edward a. reynolds west side hs
Transcription
edward a. reynolds west side hs
NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 STREET, MANHATTAN, NY, 10025 School: InspectionId Inspection Type 12231 ARCHITECTURAL - SENIOR 12304 ARCHITECTURAL - ASSOCIATE Time In Last Edited 2015-04-28 11:53AM 2015-04-28 12:23PM 2015-06-17 04:03PM 2015-05-13 01:16PM Asset Data Question Answer Was the Building Fully Accessible for Inspection? Principal(s) Information Principal Name Principal Organization Meeting with Principal? Principal Feedback Custodian Fireman Building Square Footage Comments on the Area (Square Feet) Comments on the Stories (Floors) plus Basements Comments on the Year Built Comments on the Student Population Comments on the Staff Population Comments on the Number of Classrooms Weather Facade Photo Yes Jean McTavish Edward A. Reynolds West Side High School - Manhattan No No Feedback from Principal Was not present Ali Tarat 85,000 None 3+B 1999 541 63 27 Fair West 102nd Street Facade Main Entrance Photo Main Entrance, 102nd Street Mobile Validity Version 2.0 (P) Page 1 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Roof Photo Have any Systems/Major Building Components been upgraded? Roof 1 Systems: Limited Exterior Stair repairs Years: Systems: 2015 Flooring refinished, Gymnasium Years: Systems: 2008 Flooring replaced, Library Years: Systems: 2007 Exterior Soffit, Parapet repairs Have there been any New Building Additions? Tandem Years: 2013 No New Construction No Tandem Leased Space? No Priority Condition Priority Condition Exist Last Year? Priority Category Condition Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Structural Engineer Required Structural Condition Type Condition Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Question Response Is the Primary or secondary entrance on an accessible route? Is the building a multi-story building? Are All floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Yes Yes Yes Yes Yes Yes Physical Breakdown Structure Exists Complies Required Deficiency FUNCTIONAL ACCESSIBILITY Exterior Routes Yes Exterior Entrances & Exits Exterior H/C Lifts No Exterior Ramps and Railings Yes Yes No Yes Yes Interior Routes Interior Corridor Doors And Hardware Yes Interior Corridors & Lobbies Interior Elevators Mobile Validity Version 2.0 (P) Yes Yes Page 2 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection Physical Breakdown Structure Interior H/C Lifts M506 Exists Complies No Required Deficiency No Yes Interior Lobby Doors And Hardware No Interior Ramps Rooms & Spaces Art Rooms Room 222 Yes Yes No Auditorium Cafeteria Basement Yes Yes 2nd, 3rd Floors Yes Yes Yes Yes Basement Yes Yes Room 100 Yes Yes Room 130 Yes Yes Classrooms Computer Rooms Rooms 203, 227, 327 Gymnasium Library Main Office Multi-purpose Room No Nurse's Office Room B12 Yes Yes No Pool Science Lab Rooms 202, 210 Yes Yes Toilet Rooms (boys) All Floors Yes Yes Toilet Rooms (girls) All Floors Yes Yes Toilet Rooms (staff) All Floors Yes Yes Building Template Inspection Mobile Validity Version 2.0 (P) Page 3 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response Architectural ATHLETIC FIELDS Does not exist EXTERIOR Inspected AREAWAY Does not exist AWNINGS AND CANOPIES Does not exist CHIMNEY Does not exist COPING Inspected 3- Fair Condition Deficiency CAST STONE:OPEN TRANSVERSE JOINTS WITH DAMAGED CAULKING Deficiency Location/Instance Deficiency Quantity 80 L.F. MAINTENANCE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Roof 1, Facade A Violations No violations recorded Deficiency Deficiency Location/Instance CAST STONE:CRACKED/BROKEN PIECES Deficiency Quantity 60 L.F. REPLACE-IN-KIND PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Roof 1, Facade C Violations No violations recorded CORNICE Does not exist DOORS Inspected Mobile Validity Version 2.0 (P) Page 4 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR DOORS Inspected DOOR HARDWARE Condition 2- Between Good and Fair Inspected DOORS AND FRAMES Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected LINTELS Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected TRANSOM/SIDE LIGHT Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected EXTERIOR SOFFITS 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected EXTERIOR WALLS Material Type(s) Masonry Replacement Quantity Replacement Uom 25,000 S.F. Instance on All Facades Inspected Instance Condition 3- Fair Instance Quantity Instance Quantity Uom 25,000 SF Deficiency Roof Plan Reference BRICK:MINOR CRACKS AND SPALLING Elevation Elevation Reference Deficiency Quantity Facade D 250 S.F. RESTITCH PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Main Entrance Violations No violations recorded Deficiency Mobile Validity Version 2.0 (P) BRICK:OPEN/BAD JOINTS Page 5 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR EXTERIOR WALLS Roof Plan Reference Elevation Elevation Reference Deficiency Quantity All Facades 500 S.F. REPOINT PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade A Violations No violations recorded Deficiency Roof Plan Reference BRICK:MAJOR / THRU CRACKS Elevation Elevation Reference Deficiency Quantity Facade D 100 S.F. REMOVE AND REBUILD PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 6 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR EXTERIOR WALLS Deficiency Photo 1 Top of Stair Deficiency Photo 2 Below first photo Violations No violations recorded LOADING DOCK Does not exist LOUVER Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected PARAPETS Material Type(s) Masonry, Concrete, Other Replacement Quantity Replacement Uom 8,000 C.F. Instance on All Facades Inspected Instance Condition 2- Between Good and Fair Instance Quantity Instance Quantity Uom 8,000 CF Deficiency No deficiencies recorded Inspected PLAZA DECK Instance on Concrete:Roof 3 Inspected Instance Condition 3- Fair Instance Quantity Instance Quantity Uom Installation Year Source of Installation Year 4,000 SF 1999 Custodial staff Deficiency Deficiency Location/Instance CONCRETE:OPEN JOINTS WITH DAMAGED CAULKING Deficiency Quantity 80 L.F. MAINTENANCE PRIORITY 5 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 7 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR PLAZA DECK Deficiency Photo 1 Main Entrance Violations No violations recorded Deficiency Deficiency Location/Instance CONCRETE:MAJOR LEAKAGE Deficiency Quantity 100 S.F. REPLACE PRIORITY 5 LEVEL 6 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Electrical Panel Room Violations No violations recorded Inspected ROOF Inspected Roofing Replacement Quantity Replacement Uom 26,000 S.F. LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded ROOF BARRIER Does not exist ROOF CAGE Does not exist ROOF FENCE Does not exist ROOF HATCH/SMOKE HATCH Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected ROOFING Instance on Single Ply, Fully Adhered Roof:Single Ply Fully Adhered Roofs 1 & 2 Instance Condition Inspected Instance Quantity Instance Quantity Uom "Does the roof have major mechanical equipment?' Installation Year 26,000 S.F. Yes 1999 Mobile Validity Version 2.0 (P) Page 8 of 31 4- Between Fair and Poor Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR ROOF Roofing ROOFING Source of Installation Year Custodial staff Deficiency SINGLE PLY, FULLY ADHERED ROOF:ROOFING:OPEN SEAMS Deficiency Location/Instance Deficiency Quantity 180 L.F. REPAIR PRIORITY 5 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Roof 1 Violations No violations recorded Deficiency SINGLE PLY, FULLY ADHERED ROOF:ROOFING:MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE Deficiency Location/Instance Deficiency Quantity 100 S.F. REPLACE ROOFING WITH MAJOR EQUIPMENT REMOVAL PRIORITY 5 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Room 318, also found in Gymnasium, Rooms 312, 314, 327, 328 Violations No violations recorded Inspected ROOFING DRAINS 2- Between Good and Fair Condition Deficiency Mobile Validity Version 2.0 (P) No deficiencies recorded Page 9 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR ROOF Inspected Specialties Inspected BULKHEAD/PENTHOUSE 2- Between Good and Fair Condition Deficiency No deficiencies recorded CUPOLA/ SPIRES/ TOWERS Does not exist DORMER Does not exist DUNNAGE STEEL Inspected 3- Fair Condition Deficiency Deficiency Location/Instance HEIGHT LESS THAN 18" Deficiency Quantity 20 L.F. REPLACE PRIORITY 1 LEVEL 1 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Roof 1 Violations No violations recorded Deficiency Deficiency Location/Instance MINOR RUSTING Deficiency Quantity 40 L.F. MAINTENANCE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Roof 1 Violations No violations recorded Does not exist ROOF/GRAVITY TANK Mobile Validity Version 2.0 (P) Page 10 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR ROOF Specialties Does not exist SKYLIGHT/ROOF VENT Inspected STAIRS/RAMPS: EXTERIOR Inspected BUILDING CHEEK/FLANK WALLS Condition 4- Between Fair and Poor Deficiency Deficiency Location/Instance BRICK:CRACKS/SPALLING - MAJOR Deficiency Quantity 40 S.F. REPLACE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade D at Ramp Violations No violations recorded Deficiency Deficiency Location/Instance CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJOR Deficiency Quantity 20 S.F. REPLACE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade D, top of Ramp Violations No violations recorded Deficiency Mobile Validity Version 2.0 (P) BRICK:BULGING/DISPLACED Page 11 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Deficiency Location/Instance Deficiency Quantity 40 S.F. REPLACE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade D, Main Entrance Stair Violations No violations recorded Deficiency Deficiency Location/Instance STONE:BULGING/DISPLACED Deficiency Quantity 100 S.F. REPLACE PRIORITY 5 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Main Entrance Stair Violations No violations recorded Deficiency Deficiency Location/Instance STONE:CRACKS/SPALLING - MINOR Deficiency Quantity 20 S.F. Quantity Uom Mobile Validity Version 2.0 (P) Page 12 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 REPAIR PRIORITY 4 LEVEL 2 Main Entrance Stair Violations No violations recorded Inspected RAILINGS Condition 4- Between Fair and Poor Deficiency Deficiency Location/Instance RUST - MAJOR Deficiency Quantity 50 L.F. REPLACE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Severely rusted bases at Ramp Violations No violations recorded Inspected STAIRS/RAMPS Condition 4- Between Fair and Poor Deficiency Deficiency Location/Instance CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJOR Deficiency Quantity 100 S.F. REPLACE PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 13 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Deficiency Photo 1 Landing at Main Entrance Violations No violations recorded Deficiency Deficiency Location/Instance STONE:DETERIORATED SUBSTRATE Deficiency Quantity 100 S.F. REPLACE SUBSTRATE AND RESET PRIORITY 4 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade D Violations No violations recorded Inspected WINDOWS Replacement Quantity Replacement Uom 8,000 SF EXTERIOR GUARDS Inspected Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected LINTELS Condition 3- Fair Deficiency Roof Plan Reference Mobile Validity Version 2.0 (P) STEEL:MINOR RUSTING Page 14 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response EXTERIOR WINDOWS LINTELS Elevation Deficiency Quantity 150 L.F. MAINTENANCE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Facade D above Main Entrance Violations No violations recorded Inspected WINDOWS Material Type(s) Instance on Aluminum:All Facades Aluminum Inspected Instance Condition 3- Fair Instance Quantity Instance Quantity Uom Installation Year Source of Installation Year 8,000 SF 1999 Custodial staff Deficiency Roof Plan Reference ALUMINUM:INOPERABLE BALANCE Elevation Elevation Reference Deficiency Quantity All Facades 50 EACH MAINTENANCE PRIORITY 3 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Inspected INTERIOR Does not exist AUDITORIUM CAFETERIA Mobile Validity Version 2.0 (P) Page 15 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR CAFETERIA Instance on Basement Inspected Ceiling Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Door(s) Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Fixed Equipment Does not exist Instance on Basement Floor Finish Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Sliding-folding Partition Instance on Basement Does not exist Instance on Basement Does not exist Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Stage Walls Window Curtains/Shades/Blinds Does not exist Instance on Basement Inspected CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected Ceiling Condition 3- Fair Deficiency Deficiency Location/Instance TECTUM:DAMAGED/MISSING Rooms 300, 306, 310, 312, 324, Corridor at Rooms 114, 116, 130 and Other Locations 450 S.F. REPLACE PRIORITY 3 LEVEL 2 Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Corridor at Room 114 Deficiency Photo 2 East of Room 300 Mobile Validity Version 2.0 (P) Page 16 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Violations No violations recorded Deficiency Deficiency Location/Instance TECTUM:DAMAGED/MISSING - ACTIVE LEAK Rooms 226, 302, 312, 314, 318, 327, Corridor at Room 305 and Other Locations 400 S.F. REPLACE PRIORITY 5 LEVEL 2 Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Corridor at Room 305 Deficiency Photo 2 East of Room 302 Violations No violations recorded Inspected Door(s) Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Floor Finish Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity VINYL TILES:BROKEN/DETERIORATED/MISSING TILES Rooms B16, 130, 217, 226, 230B, 237 , 310 and Other Locations 400 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Center of Room 130 Mobile Validity Version 2.0 (P) Page 17 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Deficiency Photo 2 South of Room 310 Violations No violations recorded Deficiency Deficiency Location/Instance Deficiency Quantity EPOXY FLOORING:CRACKS/SPALLING Room 202, 206, 210, 214, 216 & 218 350 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Room 210 Deficiency Photo 2 Southwest corner to Room 210 Violations No violations recorded Deficiency Deficiency Location/Instance Deficiency Quantity RUBBER NOSING:DETERIORATED Room B16 10 L.F. MAINTENANCE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Center of Room B16 Violations No violations recorded Inspected Specialties Mobile Validity Version 2.0 (P) Page 18 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Specialties Inspected Classroom Locker(s) 2- Between Good and Fair Condition Deficiency No deficiencies recorded Does not exist Fixed Seating Inspected Walls Condition 2- Between Good and Fair Deficiency No deficiencies recorded GYMNASIUM Inspected Instance on Basement Ceiling Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity METAL PAN:DAMAGED/MISSING - ACTIVE LEAK East of Room 20 S.F. REPLACE PRIORITY 5 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 East of Room Violations No violations recorded Door(s) Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Fixed Equipment Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Floor Finish Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity VINYL TILES:BROKEN/DETERIORATED/MISSING TILES Center of weight Room (within Gymnasium) 100 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 19 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR GYMNASIUM Floor Finish Deficiency Photo 1 Center of weight Room (within Gymnasium) Violations No violations recorded Seating Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Sliding-folding Partition Instance on Basement Does not exist Instance on Basement Does not exist Instance on Basement Inspected Instance Condition 3- Fair Deficiency Deficiency Location/Instance Deficiency Quantity PLASTER:CRACKS/SPALLING Along North and West of Room 200 S.F. REPLACE PRIORITY 3 LEVEL 2 Stage Walls Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 West of Room Deficiency Photo 2 North of Room Violations No violations recorded Deficiency Deficiency Location/Instance Deficiency Quantity GLAZED BLOCK:CRACKS/SPALLING Southwest corner of Room 10 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 20 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR GYMNASIUM Walls Deficiency Photo 1 Southwest corner of Room Violations No violations recorded Window Curtains/Shades/Blinds Does not exist Instance on Basement Inspected INTERIOR DOOR HARDWARE 2- Between Good and Fair Condition Inspected INTERIOR GUARDS 2- Between Good and Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity DETERIORATED/TORN-OUT/MISSING South of Gymnasium 20 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 South of Gymnasium Violations No violations recorded KITCHEN/WARMING PANTRY Inspected Instance on Basement Ceiling Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity WASHABLE TILE:DAMAGED/MISSING Near Compressor Room, South & North of Room 40 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Mobile Validity Version 2.0 (P) Page 21 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR KITCHEN/WARMING PANTRY Ceiling North of Room Deficiency Photo 2 Near Compressor Room Violations No violations recorded Door(s) Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Floor Finish Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity QUARRY TILE:BROKEN/MISSING TILES Near the Servery & Center of M op Wash Room 20 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Center of Mop Wash Room Deficiency Photo 2 Near the Servery Violations No violations recorded Walls Instance on Basement Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded LIBRARY Inspected Instance on Room 100 Built-in Furnishing Does not exist Instance on Room 100 Ceiling Mobile Validity Version 2.0 (P) Page 22 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR LIBRARY Ceiling Instance on Room 100 Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity TECTUM:DAMAGED/MISSING Center of Room 100C (within Library) 30 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Center of Room 100C (within Library) Violations No violations recorded Door(s) Instance on Room 100 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Floor Finish Instance on Room 100 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Room 100 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Walls LOCKER ROOM Instance on Basement - Boys Inspected Alternative Use No Instance on Basement - Girls Inspected Alternative Use No Ceiling Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Door(s) Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Floor Finish Inspected Instance on Basement - Boys Mobile Validity Version 2.0 (P) Page 23 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR LOCKER ROOM Floor Finish Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity CERAMIC TILE:BROKEN/MISSING TILES Near Entrance to Room 35 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Near Entrance to Room Violations No violations recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity CERAMIC TILE:BROKEN/MISSING TILES Near shower Room 30 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Near shower Room Violations No violations recorded Locker Room Lockers Instance on Basement - Boys Inspected Instance Condition 3- Fair Deficiency Deficiency Location/Instance DAMAGED UNITS Units 1, 8, 9, 18, 257, 258, 259, 260, 261, 262, 391, 392, 393, 394, 395, 396, and other units 25 EACH REPLACE PRIORITY 3 LEVEL 2 Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 24 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR LOCKER ROOM Locker Room Lockers Deficiency Photo 1 Unit 391 Deficiency Photo 2 Unit 280 Violations No violations recorded Instance on Basement - Girls Inspected Instance Condition 3- Fair Deficiency Deficiency Location/Instance DAMAGED UNITS Units 269, 270, 271, 272, 273, 274, 333, 338, 344, 403, 404, 405, 406, 407, 408, and other Units 25 EACH REPLACE PRIORITY 3 LEVEL 2 Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Unit 408 Violations No violations recorded Walls Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity CERAMIC TILE:BROKEN/ MISSING Near Entrance to Room 10 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Mobile Validity Version 2.0 (P) Page 25 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR LOCKER ROOM Walls Deficiency Photo 1 Near Entrance to Room Violations No violations recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity CERAMIC TILE:BROKEN/ MISSING Near Entrance to Room 10 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Near Entrance to Room Violations No violations recorded MULTI-PURPOSE ROOM Does not exist POOLS Does not exist SCIENCE DEMO ROOM Instance on Rooms 214, 216, 218 Inspected Alternative Use No Fixed Equipment Instance on Rooms 214, 216, 218 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded SCIENCE LAB Instance on Rooms 202, 210 Inspected Alternative Use No Fixed Equipment Instance on Rooms 202, 210 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded SCIENCE PREP ROOM Instance on Room 206 Inspected Alternative Use No Fixed Equipment Instance on Room 206 Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Mobile Validity Version 2.0 (P) Page 26 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR SHOWER ROOM Instance on Basement - Boys Inspected Alternative Use No Instance on Basement - Girls Inspected Alternative Use No Ceiling Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Door(s) Instance on Basement - Boys Does not exist Instance on Basement - Girls Does not exist Floor Finish Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Boys Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Instance on Basement - Girls Inspected Instance Condition 2- Between Good and Fair Deficiency No deficiencies recorded Walls Inspected STAIRS/RAMPS: INTERIOR Do Letter Stair Signs Exist? Yes Inspected Ceiling Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity PLASTER:CRACKS/SPALLING Stair A/3 10 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Stair A/3 Violations No violations recorded Inspected Door(s) Condition 2- Between Good and Fair Deficiency No deficiencies recorded Does not exist Partition Mobile Validity Version 2.0 (P) Page 27 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR STAIRS/RAMPS: INTERIOR Inspected Railings Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Stairs and Landings Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Walls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected STRUCTURAL Inspected COLUMNS/BEAMS/BEARING WALLS Condition 3- Fair Deficiency Deficiency Location/Instance Deficiency Quantity STEEL COLUMNS/BEAMS:MINOR RUSTING Main Entrance 50 S.F. REPAIR AND REPAINT PRIORITY 3 LEVEL 5 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Main Entrance Violations No violations recorded Inspected FLOOR STRUCTURE Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected FOUNDATION WALLS Material Type(s) Concrete Condition 4- Between Fair and Poor Deficiency CONCRETE:WATER INFILTRATION INTO NONINSTRUCTIONAL SPACE Acid Tank Room 120 S.F. INSTALL WATERPROOFING PRIORITY 5 LEVEL 5 Deficiency Location/Instance Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Acid Tank Room Violations Mobile Validity Version 2.0 (P) No violations recorded Page 28 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response INTERIOR STRUCTURAL FOUNDATION WALLS Deficiency CONCRETE:WATER INFILTRATION INTO ELECTRICAL PANEL ROOM Electrical Panel Room 25 S.F. INSTALL WATERPROOFING PRIORITY 5 LEVEL 6 No violations recorded Deficiency Location/Instance Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Inspected ROOF STRUCTURE Condition 2- Between Good and Fair Deficiency No deficiencies recorded Does not exist VAULTS-BUNKERS Inspected TOILET ROOMS - STAFF Inspected Ceiling Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Door(s) Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Floor Finish Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Stalls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Walls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected TOILET ROOMS - STUDENTS Inspected Ceiling Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Door(s) Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Floor Finish Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Stalls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Walls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected LIFE SAFETY F.D. HOLDING AREA Does not exist STEEL STAIRS Does not exist Inspected SITE CONTAINERIZATION Does not exist Drainage System for Asphalt Inspected Mobile Validity Version 2.0 (P) Page 29 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response SITE Drainage System for Asphalt Does not exist Catch Basins/Manhole - Surrounded by asphalt Inspected Drainage System for Concrete Inspected Catch Basins/Manhole - Surrounded by concrete Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Drainage System for Soil Does not exist Catch Basins/Manhole - Surrounded by Soil DRINKING FOUNTAINS Does not exist FENCES Inspected 2- Between Good and Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity CONCRETE CURB:DAMAGED/DETERIORATED On South of Building (Easement) 10 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 On South of Building (Easement) Violations No violations recorded IRRIGATION SYSTEM Does not exist PAVING Inspected Inspected DOT Sidewalk Asphalt Does not exist Concrete Inspected 2- Between Good and Fair Condition Deficiency Deficiency Location/Instance Deficiency Quantity DAMAGED/DETERIORATED/MISSING SECTIONS On w 102 Street 50 S.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 On W102 Street Violations No violations recorded Does not exist Pavers Inspected Site Sidewalks & Walkways Asphalt Does not exist Concrete Inspected Mobile Validity Version 2.0 (P) Page 30 of 31 Print Date: 6/18/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Architectural Inspection M506 Question Response SITE PAVING Site Sidewalks & Walkways Concrete Condition 2- Between Good and Fair Deficiency No deficiencies recorded Does not exist Pavers Inspected Student Non-Use Gravel Exists? Asphalt No Does not exist Concrete Inspected 2- Between Good and Fair Condition Deficiency No deficiencies recorded Does not exist Pavers Does not exist Student Use PLAYGROUNDS Does not exist PLAYING SURFACE Does not exist RETAINING WALLS Does not exist SEATING Does not exist SITE WALLS (NOT RETAINING WALLS) Does not exist STAIRS/RAMPS: EXTERIOR Inspected Inspected Railings Condition 2- Between Good and Fair Deficiency Deficiency Location/Instance Deficiency Quantity DAMAGED Northwest corner of Building Site 10 L.F. REPLACE PRIORITY 3 LEVEL 2 Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo 1 Northwest corner of Building Site Violations No violations recorded Inspected Site Cheek/flank Walls Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Stairs/ramps Condition 2- Between Good and Fair Deficiency Mobile Validity Version 2.0 (P) No deficiencies recorded Page 31 of 31 Print Date: 6/18/2015