045_09 2116.23 1.3A_Shaft Wall Assembly Product Data_A

Transcription

045_09 2116.23 1.3A_Shaft Wall Assembly Product Data_A
Submittal Transmittal
Detailed, Grouped by Each Number
KSU Foundation 1800 Kimball Office Building
Project # 26
Tel: 719.473.5321
1800 Kimball
Manhattan, KS 66502
Date:
3/2/2015
Transmitted To:
GE Johnson Hutton A Joint Venture
Fax: 719.473.5324
Mark Pfeil
Hoefer Wysocki Architecture, LLC
11460 Tomahawk Creek Parkway, Suite
400
Leawood, KS 66211
Tel: 913.307.3700
Description
Due Date
002
Shaft Wall Assembly Submittal Package
3/16/2015
Transmitted For
Delivered Via
Action
Email
Qty
Dan Martin
GE Johnson Hutton A Joint Venture
Transmitted By:
Qty
Items
Package Action
Tracking Number
Type
Specification #
Description
0001
09 21 16.23-1.3A-0
Gyp Board Shaft Wall Assemblies Product Data
Product Data
0002
09 21 16.23-1.4A-0
Gyp Board Shaft Wall Assemblies Evaluation Reports
Quality
Control
Reports
Notes
Notes
Cc:
0101
Submittal Number:
Company Name
Contact Name
Copies
Item Action
Notes
X
Remarks
092116.23-01
3/5/15
EKR
Signature
Prolog Manager
Printed on: 3/2/2015
Prolog
Signed Date
Page 1
Reviewed for general conformance with the
contract requirements and with other crafts.
Approved for submittal to the architects subject to architects and engineers approval.
DRYWALL SYSTEMS, INC.
3919 S. WEST STREET, WICHITA, KS 67217
Phone: (316) 942-4994 Fax: (316) 942-4995
045_09 2116.23 1.3A_Shaft Wall
Assembly Product Data_FA
G.E. JOHNSON CONSTRUCTION CO.
No.
RE:
Signed by:
Date: 03/02/2015
LETTER OF TRANSMITTAL
To:
Date: 2/9/2015
GE Johnson
25 N. Cascade Ave, Suite 400
Colorado Springs, CO 80903
Project:
1800 Kimball
Manhattan, KS
Attn: Dan Martin
Phone: (719) 473-5321
Fax: (785) 375-4090
WE ARE SENDING:
 Shop Drawings
 Letter
 Prints
 Change Order
 Plans
 Samples
✔ Specifications

 Other: Made from Submittal
Copies
1
SUBMITTED FOR:
✔ Approval

 Your Use
 As Requested
 Review and Comment
SENT VIA:
✔ Attached
 Separate Cover Via: Mail
Specification Section
092116.23
ACTION TAKEN:
 Approved as Submitted
 Approved as Noted
 Returned After Loan
 Resubmit
 Submit
 Returned
 Returned for Corrections
Description
Type
1.3A Product Data
Gyp Bd Shaft Wall Assemblies
Remarks:
We will just use the J-Tabbed Track for the “J-Profile Jamb Strut”.
Prepared By: Tim Rogers
Phone: (785) 320-4181
E-mail: tim.rogers@drywallsystemsks.com
Copies To:
Product Submittal Sheet
Tech Support: 888-437-3244
Engineering Services: 877-832-3206
4” 20ga ClarkDietrich Shaftwall System
Sales: 800-543-7140
clarkdietrich.com
09.22.16 (Non-Structural Metal Framing)
CT Shaftwall System
ClarkDietrich CT Cavity Shaftwall System
ClarkDietrich CT Cavity Shaftwall Studs are high-performance members
engineered to maintain shaftwall integrity. CT Studs are designed for use with
1" thick gypsum 24” wide liner panels. Gypsum liner panels are inserted into
the “T” portion of the stud and are friction fit. The system is finished with fire
rated gypsum board to complete and achieve the designated fire rating.
ClarkDietrich J-Tabbed Track is used at the floor and ceiling in shaftwall
assemblies. CT studs and gypsum shaftliner panels are friction fit between the
top and bottom J-Tabbed Track. J-Tabbed Tracks have unequal legs. The
longer leg (available in 2-1/4" and 3") is installed on the shaft side providing a
backstop for easy installation of the liner panel. Three-inch leg track is typically
used as jamb struts around closure details, including duct and door openings,
abutments and intersections.
CT Stud
Product Material Thickness:
Member
Minimum Thickness
(mils)
gauge
Design Thickness
(in.)
(in.)
CT Stud and
J-Tabbed Track /
33
20
0.0329
J-Runner
All material is produced with a coating of: G40 (G60 Available)
0.0346
CT Stud Structural Properties:
Member
Product
code
Weight
(lb / ft)
Area
2
(in )
Ix
4
(in )
Sx
3
(in )
Pcs./Skids
4" CT Stud
20ga (33mils)
CTN4
0.974
0.298
0.710
0.309
160
J-Tabbed Track / J-Runner
ASTM & Code Standards:
•
•
•
•
Shaftwall products are produced to meet or exceed ASTM C645 and A1003
UL Design No. U417, U428, U429, U497, U498, V455 and V473
PEI Assembly Evaluation Report AER-12061
MSDS & Product Certification Information available at www.clarkdietrich.com
Limiting Heights:
Deflection
Design Pressure (psf)
5
7.5
10
15
23'-0"
20'-12"
18'-7"
15'-5"**
L/240
18'-7"
15'-10"
14'-1"
12'-1"
L/360
15'-10"
13'-6"
12'-1"
10'-4"
L/120
See heights & installation notes in PEI AER-12061 report or on www.clarkdietrich.com/shaftwall
GREEN Benefits and Recycled Content:
LEED Credit MR 2 - ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
LEED Credit MR 4 - ClarkDietrich's steel products have a minimum recycled content of 34.9%, of which 24.3% is post-consumer, and 9.4% is
pre-consumer. To report a higher number for your project or seek Credit MR 5, contact Technical Services at 888-437-3244 or visit
www.clarkdietrich.com.
CD-CT400-20 © 09/14 ClarkDietrich Building Systems
Project Information
Contractor Information
Architect Information
Name:
KSU FOUNDATIONS - SUBMITTALS
Address:
KANSAS CITY MO
Name:
DRYWALL SYSTEMS, INC.
Contact: 20150204
Phone:
Fax:
Name:
Contact:
Phone:
Fax:
09 29 00
GOLD BOND® brand FIRE-SHIELD® SHAFTLINER
MANUFACTURER
National Gypsum Company
2001 Rexford Road
Charlotte, NC 28211
(704) 365-7300
Technical Information:
1-800-NATIONAL
(1-800-628-4662)
Fax:1-800-FAX NGC1
(1-800-329-6421)
Internet Home Page:
nationalgypsum.com
nationalgypsum.com/espanol
09 29 00/NGC BuyLine: 1100

DESCRIPTION
Gold Bond® brand Fire-Shield®
Shaftliner panels consist of a
fire-resistant Type X gypsum
core encased in a heavy
moisture-resistant green, 100%
recycled paper on the face and
back sides. The face paper is
folded around the long edges to
reinforce and protect the core,
and the ends are square-cut and
finished smooth. Long edges of
panels are beveled for ease of
installation.
BASIC USES
Shaftliner panels are designed to
be used to construct lightweight
fire barriers for cavity shaftwalls
(1-4 hr), stairwells and area
separation fire walls in
multifamily housing. The panels
are key components in the
I-Stud, C-T Stud and C-H Stud
Cavity Shaftwall Systems and
the H-Stud Area Separation Fire
Wall System.
ADVANTAGES
GREENGUARD CERTIFIED
ACCESSORIES
Gold Bond® brand Fire-Shield®
Shaftliner is GREENGUARD
Children & SchoolsSM Certified
for indoor
air quality
•
•
•
•
•
•
•
Fasteners
I-Studs
C-T Studs
C-H Studs
J-Track
H-Studs
C-Runner
Or
•
•
•
•
LIMITATIONS
•Exposure to excessive or
continuous moisture and
extreme temperatures should
be avoided.
•Non-load bearing.
•To prevent weakening due
to calcining, 1” Fire-Shield
Shaftliner panels, like any
gypsum wallboard, should not
be exposed to temperatures
over 125°F (52°C) for extended
periods of time.
•Limiting loads and heights not to
exceed design specification.
•Not to be used in an unlined air
supply duct.
COMPOSITION & MATERIALS
Shaftliner is a manufactured panel
with a fire-resistive Type X core
encased in moisture-resistant
paper. Contains no asbestos.

Approved metal shaftwall
and area separation fire wall
components
Drywall beads and trim
ProForm Ready Mix or ProForm Quick Set/Quick Set
Lite Compound
ProForm Joint Tape
TECHNICAL DATA
PHYSICAL PROPERTIES
Thickness, nominal
1" Type X (25.4 mm)
Width, nominal
2' (610 mm)
Length, standard
7' through 14' (2133-4267 mm)
Weight, lbs./sq.ft., nominal
Edges
Surface Burning Characteristics
(per ASTM E 84)
3.75
Double Beveled
Flame Spread: 15
Smoke Developed: 0
APPLICABLE STANDARDS AND REFERENCES
ASTM C 1396
Federal Specification SS-L-30D Type IV (Grade X)
National Gypsum Company, Gypsum Construction Guide
Job Name________________________________________________________
Contractor_______________________________________ Date_____________
•Lightweight, cost-efficient
material.
•Shaftliner is easily cut for quick
installation.
•The gypsum core will not
support combustion or
transmit temperatures greatly
in excess of 212°F (100°C) until
completely calcined, a slow
process.
•UL Classified and approved for
inclusion in specific UL firerated designs.
Submittal Approvals: (Stamps or Signatures)
09 29 00

FIRE RESISTANCE RATINGS
Fire-Shield Shaftliner is UL
classified and approved for
inclusion in specific UL firerated designs: U347, U497,
U498, U499, V451, W414
and W419.
Fire resistance ratings
represent the result of tests
on assemblies made up
of materials authorized by
National Gypsum in specific
configurations. When
selecting construction
designs to meet certain fire
resistance requirements,
caution must be used to
ensure that each component
of the assembly is the one
specified in the test. Further,
precaution should be taken
that assembly procedures
are in accordance with those
of the tested assembly. (For
copies of specific tests, call
1-800-NATIONAL.)
UL CORE DESIGNATION
Fire-Shield Shaftliner: FSW

INSTALLATION
RECOMMENDATIONS
Installation of Fire-Shield
Shaftliner should be
consistent with methosds
described in specific
application details for Cavity
Shaftwall Systems or H-Stud
Area Separation Fire Wall
Systems or other fire-rated
designs.
HANDLING PRECAUTIONS
Always store Shaftliner Gypsum
Panels flat on a level surface,
and support with properly
placed risers. Care should
be taken to avoid impact,
unwarranted flexing and
subsequent damage to board
edges, ends and corners.
Appropriate storage and
handling is outlined in
Gypsum Association GA-801.
110688 Rev. 04/13
SUBMITTAL
Head-of-Wall Deflection Track and Firestop System
Manufacturer
(800) 394-9875 ph
12098 County Rd. 150, Kimball, MN 55353
(320) 398-7660 fax info@firetrak.com www.firetrak.com
Description
The Fire Trak System consists of the Fire Trak ceiling runner with a shoulder offset
the thickness of the wall material. A second piece of wall material is fitted tight to the
roof or floor deck and then attached to the shoulder. This allows the deck and the
Fire Trak ceiling runner to move in relation to the wall studs and allows the overlapping piece of wall material attached to the Fire Trak to slide over the primary wall
material.
Benefits
Fire Trak 1 Hr. Shadowline
Standard Wall - 1” Deflection
Fire Trak is a fire rated Head-of-Wall Joint that has passed current fire and cycle
tests at U.L. without fire caulk or spray.
The system is classified and listed for use with U-400 series walls and is good for
both roof and floor assemblies.
Code Compliance
The Fire Trak System meets all standard building codes and its unique design and
exceptional performance are widely recognized and accepted by Building Officials.
Fire Trak has U.L. listings for standard walls, cavity walls and shaft walls. It is tested
and listed both parallel and perpendicular to the roof and/or floor deck.
Test Standards:
U.L. 2079 - Tests for Fire Resistance of Building Joint Systems
Fire Trak 2 Hr. Cavity Shadowline
Shaft Wall - 2” Deflection
ASTM E1966 - Standard Test Method for Fire Resistive Joint Systems
Cycling Requirements:
The test assemblies were cycled 500 times, 100 cycles at 30 CPM and
400 cycles at 10 CPM.
The system has Class I, II and III cycling capabilities.
Movement Capabilities
The Fire Trak System does not require fire caulk or spray to achieve a fire rating.
This allows the Fire Trak System substantially greater movement capabilities than
other systems. The Fire Trak System achieves a full 100% compression and/or
extension and has been tested and listed with U.L. for deflection up to 6”.
Fire Rated Condition:
Up to 3” of Compression and 3” of Extension
Fire Trak 2 Hr. Shadowline
Standard Wall - 6” Deflection
Up to 6” of Compression or Extension
Patented System
U.S. Patent No.’s 5,471,805 and 5,755,066 cover the Fire Trak System.
Creating a shoulder on a track to attach an overlapping board for the
purpose of joint movement is part of Fire Trak’s patented assembly and its
use constitutes patent infringement.
Availability
U.S. PATENT NO’S 5,471,805 AND 5,755,066
Major Credit Cards are accepted. There is a 24 hour lead time on standard profiles.
800.394.9875
www.firetrak.com
SUBMITTAL PAGE 1 OF 2
SUBMITTAL
2008 U.L. Listings
% Compression
Actual
(Deflection)
Compression
Movement
(Deflection) by “
1” compression and 1“ extension (2 ” range of motion)*
HW-D-0060
Standard wall
HW-D-0061
Cavity wall
HW-D-0117
Standard & Cavity walls
HW-D-0118
Standard & Cavity walls
HW-D-0119
Shaft wall
HW-D-0120
Shaft wall
HW-D-0400
Shaft wall
Perpendicular and parallel against steel and concrete decks
Perpendicular and parallel against steel and concrete decks
Perpendicular to metal decks with flute filled with cementious fireproofing
Perpendicular to metal decks with flute filled with fire caulk or fire spray
Perpendicular and parallel against steel and concrete decks
Perpendicular and parallel against steel and concrete decks
Parallel under steel beam
1 to 3 hour
100%
1“
1 to 3 hour
100%
1“
1 and 2 hour
100%
1“
1 and 2 hour
100%
1“
1 to 3 hour
100%
1“
1 to 3 hour
100%
1“
1 and 2 hour
100%
1“
1 to 3 hour
100%
3“
1 to 3 hour
100%
3“
1 and 2 hour
100%
3“
1 and 2 hour
100%
3“
3” compression and 3“ extension (6” range of motion)*
HW-D-1011
Standard wall
HW-D-1012
Cavity wall
HW-D-1019
Standard & Cavity walls
HW-D-1020
Standard & Cavity walls
Perpendicular and parallel against steel and concrete decks
Perpendicular and parallel against steel and concrete decks
Perpendicular to metal decks with flute filled with cementious fireproofing
Perpendicular to metal decks with flute filled with fire caulk or fire spray
* Tracks can be configured to any deflection between 1” and 6”.
Head Detail
Steel Specifications
UL HW-D-0060
TOP OF METAL DECK
MINERAL FIBER
BOTTOM OF METAL
DECK
SEE U.L. LISTINGS FOR
SEALANT OPTIONS
FIRE TRAK
SHADOWLINE
5/8" TYPE 'X' G.W.B.
METAL STUD
Perpendicular to Metal Deck
1 Hr. Rating - 1” Deflection
20 Gauge (.0356 min thickness) galvanized steel
Conforms to ASTM C-645
Steel Conforms to ASTM A-653, Minimum 33,000 ksi yield strength
Galvanized in accordance with ASTM A-924, G-40
18 Gauge (.0466 min thickness) galvanized steel
Conforms to ASTM C-645
Steel Conforms to ASTM A-653, Minimum 33,000 ksi yield strength
Galvanized in accordance with ASTM A-924, G-60
16 Gauge (.0575 min thickness) galvanized steel
Conforms to ASTM C-645
Steel Conforms to ASTM A-653, Minimum 50,000 ksi yield strength
Galvanized in accordance with ASTM A-924, G-60
Submittal Approvals
Job Name:
Contractor:
Approved By:
Date:
800.394.9875
www.firetrak.com