 Suntrio Plus Series
User Manual
SAJ Solar Inverter
Suntrio Plus Series
www.saj-electric.com
- 0 -
Suntrio Plus Series
Preface
Thank you for choosing an SAJ solar inverter. We are pleased to provide
you with first-class products and exceptional service.
This manual includes information for installation, operation, maintenance,
trouble shooting and safety. Please follow the instructions of this manual
so that we can ensure delivery of our professional guidance and
wholehearted service.
Customer-orientation is forever our commitment. We hope this document
proves to be of great assistance in your journey for a cleaner, greener
world.
Please check for the latest version at www.saj-electric.com
Guangzhou Sanjing Electric Co., Ltd.
Zero-Carbon Innovator
- 1 -
Suntrio Plus Series
Content
Preface .................................................................................................... - 1 - Chapter 1 Safety Precautions .............................................................. - 4 - 1.1 Scope of Application ............................................................................... - 4 - 1.2 Safety Instructions ................................................................................... - 4 - 1.3 Target Group............................................................................................ - 5 - Chapter 2 Preparation .......................................................................... - 6 - 2.1 Safety Instructions ................................................................................... - 6 - 2.2 Explanations of Symbols......................................................................... - 8 - Chapter 3 Product Information .......................................................... - 10 - 3.1 Application Scope of Products .............................................................. - 10 - 3.2 Specification for Product Model ........................................................... - 11 - 3.3 Overview and Dimensions of products ................................................. - 11 - 3.4 Datasheet ............................................................................................... - 12 - Chapter 4 Instructions for installation ............................................... - 14 - 4.1 Safety Instructions ................................................................................. - 14 - 4.2 Pre-installation Check ........................................................................... - 14 - 4.3 The Determination of the Installation Method and Position ................. - 16 - 4.4 Mounting Procedure .............................................................................. - 18 - Chapter 5 Electrical Connection........................................................ - 20 - 5.1 Safety Instruction for Hot-line Job ........................................................ - 20 - 5.2 Specifications for Electrical Interface ................................................... - 21 - 5.3 AC Side Connection .............................................................................. - 21 - 5.4 DC Side Connection .............................................................................. - 23 - 5.5 Communication Connection.................................................................. - 26 - Chapter 6 Debugging Instructions ..................................................... - 27 - - 2 -
Suntrio Plus Series
6.1 Introduction of Human-computer Interface .......................................... - 27 - 6.2 First Run Setup ...................................................................................... - 28 - 6.3 Monitoring Operation............................................................................ - 36 - Chapter 7 Fault Code and Troubleshooting ....................................... - 37 - Chapter 8 Recycling and Disposal .................................................... - 40 - Chapter 9 Guarantee Service ............................................................. - 41 - Chapter 10 Contact SAJ .................................................................... - 42 - - 3 -
Suntrio Plus Series
Chapter 1
Safety Precautions
1.1 Scope of Application
This User Manual describes instructions and detailed procedures for installing,
operating, maintaining, and troubleshooting of the following SAJ grid-tie inverters:
Suntrio Plus 4K;
Suntrio Plus 5K;
Suntrio Plus 6K;
Suntrio Plus 8K;
Suntrio Plus 10K
Please keep this manual all time available in case of emergency.
1.2 Safety Instructions
DANGER
· DANGER indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
· WARNING indicates a hazardous situation which, if not avoided, can result in death or
serious injury or moderate injury.
CAUTION
· CAUTION indicates a hazardous condition which, if not avoided, can result in minor or
moderate injury.
NOTICE
· NOTICE indicates a situation that can result in potential damage, if not avoided.
- 4 -
Suntrio Plus Series
1.3 Target Group
Only qualified electricians who have read and fully understood all safety
regulations contained in this manual can install, maintain and repair the inverter.
Operators must be aware of the high-voltage device.
- 5 -
Suntrio Plus Series
Chapter 2 Preparation
2.1 Safety Instructions
DANGER
· Dangerous due to electrical shock and high voltage.
· Do not touch the operating component of the inverter, it might result in burning or death.
· To prevent risk of electric shock during installation and maintenance, please make sure that
all AC and DC terminals are plugged out.
· Do not touch the surface of the inverter while the housing is wet, it might lead to electrical
shock.
· Do not stay close to the inverter while there are severe weather conditions including storm,
lighting, etc.
· Before opening the housing, the SAJ inverter must be disconnected from the grid and PV
generator; you must wait at least five minutes to let the energy storage capacitors fully
discharged after disconnecting from power source.
WARNING
·The installation,service, recycling and disposal of the inverters must be performed by
qualified personnel only in compliance with national and local standards and regulations.
·Any unauthorized actions including modification of product functionality of any form may
cause lethal hazard to the operator, third parties, the units or their property. SAJ is not
responsible for the loss and these warranty claims.
·The SAJ inverter must only be operated with PV generator. Do not connect any other source
of energy to the SAJ inverter.
·Be sure that the PV generator and inverter are well grounded in order to protect properties
and persons.
CAUTION
·The PV inverter will become hot during operation. Please do not touch the heat sink or
peripheral surface during or shortly after operation.
·Risk of damage due to improper modifications.
·Risk of damage due to improper modifications.
- 6 -
Suntrio Plus Series
NOTICE
·Public utility only
·The PV inverter is designed to feed AC power directly to the public utility power grid; do
not connect AC output of the inverter to any private AC equipment.
- 7 -
Suntrio Plus Series
2.2 Explanations of Symbols
Symbol
Description
Dangerous electrical voltage
This device is directly connected to public grid, thus all work to the inverter shall
only be carried out by qualified personnel.
DANGER to life due to high electrical voltage!
There might be residual currents in inverter because of large capacitors. Wait 5
MINUTES before you remove the front lid.
NOTICE, danger!
This is directly connected with electricity generators and public grid.
Danger of hot surface
The components inside the inverter will release a lot of heat during operation. Do
not touch metal plate housing during operating.
An error has occurred
Please go to Chapter 9 “Troubleshooting” to remedy the error.
This device SHALL NOT be disposed of in residential waste
Please go to Chapter 8 “Recycling and Disposal” for proper treatments.
Without Transformer
This inverter does not use transformer for the isolation function.
Security Certificate
The inverter complies with European product safety instructions.
CE Mark
Equipment with the CE mark fulfills the basic requirements of the Guideline
Governing Low-Voltage and Electro-magnetic Compatibility.
SAA Mark
The inverter complies with the requirement of Equipment and Product Safety Act in
Australia.
- 8 -
Suntrio Plus Series
CQC Mark
The inverter complies with the safety instructions from China's Quality Center.
No unauthorized perforations or modifications
Any unauthorized perforations or modifications are strictly forbidden, if any
defect or damage (device/person) is occurred, SAJ shall not take any
responsibility for it.
- 9 -
Suntrio Plus Series
Chapter 3
Product Information
3.1 Application Scope of Products
Suntrio Plus series products are grid-tie single phase inverters without transformers,
and the inverters are important components of grid-tie solar power systems.
The Suntrio Plus inverters change the DC generated by solar panels into AC which
is in accordance with the requirements of public grid, and send the AC into the grid,
Table 3.1 shows the structural diagram of the typical application system of Suntrio
Plus inverters.
Name
Description
Remarks
A
Solar panels
Monocrystalline or polycrystalline silicon, and thin-film PV
modules with II protection and need no ground connection
B
Inverters
C
Metering
equipment
Standard metering tool for measuring the output electric power
of inverters
D
Power grid
TT,TN-C,TN-S,TN-C-S
Suntrio Plus 4K/5K/6K/8K/10K
Table 3.1 Systematic Configuration Diagram
- 10 -
Suntrio Plus Series
3.2 Specification for Product Model
Suntrio Plus XK
①
②
① Suntrio Plus represents for product name.
② XK represents rated power XkW of inverter, for example 5K means 5kW.
3.3 Overview and Dimensions of products
The dimensions of Sununo Plus series products is shown in Figure 3.2.
Figure 3.2 Dimensions of Sunttrio Plus 4K/5K/6K/8K/10K
- 11 -
Suntrio Plus Series
3.4 Datasheet
Sunttrio Plus 4K/5K/6K/8K/10K
Type
Input (DC)
Max. DC Power [W]
Max. DC Voltage [V]
MPPT Voltage Range [V]
Nominal DC Voltage [V]
Start Voltage[V]
Min. DC Voltage[V]
Max. DC Input Current PV1 /
PV2 [A]
Number of MPPT
Number of DC Connection Sets
per MPPT
DC Switch
Output (AC)
Rated AC Power [VA]
(@230V,50Hz)
Max. AC Apparent Power [VA]
Rated AC Current[A]
Max. AC Current [A]
Nominal AC voltage/ range
Grid frequency/ range
Power factor,adjustable
Total Harmonic Distortion
(THDi)
Feed-in Phase / Connection
Phase
Efficiency
Max. Efficiency
Euro Efficiency (at 600Vdc)
MPPT Accuracy
Protection
Internal Over-voltage
Protection
DC Insulation Monitoring
DCI Monitoring
GFCI Monitoring
Suntrio
Plus 4K
Suntrio
Plus 5K
Suntrio
Plus 6K
Suntrio
Plus 8K
Suntrio
Plus 10K
4200
5300
6300
1000
160-900
600
180
150
8400
10500
11/11
22/11
2
1/1
2/1
Integrated
4000
5000
6000
8000
10000
4000
5000
6000
8000
10000
5.8
7.2
8.7
11.6
14.5
6.4
8.1
9.7
12.9
15.9
3/N/PE, 220/380V,230/400V,240/415V;180V-280V/312V-485V
50Hz,60Hz /44Hz-55Hz,54-65Hz
0.9 leading~0.9 lagging
< 3% (at nominal power)
3 /3
97.8%
97.0%
97.8%
97.2%
97.8%
97.4%
>99.5%
Integrated
Integrated
Integrated
Integrated
- 12 -
98.0
97.5
98.0
97.6
Suntrio Plus Series
Grid Monitoring
AC Short Circuit Current
Protection
Thermal Protection
Anti-island protection
monitoring
Interface
DC Connection
AC Connection
LCD Display
Display Language
Datalogger & Communication
General Data
Topology
Consumption at Night [W]
Consumption at Standby [W]
Operating Temperature Range
Cooling Method
Ambient Humidity
Altitude
Noise [dBA]
Ingress Protection
Mounting
Dimensions (H*W*D) [mm]
Net Weight [kg]
Standard Warranty [Year]
Certificates
Integrated
Integrated
Integrated
AFD
MC4/H4
Plug-in connector
3.5 inch Graphic LCD Display, Backlight, Inverter Parameter and
Data Display
Multi Language
1*RS485/1*RS232/WiFi(Optional)
Transformerless
<0.6
<10
-25°C to +60°C(45°C to 60°C with derating)
Natural Convection
0% to 100% Non-condensing
Up to 2000m (without power derating)
<29
IP65 (Indoor & Outdoor Installation)
Rear Panel
530*355*190
530*355*200
22
24.6
5 (standard)/10/15/20/25 (Optional)
IEC62109-1/2, IEC61000-6-2/3, IEC61683, IEC60068-2,
IEC62116, IEC61717, PEA/MEA, NRS 097-2-1, UTE-C-15-712-1,
VDE0126-1-1/A1, VDE-AR-N 4105, AS4777.2, AS4777.3,
C-TICK, CQC NB/T 32004, G83-2,NBR 16149, NBR 16150,
TF 3.2.1
- 13 -
Suntrio Plus Series
Chapter 4 Instructions for installation
4.1 Safety Instructions
DANGER
· Dangerous to life due to potential fire or electricity shock.
· Do not install the inverter near any inflammable or explosive items.
· This inverter will be directly connected with HIGH VOLTAGE power generation device;
the installation must be performed by qualified personnel only in compliance with national
and local standards and regulations.
NOTICE
· This equipment is suit for the pollution degree II.
· Inappropriate or the harmonized installation environment may jeopardize the life span of
the inverter.
· Installation directly exposed under intensive sunlight is not recommended.
· The installation site must have good ventilation condition.
4.2 Pre-installation Check
4.2.1 Check the Package
Although SAJ’s inverters have surpassed stringent testing and are checked before
they leave the factory, it is possible that the inverters may suffer damages during
transportation. Please check the package for any obvious signs of damage and if
such evidence is present, do not open the package and contact your dealer as soon as
possible.
- 14 -
Suntrio Plus Series
4.2.2 Check the Assembly Parts
After opening the package, please refer to Table 4.1 and 4.2 to check the
completeness of the assembly parts. Please contact your dealer if anything is
damaged or missing.
A
B
C
E
D
F
G
H
I
J
Table 4.1 Assembly Parts List
Sequence Number
Name
Quantity
Unit
A
Inverter
1
Set
B
Rear Panel
1
piece
C
DC connector
2
3
Pair
D
RS485 Connector
1
piece
E
M6×50 hex head screw
3
piece
F
Expansion tube
3
piece
G
M5×12 hex head screw and
gasket
2
piece
H
AC connector
1
piece
I
User Manual
1
Copy
J
Warranty card
1
Copy
Remarks
Suntrio Plus 4K/5K/6K
Suntrio Plus 8K/10K
Table 4.2 Quantity of Assembly Parts and Instructions
- 15 -
Suntrio Plus Series
4.3 The Determination of the Installation Method and Position
4.3.1 Mounting Method
Please mount the inverter rightly as shown in Figure4.1 below.
Figure 4.1 Mounting Method
① The equipment employs natural convection cooling, and it can be installed
indoor or outdoor.
② Please install the equipment under the guidance of Figure4.1. Vertical
installation on floor level is recommended. Mount vertically or tilted backwards by
max. 15°. Never install the inverter tilted forward, sideways, horizontally or upside
down.
③ Install the inverter at eye level for convenience when checking the LCD display
and possible maintenance activities.
④ When mounting the inverter, please consider that disassembly for service work
may be required.
- 16 -
Suntrio Plus Series
4.3.2 Installation Position
Do not expose the inverter to direct solar irradiation as this could cause power derating due to
overheating.The ambient temperature should be between -25°C ~ +60°C (-13° F ~ 140° F)
to ensure optimum operation.Choose locations with sufficient air exchange. Ensure additional
ventilation,when necessary.
To make sure the installation spot is suitably ventilated, if multiple SAJ grid-tie solar inverters
are installed in the same area, the following safety clearance in Figure4.2 shall be followed for
30CM
appropriate ventilation conditions.
50CM
50CM
30CM
30CM
Figure 4.2 Minimum Clearance - 17 -
50cm
30cm
30cm
80cm
50cm
50cm
80cm
50cm
30cm
80cm
50cm
80cm
50cm
80cm
50cm
30cm
50cm
50cm
50cm
Suntrio Plus Series
4.4 Mounting Procedure
4.4.1 Mark the Positions of the Drill Holes of the Rear Panel
The position of the drill holes can be determined by using rear panel. See Figure 4.3
below:
Figure 4.3 Dimensions of Rear Panel
4.4.2 Drill Holes and Place the Expansion Tubes
According to the guides, drill 3 holes in the wall as shown in Figure 4.4 (in
conformity with position marked in the above mentioned figure), and then place
expansion tubes in the holes using a rubber mallet.
Figure 4.4 Drill Holes
- 18 -
Suntrio Plus Series
4.4.3 Mount the Screws and the Rear Panel
The panels should be mounted in the mounting position by screws as shown in
Figure 4.5.
Figure 4.5 Mount the Rear Panel
4.4.4 Mount the Inverter
Carefully mount the inverter to the rear panel. Make sure that the rear part of the
equipment is closely mounted to the rear panel.
Figure 4.6 Mount the Inverter
- 19 -
Suntrio Plus Series
Chapter 5
Electrical Connection
5.1 Safety Instruction for Hot-line Job
Electrical connections must only be operated on by professional technicians. Please
keep in mind that the inverter is a bi-power supply equipment. Before connection,
necessary protective equipment must be employed by technicians including
insulating gloves, insulating shoes and safety helmet.
DANGER
· Dangerous to life due to potential fire or electricity shock.
· When power-on, the equipment should in conformity with national rules and regulations.
· The direct connection between the converter and high voltage power systems must be
operated by qualified technicians in accordance with local and national power grid standards
and regulations.
WARNING
·When the photovoltaic array is exposed to light, it supplies a d.c voltage to the inverter.
NOTICE
·Electrical connection should in conformity with proper stipulations, such as stipulations for
cross-sectional area of conductors, fuse and ground protection.
·The overvoltage category on DC input port is II,on AC output port is III.
- 20 -
Suntrio Plus Series
5.2 Specifications for Electrical Interface
A
B CD E
Figure 5.1 Electrical Interface
Code
A
B
C
D
E
Name
DC Input
DC Switch
RS232/Wi-Fi Port
RS485 Port
AC Quick-connect Terminal
Table 5.1 Specifications for Interface
5.3 AC Side Connection
Cross-sectional Area of Cables(mm²)
Scope
4.0-6.0
Recommended Value
6.0
Outside Diameter of the
Cables(mm)
4.2~5.3
Table 5.2 Recommended Specifications of AC Cables
- 21 -
Suntrio Plus Series
5.3.1 Feed the AC Cable Through the AC Waterproof hole.
Figure 5.2 Feed the cables
5.3.2 Connect the cables according to connection marks of L1,L2,L3,N and PE.
Figure 5.3 Connect the Cables
5.3.3 Secure all Parts of the AC Connector Tightly.
Figure 5.4 Screw the Connector
- 22 -
Suntrio Plus Series
5.3.4 Plug in the AC connector to the equipment securely, ensuring the pins are
connected directly. Then the connection of AC cable is complete.
Figure 5.5 Connect the Inverter
5.4 DC Side Connection
Cross-sectional Area of Cables(mm²)
Scope
4.0-6.0
Recommended Value
4.0
Outside Diameter of the
Cables(mm)
4.2~5.3
Table5.3 Recommended Specifications of DC Cables
DC connector is made up of the positive connector and the cathode connector
1. Insulated Enclosure
2. Lock Screw
Figure 5.6 Positive Connector
- 23 -
3. Positive Connector
Suntrio Plus Series
1. Insulated Enclosure
2. Lock Screw
3. Cathode Connector
Figure 5.7 Cathode Connector
NOTICE
·Please place the connector separately after unpacking in order to avoid confusion for connection of
cables.
·Please connect the positive connector to the positive side of the solar panels, and connect the
cathode connector to the cathode side of the solar side. Be sure to connect them in right position.
Connecting Procedures:
(1)Tighten the lock screws on positive and cathode connector.
(2)Use specified strip tool to strip the insulated enclosure of the positive and
cathode cables to the appropriate length.
1.Positive Cable
2. Cathode Cable
Figure 5.8 Connecting Cables
- 24 -
Suntrio Plus Series
(3)Feed the positive and cathode cables into corresponding lock screws.
(4)Put the metal positive and cathode terminals into positive cable and cathode
cable whose insulated enclosure has been stripped, and crimp them tightly with a
wire crimper. Make sure that the withdrawal force of the pressed cable is bigger than
400N.
(5)Plug the pressed positive and cathode cables into relevant insulated enclosure, a “click”
should be heard or felt when the contact cable assembly is seated correctly.
(6)Fasten the lock screws on positive and negative connectors into respondent insulated
enclosure and make them tight.
(7) Connect the positive and cathode connectors into positive and negative DC input
terminals of the inverter, a “click” should be heard or felt when the contact cable assembly is
seated correctly.
1. Connection Port
Figure 5.9 Connect the Inverter
NOTICE
·Before insert the connector into DC input terminal of the inverter, please make sure that the
DC switch of the inverter is OFF.
- 25 -
Suntrio Plus Series
5.5 Communication Connection
Suntrio Plus 4K/5K/6K/8K/10K is equipped with an RS232 and an RS485 interface.
(1) Connect the Wi-Fi modules with the interfaces of RS232and tighten the
screws. Please refer toWi-Fi manual for detailed information.
(2)The USB interface for RS232 is displayed in the picture below. Connect the
inverter with computer and the information of the inverter can be monitored via your
internet browser.
Figure 5.10 Nine Serial Port Cable
When using RS485 for monitoring, multi-point monitoring can be achieved by
connecting the inverter with RS485 cables. Each connection port should be attached
to the connector as shown in Figure 5.11 and Table 5.4. Make sure the connection is
tight and secure.
Figure 5.11 Three Ports Connector
Number of Connector
Color of Cables
1
Blue and white
2
Blue
3
Metal-shielded wire
Table 5.3 Assembly Sequence of RS485
- 26 -
Suntrio Plus Series
Chapter 6
Debugging Instructions
6.1 Introduction of Human-computer Interface
Figure 6.1 Human-computer Interface
Object
A
B
C
D◀
E▶
F
Description
Power indicator light: yellow light: the power system of inverter is operating
normally
Status indicator lamp: Red LED light = Fault; Green LED light = operation; when
red and green light are all off, the inverter is in initializing state or countdown for
Communication light: blue light flashing = receiving data
yellow light flashes = sending data
Moves the cursor or the focus point to the left
Moves the cursor or the focus point to the right
Starts the menu / button to confirm selection
G▲
Moves the cursor up or increases the setting value
H▼
Moves the cursor down or reduces the setting value
The inverter provides five buttons for inquiry of operational information and
parameters, these five buttons can be used repeatedly.
- 27 -
Suntrio Plus Series
6.2 First Run Setup
6.2.1 Set The Country
When the solar inverter begins to run for the first time, please configure the time of
usage, and the inverter LCD will display as below:
Figure 6.2 Set the Time
Users can press Up, Down, Left, Right and ENT buttons to set local time and confirm
the selection.Then the inverter will display the interface for country selection as
shown in Figure 6.3:
Figure 6.3 Set The Country
Please press the "ENT" button, LCD will show the countries for option. Users can
press " " or" " to select the correct country and press "ENT" button to confirm the
selection.
Note: The configuration of the country of usage must be set before inverter starts to
run for its first time, otherwise the inverter will not on-gird.If users can not locate the
corresponding country, please abort the setting and contact the after sales for
confirmation.
- 28 -
Suntrio Plus Series
6.2.2 State
If the country has been set the LCD shows the machine type when the inverter is
started up, then it automatically displays the inverter operation status: Initialization,
Normal,Wait, Fault or Update.
Data name
Initialization
Normal
Wait
Fault
Update
Explanation
Initialization of the system
The inverter in normal (function) operation
The inverter in stand-by state
A fault occurs during operation
The state of updating firmware
Turn on the AC switch, the LCD begins to count backwards, after this, the inverter
initiates connection to the grid.
6.2.3 LCD Menu
Figure 6.4 LCD Menu - 29 -
Suntrio Plus Series
6.2.4 Settings of General Parameters of the Inverter
LCD Display
1. Settings of figures
Operation Steps
Graph Set
In the main LCD interface,
press “ENT” button to enter
into the selection of “Figure”,
press▼or ▲to select. The
LCD displays daily, monthly,
yearly and gross generating
capacity.
2. Settings of System Parameter
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
Communicate Set
2. Press ENT to enter into”
Communication Settings”.
Press ▼and▲to set the
communication address of
Wi-Fi and RS485. The Fault
address is 1.
- 30 -
Suntrio Plus Series
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
Language & Time
2. Press▼and then press ENT
to enter into “Language &
Time”. Press▲and ▼to set
the language, date and time.
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
Grid Compliance
2. Press▼and then press ENT
to enter password and enter
into country setting.
- 31 -
Suntrio Plus Series
3. Press▲and▼to select
country,
Then click OK to save the
changes.
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
Clear Errors
2. Press▼and then press ENT
to enter into “Clear Fault
Records”, click OK or return
back.
1. In the main LCD interface,
press “ENT” button, then
Clear Energy
press
▶
to enter into
“Setting”.
- 32 -
Suntrio Plus Series
2. Press▼and then press ENT
to enter into “Clear Energy”,
click OK or return back.
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
LCD Setting
2. Press▼and then press ENT
to enter into “Display
Settings”, and then press
▲and▼to change the sleep
time of LCD, click OK or
return back.
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
- 33 -
Suntrio Plus Series
2. Press▼and then press ENT
to enter password, and then
enter into Factory Settings.
Factory Reset
3. Click OK to save the
changes.
1. In the main LCD interface,
press “ENT” button, then
press
▶
to enter into
“Setting”.
Change Password
2. Press▼and then press ENT
to enter password, and then
enter into Reset Password.
- 34 -
Suntrio Plus Series
3. Enter the new password
and click OK to save the
change.
6.2.5 Inquiry of Parameters of Inverter
1. Inquiry of Operating Parameters
1. In the main LCD interface, press
“ENT” button, then press
▶
to
enter into “Parameters”.
2. Press ENT to enter into
“Run-Info”, then press ▼or▲to
select the needed parameters,press
ENT to enter and to check the
parameters.
2. Inquiry of the Information of Inverter
1. In the main LCD interface, press
“ENT” button, then press
▶
to
enter into “About”.
2. Press ENT to enter into “About”
to check the equipment type, series
number, machine code, software
version of display panel, mainframe
version of the control panel and the
settings of country.
- 35 -
Suntrio Plus Series
6.3 Monitoring Operation
The equipment is equipped with an RS232 and an RS485 interface, and the RS232
interface can be connected to Wi-Fi modules or USB interface which can be used in
the monitoring of the operation status.
① The equipment can be connected to local internet via a Wi-Fi module and the
SAJ web server which is embedded in the machine, following this, the operational
status of the inverter can be monitored.
② By connecting the internet through a Wi-Fi module and uploading the data of the
inverter to server, users can monitor the operational information of the inverter by
web version web portal or mobile APP (please download the mobile APP from
SAJ’s official website) remotely.
③ Connecting the inverter to computer by nine-serial port cable, the operational
information of the inverter can be read by the appropriate computer software.
④ Users can apply a Modbus protocol through RS485 together with an SAJ Logger
to monitor the data of the inverter. For detailed operation please refer to the SAJ
Logger User Manual.
- 36 -
Suntrio Plus Series
Chapter 7 Fault Code and Troubleshooting
LCD displays Fault codes as shown in the table below:
Error Code
Explanation
01
Relay Error Master
02
Storer Error Master
03
High Temperature Master
04
Low Ttemperature Master
05
Interior Communication Master
06
GFCI Devices Error Master
07
DCI Devices Error Master
08
Current Sensor Master
09/11/13
L1/L2/L3 Voltage High Master
10/12/14
L1/L2L3 Voltage Low Master
15/16/17
L1/L2/L3 Average Voltage of 10 mimutes High Master
18/20/22
L1/L2/L3 Frequency High Master
19/21/23
L1/L2/L3 Frequency Low Master
24/25/26
L1/L2/L3 Grid Lost Error Master
27
GFCI Error Master
28/29/30
L1/L2/L3 DCI Error Master
31
Insulation Error Master
32
Bus Voltage unbalance Master
33
Bus Voltage High Master
34
Bus Voltage Low Master
35/36/37
L1/L2/L3 Current High Master
38
Bus Voltage High Of Hardware Master
39/40
PV1/PV2 Current High of Hardware Master
41/42/43
L1/L2/L3 Current High of Hardware of Grid Master
45/46/47/48
Fan 1/2/3/4 Error Master
50
Lost interior communication Slave
51/52/53
L1/L2/L3 Data Consistency of Voltage Error Slave
54/55/56
Data Consistency of Frequency Error Slave
- 37 -
Suntrio Plus Series
57
Data Consistency of GFCI Slave
58/59/60
L1/L2/L3 Data Consistency of DCI Slave
61/63/65
L1/L2/L3 Grid Voltage High Slave
62/64/66
L1/L2/L3 Grid Voltage Low Slave
67/69/71
L1/L2/L3 Frequency High Slave
68/70/72
L1/L2/L3 Frequency Low Slave
73/74/75
L1/L2/L3 No Grid Error Slave
76/77
PV1 /PV2 Voltage High Slave
78/79
PV1/PV2 current High Slave
Table7.1 Error Code
General troubleshooting methods for inverter are as follows:
Fault Information
Relay Error
Eeprom Error
Temperature High
Error
GFCI Device Error
DCI Device Error
Cureent Sensor Error
AC Voltage Error
Troubleshooting
If this error occurs frequently, please contact your distributor or
phone SAJ.
If this error occurs frequently, please contact your distributor or
phone SAJ.
Check whether the radiator is blocked, whether the inverter is in too
high or too low temperature, if the above mentioned are in normal,
please contact your distributor or phone SAJ.
If this error occurs frequently, please contact your distributor or
phone SAJ.
If this error occurs frequently, please contact your distributor or
phone SAJ.
If this error occurs frequently, please contact your distributor or
phone SAJ.
·Check the volt of the grid
·Check the connection between the inverter and the grid.
·Check the settings of the on-grid standards of the inverter.
·If the volt of the grid is higher than the volt regulated by local grid,
please inquire the local grid workers whether they can adjust the volt
at the feed point or change the value of the regulated volt.
·If the volt of the grid is in regulated range as allowed and LCD still in
this error, please contact your distributor or phone SAJ.
- 38 -
Suntrio Plus Series
Frequency Error
No Grid Error
GFCI Error
DCI Error
ISO Error
Current High
Bus Voltage High
PV Current High
PV Voltage Fault
Lost Communication
Check the set of country and check the frequency of the local grid, if
the above mentioned are in normal, please contact your distributor or
phone SAJ.
Check the connection status between the AC side of the inverter and
the grid, if the above mentioned are in normal, please contact your
distributor or phone SAJ.
Check the insulation resistance of the positive side and cathode side
of the solar panel; check whether the inverter is in wet environment;
check the grounding of the inverter. If the above mentioned are in
normal, please contact your distributor or phone SAJ.
If this error exists always, please contact your distributor or phone
SAJ.
Check the insulation resistance of the positive side and cathode side
of the solar panel; check whether the inverter is in wet environment;
check whether the grounding of the inverter is loose or not. If the
above mentioned are in normal, please contact your distributor or
phone SAJ.
Check the connection status between the inverter and the grid and test
whether the volt of the grid is stable or not, if the above mentioned are
in normal, please contact your distributor or phone SAJ.
Check the settings of the solar panel. SAJ’s system design software
can help you.If the above mentioned are in normal, please contact
your distributor or phone SAJ.
If this error exists always, please contact your distributor or phone
SAJ.
Check the settings of the solar panel. SAJ’s system design software
can help you. If the above mentioned are in normal, please contact
your distributor or phone SAJ.
Check the connection of communication cables between control
panel and display panel. If the above mentioned are in normal, pleae
contact your distributor or phone SAJ.
Table 7.2
Troubleshooting
- 39 -
Suntrio Plus Series
Chapter 8
Recycling and Disposal
This device should not be disposed as residential waste. An Inverter that has reached
the end of its life and is not required is to be returned to your dealer or you must find
an approved collection and recycling facility in your area.
- 40 -
Suntrio Plus Series
Chapter 9
Guarantee Service
Please refer to the warranty card.
- 41 -
Suntrio Plus Series
Chapter 10 Contact SAJ
Guangzhou Sanjing Electric Co., Ltd.
SAJ Innovation Park, No.9, Lizhishan Road, Guangzhou Science City, Guangdong,
P.R.China.
Postcode: 510663
Web: http: //www.saj-electric.com
Technical Support & Service
Tel: +86 20 6660 0082
Fax: +86 20 6660 8589
E-mail: service@saj-electric.com
International Sales
Tel: 86-20-66608618/66608619/66600082/66600086
Fax: 020-66608589
E-mail: info@saj-electric.com
Domestic Sales
Tel: 020-66600058/66600082
Fax: 020-66608589
- 42 -