T R 8 0 0 We b
• 8 Measuring inputs for
temperature or standard
signals
• Logging of data
• 4 x 8 alarms
• sends email on alarm
• Interface RS485 and
Ethernet
• NEW: supports IEC 61850
(GOOSE)
TR800Web Web-IO Universal-Relay with 8 inputs
for Temperature-Sensors and other
signals
MU2000K
for monitoring and logging of analog signals and
operating and quering with browser over TCP/IP
• 8 measuring inputs Pt 100/1000 (RTD), thermocouple and DC 0-10 V, 0/4-20 mA
• 4 alarms/relays, each with 1 limit per input
• NEW: supports IEC 61850 (GOOSE)
• in Browser via internet/intranet:
- Configuration and display of values
- Alarms with email
• Logging of up to 150.000 values per measu ring input. Volume unlimited with ftp-upload
• AJAX for data-readout in html
• Interface RS 485 (MODBUS)
RCM1000V
Residual Current Monitor for detection of insulation faults
in grounded power supply systems. Recognizes
insulation faults before a damage occurs.
• Monitoring of residual currents
• 2 limits warning and alarm
• Monitoring of 2 x over- or undercurrent or
windows
• Input for current transformer STWA3D with monitoring of transformer
• Measuring range AC 0,010…9,999 A, display can be scaled
• 4 digits bright LED-display for measured values
and programming
• LEDs for alarms, states of relays and units
• Limit, hysteresis, switching delay and switch off delay individually programmable
• Universal supply voltage AC/DC 24-240 V
Universal-Measuring-Transducer for
AC and DC, Voltage and Current
for measuring of currents e.g. at plants for own generation of electricity
• Measuring input voltage AC/DC 600 V
(pre-set 60/150/300/600 V)
• Measuring input current AC/DC 5A
(pre-set 1/5 A)
•Zero and full scale for other ranges can be
scaled by the user easily with 2 buttons
• Outputs DC 0/4-20 mA, 0/2-10 V
• Insulation between input, output and
supply voltage
• Universal power supply AC/DC 24-240 V
COSFI100V
Current-Monitor for increasing of own
consuption in plants for own generation of electricity
by switching on or off of loads, depending on
available power
• Direction sensitive measuring of AC-current
• Measuring of direction of energy flow and
prevents from feeding in energy
• Digital display (scalable when transformer is used)
• 2 independent limits / relays with function min-, max- or window
• Hysteresis and switching delay programmable
• Monitoring of cosφ for protection from overload
• Universal supply voltage AC/DC 24-240 V
Monitoring of Voltage and
Frequency for Grid- and Plant Protection according to VDE-AR-N 4105
for applications at plants for own generation of
electricity
• Protection from under- and overvoltage
• Protection from under- and overfrequency
• Monitoring of 10-minutes-average
• One-fault-proof
• Preset according to VDE-AR-N 4105 and bdew
- Certificates G59/3 and G83/2 für Great Britain
- Certificate ÖNORM for Austria
- Certificate DIN V VDE 0126-1-1,
VFR2013/VFR2014
- Sealing of settings
- Application in medium voltage grids
- Monitoring of vector-shift and ROCOF possible
SW32V
Voltage-Monitor for DC, AC and
3-phase voltages
MSR220KA/
MSR220VA
SIL
IEC 61508
MU1001K
for monitoring of over- and/or undervoltage
• Direct voltage DC 10…600 V
• Alternating voltage AC 20…480 V
• 3-Phase voltage with/without neutral 3AC 35…830 V
• preset values for grid- and plant protection acc. to BDEW standard
• 2 alarms / relays
• Monitoring of over- and/or undervoltage with every alarm
• Monitoring of asymmetry and phase-se-
quence can be selected
• Measuring of True-RMS
• short response times down to 50 ms
• variable relay-functions
• Universal power supply AC/DC 24…240 V
• Housing for DIN-rail-mount, 70 mm wide, mounting height 55 mm
MINIPAN352P
Measuring Instrument for Current,
Voltage, Temperature and Resistance, 2 Limits, 4-Digits, 72x72mm
• Measuring inputs DC and AC (TrueRMS)
300 mV, 1 A, 5 A, 500 V, 10 V, 20 mA
• Measuring Inputs temperature
Pt 100 (RTD), Pt 1000, KTY, 2/3-wire
Thermocouples B, E, J, K, L, N, R, S, T
• Resistance 500 Ohm/30 kOhm
• Easy programming with 3 buttons
• EasyLimit for easy setting of limits
• Storing of MIN and MAX- values
• Supply-voltage for external measuring transducer
• Code-lock against manipulation of set-
tings
• Universal supply AC/DC 24-240 V
• Option: output 4-20 mA (potential free)
PTC-Relay with ATEX-approval acc. to
RL 94/9/EG, SIL 1 (IEC 61508), PL c (ISO
13849)
For application as protection against inadmissible
heating up in areas with explosive gas (zones 1
and 2) or dust (zones 21 and 22)
• ATEX-approval acc. to directive RL 94/9/EG
• SIL 1 (IEC 61508), PL c
• Ex II G [Ex e] [Ex d] [Ex px], Ex II D [Ex t] [Ex p]
• 1 PTC-circuit, 1-6 PTC, monitoring of short-
circuit
• MSR-types with electronic reclosing lock
• MS220KA for DIN-rail mount, 22,5 mm wide
• MS220VA for fuse-box mount, 35 mm wide
• MS(R)220KA: UL recognized component
Universal-Measuring-Transducer for
DC Voltage and Current
for measuring currents e.g. charging and discharging at batteries, and voltages up to DC300V
• Current DC ± 0-300 mV
(pre-set 60/150/300 mV, ±60/150/300 mV). Measuring with external Shunt
• Voltage DC 0-10V, ±10V
• Voltage DC 0-300 V
(pre-set 20/50/100/200/300 V)
• Outputs DC 0/4-20 mA, 0/2-10 V
• Insulation between inputs, outputs and
supply voltage
• Universal power supply AC/DC 24-240 V
MSF220VL
PTC-Resistor-Relay for
Dry-Transformers, Fan, Warning,
Trip Winding and Trip Core
for monitoring of dry transformers, integrated
monitoring of temperature of core
• 4 inputs for PTC
• 4 output-relays
• Programs for diferent applications
• Intelligent control of fan
• Automatic fan-test 1x/week
• Monitoring of sensors
• No tripping-signal when switching on
• Test-button
• LEDs for alarms, states of relays and sensors
• Universal power supply AC/DC 24…240 V
M easur i ng, Co n t r o l l i n g , M o n i to rin g o n h ig h e s t le v e l
ZIEHL industrie-elektronik GmbH + Co KG
Daimlerstr. 13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, e-mail: info@ziehl.de, www.ziehl.de
Edition November 2014
UFR1001E