REACTa - Swegon
Transcription
REACTa - Swegon
REACTa 20150710 / Art. no. 15 45 221 REACT Installation Instruction – English Installation Handling Technical data • The contents of this installation document, including commissioning and maintenance instructions, are all collected in the document REACT-m (pdf format), available for download (languages: EN/SE/FI/FR/DE/RU), from www.swegon.com. • Straight section requirement – Air flow measuring of REACT requires a straight section of duct before the unit (in air flow direction), according to installation figures. Edit 10° 1 • REACT may only be installed in spaces with an ambient temperature in the range 0-50°C. Mode • All service must be done with the power supply disconnected. Operating data Figure 4. Installation in a duct system. The ducts must be firmly fixed to the frame of the building on each side of the REACT unit. Figure 8. The REACT interface. 1 – Select desired mode by turning the "Mode" wheel. 2 – Set values and select sub-settings by turning the ”Edit" wheel. 3 – The displayed value blinks twice when a new value is accepted. 4 – ”Gear release” button. Menus 0° – +50°C Air-flow temperature: 0° – +50°C Vnom Running time open/close (90 degrees): 5 Nm - 100 s Adr Legend to figures 2-4: 1. Circular Variable-flow damper REACT 2. Clamp, FSR 3. Sound attenuator with baffle A (mm) Size A + 10 mm A (mm) 15 Nm - 150 s 250 522 532 125 472 482 315 552 562 160 472 482 400 695 705 Electrical data 200 472 482 500 822 832 Supply voltage Dimensions B and H (WxH in mm) can be read off the label on the delivered product. Straight sections before REACT – Rectangular ducts Type of obstruction E (m2=5%) E (m2=10%) One 90°-bend E=3xB E=2xB One T-piece E=3xB E=2xB Legend to figures 5-6: E = Straight section of duct 1 = Rectangular REACT Mode Vmax • Vmin value should be lower than Vmax. Test -20° – +80°C Mode Vmax • Vmax value should be greater than Vmin. Test 2 = t 500 mm length of straight duct 3 = Sound attenuator with baffles 4 VA REACT 10 Nm 2,5 W 4,5 VA REACT 15 Nm 3W 4,5 VA • Automatic disconnection after 10 hours. Vmin Adr 2.5 W Test Flow Power consumption, for transformer rating: REACT 5 Nm • Select new value for Vmax with the edit wheel. Vmin Adr 24 V AC/DC +-20%, 50/60 Hz Vmax Flow Vnom Vnom Installation – rectangular version • Select new value for Vmin with the edit wheel. Vmin Adr Ambient temperature: Vmin Flow Vnom Storage and transport 482 • Illuminated "dot" in the display indicates the selected mode. Vmax Test A + 10 mm 472 • Toggle between l/s and m3/h using the edit wheel. Vmin Mode 100 Flow Flow 10 Nm - 150 s Size Mode • Turn the edit wheel to select inbetween: Vmax Test oFF on oP cL Lo Hi 123 Connections BU-BN – Operating voltage 24 V AC/DC BU-BK – Control signal 0..10/(2..10) V BU-GY – Feedback signal 0..10/(2..10) V Load for output GY: max 0.5 mA • Displays selected input and reference signal. Vmin Vmax • Toggle between 0-10 and 2-10 V using the edit wheel. Test E Figure 2. Straight section requirements, circular ducts. a. Damper opens fully, 24 V AC (positive rectified half-wave). b. Vmax, 24 V AC/DC. c. Vmin, no signal, Mode: 0..10 V. d. Damper closes fully, ground/earth (-): 0..10 V – CLOSED if Vmin = 0. 2..10 V – CLOSED. e. Regulation with the control signal, default 0..10 V (alt. 2..10 V). Flow Vnom Mode Flow Vnom Figure 5. Straight section requirements. Modbus version Standard version 227VM-024-05 227V 5 Nm 3 W 5 VA V 100s (90°) 95° 250 Pa max. 100 kPa 1 2 3 227VM-024-05 227V 27V 1 2 3 4 BU BN BK GY - + QX Y - + Y 1 - 0..10 V DC (2..10 V DC) Extract air 470 mm ≥500 mm Swegon reserves the right to alter specifications. Figure 6. Straight section requirements, rectangular REACT and sound attenuator with baffles. Installation with a length of straight duct applies to both the supply air and the extract air. N L 24 V AC/DC 3 4 A B 2 3 4 A XX / XX B BU BN BK GY WH WH U b. 2 QX 4 3 a. 1 BU BN BK GY WH WH 5 Nm 3 W 5 VA V + Y U 10 00s (90°) 95° 100s 25 50 Pa max. 100 kPa 250 U XX / XX BU BN BK GY Supply air Figure 3. REACT requires a duct of ~2 x ØD between the REACT and a sound attenuator fitted with baffles. NOTE: Ducts must be fixed on both sides of REACT. • Used for factory configuration. Vmax Test Straight sections before/after REACT – Sound attenuator with baffles 2 Vnom Vmin Mode 1 • Is used to set the communication settings for the unit when using Modbus communication. See the installation manual for further instructions. Vmax Test Adr E Adr Vmin Adr – Test mode is off, actuator resumes control. – Test mode is on, damper stays in current position. – Opens the damper fully. – Closes the damper fully. – Low flow, forces the actuator to Vmin. – High flow, forces the actuator to Vmax. – Displays current software version. Mode Flow Vnom Adr Mode E Made in Germany 24 VAC/DC 50/60 Hz 0...+50°C IP 42 Do not open Ambient air temperature: Installation measurements – circular version Vmax Test • REACT is not suitable for use in explosive environments. c. d. e. + Y Figur 7. Connections, standard version. Swegon reserves the right to alter specifications. U 0..10 V DC (2..10 V DC) BU = Blue (1) BN = Brown (2) BK = Black (3) GY = Grey (4) 0..10 V DC (2..10 V DC) 4 227VM Vmin Adr • The product should always be installed with its flow meter facing downstream, see air direction arrows on the product label. Min 100 mm Installation – circular version I/s Test m3/h Flow Vnom • All interconnected regulating equipment must have the same polarity, i.e. the neutral wire must be correctly connected. Min 500 mm Figure 1. Space required for installation and permissible ambient temperature. 3 2 To obtain the correct functionality, it is very important that the following is taken into account: a. N L 24 V AC/DC b. A B Modbus c. d. e. BU = Blue (1) BN = Brown (2) BK = Black (3) GY = Grey (4) WH = White (A, B) 0..10 V DC (2..10 V DC) Figur 9. Connections, Modbus version. 20150710 www.swegon.com REACTa 20150710 / Art. no. 15 45 221 REACT Monteringsanvisning – Svenska Montering Tekniska data • Monteringsanvisningarna i detta dokument, inklusive injusterings- and skötselinstruktioner finns samlade i dokumentet REACT-m (pdf-format), tillängligt för nerladdning på språken EN/SE/FI/FR/DE/RU från www.swegon.com. • Raksträckekrav – REACTs luftflödesmätning kräver raksträcka före enheten (i luftriktningen) enligt montagefigurerna. Det är av största vikt att följande beaktas: • Produkten får endast installeras i utrymmen med temperatur mellan 0–50°C. • All inkopplad reglerutrustning måste ha samma polaritet dvs att systemnollan kopplas rätt. • REACT är ej lämplig för användning i explosiva miljöer. • All service måste utföras med frånkopplad strömförsörjning. Min 500 mm Handhavande Omgivningstemperatur: 0° – +50°C Luftflödestemperatur: 0° – +50°C Gångtid öppet/stängt (90 grader): 5 Nm - 100 s 15 Nm - 150 s Mode Montering – cirkulärt utförande Förklaringar till figur 2-4: 1 = Cirkulärt VAV-spjäll REACT 2 = Fästsvep FSR 3 = Ljuddämpare med baffel eller centrumkropp A (mm) A + 10 mm Storlek A (mm) A + 10 mm Lagring och transport 100 472 482 250 522 532 125 472 482 315 160 472 482 400 695 705 200 472 482 500 822 832 562 Mått BxH (mm) framgår av produktetiketten på levererad produkt. Raksträcka före REACT i rektangulära kanaler Typ av störning E (m2=5%) E (m2=10%) -20° – +80°C 24 V AC/DC +-20%, 50/60 Hz Effektförbrukning, dimensionering av transformator: REACT 5 Nm 2,5 W Vmax • Vmin skall vara mindre än Vmax. Test Mode Vmax • Vmax skall vara större än Vmin. Test Test Flow 4,5 VA 3W 4,5 VA • Automatisk bortkoppling efter 10 timmar. Vmin Mode Vmax • Vrid edit-hjulet för att välja mellan följande lägen: Test oFF on oP cL Lo Hi 123 Inkoppling BU-BN –matningsspänning 24 V AC/DC BU-BK – styrsignal 0..10/(2..10) V 0..10/(2..10) V E=3xB E=2xB BU-GY – ärvärdessignal E=3xB E=2xB Belastning på utgång GY: max 0,5 mA • Visar vald styr- och återföringssignal. Vmin Adr Mode Vmax • Växla mellan 0-10 och 2-10 V via edit-hjulet. Test Flow Vnom a. Spjäll öppnar helt, 24 V AC till diod (positiv halvvåg). b. Vmax, 24 V AC/DC. c. Vmin, ingen signal, Mode: 0..10 V. d. Spjäll stänger helt, jord (-): 0..10 V – STÄNGD om Vmin = 0. 2..10 V – STÄNGD. e. Reglering med styrsignal, default 0..10 V (alt 2..10 V). Adr • Används för att ställa in kommunikationsinställningarna när Modbus används. Se installationshandboken för vidare instruktioner. Vmin Adr Mode Vmax Test Flow Vnom Vnom • Används för fabrikskonfigurering. Vmin Adr Mode – Test läget avstängt, regulatorn reglerar normalt – Test läget är på, spjället låser sin position – Öppnar spjället fullt – Stänger spjället helt – Spjället reglerar till valt Vmin – Spjället reglerar till valt Vmax – Visar aktuell mjukvaruversion Mode Flow Vnom Förklaringar till figur 5-6: E = Raksträcka 2 = Rak kanal t500 mm 1 = Rektangulär REACT 3 = Ljuddämpare med baffel Figur 2. Raksträckekrav cirkulära kanaler. • Välj nytt värde för Vmax via edit-hjulet. Vmin Adr Adr T-stycke E Vmax Flow Vnom REACT 15 Nm • Välj nytt värde för Vmin via edit-hjulet. Vmin Mode 4 VA 2,5 W Vmin Flow Adr En 90°-böj E • ”Tänd” fyrkant i displayen indikerar vald enhet. Test REACT 10 Nm Montering – rektangulärt utförande • Växla mellan l/s och m3 /h via edit-hjulet. Vmin Vmax Vnom 552 Flow Flow Mode Matningsspänning Made in Germany 24 VAC/DC 50/60 Hz 0...+50°C IP 42 Do not open Vnom Elektriska data Storlek Vmax Test Vnom Figur 1. Monteringsutrymme och omgivningstemperatur. Vmax Test Modbusversion Standardversion Figur 5. Raksträckekrav rektangulära kanaler. 227VM-024-05 227V 5 Nm 3 W 5 VA V 100s (90°) 95° 250 Pa max. 100 kPa + QX Raksträcka före/efter REACT – ljuddämpare med baffel 1 2 3 227VM-024-05 227V 27V 1 2 3 4 BU BN BK GY - Y - + Tilluft E 1 2 Y 1 - 0..10 V DC (2..10 V DC) Frånluft Figur 3. Raksträckekrav på ~2 x ØD vid ljuddämpare med baffel eller centrumkropp. OBS: Kanalerna måste vara fixerade på båda sidor om REACT. Rätten till konstruktionsändringar förbehålls. 2 3 4 A 3 4 A c. d. e. + Y U 0..10 V DC (2..10 V DC) BU = Blå (1) BN = Brun (2) BK = Svart (3) GY = Grå (4) a. b. c. d. BU = Blå (1) BN = Brun (2) BK = Svart (3) GY = Grå (4) WH = Vit (A, B) e. 470 mm ≥500 mm Figur 6. Raksträckekrav rektangulär REACT och ljuddämpare med baffel. Montage med raksträcka gäller både till- och frånluft. N L 24 V AC/DC B XX / XX B BU BN BK GY WH WH U b. 2 QX 4 3 a. 1 BU BN BK GY WH WH 5 Nm 3 W 5 VA V + Y U 10 00s (90°) 95° 100s 25 50 Pa max. 100 kPa 250 U XX / XX BU BN BK GY 0..10 V DC (2..10 V DC) Figur 7. Kopplingsschema, standardversion. Rätten till konstruktionsändringar förbehålls. 4 227VM Vmin Adr Adr Omgivningstemperatur: Installationsmått – Cirkulärt utförande I/s Test m3/h Flow Vnom Menyer 10 Nm - 150 s Figur 4. Installation i kanalsystemet. Kanalerna måste fixeras i byggnadsstommen på vardera sida av REACT. Edit 10° 1 Figur 8. REACT gränssnitt. 1 – Välj önskad funktion genom att vrida på ”Funktionshjulet”. 2 – Sätt värden eller välj undermenyer genom att vrida på ”Edit"-hjulet. 3 – Värdet blinkar två gånger när ett nytt värde accepterats. 4 – Frikopplingsknapp. Driftdata Min 100 mm 3 2 N L 24 V AC/DC A B Modbus 0..10 V DC (2..10 V DC) Figur 9. Kopplingsschema, Modbusversion. 20150710 www.swegon.com