24 VDC, max. 500 mA) A1... A3 not used Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red, blinking = cross-wire short Enabling status: LED1/contact1, yellow/contact2 EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 55 ºC Storage and transport – 25 °C … + 85 ºC temperature: Approvals F C Ordering details Note AST ➀➁ -AS➂➃ No. ➀ ➁ Replace Description 02 11 1 NC/1 NC 1 NO/1 NC AS-i connection: M12 connector Cable (2m) ST L No. Replace ➂ 2 4 6 ➃ ST 18 Description Sensor connection: 2 x 2-single conductors (2 safety inputs) 1 x 4-single conductors (2 safety inputs) 1 x 6-single conductors (2 safety inputs and 1 semiconductor output) Sensor connection: M12 connector with 2m cable 2 x 2 and 1 x 4 (option) A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: Aux – (6) (AST...6) 3: AS-i – 4: Aux + (6) (AST...6) AS-Interface Safety at Work R S Note C OR Wiring diagram • The wiring diagram is shown with guard doors closed and in de-energised condition. • The AST module can on be used for the connection of potential-free contacts. Additional LED’s on the connecting wire are not acceptable. • Monitoring a sliding guard door using two position switches with safety function. The NC contact must have positive break when the guard door is opened. BU BU BN BN Sensor connection AST 02 ST 2 AS-i connection AZM 170-11z • The module AST...AS is monitored by the AS-Interface. The locking solenoid is powered by an external power supply. Connection to the AS-Interface and the auxiliary power is made via a single M12 connector or via a 4-pole connecting cable. A1 A2 13 14 21 22 BN BU WH BK RD GY • The passive connection module (see page 29) links up the external solenoid power supply (auxiliary power supply, black cable) and the AS-i network connection (yellow cable) to a single M12 connector. A 4-wired cable makes the connection to the AST…ST6 module. Sensor connection • An internal output controls the solenoid operation. Depending on the interlocking device, output bit A0 locks or unlocks the actuator. Output bit A0 has the same address as the safety inputs. AST 11 ST 6 AS-i connection 19 AS-Interface Safety at Work R S AST LC ST-AS Technical data Standards: Enclosure: AS-Interface connection type: Protection class: AS-Interface operating voltage: 16,5 70 66 ca. 2000 ca. 500 25 2 M30x1,5 ¤28 ST1 ST2 • Input module for 2 monitored PNP semiconductor outputs for light curtains and light grids • AS-Interface LED status display • AS-Interface M12 connector • Thermoplastic enclosure • Long life • Protection class IP 67 EN 50295, EN 60947-5-1, EN 954-1, EN 61496-1 glass-fibre reinforced thermoplastic, self-extinguishing AST LC ST-AS 20 Connector ST (male) 1 2 1: 2: 3: 4: 4 3 AS-i + spare AS-i – spare connector M12 IP 67 to EN 60529 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: ≤ 50 mA AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission off D0/D1 = static code “00” 1 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 ... A3 not used Parameter bits: P0 .. P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red, OSSD1/2; Enabling status: LED yellow Power supply PELV power supply for AOPD: to IEC 364-4-41 Reaction time: ≤ 20 ms EMC rating: conforming to EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: C Ordering details OR Note Approvals F C Note A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. Connector ST1 (male) 1 2 1: 2: 3: 4: 5: 4 3 5 Connector ST2 3 4 2 1 5 + 24 VDC OSSD 1 GND OSSD 2 FE (function earth) (female) 1: 2: 3: 4: 5: + 24 VDC spare GND spare FE (function earth) AS-Interface Safety at Work R S Note C OR Wiring diagram • The wiring diagram shows an active optoelectronic device (AOPD) (type SLC/SLG) with a safety input module AST LC ST-AS (Opto-Tube) connected to the AS-i Safety at Work system. Emitter module • The Opto-Tube is directly connected to the receiver module (ST2). The AOPD receives its 24 VDC power supply via the second M12-cable connection (ST1). Receiver module • The Opto-Tube itself is connected via the M12 connector (ST) to the AS-i network. Before hand the module has to be programmed with an individual adress (1 - 31). ST2 see note • The emitter module has be wired up separately as described in its mounting and wiring instruction. 24 VDC (ST1) AS-i (ST) 21 AS-Interface Safety at Work R S ASU command devices Technical data Standards: AS-Interface connection type: Protection class: (see ordering data) IP 65 (front) IP 20 (rear of the front plate) AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: AS-Interface specification: ≤ 50 mA Profile IO-Code ID-Code ID-Code1: ID-Code2 22 71 max. 6 29 Ø 38,5 23,5 75 38 • Emergency-Stop button • Compact embeddable command devices with ASU adapter box • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector, IDC connector • Miscellanous positioning parts (metal, plastic) • Mounting hole 22.3 mm (to EN 50 007) • Protection class IP 65 (from front) Inputs: Contact 1 OR Technical data EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced polyamide nylon, self-extinguishing Enclosure: C Actuating elements Al-metal actuating element: Resistance to shock: max. 15 g / 22 ms* (temporary data) Resistance to vibration: max. 0.35 mm, 0 … 150 Hz Plastic actuating element: Resistance to shock: max. 15 g / 22 ms* (temporary data) Resistance to vibration: max. 0.35 mm, 0 … 150 Hz * preliminary data S-7.B 0x7 0xB 0xF 0xE Status on Data bits D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Resistance to shock: 110 g/4 ms…30 g/18 ms, no bouncing (for actuating heads with higher respectively lower weight) Resistance to vibration: 20 g / 10 …200 Hz (for actuating heads with higher respectively lower weight) conforming to EMC rating: EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: ≥ Approvals F C Ordering details EFP ➀ -AS 110 ➁DRZ 40 RT No. ➀ ➁ 22 Replace ST DT ME E K Contact block Actuating element Note Note Addressing through flat cable connection or through M12 connector. Description M12 connector Flat cable connection (DC) optional: 2 m cable, cable gland, flying lead Metal actuating element Plastic actuating element 1 1 2 4 3 The positioning parts are not included in delivery. 2 M12 connector: 1: AS-Interface + 2: spare 3: AS-Interface – 4: spare Mounting One-hole fixation 22.3 mm + 0.4 mm to EN 50 007 (a tail cut-out as displacement protection is not required for Elan devices) Flat cable connection: 1: AS-i + 2: AS-i – AS-Interface Safety at Work R S ASU command devices C OR Technical data Standards: EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced polyamide nylon, self-extinguishing Enclosure: AS-Interface connection type: Protection class: (see ordering data) IP 65 (front) IP 20 (rear of the front plate) AS-Interface operating voltage: ≤ 22 71 max. 6 14 Ø 29,5 (29,8) Ø 22 (25) 23,5 75 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification: Profile S-7.B IO-Code 0x7 ID-Code 0xB ID-Code1: 0xF ID-Code2 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Resistance to shock: 110 g/4 ms…30 g/18 ms, no bouncing (for actuating heads with higher respectively lower weight) Resistance to vibration: 20 g / 10 …200 Hz (for actuating heads with higher respectively lower weight) conforming to EMC rating: EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: 38 • Push button • Compact embeddable command devices with ASU adapter box • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector, IDC connector • Miscellanous positioning parts (metal, plastic) • Mounting hole 22.3 mm (to EN 50 007) • Protection class IP 65 (from front) ≥ Approvals F C Ordering details EFP ➀ -AS 033 ➁ DT ➂ No. ➀ ➁ ➂ Replace ST DT ME E K GN* SW* BL* Contact block Actuating element Note Note Addressing through flat cable connection or through M12 connector. Description M12 connector Flat cable connection (DC) optional: 2 m cable, cable gland, flying lead Metal actuating element Plastic actuating element Green push-button Black push-button Blue push-button Other colours on request 1 1 2 4 3 Mounting One-hole fixation 22.3 mm + 0.4 mm to EN 50 007 (a tail cut-out as displacement protection is not required for Elan devices) The positioning parts are not included in delivery. 2 M12 connector: 1: AS-Interface + 2: spare 3: AS-Interface – 4: spare Flat cable connection: 1: AS-i + 2: AS-i – * Push-buttons in different colours available on request. 23 AS-Interface Safety at Work R S ASU command devices C OR Technical data Standards: EN 50295, EN 60947-5-1 EN 954-1 glass-fibre reinforced polyamide nylon, self-extinguishing Enclosure: AS-Interface connection type: Protection class: (see ordering data) IP 65 (front) IP 20 (rear of the front plate) AS-Interface operating voltage: ≤ ≤ 22 71 max. 6 14 Ø 29,5 (29,8) Ø 22 (25) 23,5 75 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA, with illuminated pushbutton 70 mA AS-Interface specification : Profile S-7.B IO-Code 0x7 ID-Code 0xB ID-Code1: 0xF ID-Code2 0xE Inputs: Contact Status Data bits on D0/D1 = dynamic code 1 transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 Indicator lamp A1 ... A3 not used Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red LED yellow Enabling status: Resistance to shock: 110 g/4 ms…30 g/18 ms, no bouncing (for actuating heads with higher respectively lower weight) Resistance to vibration: 20 g / 10 …200 Hz (for actuating heads with higher respectively lower weight) EMC rating: conforming to EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport temp.: – 25 °C … + 85 ºC 38 • Illuminated push-button • Compact embeddable command devices with ASU adapter box • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector, IDC connector • Miscellanous positioning parts (metal, plastic) • Mounting hole 22.3 mm (to EN 50 007) • Protection class IP 65 (from front) ≥ Approvals F C Ordering details EFP ➀ -AS 03L ➁ DL ➂ No. ➀ ➁ ➂ Replace ST DT ME E K GN* SW* 24 Contact block Actuating element Note Note Addressing through flat cable connection or through M12 connector. Description M12 connector Flat cable connection (DC) optional: 2 m cable, cable gland, flying lead Metal actuating element Plastic actuating element Green illuminated push-button Black illuminated push-button Other colours on request 1 1 2 4 3 Mounting One-hole fixation 22.3 mm + 0.4 mm to EN 50 007 (a tail cut-out as displacement protection is not required for Elan devices) The positioning parts are not included in delivery. 2 M12 connector: 1: AS-Interface + 2: spare 3: AS-Interface – 4: spare Flat cable connection: 1: AS-i + 2: AS-i – * Push-buttons in different colours available on request. AS-Interface Safety at Work R S ASU command devices C OR Technical data Standards: EN 50295 EN 60947-5-1 EN 954-1 glass-fibre reinforced polyamide nylon, self-extinguishing Enclosure: AS-Interface connection type: Protection class: (see ordering data) IP 65 (front) IP 20 (rear of the front plate) AS-Interface operating voltage: • Other ASU command devices on request 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification : Profile S-7.B IO-Code 0x7 ID-Code 0xB ID-Code1: 0xF ID-Code2 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Switching frequency: 3600/h Resistance to shock: 30 g/18 ms, no bouncing (for actuating heads with higher respectively lower weight) Resistance to vibration: 15 g / 10 ... 200 Hz (for actuating heads with higher respectively lower weight) conforming to EMC rating: EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport temp.: – 25 °C … + 85 ºC ≤ ≥ Approvals F C Ordering details on request Note Addressing through flat cable connection or through M12 connector. 1 1 2 4 3 2 M12 connector: 1: AS-Interface + 2: spare 3: AS-Interface – 4: spare Flat cable connection: 1: AS-i + 2: AS-i – 25 AS-Interface Safety at Work R S ZS 71 AS Technical data ø 10 40 30 10 53,5 6 ≤ ≤ 8 18 12 56 22 105 24 33 15 17,5 M 12 52 M 12 42 • Pull-wire Emergency-Stop switch • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Metal enclosure • Various spring force variants (actuating forces) • Adjustable actuating force • Wire up to 20 m long • Reset by push button or key possible • Protection class IP 65 (with push button and external watertight collar) Approvals F C Ordering details ZS 71➀ -AS ➁➂ -➃ -➄ / ➅ No. Replace Description ➀ ➁ ST1 Connector Without watertight collar With watertight collar Without safety function Push button reset Key reset Without position indicator With position indicator Without indicator lamp With indicator lamp Pre-tensioning force: For wire length 0 - 5 m For wire length 5 - 20 m ➂ ➃ W VD VS ➄ A ➅ G 55 N 200 N 26 Standards: EN 50295, EN 60947-5-1, EN 954-1 Enclosure: cast aluminium, enamelled Cover: thermoplastic ultramid AS-Interface connection type: connector M12 x 1 Protection class: IP 54 IP 65 for version with push button reset and watertight collar AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA, with indicator lamp 130 mA AS-Interface specification: Profile S-7.B IO-Code: 0x7 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Status Data bits Contact 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 Indicator lamp (optional) A1 … A3 not used Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mechanical life: > 1 million operations Maximum cable length: 20 m Features: wire pull and breakage detection EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport – 25 °C … + 85 ºC temperature: Note A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare A wide range of accessories is available. For selection, see Main catalogue „Safety technology“. C OR AS-Interface Safety at Work R S ZS 73 AS 6,5 75 105 48 30 5 15 M 12 M 12 70 28 98 56 • Pull-wire Emergency-Stop switch • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Metal enclosure • 4 various spring force variants (actuating forces) • Adjustable actuating force • Wire up to 50 m long • Reset by push button or key possible • Protection class IP 65 (with push button and external watertight collar) Approvals F ZS 73➀ -AS ➁➂ -➃ / ➄ No. Replace Description ➀ ➁ ST1 Connector Without watertight collar With watertight collar Without safety function Push button reset Key reset Without indicator lamp With indicator lamp Pre-tensioning force: For wire length 0-10 m For wire length 10-20 m For wire length 20-30 m For wire length 30-50 m ➃ ➄ Standards: EN 50295, EN 60947-5-1, EN 954-1 Enclosure: cast aluminium, enamelled Cover: thermoplastic ultramid AS-Interface connection type: connector M12 x 1 Protection class: IP 54 IP 65 for version with push button reset and watertight collar AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA, with indicator lamp 130 mA AS-Interface specification: Profile S-7.B IO-Code: 0x7 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Status Data bits Contact 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 Indicator lamp (optional) A1 … A3 not used Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mechanical life: > 1 million operations Maximum cable length: 50 m Features: wire pull and breakage detection EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport – 25 °C … + 85 ºC temperature: ≤ ≤ C Ordering details ➂ OR Technical data 170 25 C W VD VS G 80-100N 120-180N 195-275N 295-390N Note A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare A wide range of accessories is available. For selection, see Main catalogue „Safety technology“. 27 AS-Interface Safety at Work R S ZS 75 AS Technical data 69 54 23 52 66 160 33 19,5 76 71 80 6,5 154 14 12 27 M 12 M 12 70 100 • Pull-wire Emergency-Stop switch • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Metal enclosure • 4 various spring force variants (actuating forces) • Adjustable actuating force • Wire up to 50 m long • Reset by push button or key possible • Protection class IP 65 (with push button and external watertight collar) Approvals F ZS 75➀ -AS ➁➂ -➃ / ➄ No. Replace Description ➀ ➁ ST1 Connector Without watertight collar With watertight collar Without safety function Push button reset Key reset Without indicator lamp With indicator lamp Pre-tensioning force: For wire length 0-10 m For wire length 10-20 m For wire length 20-30 m For wire length 30-50 m ➃ ➄ W VD VS G 80-100N 120-180N 195-275N 295-390N 28 ≤ ≤ C Ordering details ➂ Standards: EN 50295, EN 60947-5-1, EN 954-1 Enclosure: cast aluminium, enamelled Cover: cast aluminium, enamel finish AS-Interface connection type: connector M12 x 1 Protection class: IP 54 IP 65 for version with push button reset and watertight collar AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA, with indicator lamp 130 mA AS-Interface specification: Profile S-7.B IO-Code: 0x7 ID-Code: 0xB ID-Code1: 0xF ID-Code2: 0xE Inputs: Status Data bits Contact 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Outputs: A0 Indicator lamp (optional) A1 … A3 not used Parameter bits: P0 … P3 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Enabling status: LED yellow Mechanical life: > 1 million operations Maximum cable length: 50 m Features: wire pull and breakage detection EMC rating: conforming to EMC Directive Ambient temperature: – 25 °C … + 60 ºC Storage and transport – 25 °C … + 85 ºC temperature: Note A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare A wide range of accessories is available. For selection, see Main catalogue „Safety technology“. C OR AS-Interface Safety at Work R S OR System components System components System components IDC connector M Passive connection module Terminal mounting + + Aux - 50 - Aux M5 21 9 AS-i Ø 30 AS-i C 5 free 2 Aux - 4 Aux + 3 AS-i 1 - AS-i + 34 50 64 Rundsteckverbinder M12 IDC connector K Passive connection module Terminal mounting Ordering details Ordering details Ordering details IDC connector M Connection from the AS-i flat cable (yellow) to M12 connector Passive connection module 0911 ANC 101 Passive connection module (IDC) for the yellow and black flat cable to a M12 connector plug Terminal mounting H 30 Mounting brackets for all AS-i Tube modules with M30 housing IDC connector K Connection from the AS-i flat cable (yellow) to a circular cable 29 AS-Interface Safety at Work R S ASF 2 CC Technical data Standards: Enclosure: AS-Interface connection type: 31 80 51 102 • Input module • 2 safe inputs for mechanical contacts • Cross-wire monitoring • Cage clamp terminals for safety device connection • LED function display • IDC technology for AS-Interface flat cable • Protection class IP 67 OR Wiring diagram EN 50295, EN 954-1 black IDC to the flat cable AS-Interface Cage clamp terminals: max. 2,5 mm2 (incl. conductor ferrules) AS-Interface operating voltage: 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof Protection class: IP 67 AS-Interface operating current: < 70 mA Inputs: 2 safe inputs for mechanical contacts, monitored for cross-wired circuit, cable length < 30 m Input signal: „S+1, S+2“: le < 10 mA, pulsed AS-Interface specification: (V 2.1) Profile: S-0.B IO-Code: 0x0 ID-Code: 0xB 0xF ID-Code1: ID-Code2: 0xE Inputs: Contact Status Data bits 1 on D0/D1 = dynamic code transmission 1 off D0/D1 = static code “00” 2 on D2/D3 = dynamic code transmission 2 off D2/D3 = static code “00” Parameter bits: P0 … P1 not used Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green, communication LED red Switching condition: LED yellow EMC rating: conforming to EMC Directive – 25 °C … + 60 ºC Ambient temperature: Storage and transport – 25 °C … + 85 ºC temperature: S+1 RES S-1 S-2 RES S+2 FAULT POWER 45 66 C S Inputs 2 1 S+1 RES S-1 S-2 RES S+2 FAULT POWER Inputs 2 1 Approvals F C Ordering details ASF 2 CC The base module ASF KM1 is the electromechanical link between the AS-Interface flat cable and the user module (ASF 2CC). 30 Note Note The safe AS-Interface input module offers two universal safety relevant inputs for mechanical contacts. The safe switches are connected to cage-clamp terminals inside the module housing. The signal voltage is supplied by the module itself. The wiring diagram is shown with guard doors closed and in de-energised condition. The two safe input channels are cross-wire monitored. Monitoring a sliding guard door using two position switches with safety function. The NC contact must have positive break when the guard door is opened. Please note that for the correct use of the input module there must be two jumpers present (1+2 and 5+6, see electrical connection). AS-Interface Safety at Work R S ASF KM1 C OR Technical data Standards: Ue: 80 ¤ 9,6 26 18,5 45 18,5 36 36 EN 50295 26,5 … 31,6 V (according to AS-Interface specification) max. 2 A Ie: AS-Interface specification: EMS AS-Interface connection type: 2 flat cables AS-Interface (IDC) Protection class: IP 67 to EN60529 (only in combination with ASF 2 CC) Ambient temperature: – 25 °C … + 60 ºC Storage and transport temperature: – 25 °C … + 85 ºC Special features: 2 parallel cable channels for various T- and Cross-junctions Mounting: top hat section rail or screw mounting 26 ¤ 5,8 • Base module • Base module without address jack • AS-Interface interface for user module • Connection of AS-Interface flat cable • Top hat section rail or screw mounting Approvals Ordering details ASF KM 1 Note The base module is the electro-mechanical link between the AS-Interface flat cable and the user module (i.e. ASF 2CC). Note AS-i AS-i + + - +Contacts to module 31 AS-Interface Safety at Work R S ASF PM Technical data Interface: Operating device: Operating duration: Power supply: Display: Keyboard: ↑ ↓ Protection class: Ambient temperature: Storage and transport temperature: Dimensions: C OR Note AS-Interface, short-circuit- and overload-proof 230 VAC, plug-in charging unit, included in the delivery package 8 h or > 250 read/write cycles with fully charged batteries battery mode, charging time before use about 14 h LC-display 5 keys, membrane keys IP 20 0 °C … + 55 ºC – 20 °C … + 55 ºC 80 x 34 x 214 mm • Hand-held programming device • Addressing and Programming up to a maximum of 62 Slaves (A/B-Slaves) • Read/write operation of slave data • Displaying the IO-code • Read/write operation of parameter data • Displaying the address mode / ID-code • Displaying the peripheral fault flags • Determining the slave address • Re-addressing with checking • Slave connection is short-circuit and overload proof • Mech. connection with the help of the universal adapter • Battery charger included with delivery The LCD displays the address, the operating mode or an error code. The AS-Interface hand held programming device will be switched on by pressing the button “ADR”. It shuts down independently after about one minute when not in use. • Pressing the “ADR” button causes the current slave address to be displayed • The two keys “ ↑ “ and “ ↓ “ can be used to select the programmable address from the address ring (i.e. 0 ...31, 0 ...31A, 0 ...31B) • A short key stroke causes the page to turn stepwise, whereas holding down the key causes the pages to scroll continuously (0.5s per address) • Pressing the “PRG”-key causes the new address to be loaded into the slave • The correct programmed address is automatically displayed after about 0.5s • Holding down “ADR” and “PRG” simultaneously will automatically set back the slave address to zero • Other key combinations do not trigger any further action Approvals C Ordering details ASF PM Note The LCD displays the address, the operating mode or an error code. „ ↑ “ button = increments slave address „MODE“ button = changes the working mode = decrements „ ↓ “ button slave address „PRG“ button = programming of the new slave address „ADR“ button = reading a slave address / switches on the device Error messages F1: AS-Interface overload F2: Slave not found F3: Programming error F4: Destination address busy F5: Zero address already occupied F6: Standard slave found instead of an extended slave F7: Extended slave found instead of a standard slave F8: Reception error LOBAT = Recharge batteries ! After the first indication approx. 30 read/write operation are still possible. Load the accumulator only with the charger included within this delivery. AS-Interface Safety at Work R S TG...-A C OR Technical data Standards: EN 50295 EN 60947-5-1 EN 954-1 PA + POM Enclosure: AS-Interface connection type: Protection class: AS-Interface operating voltage: connector M12 x 1 IP 65 26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proof AS-Interface operating current: 50 mA AS-Interface specification : Profile S-B.A IO-Code 0xB ID-Code 0xA ID-Code2 0xE Outputs: Data bits Function D0 LED 1 (G) D1 LED 2 (R) Inputs: Data bits Function D2 NO contact 1 D3 NO contact 2 (optional) Input module address: default on address 0, programmable via the AS-Interface Master or Hand-held programming device Indications: AS-Interface: voltage LED green communication LED red EMC rating: conforming to EMC Directive Ambient temperature: – 20 °C … + 60 ºC Storage and transport temperature: – 25 °C … + 85 ºC ≤ 10 M12 x 1 60 80 4 8,5 200 • Door handle switch • Integrated AS-Interface • AS-Interface LED status display • AS-Interface M12 connector • Enabling button • Coloured signal LEDs (optional) • Protection class IP 65 48 30 150 Approvals C Ordering details TG-S GR xx-A Further devices on request. Note A separate address jack is not available as an option. The addressing must take place via the cable end or the M12 connector. 1 2 4 3 1: AS-i + 2: spare 3: AS-i – 4: spare 33 German agencies International agencies 01 02 03 04 19 12 05 16 09 08 Argentina - Argentinien Condelectric S. A. Hipólito Yrigoyen 2591 1640 Martinez Pcia. de Buenos Aires Telefon: +54 (11) 47 97 58 87 Telefax: +54 (11) 47 97 58 87 E-Mail: info@condelectric.com.ar Internet: www.condelectric.com.ar 11 10/15 Stammhaus K.A. Schmersal GmbH Industrielle Sicherheitsschaltsysteme Postfach 24 02 63, 42232 Wuppertal Möddinghofe 30 42279 Wuppertal Telefon: +49-(0) 2 02-64 74-0 Telefax: +49-(0) 2 02-64 74-1 00 E-Mail: info@schmersal.de Internet: www.schmersal.com 01 02 03 04 05 14 Hamburg K.A. Schmersal GmbH Geschäftsstelle Hamburg Zunftstraße 8 21244 Buchholz i.d.N. Telefon: +49-(0) 41 81-9 22 0-0 Telefax: +49-(0) 41 81-9 22 0-20 E-Mail: gshamburg@schmersal.de Berlin KSA Komponenten der Steuerungsund Automatisierungstechnik GmbH Buchholzer Str. 62-65 13156 Berlin Telefon: +49-(0) 30-47 48 24 00 Telefax: +49-(0) 30-47 48 24 05 E-Mail: info@ksa-gmbh.de Internet: www.ksa-gmbh.de Hannover ELTOP GmbH Robert-Bosch-Str. 8 30989 Gehrden Telefon: +49-(0) 51 08-92 73 20 Telefax: +49-(0) 51 08-92 73 21 E-Mail: eltop@eltop.de Internet: www.eltop.de Münster K.A. Schmersal GmbH Geschäftsstelle Münster Am Vechte Ufer 22 48629 Metelen Telefon: +49-(0) 25 56-9 38 30 Telefax: +49-(0) 25 56-93 83 73 E-Mail: gsmuenster@schmersal.de Köln Stollenwerk Technisches Büro GmbH Scheuermühlenstr. 40 51147 Köln Telefon: +49-(0) 22 03-9 66 20-0 Telefax: +49-(0) 22 03-9 66 20-30 E-Mail: info@stollenwerk.de Ruhrgebiet K W S Elektronik Schumacher Saarstr. 19a 53919 Weilerswist Telefon: +49-(0) 22 54-33 80 Telefax: +49-(0) 22 54-18 58 E-Mail: k-w-s-@t-online.de 34 12 16 08 19 Siegen Siegfried Klein Elektro-Industrie-Vertretungen Schloßblick 38 57074 Siegen Telefon: +49-(0) 2 71-67 78 Telefax: +49-(0) 2 71-67 70 E-Mail: info@sk-elektrotechnik.de Frankfurt K.A. Schmersal GmbH Geschäftsstelle Frankfurt Kilianstädter Straße 38 61137 Schöneck Telefon: +49-(0) 61 87-9 09 56-0 Telefax: +49-(0) 61 87-9 09 56-6 E-Mail: gsfrankfurt@schmersal.de Saarland Herbert Neundörfer Werksvertretungen Saargemünder Str. 68a 66130 Güdingen Telefon: +49-(0) 6 81-87 54 54 Telefax: +49-(0) 6 81-87 54 53 E-Mail: info@herbert-neundoerfer.de Internet: www.herbert-neundoerfer.de Leipzig K.A. Schmersal GmbH Geschäftsstelle Leipzig Nonnenstraße 11c 04229 Leipzig Telefon: +49-(0) 3 41-4 87 34 50 Telefax: +49-(0) 3 41-4 87 34 51 E-Mail: gsleipzig@schmersal.de Australia - Australien NHP Electrical Engineering Products Pty. Ltd. 43 - 67 River Street, PO Box 199 Richmond 3121 Melbourne, Victoria Telefon: +61-(0) 3-94 29 29 99 Telefax: +61-(0) 3-94 29 10 75 E-Mail: products@nhp.com.au Internet: www.nhp.com.au Austria - Österreich AVS-Schmersal Vertriebs Ges. m.b.H. Biróstraße 17 1232 Wien Telefon: +43-(0) 1-6 10 28 Telefax: +43-(0) 1-6 10 28-1 30 infoservice@avs-schmersal.co.at Internet: www.avs-schmersal.co.at Belgium - Belgien Schmersal Belgium NV/SA Nieuwlandlaan 16B Industriezone B413 3200 Aarschot Telefon: +32-(0) 16-57 16 18 Telefax: +32-(0) 16-57 16 20 E-Mail: info@schmersal.be Internet: www.schmersal.be Brazil - Brasilien ACE Schmersal Eletroeletrônica Industrial Ltda. Rodovia Boituva-Porto Feliz, Km 12 Vila Esplanada – CEP: 18550-000 Boituva – SP Telefon: +55-(0) 15-32 63-98 66 Telefax: +55-(0) 15-32 63-98 90 E-Mail: export@aceschmersal.com.br Internet: www.aceschmersal.com.br 09 Bayern Nord K.A. Schmersal GmbH Geschäftsstelle Nürnberg Beethovenstr. 14 91074 Herzogenaurach Telefon: +49-(0) 91 32-73 70 00 Telefax: +49-(0) 91 32-73 48 44 E-Mail: gsnuernberg@schmersal.de Bolivia - Bolivien International Fil-Parts Import/Export S.R.L 3er. Anillo, 1040, Frente al Zoo Santa Cruz de la Sierra Telefon: +591 (3) 3 42 99 00 Telefax: +591 (3) 3 42 36 37 E-Mail: presidente@filparts.com.bo Internet: www.filparts.com.bo 10/ 15 Bayern Süd Ing. Adolf Müller GmbH Industrievertretungen Elly-Staegmeyr-Str. 15 80999 München Telefon: +49-(0) 89-8 12 60 44 Telefax: +49-(0) 89-8 12 69 25 E-Mail: info@ingam.de Canada - Kanada Schmersal Canada LTD. 10 Riverside Drive Orangeville / Ontario L9V1A5 Telefon: (905) 495-7540 Telefax: (905) 495-7543 E-Mail: info@schmersalusa.com Internet: www.schmersalusa.com 11 Stuttgart Labor-Schütz GmbH Industrievertretungen Eichwiesenring 6 70567 Stuttgart Telefon: +49-(0) 7 11-7 15 46-0 Telefax: +49-(0) 7 11-7 15 46-18 E-Mail: hv@schuetzinger.de Internet: www.schuetzinger.de Chile - Chile Vitel S.A. Chiloé 1189 Casilla 440-3 Santiago Telefon: +56 (2) 5 56 26 46 Telefax: +56 (2) 5 55 57 90 E-Mail: francisco@vitel.cl Internet: www.vitel.cl Colombia - Kolumbien Cimpex Ltda. Calle 53 No. 45-112 - Of. 1401 Apartado Aereo 2429 Medellin Telefon: +57-4-2 51-59 72 Telefon: +57-4-2 51-59 87 Telefax: +57-4-2 51-46 08 E-Mail: cimpex@epm.net.co Costa Rica - Costa Rica Euro-Tec, S.A. Apartado Postal 477 1250 Escazú San José Telefon: +5 06-2 84 78 69 Telefax: +5 06-2 96 15 42 E-Mail: eurotec@amnet.co.cr PR China - VR China Schmersal Industrial Switchgear Co. Ltd. Central Plaza 1001 Huang Pi Bei Road 227 200003 Shanghai Telefon: +86-21-63 75 82 87 Telefax: +86-21-63 75 82 97 E-Mail: sales@schmersal.com.cn Internet: www.schmersal.com.cn Czech Republic Tschechische Republik Mercom Componenta spol. s.r.o. Ruská 67 100 00 Praha 10 Telefon: +4 20-(0) 2-67 31 46 40 Telefax: +4 20-(0) 2-71 73 32 11 E-Mail: mercom@mercom.cz Denmark - Dänemark Schmersal Danmark A/S Lindegårdsvej 17A 2920 Charlottenlund Telefon: +45-70 20 90 27 Telefax: +45-70 20 90 37 E-Mail: info@schmersal.dk Internet: www.schmersal.dk Finland - Finnland Advancetec Oy Malminkaari 10B PO Box 149 00701 Helsinki Telefon: +3 58-(0) 9-3 50 52 60 Telefax: +3 58-(0) 9-35 05 26 60 E-Mail: advancetec@advancetec.fi Internet: www.advancetec.fi France - Frankreich Schmersal France SAS 8, rue Raoul Follereau BP 18 38180 Seyssins Telefon: +33-4 76 84 23 20 Telefax: +33-4 76 48 34 22 E-Mail: info@automatisme-etcontrole.fr Internet: www.automatisme-et-controle.fr Greece - Griechenland Kalamarakis Sapounas S.A. Ionias & Neromilou PO Box 46566 13671 Chamomilos Acharnes Athens Telefon: +30-(0) 210-2 40 60 00-6 Telefax: +30-(0) 210-2 40 60 07 E-Mail: ksa@ksa.gr Honduras - Honduras Lusitana International Apdo. Postal #783 21105 San Pedro Sula Tegucigalpa Telefon: +5 (04) 3 93-16 40 Telefax: +5 (04) 5 50-22 52 E-Mail: jaimefernandes2002@yahoo.com Hungary - Ungarn NTK Ipari-Elektronikai és Kereskedelmi Kft Mészáros L. u. 5. 9023 Györ Telefon: +36-(0) 96-52 32 68 Telefax: +36-(0) 96-43 00 11 E-Mail: info@ntk-kft.hu Internet: www.ntk-kft.hu India - Indien Arihant Electricals 24/4866, Ansari Road Darya Ganj, Sheel Tara House 102222 New Delhi Telefon: +91-11-23 26 21 76 Telefax: +91-11-23 27 35 54 E-Mail: info@arihantelectricals.com Indonesia - Indonesien P.T. Wiguna Sumber Sejahtera JI. Kesehatan Raya No. 36 Jakarta 10160 Telefon: +62-(0) 21-34 83 42 30 Telefax: +62-(0) 21-34 83 42 31 E-Mail: email@ptwiguna.com Internet: www.ptwiguna.com Israel - Israel A.U. Shay Ltd. 23 Imber St. Kiriat. Arieh. P.O. Box 10049 Petach Tikva Telefon: +9 72-3-9 23 36 01 Telefax: +9 72-3-9 23 46 01 E-Mail: shay@uriel-shay.com Italy - Italien Schmersal Italia s.r.l. Via Molino Vecchio, 206 25010 Borgosatollo, Brescia Telefon: +39-0 30-2 50 74 11 Telefax: +39-0 30-2 50 74 31 E-Mail: info@schmersal.it Internet: www.schmersal.it Japan - Japan Elan-Schmersal Japan Branch Office 3-39-8 Shoan, Suginami-ku, Tokyo 167-0054 Telefon: +81-(03)-3247-0519 Telefax: +81-(03)-3247-0537 E-Mail: safety@elanjp.com Korea - Korea MEC Manhani Electric Co. Ltd. 576-8, Bisan-2dong Dongan-Ku Anyang-City Kyungi-Do 431-821 Telefon: +82-(0) 31-4 63-33 00 Telefax: +82-(0) 31-4 63-33 98 Telefax: +82-(0) 31-4 63-33 99 E-Mail: andy@hanmec.co.kr Malaysia - Malaysien Ingermark (M) SDN.BHD No. 29, Jalan KPK 1/8 Kawasan Perindustrian Kundang 48020 Rawang, Selangor Darul Ehsan Telefon: +6 03-60-34 27 88 Telefax: +6 03-60-34 21 88 E-Mail: ingmal@tm.net.my Mexico - Mexiko ISEL SA de CV Via Lopes Mateos 128. Col Jacarandas 54050 Tlalnepantla Edo. de Mexico Telefon: +52 (55) 53 98 80 88 Telefax: +52 (55) 53 79 39 85 E-Mail: isel@prodigy.net.mx Internet: www.isel.com.mx Hatenboer Elektro BV Postbus 200 2170 AE Sassenheim Telefon: +31-(0) 2 52-21 90 12 Telefax: +31-(0) 2 52-23 29 38 E-Mail: info@hatenboer.com Internet: www.hatenboer.com Mercom Componenta spol. s.r.o. Ruská 67 100 00 Praha 10 Czech Republic Telefon: +4 20-(0) 2-67 31 46 40 Telefax: +4 20-(0) 2-71 73 32 11 E-Mail: mercom@bohem-net.cz Norway - Norwegen Schmersal Nordiske Hoffsveien 92 0377 Oslo Telefon: +47-22 06 00 70 Telefax: +47-22 06 00 80 E-Mail: info@schmersal.no Internet: www.schmersal.se Slovenia - Slowenien Tipteh d.o.o. Ulica Ivana Roba 21 1000 Ljubljana Telefon: +386-1-2 00 51 50 Telefax: +386-1-2 00 51 51 E-Mail: info@tipteh.si Paraguay - Paraguay All-Med Importación - Exportación Representaciones Tacuary No. 1318e / 1 ra. Y 2da. Asunción Telefon: +595 (21) 37 04 40 Telefax: +595 (21) 37 16 87 E-Mail: allmed@telesurf.com.py Spain - Spanien Schmersal Ibérica, S.L. Pol. Ind. La Masia Camí de les Cabòries, Nave 4 08798 Sant Cugat Sesgarrigues Telefon: +34 - 93 897 09 06 Telefax: +34 - 93 396 97 50 E-Mail: info@schmersal.es Internet: www.schmersal.es Poland - Polen Schmersal - Polska Sp.j. ul. Kremowa 65A 02-969 Warszawa Telefon: +48-(0) 22-8 16 85 78 Telefon: +48-(0) 22-8 16 85 79 Telefax: +48-(0) 22-8 16 85 34 E-Mail: office@schmersal.pl South Africa - Südafrika A+A Dynamic Distributors (Pty) Ltd. 3 Ruarch Street Park Central Johannesburg PO Box 38247 2016 Booysens Telefon: +27-11-4 93 50 22 Telefax: +27-11-4 93 07 60 E-Mail: awkayser@iafrica.com Portugal - Portugal Schmersal Ibérica, S.L. Apartado 30 2626-909 Póvoa de Sta. Iria Telefon: +351 - 21 959 38 35 Telefax: +351 - 21 959 42 83 E-Mail: info@schmersal.pt Internet: www.schmersal.pt Sweden - Schweden Schmersal Nordiska AB Klockarns Väg 1 43533 Mölnlycke Telefon: +46-(0) 31-3 38 35 00 Telefax: +46-(0) 31-3 38 35 35 E-Mail: info@schmersal.se Internet: www.schmersal.se Russia - Russland AT electronics Moskau ul. Avtosavodskaya 16-2 109280 Moskau Telefon: +7- (0) 95 -1 01 44 25 Telefax: +7- (0) 95-2 34 44 89 E-Mail: info@at-e.ru Internet: www.at-e-ru Switzerland - Schweiz Schmersal Schweiz AG Freilagerstr. 25 8047 Zürich Telefon: +41-(0) 43-3 11 22 33 Telefax: +41-(0) 43-3 11 22 44 E-Mail: info@schmersal.ch AT Petersburg Polytechnicheskaya str, d.9,B 194021 St. Petersburg Telefon: +7-(0) 81 27 03-08-17 Telefax: +7-(0) 81 27 03-08-34 E-Mail: spb@at-e.ru Serbia/Montenegro - Serbien Tipteh d.o.o. Beograd Bulevar AVNOJ-a45D, lokal 18 11070 Novi Beograd Telefon: +3 81-11-3 13 10 57 Telefax: +3 81-11-3 01 83 26 E-mail: vecerka@ptt.yu Internet: www.tipteh.co.yu Singapore - Singapur Tong Sim Marine & Electric Co. 46 Kaki Bukit Crescent Kaki Bukit Techpark 1 Singapore 416269 Telefon: +65-67 43 31 77 Telefax: +65-67 45 37 00 E-Mail: tongsim@singnet.com.sg Internet: www.tongsim.com Slovakia - Slowakei Schmersal Ltd. Sparrowhawk Close Unit 1, Beauchamp Business Centre Enigma Park Worcs WR14 1GL, Malvern Telefon: +44-(0) 16 84-57 19 80 Telefax: +44-(0) 16 84-56 02 73 E-Mail: support@schmersal.co.uk Internet: www.schmersal.co.uk Ukraine - Ukraine AT Electronics Kiev Zlatoustovskaya str. 32 01135 Kiev Telefon: +38- (0) 44-4 82 22 19 +38- (0) 44-4 86 91 25 Telefax: +38- (0) 44-2 19 22 19 E-Mail: info@at-e.com.ua Internet: www.at-e.com.ua Uruguay - Uruguay Gliston S.A. Pedernal 1896 – Of. 203 CP 11800 Montevideo Telefon: +598 (2) 2 00 07 91 Telefax: +598 (2) 2 00 07 91 E-Mail: colmedo@gliston.com.uy Internet: www.gliston.com.uy USA - USA Schmersal Inc. 660 White Plains Road Suite 160 Tarrytown, NY 10591 Telefon: +1-(0) 9 14-3 47-47 75 Telefax: +1-(0) 9 14-3 47-15 67 E-Mail: info@schmersalusa.com Internet: www.schmersalusa.com Venezuela - Venezuela EMI Equipos y Sistemas C.A. Calle 10, Edf. Centro Industrial Martinisi, Piso 3, La Urbina Caracas Telefon: +58 (212) 2 43 50 72 Telefax: +58 (212) 2 43 50 72 E-Mail: jpereira@emi-ve.com Taiwan - Taiwan Leader Camel Enterprise Co., Ltd. No. 453-7, Pei Tun Rd. Taichung, Taiwan Telefon: +886-4-22 41 32 92 Telefax: +886-4-22 41 29 23 E-Mail: camel88@ms46.hinet.net Internet: www.leadercamel.com.tw Thailand - Thailand M. F. P. Engineering Co. Ltd. 64-66 Buranasart Road Sanchaoporsva Bangkok 10200 Telefon: +66-2-2 26 44 00 Telefax: +66-2-2 25 67 68 E-Mail: raty@ksc.th.com Turkey - Türkei BETA Elektrik Sanayi Ve Ticaret Dogan Bektas Okçumusa Caddesi Anthem Han No. 44 34420 Karaköy / Istanbul Telefon: +90-212-235 99 14 Telefax: +90-212-253 54 56 E-Mail: info@betaelektrik.com Internet: www.betaelektrik.com UK - Großbritannien Netherlands - Niederlande 35 Möddinghofe 30 D-42279 Wuppertal Postfach 24 02 63 D-42232 Wuppertal Telefon +49 - (0)2 02 - 64 74 - 0 Telefax +49 - (0)2 02 - 64 74 - 1 00 E-Mail info@schmersal.de Internet http://www.schmersal.com 3.000 / L.D. / 04.2006 / Teile-Nr. 1171696 / Ausgabe 03 K.A. Schmersal GmbH Industrielle Sicherheitsschaltsysteme