141027_PEP SSA MZ_Sub Sector Analysis PV Tourism_final
Transcription
141027_PEP SSA MZ_Sub Sector Analysis PV Tourism_final
SUBSECTOR ANALYSIS Qualitative Photovoltaic Power Supply for the Mozambican Tourism Sector www.renewables-made-in-germany.com Imprint Authors Dipl. Ing. (FH) Joerg Behrschmidt, Engineer Harald Olk, Electrical Engineering Master Technician June 2014 Publisher Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ) GmbH On behalf of the German Federal Ministry for Economic Affairs and Energy (BMWi) Contact Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ) GmbH Köthener Str. 2, 10963 Berlin, Germany Email: pep-subsaharan-africa@giz.de Web: www.giz.de/projektentwicklungsprogramm Web: www.renewables-made-in-germany.com Cover Picture: Massinga Beach Lodge 2014 This subsector analysis is part of the Project Development Programme (PDP) Sub-Saharan-Africa. PDP Sub-Saharan-Africa is implemented by the Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ) GmbH on behalf of the German Federal Ministry for Economic Affairs and Energy (BMWi) under the “renewables – Made in Germany” initiative. More information about PDP and about renewable energy markets in Sub-Saharan-Africa and South-East Asia can be found on the website www.giz.de/projektentwicklungsprogramm. This publication, including all its information, is protected by copyright. GIZ cannot be liable for any material or immaterial damages caused directly or indirectly by the use or disuse of parts. Any use that is not expressly permitted under copyright legislation requires the prior consent of GIZ. All contents were created with the utmost care and in good faith. GIZ assumes no responsibility for the accuracy, timeliness, completeness or quality of the information provided. Content List of Tables ii Currency iii Measurement iii List of Acronyms iv Executive Summary 1 1 Framework Conditions 2 1.1 Weather Data Inhambane 2 1.2 Basic Parameters: Energy Prices and Grid Reliability 3 1.3 Status of Photovoltaic in Mozambique 1.3.1 Technical 1.3.2 Financial 5 5 5 1.4 Basic Findings of the Energy Audit 6 1.5 Classification of Hotel Facilities 8 1.6 Possible Applications for Solar PV-Systems 1.6.1 PV-Island System 1.6.2 PV-Backup System 1.6.3 PV-Diesel-Hybrid System (PV operating as Negative load) 1.6.4 PV-Diesel-Hybrid System (PV operating as Main Resource) 8 9 9 9 9 2 3 1.7 Recommendations for Components 10 End Clients and Structures 11 2.1 PV Sizing 11 2.2 System Cost PV-System and Battery-Systems 12 2.3 Payback Period of PV- and Battery-System 12 Conclusions and Recommendations 14 3.1 General Conclusions 14 3.2 Recommendations for the Examined Hotel Facilities 15 Annex A1. PVSyst Simulation for Calculating the Specific Yield 18 A2. Assumptions Cost of PV-systems 21 A3. OPEX of PV-systems 22 A4. Cost Storing Capacity of Battery Systems 23 A5. Cost of Diesel Generators per kWh 24 A6. Pay Back Period 25 A7. Load Profile Azura 26 A8. Interest Rates Mozambique 27 A9. Fact Sheets 28 i List of Tables Table 1 Global Solar Irradiation in Inhambane[17] 2 Table 2 Ambient Temperature in Inhambane (Source: authors’ illustration) 3 Table 3 Customs Classification of Goods (Source: authors’ illustration) 6 Table 4: Base Scenario Consumption Hotel Facilities, 100% Occupancy (Source: authors’ illustration) 8 Table 5: PV Generator and Battery Sizing (Source: authors’ illustration) 11 Table 6: Cost Overview (Source: authors’ illustration) 12 Table 7: Overview Yearly Profit and Payback Period (Source: authors’ illustration) 13 Table 8: Key figures for the Locations Evaluated (Source: authors’ illustration) 15 Table 9 OPEX of PV-Systems (Source: authors’ illustration) 22 Table 10: Cost of Battery Systems According [4] 23 Table 11: Overview Cost of Diesel Generator (Source: authors’ illustration) 24 Table 12: Payback Period with Unit Cost of 0.32EUR/kWh (Source: authors’ illustration) 25 Table 13: Payback Period with Unit Cost of 0.25EUR/kWh for Azura (Source: authors’ illustration) 25 List of Figures Figure 1 Electricity Tariffs EDM, September 2013[11] 4 Figure 2 Locations for the Energy Audit (Source: authors’ illustration) 6 Figure 3 Load Distribution Travessia (Source: authors’ illustration) 7 Figure 4 Load Distribution Massinga (Source: authors’ illustration) 7 Figure 5 Load Distribution Azura (Source: authors’ illustration) 7 Figure 6 PV-Island System Function 9 [2] Figure 7 Backup-System by Reference to the SMA Backup Solution 9 [2] Figure 8 Block Diagram PV-Diesel-Hybrid System (Main Resource) 9 [2] Figure 9 Distribution about the Cost per Unit Produced Electricity (Source: authors’ illustration) 24 Figure 10 Measurement Results of Power and Power Factor in Azura (Source: authors’ illustration) 26 Figure 11 Load Profile Azura (Source: authors’ illustration) 26 Figure 12 Mozambique Lending Interest Rate (Percent, Source: The World Bank) [16] 27 ii Currency 1 USD = 31,149 MZN (April 2014) 1 EUR = 43.133 MZN (April 2014) Measurement W kW MW Watt Kilowatt Megawatt Wp kWp MWp Watt peak Kilowatt peak Megawatt peak Wh kWh MWh GW K Gigawatt Kelvin GWp l Gigawatt peak Litre GWh Watt hour Kilowatt hour Megawatt hour Gigawatt hour iii List of Acronyms Gen-Set Diesel generator plus control LV Low voltage MV Medium Voltage PV Photovoltaic PV-System PV plant (turnkey) VAT Value added tax iv QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR Executive Summary The renewable energy market in Sub-Saharan African countries has been taken into consideration by the international public and private investors in the recent few years. The German Ministry for Economic Affairs and Energy (BMWi), within the initiative “renewables – Made in Germany”, supports private sector cooperation and the development of sustainable framework conditions with the Project Development Program (PDP). The PDP works closely together with both German and local companies from Ghana, Kenya, Mozambique and Tanzania. The Deutsche Gesellschaft für Internationale Zusammenarbeit GmbH (GIZ) is responsible to implement the PDP in Sub-Saharan African countries. Moreover, GIZ has been given the task to determine the potential for renewable energy (and energy efficiency) in the Mozambican tourism sector, which is the objective of this paper. Specifically, this paper focuses on the potential of the photovoltaic market within the tourism sector in Mozambique. The overall goal is to inform the tourism sector about the possibilities of PV power supply and to show the private sector possible clients and their demand. The first kick-workshop with the tourism sector was held in November 2013 in Inhambane, Mozambique. As a result, the decision was made to conduct energy audits of the energy consumption covering the coast of Inhambane with its simple and luxurious hotels in order to get clear and complete data. Hereinafter, the data was used as input for this analysis. The energy auditing study has suggested 3 different scenarios for the use of the solar PV in Mozambican tourism sector: PV-backup system, PV-diesel-hybrid system and PV-island system. The availability of solar irradiation in Mozambique is extremely encouraging for implementing solar PV systems. Furthermore, it fits the governments profile for improving and developing the rural electrification. However, it should be taken into consideration that there are still many obstacles for the development of solar energy projects in Mozambique such as missing incentive instruments (e.g. feed-in tariffs) and high interest rates. Plus, electricity from the national grid is very cheap and economic feasibility of grid connected PV hard to reach. Despite the dynamic and challenging political and financial framework, it is possible to realize PV projects. Precondition is the use of higher equity or financing the project from outside of Mozambique. The production cost per kWh electricity from a PV-system is below the production cost of a diesel generator in off grid applications, therefore adding PV to a diesel generator mini grid to build a PV-diesel-hybrid system is an option. In regions where grid failures occur very often, PV-backup systems provide a much higher reliability for the power supply for the tourism sector. Especially for low consumption hotel facilities in remote areas a PV-island system with battery storage is the best option. To convince hotel managers to implement PV in their power supply, three main topics could be identified: higher service quality due to a more reliable or longer electricity supply per day, short payback times for the investment, and eco-tourism as a quality label of the hotel. 1 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 1 Framework Conditions This subsector analysis should show the actual status, the possibilities and the relevance of photovoltaic for the tourism sector in Mozambique. It has been carried out on the basis of energy audits done for three hotel facilities with own power supply and for one hotel connected to the grid. All four hotels are located in the province of Inhambane and near its capital, the city of Inhambane, which acts as a hub for the tourism sector. In this chapter the background for photovoltaic will be outlined, including the current status of the photovoltaic market, electricity prices, the results of the energy audits and the climate conditions. The evaluation of promotion programs as part of the global efforts for climate protection, for example the “Nationally Appropriate Mitigation Action” (NAMA), is not part of this study. 1.1 Weather Data Inhambane The province of Inhambane is located within the tropical latitude. The global irradiation on horizontal plane with an average of 1,935 kWh per year is high, hence a very good energy production of photovoltaic plants is possible. Table 1 shows the irradiation for different cities within the province of Inhambane as a 30 years average. The selection of the cities indicates the distribution of irradiation within the region. The irradiation data for Inhambane, Massinga and Vilanculos correspond to the location of the hotel facilities, selected for the energy audit. Inhambane Massinga Vilanculos Zavala Govuro Funhalouro Mabote Panda Latitude 23°52'S 23°19'S 22° 0'S 24°41'S 21°19S 23° 5'S 21°58'S 24° 3'S Longitude 35°23'E 35°22'E 35°18'E 34°25'E 34°35'E 34°23'E 33°37'E 34°43'E 22 63 121 108 177 157 4 116 Altitude [m] Global Solar Irradiation (kWh/m²/a) January 199.4 201.1 205.3 198.3 195.3 199.2 196.9 196.7 February 164.6 169.4 175.8 170.5 170.5 170.8 172.4 164.7 March 170.0 173.2 179.5 168.7 177.2 173.9 175.7 169.1 April 139.2 142.8 154.3 138.7 157.6 146.3 154.7 139.8 May 122.0 124.7 136.0 120.5 139.3 130.1 137.8 122.5 June 105.1 107.4 118.7 104.9 122.3 113.4 121.0 107.2 July 118.5 119.8 127.5 115.1 129.8 123.3 130.6 118.3 August 142.8 144.6 152.1 137.6 152.4 146.4 153.8 142.0 September 159.2 161.7 172.0 153.2 169.6 163.8 171.9 157.3 October 184.3 186.0 194.5 175.7 185.9 183.3 189.5 178.7 November 188.3 189.6 195.5 178.2 183.5 184.0 185.1 183.0 December 203.2 203.6 207.2 202.4 195.8 200.8 201.5 199.2 1,896.6 1,923.7 2,018.2 1,863.6 1,979.1 1,935.2 1,990.9 1,878.4 Annual Table 1: Global Solar Irradiation in Inhambane[17] 2 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR Table 2 gives an overview about the medium ambient temperatures[17] of the different cities. It shows that the monthly average is high. The spread of the monthly average between summer and winter time with around 8K is low compared to Europe, where the spread is around 20K. Basically the temperature is distinctly above 0°C. Inhambane Massinga Vilanculos Zavala Govuro Funhalouro Mabote Panda Latitude 23°52'S 23°19'S 22° 0'S 24°41'S 21°19S 23° 5'S 21°58'S 24° 3'S Longitude 35°23'E 35°22'E 35°18'E 34°25'E 34°35'E 34°23'E 33°37'E 34°43'E 116 22 63 121 108 177 157 26.7 26.3 26.0 26.0 26.0 4 Altitude [m] Ambient Temperature (°C) January 26.4 26.0 26.5 February 26.4 26.0 26.4 26.9 26.0 25.9 25.8 25.9 March 25.5 24.9 25.3 26.0 24.7 24.7 24.6 24.9 April 23.7 23.2 23.6 24.3 22.9 22.8 22.7 23.0 May 21.6 21.0 21.3 22.2 20.5 20.4 20.3 20.7 June 19.9 19.3 19.7 20.4 18.7 18.6 18.4 18.9 July 19.3 18.7 19.0 19.7 18.3 18.0 17.9 18.3 August 20.8 20.3 20.7 21.2 20.4 20.1 20.2 20.2 September 22.3 22.0 22.6 22.5 22.7 22.3 22.7 22.1 October 23.6 23.4 24.2 23.8 24.6 23.9 24.5 23.5 November 24.9 24.6 25.3 25.1 25.7 25.0 25.4 24.7 December 26.0 25.6 26.1 26.4 26.2 25.8 26.0 25.8 Annual 23.4 22.9 23.4 23.7 23.1 22.8 22.8 22.8 Table 2: Ambient Temperature in Inhambane (Source: authors’ illustration) In the peak season the irradiation is nearly twice as much as during off-season. This matches well with the seasonal energy demand of the hotel facilities and benefits the tourism of Mozambique. Taking into account the irradiation average in Table 1 and the temperatures in Table 2, a simulation had been performed to predict the prospective energy yield of a PV plant. The simulation was done with the planning software PVSyst 6.25. The set of parameters describes a standard PV-system with crystalline solar panels and string inverters connected to the low voltage grid. The expected energy yield in the province of Inhambane is about 1,600 kWh/kWp (see Annex A1). 1.2 Basic Parameters: Energy Prices and Grid Reliability To the time of this study, Mozambique is one of the important exporters for electricity in southern Africa. However, the electricity grid of Mozambique covers only a part of the country. The key facts describing the supply of electricity are the following: ■ Availability The grid connection systems of the rural areas, and therefore the connection of areas of interest for the tourism sector, are weak. As a direct consequence most hotel facilities run their own power supplies, mostly driven by diesel generators. ■ Reliability Mozambique has the ambitious target to connect all 128 regional cities by the end of 2014[5] and to the complete the transmission grid by 2017. Nevertheless the reliability of the grid, which is insufficient today, and the availability of the distribution grid will be a topic to take into account furthermore. 3 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR ■ Energy Prices EDM The electricity tariffs of the national power company EDM (indicated on its website) are shown in Figure 1. Hotel facilities rank among the major consumers of low and medium voltage connections (‘Grandes Consumidores de Baixa Tensão, Média Tensão’). Social Tariff, Household, Agriculture and General (Low Voltage) Recorded Consumption (kWh) From 0 to 100 Sale Price Household Farming Social Tariff Tariff Tariff (EUR ct/kWh) (EUR ct/kWh) (EUR ct/kW) Flat Rate General Tariff (EUR ct/kW) (EUR) 2.48 From 0 to 300 5.80 6.21 6.89 1.98 From 301 to 500 8.18 8.83 9.83 1.98 Above 500 8.60 9.67 10.76 1.98 7.37 8.60 9.88 Pre-Payment 2.48 Major Consumers of Low, Medium and High Voltage Class of Consumers Major Cons. LV (GCBT) Medium Voltage (MT) Farming Medium Voltage (MTA) High Voltage (AT) Sale Price Flat Rate (EUR ct/kWh) (EUR/kW) (EUR) 3.85 2.96 5.79 3.18 3.32 27.19 2.87 3.32 27.19 2.85 3.65 27.19 Note: For the tariff " Farming Medium Voltage " the power rating to be invoiced will be the peak power used Figure 1: Electricity Tariffs EDM, September 2013[11] ■ Electricity Prices for Hotel Facilities On-grid The tariff of ‘Grandes Consumidores’ is divided into a demand rate, working price and a fix price. The assessment of different electricity bills of three Casa Rex hotels of February 2014 shows a working price for a consumer connected to the low voltage grid (BT) including VAT of 1,767Mt/kWh (0.041EUR/kWh) and for the medium voltage connected consumer of 1,463Mt/kWh (0.034EUR/kWh). This is an increase of around 6% to the EDM tariffs September 2013 see Figure 1. With an increase of this amount, the actual total cost for electricity interpreted in terms of kWh is around 2.06 MT/kWh (0.047EUR/kWh) to 2.7 MT/kWh (0.063EUR/kWh). ■ Electricity Generation Prices from Diesel-fuelled Generator Sets The price for diesel is approximately 0.85EUR/l[12], [13].With a generator set efficiency of approx. 3.0 kWh/l (net electricity production for small generator systems), of the price amounts to 0.28 EUR/kWh. In addition to the fuel costs, a tax for generators used for off grid installations applies in Mozambique. The costs for maintenance are approx. 0.02 – 0.03EUR/kWh, whereas the amount for small generators is higher than for larger ones. Depending on the generator type, the lifetime of a diesel generator can be expected between 3,000 to 25,000 hours.[14] Taking this into account, the reserve for replacement investment can be calculated as 0.02EUR/kWh (see Annex A5). 4 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR In total the electricity generation, including maintenance and (re-)investment cost, can be calculated as approx. 0.32EUR/kWh for an off grid electricity supply using diesel generators. ■ Electricity Generation Prices with PV Plants In Mozambique, the electricity generation costs could be calculated as an estimated specific production of 1,600kWh/kWp per year for a standard PV-system with crystalline solar panels and string inverters. At the present, the system costs are 1,760 EUR/kWp for small systems up to 30kWp (see Annex A2). The expected lifetime of a PV system is 20 to 25 years. With operational expenses of 6.5% on average of the annual turnover (see Annex A3) and a module degradation of 0.3% per year the generation costs are 0.06EUR/kWh for a fully self-financed PV-system. Conclusions Due to a low electricity prices for grid connected consumers and lack of an e.g. feed-in tariff system, a first analyse of the existing situation suggests that a profitable implementation of PV as a grid connected system cannot be reached. Finally, it is important to highlight that, due to high diesel prices, especially PV-systems for off-grid applications are a good opportunity. 1.3 Status of Photovoltaic in Mozambique 1.3.1 Technical The limited number of manufactures of solar PV modules and PV-systems has a negative influence on module prices. Fosera Southern Africa Limitada, a private factory in Maputo, assembles pico solar photovoltaic systems with 1.5Wp, 2.5Wp and 5.0Wp per PV kit. Pico systems are defined as systems with a power output up to 10W. The PV kits are used for household lighting and mobile charging.[1] In order to solve this bottleneck, the government of Mozambique has signed a contract with the Indian government to build a factory for assembling solar PV modules with a capacity of around 200Wp for a production capacity of 5MWp.[1] Although it seems encouraging, experts are not so optimistic about the success of this project. However, another issue lies in the lack of expertise of solar PV and qualified technicians in rural areas. Knowledge of solar PV is limited to some companies, which are mostly located in Maputo. 1.3.2 Financial The financial key figures for renewable energy projects are: ■ Feed-In Tariff The government of Mozambique has not announced incentives specifically for renewable energies yet. Especially no feed-in tariff for PV exists up to now. A draft of feed-in tariff law is under discussion since September 2013, and the expected announcement for the beginning of 2014 is very much delayed. The proposed tariffs are likely to be reduced before approval, as they are higher than needed (from: up to 10 kWp = 33.25 EURCt/kWh to 18.96EURCt/kWh for large scale projects up to 10 MWp). ■ Other incentives Apart from a feed-in tariff system, Mozambique has designed also other incentives in other areas, such as encouraging investments in certain parts of the country, generating employment and promoting exports. For this purpose, reduced taxes and custom duties are available.[3],[10] ■ FUNAE A slightly different approach is taken by the governmental agency ‘Fundo de Energia’ (FUNAE) which has been created to improve the rural electrification and access to energy for the Mozambican population. Its 5 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR approach is to supply financial aid and financial guarantees for projects that comply with the requirements of FUNAE. ■ Value added Tax The value-added tax (VAT) in 2014 amounts to 17 %. ■ Custom Duties Custom duties are levied on the value of goods (including freight and insurance) classified according Table 3. According to the TKN Report[9] page 19, it could be possible for PV projects to benefit from exemptions from customs and VAT. DESCRIPTION Raw Materials Intermediate Goods Capital Goods Consumer Goods Essential Goods Fuel Electricity CLASS M I K C E N W RATES 2.5% 7.5% 5.0% 20% 0.0% 5% 0.0% Table 3: Customs Classification of Goods (Source: authors’ illustration) ■ Bank Loans So far most renewable energy projects were funded by donor organizations. At the national level, banks are generally not familiar with the specifics of renewable energy projects. Therefore, a high risk perception has been experienced: accordingly there is an extreme caution in granting loans. The general financing tenors of 5 to 7 years do not match the typical requirements for renewable energy projects of 10 to 15 years or more.[3] Special interest rates for renewable energy projects are not known at the time of writing this report. According to the Monthly Bulletin of the ‘Banco de Moçambique’, the actual interest rate for loans is 19.81% (Annex A8). Conclusion Up to now the financing sector is not developed to support PV projects with favourable terms. In Mozambique a direct promotion of technologies for the use of renewable energy and therewith PV does not exist yet. A kind of support is given only by indirect measures, such as relief from custom duties and VAT, which also can be used for conventional technologies. [3],[10] 1.4 Basic Findings of the Energy Audit This subsector analysis is based on the energy audits of three hotel facilities (Travessia, Massinga and Azura) located in the coastal region of Inhambane and equipped with their own power supply. These hotel facilities are more than 6 km away from the medium voltage grid. A fourth hotel (Casa Rex) examined is located in Vilanculos and has direct connection to the medium voltage grid using an own transformer. The hotel facilities are aimed at different categories of guests with different requirements to equipment and air conditioning. This results in different demands of electricity. Figure 2: Locations for the Energy Audit (Source: Google Maps) 6 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR The key facts are the following: ■ Travessia ■ ■ ■ ■ ■ Massinga ■ ■ ■ ■ ■ Buildings: & Infrastructure: 4 ‘Family Cottages’ with 3 rooms each for up to 4 persons; 2 ‘Couple Cottages’, with 2 rooms for 2 persons, pool bar, restaurant, kitchen, laundry, staff quarter, manager house. Electrical: equipment: Lamps, assumed 4 pcs per room, walkway lighting, around 100 pcs with 3 watt, operating hours 3 to6 per night, wall socket for charging of mobile, laptop and camera, fan, 1 per rooms, 3 refrigerators, 2 deep freezers for bar and kitchen, no air conditioning, water heating with solar water heaters. Consumption estimation: Travessia is optimized for low consumption and still under Figure 3: Load Distribution Travessia construction. The needed power is calculated with approx. 4 kW and (Source: authors’ illustration) the electrical consumption with 17 – 20kWh per day. Power Supply: A PV-system should be used as main power supply and a diesel generator as backup system. Buildings & Infrastructure: 32 Villas, all with air conditioning & fridge, pools belonging to the villas are without pool pump, warm water supply by gas separated for each villa, energy saving lamps for lighting the villas and walkways. Electrical equipment: Diesel Genset with 72 kW power output feeding local mini grid; operating time 10 – 12 hours per day until 10:00 PM, distance to the grid is around 12km, grid connection is scheduled because of construction of holiday cottages behind the villas, warm water supply by gas separate for each villa, energy saving lamps for lightning villas and ways. Figure 4: Load Distribution Massinga Consumption estimation: (Source: authors’ illustration) Needed power approx. 70kW, electrical consumption 400kWh per day. Power Supply: A diesel generator is used as main power supply. A second one is installed as backup system. For the future a connection to the grid is planned. Azura, Benguerra Island ■ ■ Buildings & Infrastructure: 16 Villas, all with air conditioning, swimming pool & fridge, cold room and refrigerating room for the restaurant. Electrical equipment: Mini Grid, 200kVA Generator for 24/7 use, power supply contracted to ELGAS Maputo; ELGAS supplies electrical power via generator operated with natural gas via gas pipeline from main land, ELGAS is owner of the equipment and performs the O&M, payment based on consumed kWh, use of backup diesel generator during failures of the gas driven generator; Azura has to provide and to pay the diesel. Figure 5: Load Distribution Azura (Source: authors’ illustration) 7 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR ■ ■ 1.5 Consumption estimation: Needed power approx. 200kW, electrical consumption 2,100kWh per day. Power Supply: A gas generator is used as main power supply. The generator is operated by the gas supplier. A diesel generator is installed as backup system. Classification of Hotel Facilities The hotel facilities evaluated during the energy audit are all equipped with restaurant, kitchen, bar, lounge, central pool, laundry area and staff quarters. The hotels operate their own water pumps for the water supply. The main differences among the hotels are represented by the different use of air conditioning in the guest rooms. A distinction can be made as it follows: facilities with no air conditioning, facilities with air conditioning during a restricted time per day, and facilities with air conditioning without a restricted use. In rare cases the hotel facilities operate cold rooms. In most cases they run refrigerators, deep-freezers or chest freezers. The water heating is realized using decentralized gas. In one case a solar water heating system is installed. Base on the energy audit, three basic scenarios have been identified regarding the different equipment features. The scenarios are shown in Table 4 for the peak season. The outlined consumption values are defined according the consumption of the corresponding hotel facilities. Base Scenario Low Consumption (8 Cottages, 24 People, 100% occupancy) Medium Consumption (32 Cottages, 48 People, 100% occupancy) High Consumption (16 Cottages, 38 People, 100% occupancy) Peak Power 4kW 70kW 150kW Consumption per Day 25kWh/d 420kWh/d 2,100kWh/d Yearly Consumption* Remarks 9.1MWh/a Rooms with LED lights and outlets for low consumption devices (notebook, mobile), no air conditioning and no refrigerator 153MWh/a Rooms with LED lights, hair dryer and outlets for low consumption devices (notebook, mobile), air conditioning only for a few hours per day, one refrigerator per guest house 766MWh/a Rooms with LED lights, hair dryer and outlets for low consumption devices (notebook, mobile), air conditioning for the whole day, one refrigerator per guest house, pool pumps Table 4: Base Scenario Consumption Hotel Facilities, 100% Occupancy (Source: authors’ illustration) *Estimated Annual Average Energy Demand 1.6 Possible Applications for Solar PV-Systems The discussions during the energy audit with owners and technicians of the hotel facilities have revealed different issues with their actual power supply. Therefore, four possible applications for solar PV-systems have been assessed and described as it follows: 8 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 1.6.1 PV-Island System PV-Island systems or so called stand-alone PV-systems are autonomous power grids that are supplied only with energy from photovoltaic source. The PV generator as the source of renewable energy is the crucial component of the stand-alone power system. It can be coupled to the grid either as DC or as AC variant. For this study, a distinction between these two types is not necessary. To supply the grid with electricity during night time or to add power to the grid in case the power of the PV-system is not sufficient, a battery is used. The capacity of the battery is crucial for covering the time without electricity. The battery or stand-alone power inverter is the important part of the AC coupled system. It ensures that generated and load power are balanced at all times. For an emergency case, a diesel generator Figure 6: PV-Island System Function [2] could be implemented as backup-system. 1.6.2 PV-Backup System The instability of the grid causes problems with computers and, in case of long grid outages, it is not possible to keep refrigerated food cooled. A PV-Backup system allows grid connected PV-systems to achieve temporary independence from the public power grid. In the event of a power outage, the backup system continues to provide electricity to the in-house grid to ensure stable power supply for office systems, cash systems, refrigerators, guest rooms and lighting. The system basically consists of a backup inverter, a PV system, and Figure 7: Backup-System by Reference to the SMA a storage battery. During normal operation, one or more solar Backup Solution [2] inverters feed electricity from the PV system into the in-house or public grid or charge the battery. The backup system will only activate in the event of a grid failure or outage. The switching mechanism will then disconnect both PV system and power consumers from the public grid in accordance with the applicable standards, while supply to the in-house grid continues from the battery. 1.6.3 PV-Diesel-Hybrid System (PV operating as Negative load) The electricity price per kWh produced with diesel generators in off-grid applications exceeds the generating costs of an optimized PV-system. To reduce the electricity production of the diesel generator, a PV-system can act as so called negative load, which means that it reduces the load of the diesel generator without the need of additional control for synchronizing the PV-system with the diesel generator. The inverters of the PV-system are directly connected to the in-house grid. The PV-system feeds in the whole produced electricity to the time of production and reduces the load of the diesel generator. 1.6.4 PV-Diesel-Hybrid System (PV operating as Main Resource) Within the PV-diesel-hybrid system the PV-system is designed to cover around 70% of the consumption, while the diesel generator covers the remaining 30%. Batteries are used to optimize the runtime of the diesel generator and to adapt the profile of the PV production to the load-profile. An additional power inverter with management functions is needed to guarantee the stable operation of the power supply system even in Figure 8: Block Diagram PV-Diesel-Hybrid System (Main Ressource) [2] 9 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR case of that only the PV-system supplies the needed energy and the diesel generator is switched off. Battery, generator, power and load management complement each other to provide a comprehensive system management. All the necessary variables are measured or calculated by the power inverter. This ensures that no switching activity or set point alteration will be left to chance. 1.7 Recommendations for Components The important parameters for choosing the right components are weather conditions and availability of trained technicians for installation and operations and maintenance. The impact can be described as follows. ■ PV modules Inhambane is a province with high average temperatures and seasons with high humidity. The long term average for global horizontal Irradiance is approx. 1,935 kWh/m² per year, which is very high. These conditions have to be considered for selecting the right quality of modules. As important as the climatic demands, it is the lack of trained technicians. Therefore the PV-systems should be designed as simple as possible. Special requirements like grounding of the negative pole should be avoided. ■ Inverters The type of the inverter depends on the principle design of the generator, for example grounding of the negative pole. To ease the planning, the decision about the use of one or three phase inverters should comply with the installed grid (230V / 400V). The choice of the inverter has to consider the climatic demands and the lack of trained technicians. It should be nearly maintenance free. ■ Cabling The irradiation in Mozambique is very high. Although solar cables are UV resistant, an additional protection is recommended in case the cables are directly exposed to sunlight. ■ Structures The structure could be built with local material or as steal construction usually used in Europe. Static calculation should be provided. All components should be resistant against salty air, because in most cases the hotel facilities are located at the coast. Further considerations are based on PV-systems built with crystalline solar modules and string inverters. 10 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 2 End Clients and Structures 2.1 PV Sizing The size of the possible PV-system depends on the consumption profile of the hotel facility and the requirements defined above. The following issues have been considered: ■ To avoid grid instability greater than 20ms the PV-system used for the scenario ‘Backup’ has to switch to off-grid operation within this time. Otherwise an additional UPS is necessary to secure computers against switching of. The power rating of computers and refrigerators/deep-freezers are calculated with 0,5kW for the scenario ‘Low consumption” and 1kW for the other ones. To secure this power rating and the recharge of the batteries, the module power is set to twice the needed power rating. The size of the battery is calculated to provide electricity for 24 hours without support of the PV-system. ■ The scenario ‘PV as negative load’ in a PV-diesel-hybrid system does not use special management devices to synchronize diesel generator and PV-system. Sizing the PV-system is aimed to insure that the load demand for the diesel generator is above the minimum possible part load named in the data sheet. For Azura the minimum load during the day is 70kW. The minimum part load of the generator is 10 % of the maximum 200kW (=20 kW). The difference of 50kW can be provided by a PV-system. This is around 25 % of the maximum generator power. For the calculations below the size of the PV-system is set to 20 % of the maximum power. The maximum power of the base scenario ‘Low consumption’ is very low. Therewith the maximum power calculated for a PV-system as ‘Negative load’ is too small for designing a valid PV-system. ■ The scenario ‘Main resource’ in a PV-diesel-hybrid system uses a special control device to optimize the use of the diesel generator and the PV-system. To avoid frequent starts and stops of the generator, batteries are needed. The calculation was made to generate around 70% of the yearly consumption using solar power and to provide battery capacity for one day. The size of the PV-system and the battery are calculated according to the recommendations of SMA[2]. For this calculation the efficiency of the system is assumed to be 75%. The yearly output of the PV-system is calculated as 1,600kWh/kWp (compare Annex A1). ■ For the scenario ‘low consumption’ as main resource, an off-grid application only with PV and batteries has been chosen. The following table shows the sizing for the different scenarios: Size PV Generator (kWp) / Battery Capacity (kWh) Backup Negative Load Main Resource Low Consumption 1kWp / 12kWh Medium Consumption 2kWp / 24kWh 14kWp / 0kWh 90kWp / 470kWh High Consumption 2kWp / 24kWh 30kWp / 0kWh 460kWp / 2,350kWh - / -1 6kWp / 30kWh Table 5: PV Generator and Battery Sizing (Source: authors’ illustration) 1 Not considered due the low system power 11 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 2.2 System Cost PV-System and Battery-Systems As outlined on page 5 the PV-system costs are 1,760EUR/kWp for calculating the capital expenditure of PV-systems (see Table 6). The capital expenditure for battery-systems varies extreme. On the one hand, the difference is caused by diverse technologies; on the other hand, the spread within one technology is also high (see Annex A4). The cost for the storing capacity of battery systems is calculated to be 730EUR/kWh. This value is used for creating Table 6. Base of the following cost calculation is the system sizing shown in Table 5. Capital Expenditure Low Consumption Medium Consumption High Consumption Backup Negative Load Main Resource PV-system 1,760EUR -2 10,560EUR Off grid control/battery 8,760EUR - 21,900EUR Total cost 10,520EUR PV-system 3,520EUR 24,640EUR 158,400EUR Off grid control/battery 17,520EUR 0EUR 343,100EUR Total cost 21,040EUR 24,640EUR 501,500EUR PV-system 3,520EUR 52,800EUR 809,600EUR Off grid control/battery 17,520EUR 0EUR 1,715,500EUR Total cost 21,040EUR 52,800EUR 2,525,100EUR 32,460EUR Table 6: Cost Overview (Source: authors’ illustration) 2.3 Payback Period of PV- and Battery-System For the cost assessment of the scenario ‘backup’ one outage of the power-supply with a duration around one day is assumed per year. The damage caused is assumed to be 500€ for a small hotel facility and 1,000€ for larger hotel facilities. For the cost assessment of the scenarios ‘negative load’ and ‘main resource’ only the additional cost for the PV-system and the battery-system was considered. The cost of the diesel generator for the conventional and the PVdiesel-hybrid systems is assumed to be equal. The payback period is calculated in comparison to the avoided fuel and maintenance cost of the diesel generator. To calculate the payback period, a price of 0.32EUR/kWh was assumed corresponding to the electricity prices of diesel generators. For the calculation of the payback period, the following parameters were considered additionally: ■ 2 100% own capital Not considered due the low system power 12 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR ■ Degradation of the PV-system 0,3% per year ■ OPEX 6.5% ■ Expected lifetime of 20 years ■ Average energy yield of the first year with 1,600kWh/kWp The results of the cost assessment are shown in Table 7: Capital Expenditure Low Consumption Medium Consumption High Consumption Backup Negative Load Main Resource Yearly profit 400EUR - 2,509EUR Payback period 26.3 a - 12.9 a Yearly profit 850EUR 6,504EUR 37,629EUR Payback period 24.8 a 3.8 a 13.3 a Yearly profit 850EUR 13,937EUR 192,324EUR Payback period 24.8 a 3.8 a 13.1 a Table 7: Overview Yearly Profit and Payback Period (Source: authors’ illustration) The calculations above illustrates that it is possible to set up PV projects regarding economic aspects. The calculation of the payback period and the yearly profit shows that it is profitable to implement PV-systems as negative load to reduce the operation cost of diesel generator. The profitability is given in a short time. Using PV-system with batteries as ‘Main Resource’ is profitable, too. The profitability is given in the medium term. The payback time for a PV-system with batteries as ‘Backup’ is very long. In the medium term it is not profitable. However, adding a backup-system to an unstable grid can reduce outages of electrical devices, like computers. In addition, it can enhance the lifetime of electrical devices by reducing voltage peaks. In grid connected hotels a PV-system can stabilize the internal hotel grid (load curve fits well to production curve of solar PV). In off-grid applications, the time of electricity availability can be increased. Therefore, it is possible that the decision of a hotel manager will not be driven only by economic aspects. 13 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 3 Conclusions and Recommendations 3.1 General Conclusions In Mozambique the main precondition for the use of PV-systems, a high irradiation, is fulfilled. The solar irradiation is very high, especially from October to March, which is the main season for tourism in Mozambique. This gives reason to predict a lot of possibilities for setting up profitable PV projects in the tourism sector. However photovoltaic is only one solution among many to provide energy to people in Mozambique. Because of this competition among the different energetic sources, PV has to compete against conventional systems in order to win a position in the market. An active promotion of PV as energetic technology (for example with a feed-in tariff system) would change that situation but is not in place yet. In order to promote PV directly, the following policy could be implemented: ■ No duty should be levied for imported components. This would be very helpful for financing PV projects, in particular because the main components come from abroad. Concerning the financial aspect, the general conditions for the financing PV projects with local banks support are difficult, in particular for these main reasons: ■ The interest rates claimed by local banks are very high. ■ The repayment term does not fit to the usual lifetimes for PV-systems of 20 years Therefore, it is necessary to find financing solutions independent from banks in Mozambique. Moreover, it should be considered that most new projects in the tourism sector cannot be connected to the grid; therefore an own power supply is needed (mainly it is used diesel generator). For such cases different applications of PV are possible: ■ The use of PV is mostly profitable for applications that do not need a secured power supply for the entire day. This could be the case for example of a power supply of water pumps, for water supply or pool pumps. ■ Especially for hotel facilities using air conditioning systems, a PV-system can take over a part of the load of the diesel generator. In that case it acts as negative load, reducing both the use and the cost of the diesel generator. ■ With an expected price decrease for battery systems in the next few years, it is expected that the PV-system will become the most used energetic resource for off-grid solutions. In this new scenario, the diesel generator will be used only as backup system. It should be noted that only a few trained people are located in Mozambique, mainly in Maputo. Therefore, the PVsystems should be easy to maintain and it is recommended necessary training for people to maintain the systems. The training is also useful for developing measures for rural electrification, which is a stated target of the government. Considering economic aspects, it is possible to implement PV-systems into the power production for off-grid solutions. At the moment, a profitable solution is represented by the combination of PV-system and diesel generator. In this combination the PV-system acts as negative load reducing the use and cost of the diesel generator. With an expected price decrease for battery systems in the next few years, it is expected that the PVsystem will become the most used energetic resource for off-grid solutions. In this new scenario, the diesel generator will be used only as backup system. However, it has to be taken into account that a hotel normally has a very low interest in the production of electricity. In such cases the focus is very much on the service to their guests. Thus, energy contracting could be the best solution for implementing PV in the energy supply of hotels in Mozambique. 14 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 3.2 Recommendations for the Examined Hotel Facilities According the findings above, the installation of a PV-system as negative load is a good option for Massinga and Azura. In Azura the rooftop of the laundry and the staff canteen can be used to install approx. 20kWp for the first step. The place is close to the main junction box that will reduce cable losses. For Travessia the installation of a PV-system with battery is meaningful. The size of the PV-system is designed for a system as main resource. Casa Rex is connected to the grid. Using PV as negative load only is not seen as advisable. Casa Rex often suffers from grid failures. Because of that, it can make sense to implement a PV-system with battery as backup system. The energy of the PV-system not used for the backup function can be used to reduce the energy purchased from the grid. Table 8 shows the key figures for the hotel facilities examined, including energy values and recommendations for sizing possible PV-systems. Island System Grid Connected System A1) PV/Battery System A2) PV/Hybrid System B1)Self Consumption B2) Back up System Gen-Set only as back up Gen-Set 3-4 hours per day Negative load Back up function Travessia Beach Camp Massinga Beach Camp Azura at Casa Rex Benguerra Island Off Grid, conn. Expensive Off Grid, expensive Off Grid Off Grid, conn. expensive 17- 20 kWh/day 400 kWh/day 1800 – 2500 kWh/day 300- 500 kWh/day 4 kW peak load 72 kW peak load 150 kW peak load 50 kW peak load 7 kWp 15 kWp 20 kWp 2 kWp Battery: 48 kWh 24kWh 0 kWh 24 kWh CAPEX: 25 tEUR 44 tEUR 35 tEUR 21 tEUR PV: Table 8: Key figures for the Locations Evaluated (Source: authors’ illustration) 15 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR References [1] BHKW-Kenndaten 2011, ASUE Arbeitsgemeinschaft für sparsamen und umweltfreundlichen Energieverbrauch e.V., 2011 [2] Installation - Quick Reference Guide Off-Grid Systems Off-Grid Systems with Sunny Island 6.0H / 8.0H, SMA Solar Technology AG, http://files.sma.de/dl/17632/Off-Grid-IAS-en-21W.pdf [3] IRENA Report Mozambique Renewables Readiness Assessment 2012, 2012 [4] Kurzexpertise Wirtschaftlichkeit Batteriespeicher; Christian Lorenz&Gerd Schröder Leipziger Institut für Energie GmbH, 01/2014 [5] Marktreport Mosambik 2013, Guido Radel, Julia Becker, Dominik Baranowski, 2013, AHK Portugal [6] Statistische Zahlen der deutschen Solarstrombranche (Photovoltaik) 02/2014, Bundesverband Solarwirtschaft e.V. (BSW-Solar), April 2014 [7] Statistische Zahlen der deutschen Solarstrombranche (Photovoltaik), Bundesverband Solarwirtschaft e.V. (BSW-Solar), 04/2014 [8] TechnologyCompendium 2 Solar Stand-Alone Power and Backup Power Supply, SMA Solar Technology AG (http://files.sma.de/dl/10040/INSELVERSOR-AEN101410.pdf#sthash.e6Awez2g.dpuf) 04/2010 [9] TKN Report - Investment Incentives for Renewable Energy in Southern Africa: The case of Mozambique; Boaventura Chongo Cuamba, Amílcar dos Santos Cipriano Ruth Henrique Jaime Turatsinze; January 2013; Maputo, Mozambique [10] ZIELMARKTANALYSE MOSAMBIK, Deutsche Industrie- und Handelskammer für das Südliche Afrika, 2014 [11] http://www.edm.co.mz/, © 2014 EDM - Electricidade de Moçambique, E.P, 6/2014 [12] MyTravelCost May/2014; http://www.mytravelcost.com/Mozambique/gas-prices/ [13] GlobalPetrolPrices.com May/2014; http://www.globalpetrolprices.com/Mozambique/diesel_prices/ [14] Compare http://mittronik.com/start/dieselgenerator.php, 06/2014, Copyright © 2002-2013 by MITTRONIK and http://www.elmag.at/index.htm?/produkte/10/stromerzeuger_dauerlaeufer.htm, 6/2014, ELMAG Entwicklungs- und Handels-GmbH [15] http://www.bancomoc.mz/Files/DEE/February%202014.pdf [16] http://www.theglobaleconomy.com/Mozambique/Lending_interest_rate/, TheGlobalEconomy.com, 06/2014 [17] Sources: SolarGIS v1.8 of GeoModel Solar s.r.o. using Meteosat IODC Satellit (© EUMETSAT, Deutschland) 1999 – 2011 and meteonorm 7 of Meteotest Genossenschaft using Global Energy Balance Archive 1981 – 1990. 16 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR Annex 17 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A1. PVSyst Simulation for Calculating the Specific Yield 18 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 19 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR 20 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A2. Assumptions Cost of PV-systems In Mozambique, the actual prices for the main components of a PV-system up to 30kWp without freight costs are 0.75EUR/Wp for PV panels and 0.32EUR/Wp for inverters. PV panels and inverters amount to around 70% of the total system costs. The freight costs can be assumed with around 15%. With this, the total costs per kWp are 1,760EUR. 21 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A3. OPEX of PV-systems Cost Unit Annual estimated cost in percentage of the annual turnover exposure Maximum annual estimated cost Minimum annual estimated cost Average estimated cost Losses through operational current, shutdown, energy meter and others 1-2% 2.0% 1.0% 1.5% Insurance 1-2% 2.0% 1.0% 1.5% Operation Management & Maintenance 1-6% 6.0% 1.0% 3.5% 10.0% 3.0% 6.5% Total Table 9: OPEX of PV-Systems (Source: authors’ illustration) 22 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A4. Cost Storing Capacity of Battery Systems To guess costs for battery systems (battery and controller) table 1 of “Kurzexpertise Wirtschaftlichkeit Batteriespeicher”[4] is used as base for creating the overview in Table 10. The “Storage Capacity net” used for calculating the total costs is the usable capacity, which differs from that on the nameplate. For example, the usable storage capacity of a lead-acid battery with a nameplate capacity of 10kWh is around 5kWh only. Nedap Deutsche Energy EnergieverSystems sorgung SMA Prosol Invest E3/DC Bosch Voltwerk Kostal Solar Electric IBC Solar IBC Solar Lead-acid Lead-acid Leadacid Lithium Lithium Lithium Lead-acid Leadacid Lithium kWh 7.4 16 7.4 10.2 5.4 11 11.6 8 6.3 kWh 3.7 8 3.7 7.1 4.1 6.6 5.8 4 5.7 EUR 7,800 7,990 8,900 15,300 12,000 28,500 12,000 8,500 11,300 EUR 800 500 500 800 550 500 400 400 400 EUR 2,324 1,061 2,541 2,268 3,061 4,394 2,138 2,225 2,053 Technology Storage Capacity Nameplate Storage Capacity net End Client Price Installation Costs Total Costs per kWh Table 10: Cost of Battery Systems According [4] The spread of the given cost per capacity unit is huge. For Mozambique it can be assumed, that lead-acid batteries will be used due to the investment cost. Therefore, the following considerations are for lead-acid batteries. A validation of the costs for systems with lead-acid batteries given in Table 10 reveals an average cost reduction around 10% until now. Generally, one can assume a cost decrease with the size of the battery capacity due the fact one control-unit can handle a greater amount of battery capacity as used for creating Table 10. For the named systems the share of the controller is around 50% of the total cost. We assume that the decrease for systems with a storage capacity net 12kWh and above is around 60%. With this, the average cost for the storage capacity net of systems with lead-acid batteries is around 730EUR/kWh. 23 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A5. Cost of Diesel Generators per kWh The following table gives an overview about the cost for diesel generators. kV A Motor Hersteller Typ Verbr. 75% Preis EUR Preis spezifisch EUR/kVA Lebensdauer h Invest EUR/h Invest EUR/kWh 4.5 Yanmar L100N 1.9 4,478.02 995.12 5000 0.199 0.044 5 Yanmar L100N 1.9 4,653.00 930.60 5000 0.186 0.037 MP73DE 6 Kubota Z482 2.4 6,385.00 1064.17 5000 0.213 0.035 MP83TDE 7 Kubota Z482 2.4 6,539.00 934.14 5000 0.187 0.027 MP103DE 9 Kubota D722 3.1 6,858.01 762.00 5000 0.152 0.017 MP113TDE 10 Kubota D722 3.1 6,592.01 659.20 5000 0.132 0.013 MP123DE 11 Kubota D902 3.5 7,569.00 688.09 5000 0.138 0.013 MP133TDE 12 Kubota D902 3.5 7,598.00 633.17 5000 0.127 0.011 14.4 Kubota D1105 4.5 8,452.00 586.94 5000 0.117 0.008 17 Kubota D1105 4.5 8,240.00 484.71 5000 0.097 0.006 MP193DE 17.1 Kubota V1505 6.5 10,135.99 592.75 5000 0.119 0.007 MP243TDE 23 Kubota V1505 6.5 9,794.00 425.83 5000 0.085 0.004 MPG6000DE MPG6000TD E MP163DE MP183TDE Table 11: Overview Cost of Diesel Generator (Source: authors’ illustration) Figure 9 shows the distribution of the invest for a diesel generator per produced energ unit. The average is 0.018EUR/kWh. Figure 9: Distribution about the Cost per Unit Produced Electricity (Source: authors’ illustration) 24 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A6. Pay Back Period The payback period for off grid systems is basically influenced by the cost of electricity caused by the use of the diesel generator. For this assessment it was assumed a fixed price per unit of electricity (EUR/kWh). The following Table 12 shows the results using 0.32EUR/kWh without price increase. The interest rate considered the possibility to get loans outside Mozambique. The calculation considered the use of 100% debt capital. Energy Yield [kWh/kWp] Interest Rate Degradation [%] Running Costs [%] Running Time [a] Backup Low Consumption Negative load Main Resource Backup Medium Consumption Negative load Main Resource Backup High Consumption Negative load Main Resource 1,600 0.0% 0.3% 6.5% 20 Invest [€] 10,520 32,460 21,040 24,640 501,500 21,040 52,800 2,525,100 PV Production per Year Used Share PV Production Salary PV Savings Costs Yearly Profit Payback Period [kWh] 1,553 9,316 3,105 21,737 139,738 3,105 46,579 714,216 [%] [€/kWh] 0.32 0.32 0.32 0.32 0.32 0.32 0.32 0.32 [€] 500 2,683 1,000 6,956 40,245 1,000 14,905 205,694 [€] 100 174 150 452 2,616 150 969 13,370 [€] 400 2,509 850 6,504 37,629 850 13,937 192,324 [a] 26.3 12.9 24.8 3.8 13.3 24.8 3.8 13.1 90% 100% 90% 100% 90% Table 12: Payback Period with Unit Cost of 0.32EUR/kWh (Source: authors’ illustration) Azura negotiate a contract all cost (investment, operation, full cost etc.) are included into the price of the energy unit with 0.25EUR/kWh. Table 13 shows the payback period considering this contract. Energy Yield [kWh/kWp] Interest Rate Degradation [%] Running Costs [%] Running Time [a] Backup Low Consumption Negative Load Main Resource Backup Medium Consumption Negative Load Main Resource Backup High Consumption Negative Load Main Resource 1,600 0.0% 0.3% 6.5% 20 Invest [€] 10,520 32,460 21,040 24,640 501,500 21,040 52,800 2,525,100 PV Production per Year Used Share PV Production Salary PV Savings Costs Yearly Profit Payback Period [kWh] 1,553 9,316 3,105 21,737 139,738 3,105 46,579 714,216 [%] [€/kWh] 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 [€] 500 2,096 1,000 5,434 31,441 1,000 11,645 160,699 [€] 100 136 150 353 2,044 150 757 10,445 [€] 400 1,960 850 5,081 29,397 850 10,888 150,253 [a] 26.3 16.6 24.8 4.8 17.1 24.8 4.8 16.8 90% 100% 90% 100% 90% Table 13: Payback Period with Unit Cost of 0.25EUR/kWh for Azura (Source: authors’ illustration) 25 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A7. Load Profile Azura Figure 10: Measurement Results of Power and Power Factor in Azura (Source: authors’ illustration) Figure 11: Load Profile Azura (Source: authors’ illustration) 26 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A8. Interest Rates Mozambique The average interest rate of Mozambique from 2009 to 2012 was 20.2% (Figure 12). According the Monthly Bulletin of the Banco de Moçambique [15] the actual interest rate for loans is 19.81%. Figure 12: Mozambique Lending Interest Rate (Percent, Source: The World Bank)[16] 27 QUALITATIVE PHOTOVOLTAIC POWER SUPPLY FOR THE MOZAMBICAN TOURISM SECTOR A9. Fact Sheets 28 Renewable Energy Project Development Programme (PDP) Mozambique Photovoltaic Power Supply for the Mozambican Tourism Sector Fact Sheet: Travessia Beach Camp Background Region about 60 km north of Inhambane town. In Mozambique, approximately 13 % of the country Coming from Inhambane 20 km before Massinga, is connected to the grid. In the other regions, diesel a dusty road of 6 km length leads to the lodge. No generators are usually used for power supply. The grid access is available or scheduled. fuel has high costs; therefore the electricity prices Concept are also high. These regions are of huge interest for Tourism for families, couples & individuals aim to the tourism sector, due to its amazing landscape enjoy and places for diving. Therefore several hotels surroundings. A place for people who enjoy facilities have been developed. However, the understated barefoot luxury in Eco Tourism style. distance to the public grid is a challenge for the Travessia Lodge is a completely new constructed hotels. Lodge. The owners aim to follow a very committed To gather information about the local situation, an approach to provide eco-tourism powered by energy audit has been performed at three different renewable energies. sites. On the basis of this information, possible Buildings & Infrastructure solutions for the power supply were elaborated - 4 ‘Family Cottages’ with 3 rooms each for up to 4 using photovoltaics as additional power source. exclusive time in completely natural persons This fact sheet shows the details of Travessia. - 2 ‘Couple Cottages’, with 2 rooms for 2 persons Location - Pool bar, restaurant, kitchen, laundry, staff Travessia Beach Camp3 is located in Inhambane quarter, manager house - Power house & PV area is best located for actual 3 https://www.facebook.com/TravessiaLodge?fref=ts 5 wire cable will allow for switch off walk way lights planning and for a scheduled extension. Electrical equipment in 3 steps. - Lamps, assumed 4 pcs per Room + Improved operation - Walk way light, around 100 pcs a 3 Watt, 3 - 6 h Make production and consumption visible due to per night kWh-meters and set up a long distance monitoring - Wall socket for charging of cell phone, laptop and for control by experts. camera - Fan, 1 per rooms - 3 refrigerators, 2 deep freezer for bar and kitchen - No air conditioning - Water heating with solar water heater Figure 3: Monitoring display (Source: Discovergy.com) Power Supply System (planning figures) + Set up an energy policy! Consumption estimation 17 – 20kWh/24h Assign responsibilities follow up by record keeping. Reaching targeted goals will be beneficiary for the person in charge and the whole staff. Operating deep freezer and refrigerators properly can help to increase solar energy consumption and reduce night time load. Electrification Concept using PV The owner of Travessia reserved an area for the installation of approximately 7kWp PV-system Figure 1: Load Distribution (Source: authors’ illustration) Electrification Concept Precondition of the power supply with a combination of PV and battery is an energy efficiency approach. Figure 2: PV Area Travessia (Source: authors’ illustration) Energy efficiency approach close to the power house. The electricity supply of + Use only most energy efficient equipment the pump for the pool at the bar is realized with (LED of best quality, Cold Chain in A+++, etc.) two solar panels at the rooftop of the bar. Normally + Optimized electrical infrastructure these panels are invisible for the guests. Also the Cable sizing and cable layout has a considerable water pumps currently have an own power supply impact on the annual consumption. It can help with PV panels. reducing cable losses and allowing an intelligent The supply with electricity will be done with a control of electrical consumers. For instance a combination of PV and batteries systems. The batteries are sized to cover consumption up to 3 days without sun light. As backup system an existing diesel generator is used. Pool and water pumps stay independent. Cost estimation for Power Supply System Off Grid Island System, with Generator back up Rooms, accommodation capacity 8 Cottages Consumption per 24 h (estimate) 17 KWh PV Power 7 KWp Battery Bank capacity 48 KWh Estimate Total System Cost 22,000 EUR Extension, add. 8- 10 houses, scheduled next 2-3 years Figure 4: Possible PV-system solution (Source: authors’ illustration) Renewable Energy Project Development Programme (PDP) Mozambique Photovoltaic Power Supply for the Mozambican Tourism Sector Fact Sheet: Massinga Beach Lodge paved road from Maputo to Massinga town. Background In Mozambique, around 13 % of the country is connected to the grid. In the other regions diesel generator are usually used for power supply. The fuel has high costs; therefore the electricity prices The last 10 km are sandy and suitable for 4x4 vehicles only. Power supply, demand & distribution - 32 Villas, all with air condition & fridge - Pool belonging to the villas are without pool are also high. These regions are of huge interest for the tourism, due to their amazing landscape and pump - places for diving. For this reason, several hotels have been built on the area. However, the distance to the public grid is a challenge for these hotels. turn-on time 10 – 12 h/day until 10:00 PM - Distance to the grid around 12km - Grid connection scheduled because of To gather information about the local situation, an construction of holiday cottages behind the energy audit has been done at three different sites. On the basis of this information, possible solutions villas - for the power supply were elaborate using photovoltaic energetic source. This fact sheet shows the details of Massinga Beach Lodge. Location Massinga Beach Lodge is accessible by flights to Inhambane. The lodge provides airport transfers. However, also self-drive is allowed through a good Local mini Grid by own 72 kW diesel generator; Warm water supply by gas separate for each villa - Energy saving lamps for lightning villas and ways - Possible PV-system Solution can be backup or an independent system. Business Model “Holiday Home” for sale Consumption & distribution estimated 400kWh / 24h Holiday Homes A Villa type beach house in guarded compound is a newly upcoming business model. Turn-key construction mostly with gen set back up system. Business Opportunity Contact construction companies to include renewable energies for back & self of selected circuits. Alongside with the introduction of solar thermal, a new market will be developed. Best practice solutions need to be developed. Figure 1: Load Distribution (Source: authors’ illustration) Demand and distribution depend very much on the occupancy rate. The estimations are done considering 100 % occupancy. A turn-on time for the generator of 10-12h is assumed. It is estimated that after grid connection the consumption will grow und will be above 1000kWh /24 h. Figure 2: Floor Plan of a House for Sale as Holiday House (Source: authors’ illustration) Electrification Concept Massinga Beach Lodge provides itself with self-consumption of photovoltaic. It can electricity by running an own diesel generator only estimated until the end of 2014. To save cost, the turn-on install up to 10 % time of the generator is restricted. of the maximum At the moment, the connection to the grid with generator power Off Grid Grid Connection scheduled estimated of PV to reduce 400kWh/day cost of 250.000 EUR is under to PV/Hybrid System Gen-Set 3-4 hours per day 70kW peak load construction: it has been necessary since several fuel cost. private holiday cottages are planned to be realized. The back-up is PV 15kWp Massinga rather Battery 12kWh Cost estim. 46 t€* Beach Lodge will build the grid connection at its own charge. The operation will be interesting be for Figure 3: Possible PV-System Solution (Source: authors’s illustration) *Rough cost estimate intern. procurement, excl. transport done by the national grid operator, after signing the lodge owner over the property rights. Because of this, Massinga as soon the lodge Beach Lodge in the future will only pay the normal is connected to tariffs or electricity. the grid. It secures against blackouts of the grid Electrification Concept using PV accompanied by the use of the diesel generator. Massinga Beach Lodge has a huge potential for Renewable Energy Project Development Programme (PDP) Mozambique Photovoltaic Power Supply for the Mozambican Tourism Sector Fact Sheet: Azura at Gabriels, Benguerra Island Background town and location of the international airport. In Mozambique, around 13 % of the country is For the transfer of the guests between the airport connected to the grid. In the other regions, diesel and Benguerra Island, a state of the art helicopter generators are usually used for power supply. The is used. fuel has high costs; therefore the electricity price is Power supply, demand & distribution also high. These regions are of huge interest for the Following the key facts of the hotel facilities: tourism due to its amazing landscape and places - for diving. For this reason, several hotels have been 16 Villas, all with air condition, swimming pool & fridge built on the area. However, the distance to the - Cold room and freezer room for the restaurant public grid is a challenge for these hotels. - Mini Grid, 200kVA Generator for 24/7 To gather information about the local situation, an - Power supply contracted with ELGAS energy audit has been done at three different sites. Maputo; ELGAS supplies electrical power via On the basis of this information, possible solutions generator operated with natural gas for the power supply were elaborate using - Gas supply via gas pipeline from main land photovoltaic energetic source. - ELGAS owns services and maintains the generator; Payment up on consumed kWh This fact sheet shows the details of Azura at - Use of diesel generator during breakdown of Gabriels, Benguerra Island. the gas generator; Azura has to provide and to Location pay the fuel Azura is located on Benguerra Island, within the - Possible PV-system Solution: Back-up Bazaruto Marine National Park. Benguerra Island &“negative load” solution for reduction of lies 14 km north east of Vilanculos, the nearest electricity cost from mini grid Consumption & distribution estimated up to 2,100kWh / 24h freezer room. Energy-saving PV measures are estimated to be up to 10 % replacement of the maximum generator power (see figure below). With an optimized operation and an additional control, it is assumed to substitute up to 30 % of the energy production with PV power. The backup is rather interesting for the lodge owner as he is interested to have backup power during black outs, especially for the ‘Presidential Villa’ (mainly for upper-class guests). Black outs may occur because of problems with the gas supply or technical problems with the gas generator. Grid Connected System PV in Net-metering, Negative Load Incl. Back up function Figure 1: Load Distribution (Source: authors’ illustration) 2,100kWh/day Demand and distribution depend very much on the occupancy rate. The estimations are 150kW peak load done considering 100 % occupancy. Electrification Concepts using PV The contract for the lodge is free of capex costs that PV 20kWp Battery 12kWh Cost estim. 46 t€* are included into the purchase price. The price for Figure 3: Possible PV-System Solution authors’s illustration) electricity of 0.34 US Dollar per kWh is reasonable *Rough cost estimate intern. procurement, excl. transport to be considered for investment decisions for a PV- (Source: system. Azura has a huge potential for self-consumption of Alternative: PV by the contractor photovoltaic power, due to the cold room and the Since there are 3 lodges on the Island, the natural gas supplying pipeline from the main land became a profitable viable. However, power supply by generator 24 / 7 is a challenge material demanding approach. Thus even ELGAS as owner & operator of the power supply unit could be interested to complement photovoltaic energy. Figure 2: Load Curve Azura 22. / 23. March 2014 (Source: authors’ illustration) the system with