Dual Maximum VAV Box Controls
Transcription
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor‐engineering.com Agenda VAV Box basics • • VAV Box control logic • • • • Sizing VAV Boxes How low can you go? Conventional VAV box control logic “Dual Maximum” control logic Non-complying dual maximum control logic Determining setpoints How well does “Dual Maximum” logic work? • ASHRAE RP-1515 Results VAV Box Sizing Oversized box • Less pressure drop • Less noise • Higher box min → more reheat, higher fan energy • Cost more Undersized box • Higher pressure drop • More noise • Lower box min → less reheat, lower fan energy VAV Box Sizing: LCC Analysis Compared ∆TP from 0.3” to 0.8” Low rise office building Sensitivity Analysis • • • • • • • TP SP VP Climate Loads operating schedules Utility rates Load calc’ (aggressive, conservative) 8 bit versus 10 bit A/D converter SAT (50°F-60°F), SAT reset, SP reset RESULT: Size VAV Boxes for ~0.5” ∆TP VAV Box Sizing: Sample Calc. Outlet Outlet Max Radiated Inlet ∆SP ∆VP ∆TP width height CFM NC* dia. (in. (in. (in. (in.) (in.) (in.) w.g.)* w.g.) w.g.) 4 4 12 8 0.08 0.42 0.50 230 21 5 5 12 8 0.15 0.35 0.50 333 20 6 6 12 8 0.24 0.25 0.49 425 21 7 7 12 10 0.25 0.25 0.50 580 20 8 8 12 10 0.33 0.17 0.50 675 22 9 9 14 13 0.27 0.23 0.50 930 17 10 10 14 13 0.32 0.18 0.50 1100 19 12 12 16 15 0.32 0.17 0.49 1560 19 14 14 20 18 0.31 0.19 0.50 2130 18 16 16 24 18 0.32 0.18 0.50 2730 22 *From selection software using ARI 885-95 and assuming inlet SP = 1.5 and outlet SP = 0.25 Nominal size What is the lowest minimum? • Function of –DDC Controller: What’s the lowest controllable velocity pressure (VP) signal? • DDC velocity pressure transducer accuracy • A/D converter resolution (bits) –VAV Box: • Amplification factor, F • Inlet size, D FPM min VPmin 4005 F CFM min D 2 FPM min 4 Why Not Just Look in the VAV Box Catalog? Equates to ~0.03” minimum VP and about 30% of design CFM for typical box selections Why Not Just Look in the VAV Box Catalog? Still too high Good Advice! NEVER use Box manufacturer’s minimums! Controllable VP Minimum Some manufacturers list the range in catalog Some you have to ask Most available from ASHRAE RP 1353 and PG&E research projects (see references) • Almost all controllers ± 10% at 0.003” Specify allowable setpoint ≤ 0.004” Typical DDC Performance 30 Nailor VAV Box “A” Titus VAV Box “B” Flow Error [cfm] 20 10 0 -10 -20 -30 -40 0 100 200 300 400 500 Reference Flow [cfm] Highly accurate down to about 50 CFM (0.003”) 600 700 800 Flow Probe Amplification K 10000 7000 3665 2806 C F M @ 2062 1432 1160 916 22 inch 1000 I n l e t C F M 100 S i z e 702 16 inch 14 inch 515 12 inch 358 10 inch 9 inch 8 inch 229 7 inch 6 inch I n c h S i g n a l 4005 A F K 2 5 inch F = amplification factor K = actual flow in CFM at flow probe output of 1.0” w.c. A = is the nominal inlet area in ft2 4 inch 10 0.01 O n e 0.1 Flow Probe Velocity Pressure Signal (Inches W.G.) 1 Typical Flow Probe Performance 2000 V e lo c ity [fp m ] 1000 500 200 100 50 .001 .005 .01 .05 Flow Grid Pressure [iwc] F slope ~ 2 . 6 .1 .5 1 Specify ≥2.0 Sample Controllable Minimum VPmin FPM min 4005 F D 2 CFM min FPM min 4 Box Inlet Diameter 6 8 10 12 14 16 0.004 170 4005 2.3 Minimum Maximum CFM at 0.004 Minimum Ratio Minimum Ratio CFM at 0.5 at lowest at Highest in.w.g. sensor in.w.g. Maximum, % Maximum, % reading pressure drop 425 33 7.8% ‐ 715 58 8.1% 13.6% 1,100 91 8.3% 12.7% 1,560 130 8.3% 11.8% 2,130 177 8.3% 11.3% 2,730 232 8.5% 10.9% VAV Reheat Control Q: Why do some buildings use 3 -5 times as much energy as others? Boiler Input (Btu/sf) 2,500 Site #1 Site #2 2,000 1,500 1,000 500 0 Mar-02 A: Reheat Apr-02 May-02 Jun-02 Jul-02 Conventional VAV Control Conventional VAV Box Minimum Setpoint No less than larger of: • Minimum ventilation rate Per Title 24 • Controller minimum Not an issue for conventional logic – see discussion above • Limit “dumping” Not an issue – see RP-1515 results below • Limit stratification No more than 20°F above space temperature (~≤95°F) per Standard 90.1 No more than larger of: • 30% of cooling maximum Per Title 24/Standard 90.1. Now only allowed for non-DDC controls • Minimum ventilation rate Title 24 VAV Control Requirement for zones with DDC Dual Maximum Control per Title 24 and Standard 90.1 for DDC Dual Maximum Logic in Action Start heating, increase DAT setpoint At 50% Heat, start increasing airflow Sort of Dual Maximum Control (Found in some configurable controllers) T-24 Sort of Dual Maximum Control (Found in some configurable controllers) Title 24 VAV Box Dual Maximum Control Setpoints per Title 24 and Standard 90.1 Minimum: 1. No less than larger of: Minimum ventilation rate for the zone Controller minimum 2. No more than 20% of cooling maximum Heating Maximum: 1. No less than larger of: MARK VR‐101 VR‐102 VR‐103 INLET SIZE 12 10 6 COOL 1035 810 210 DESIGN CFM MIN HEAT 135 260 90 230 50 50 Minimum Limit stratification - ≤20°F SAT above space temperature (≤~90°F to 95°F) 2. No more than 50% of cooling maximum Always use Option 1 above • • Do not use code maximum just because it’s legal! Avoid using %-of-cooling-maximum setpoints – boxes are usually oversized! What about Standard 62.1 Multiple Spaces compliance? Oakland Office - VAV System with Outdoor Air Economizer How Well Does “Dual Max” Logic Actually Work? RP-1515 results… RP 1515, "Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers" Objectives Measure energy savings & validate simulations Identify comfort issues that may occur at low flow Funding California Energy Commission - PIER ASHRAE UC Berkeley - Center for the Built Environment Research Team UC Berkeley Taylor Engineering Price Industries Method Field Study in 7 buildings Background survey “Right now” survey matched to zone trends Energy monitoring Laboratory Study Air distribution for various diffuser types Yahoo! Sunnyvale Campus 1073 Zones 3700 Occupants Plaque face diffusers 800 Ferry Building 22 Zones Perforated Diffuser with blades in face Measured flow fractions: Yahoo campus 0.15 Cool Season All Occupied Hours Low Minimum 30% Minimum Low Minimum 30% Minimum 0.00 0.00 0.05 0.05 Density Density 0.10 0.10 0.15 Warm Season All Occupied Hours 0 20 40 60 Flow Fraction [%] 80 100 0 20 40 60 Flow Fraction [%] 80 100 Total Electricity Usage Energy Savings Occupant Comfort Survey Questions • When the logic changed from conventional (High minimum) to Dual Maximum (Low minimum): Approach • 3 surveys: • • • Did occupants become less comfortable? Was their sense of air movement stronger due to “dumping”? Yahoo warm and cool seasons 800 Ferry building warm season 3 – 4 weeks of surveying each season Switched between high and low minimum operation in the middle of each survey period Surveys administered 3 times/day About 10,000 responses received "How satisfied are you with the temperature in your workspace?“ HIGH min flow rate % dissatisfied of people 30.0% LOW min flow rate 249 25.0% 681 20.0% 15.0% 463 1408 10.0% 766 1793 5.0% 0.0% 800 Ferry Building Yahoo! Cool season Yahoo! Warm season % Dissatisfied people HIGH Conventional LOW Dual Maximum 800 Ferry Building 27.3% 12.5% Yahoo! cool season 8.7% 9.4% Yahoo! warm season 20.1% 10.3% Thermal sensation distribution (Yahoo! warm season) Loads are very low! 0.2 0.5 1 CFM/FT2 at 20˚F ∆T 140 Zones, 2 buildings, 1 warm month (Sept) What happens when load is less than airflow minimum? Conventional Logic Actual Required CFM Dual Max Logic Air temperature (800 Ferry building) High flow: average Tair = 71.2ºF 85 Low flow: average Tair = 73.3ºF HIGH minimum flow rate LOW minimum flow rate 75 70 Dates 10/03 10/04 51 74 1.5 45 74 1.1 64 73 1.9 25 74 1.1 37 74 1.4 67 75 1.3 27 75 1.2 48 73 2.1 10/20 09/30 30 73 1.6 10/19 09/29 23 72 0.89 10/18 09/28 65 71 2 10/17 09/27 34 71 1.5 10/14 47 70 1.6 10/13 41 71 1.8 10/12 35 71 1.4 10/11 36 71 1.5 10/10 45 72 1.6 10/07 35 71 1.5 10/06 23 71 1.8 10/05 27 72 2 09/26 60 N 14 Mean 72 sd 1.4 09/23 65 09/22 zone temperature [F] 80 How about Drafts? (800 Ferry building) Perceived air quality CBE background survey results Price Lab Tests Perforated diffusers with blades in the neck, Cooling Mode. Results: • Negligible impact on ADPI – all near 1 • Negligible impact on ACE – all near 1 Dual Maximum VAV Box Logic Summary Title 24 requires Dual Maximum logic for VAV zones with DDC Setpoints • Set minimum and heating-maximum setpoints as low as possible Minimum allowed by controls is seldom a factor if box properly sized Do not use maximum allowed by T-24 just because it is legal Cost impact • Requires discharge temperature sensor This is nice for diagnostics anyway • Usually requires programmable zone controller Configurable controller programming should soon catch up Performance • • • Thermal comfort improves with low flow operation Dumping & draft are not an issue at low flow Energy savings are significant and similar to simulation predictions Bibliography Taylor S., Stein J.; “Sizing VAV Boxes”, ASHRAE Journal, March 2004 Dickerhoff D., Stein J.; “Stability and Accuracy of VAV Terminal Units at Low Flow”, PG&E 0514, http://www.etcc-ca.com/reports/stability-and-accuracyvav-terminal-units-low-flow Lui R., Wen J.; Stability and Accuracy of VAV Box Control at Low Flows”, ASHRAE 1353-RP Taylor S. “Dual Maximum VAV Box Logic”, ASHRAE Journal, December 2012 Questions? Steve Taylor staylor@taylor-engineering.com
Similar documents
air barriers for masonry walls - Masonry Contractors Association of
Sample AB specification – section 07262 9:9;<=*><9?@AB;ACD EF
More information10GHz high power amplifiers
Rp power dissipation (2x) Rp=Vpmin.sqr/Rp Rp diss = -0.5V sqr / 25 10mW use 1/4W res.
More information