Installation and Operating Instructions
Transcription
Installation and Operating Instructions
Leader in Level Measurement For Assistance Call 1-800-527-6297 Outside North America + 215-674-1234 Installation and Operating Instructions ThePointTM Series Two Wire Point Level Switch + 215-674-1234 Outside North America 1-800-553-9092 US and Canada www.drexelbrook.com drexelbrook.service@ametek.com AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in this manual, including, but not limited to, implied warranties or fitness for a particular purpose. Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of material. All information contained in this manual is subject to change without notice Copyright 2005 AMETEK Drexelbrook EDO # 02-05-243 PNT1-LM ISSUE# 5 ThePointTM Series Two Wire Point Level Switch An ISO 9001 Certified Company 205 Keith Valley Road, Horsham, PA 19044 US and Canada: 1-800-553-9092 International: +1 215-674-1234 24-Hour Service: +1 215-527-6297 Fax: +1 215-674-2731 E-mail: drexelbrook.info@ametek.com Website: www.drexelbrook.com Register ThePoint TM and extend your warranty to 24 months 24 Month Warranty Registration at... www.drexelbrook.com Extend your warranty! ...from 12 months to 24 months by registering your purchase. Please go to www.drexelbrook.com and click on the pull down menu "Contact Us" than "Warranty Registration" and fill out the form. Table Of Contents Section 1:Introduction ........................................................................................................ 1 1.1 System Description .............................................................................................. 1 1.2 Technology ........................................................................................................... 1 1.3 Model Number...................................................................................................... 2 1.4 Housing Dimensions ........................................................................................... 4 Section 2:Installation .......................................................................................................... 5 2.1 Unpacking ............................................................................................................ 5 2.2 Mounting And Installation Guidelines................................................................... 5 2.3 Input Wiring .......................................................................................................... 7 2.4 Output And Led Status........................................................................................ 8 2.5 Electronic Unit ..................................................................................................... 9 2.5.1 Time Delay ........................................................................................................... 9 2.5.2 Time Delay Action ................................................................................................ 9 2.5.3 Current Output Assignment.................................................................................. 9 2.5.4 Failsafe .............................................................................................................. 10 2.5.5 Recal .................................................................................................................. 10 2.6 Spark Protection................................................................................................. 11 2.7 Sensing Element Connection............................................................................. 11 Section 3:Troubleshooting ............................................................................................... 15 3.1 Testing Sensing Element.................................................................................... 15 3.2 Testing Electronic Unit ........................................................................................ 16 3.3 Over Range ........................................................................................................ 17 3.4 Under Range...................................................................................................... 17 3.5 Testing Integral Cable......................................................................................... 17 3.6 Testing Remote Cable ........................................................................................ 18 3.7 Factory Assistance ............................................................................................. 18 3.8 Field Service ...................................................................................................... 19 3.9 Customer Training .............................................................................................. 19 3.10 Equipment Return .............................................................................................. 19 Section 4:Specifications................................................................................................... 21 Section 5:Approvals Available ......................................................................................... 23 Section 6:Control Drawings ............................................................................................. 25 6.1 Fm Control Drawings.......................................................................................... 25 6.2 Atex Control Drawings........................................................................................ 39 Appendix A Shortening Or Lengthening Sensing Element....................................................A1 The Point™ Series SECTION 1: 1.1 Introduction INTRODUCTION System Description The AMETEK Drexelbrook ThePoint™ Series uses No-Cal™ technology to detect the presence or absence of material without calibration or initiation via setpoint adjustments, push-buttons, or magnets. The sensing element must be uncovered before applying power. 1.2 Technology k air d C Installation is simple and easy. Simply apply power and ThePoint system is ready to detect the presence or absence of material. Since ThePoint instrument does not require calibration or setpoint adjustments, it is capable of operating in non-dedicated tanks regardless of the material being measured. A d k air C A k media k media kA C= d kA C = d Figure 1-1 Simple Capacitance Probe In a simple capacitance probe type sensing element, when the level rises and material covers the probe, the capacitance within the circuit between the probe and the media (conductive applications) or the probe and the vessel wall (insulating applications) increases. This is due to the dielectric constant (k) of the material which causes a bridge misbalance. The signal is demodulated (rectified), amplified, and the output is increased. There are drawbacks, however, especially when there is coating of the probe. An RF Admittance level transmitter is the next generation. Although similar to the capacitance concept, ThePoint employs a radio frequency signal and adds the Cote-Shield™ circuitry within the Electronics Unit. This patented Cote-Shield™ circuitry is designed into ThePoint series and enables the instrument to ignore the effect of buildup or material coating on the sensing element. The sensing element is mounted in the vessel and provides a change in RF admittance indicating presence or absence of material. The Cote-Shield element of the sensing element prevents the transmission of RF current through the coating on the sensing element. The only path to ground available for the RF current is through the material being measured. The result is an accurate measurement regardless of the amount of coating on the probe, making it by far the most versatile technology, good for very wide range conditions from cryogenics to high temperature, from vacuum to 10,000 psi pressure, and works with all types of materials. Figure 1-2 RF Admittance Probe with Cote-Shield 1 The Point™ Series 1.3 Introduction Model Number ThePoint™ Technology P RF Admittance Measurement Type N No Calibration, Point Level H No Calibration, Point Level, with High Sensitivity Input T Two Wire Power Supply 13 to 30 Vdc Output 0 8-16 mA Housing 0 1 2 3 4 No Approvals, NEMA 4X/IP66, M20 x 1.5 conduit entries No Approvals, NEMA 4X/IP66 3⁄4" NPT conduit entries CENELEC/ATEX pending - not available FM Approved CSA Approval pending - not available Electronics 0 Integral 1 Remote, no cable 2 Remote with 3 m (10 feet) cable 3 Remote with 7.6 m (25 feet) cable 4 Remote with 10.6 m (35 feet) cable 5 Remote with 15.2 m (50 feet) cable 6 Remote with 23 m (75 feet) cable continued on next page Sensing Element Application General purpose Sensing Element 700-1202-001 remote 700-1202-021 integral Pressure/Temperature 13.8 bar @ 232˚C (200 PSI @ 450˚F) Wetted Parts 316SS and PEEK 01 Floating roof with cable attachment and brass bottom weight 700-1202-012 remote 700-1202-022 integral 13.8 bar @ 177˚C (200 PSI @ 350˚F) 316SS, Brass, and PEEK 02 General purpose, 700-1202-014 remote longer insertion lengths 700-1202-024 integral with cable attachment and 316SS bottom weight 13.8 bar @ 177˚C (200 PSI @ 350˚F) 316SS and PEEK 03 Proximity 700-1202-018 remote 700-1202-028 integral 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and PEEK with 76 mm (3) 316SS proximity plate 04 General purpose, high temperature and pressure 700-1202-041 remote 700-1202-042 integral 69 bar @ 121˚C (1000 PSI @ 250˚F) 20.7 bar @ 232˚C (300 PSI @ 450˚F) 316SS and PEEK 06 General purpose with FDA approved materials of construction 700-1202-031 remote 700-1202-031 integral 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and FDA grade PEEK 07 General purpose Granular materials 700-1202-010 remote 700-1202-020 integral 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and PEEK with 7/8 inch dia. 316SS collar 09 General purpose Granular materials with FDA approved materials of construction 700-1202-033 remote 700-1202-034 integral 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and FDA grade PEEK with 7/8 inch dia. 10 Corrosive liquids (2)(4)(9) 700-0001-018 3.4 bar @ 149˚C (50 PSI @ 300˚F) PFA 11 General purpose, 700-0201-005 higher pressure TFE compatibility required 69 bar @ 38˚C (1000 PSI @ 100˚F) 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and TFE 12 Corrosive material, higher pressure 700-0201-005 Hastelloy C 69 bar @ 38˚C (1000 PSI @ 100˚F) 13.8 bar @ 232˚C (200 PSI @ 450˚F) Hastelloy C and TFE 13 Sanitary (3) 700-0201-036 69 bar @ 38˚C (1000 PSI @ 100˚F) 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316/316L SS and TFE 14 General Purpose, low pressure 700-0202-002 3.4 bar @ 149˚C (50 PSI @ 300˚F) 1.4 bar @ 232˚C (20 PSI @ 450˚F) 316SS and TFE 15 Heavy duty, agitated tanks or material with high bulk density (1) 700-0202-043 69 bar @ 38˚C (1000 PSI @ 100˚F) 13.8 bar @ 232˚C (200 PSI @ 450˚F) 316SS and TFE 17 Sanitary (3) lowpressure 700-0202-036 3.4 bar @ 149˚C (50 PSI @ 300˚F) 1.4 bar @ 232˚C (20 PSI @ 450˚F) 316SS and TFE 18 Corrosive material, higher pressure with waterlike viscosity (4) 700-0001-022 69 bar @ 38˚C (1000 PSI @ 100˚F) 34.5 bar @ 149˚C (500 PSI @ 300˚F) TFE 20 Miniature Pilot Plant Sensor (1)(7) 700-0209-002 6.9 bar @ 121˚C (100 PSI @ 250˚F) 0 bar @ 232˚C (0 PSI @ 450˚F) 316 SS and TFE 00 P T 0 2 316SS collar The Point™ Series 1.3 Introduction Model Number (continued) Sensing Element (continued from previous page) Fly Ash Precipitators, Baghouse, and Economizers (1) (6) Application Sensing Element Pressure/Temperature 31 No hopper Installation 700-0029-001 0.1 bar @ 260˚C (2 PSI @ 500˚F) 32 Hopper Installation up to 200mm (8 inches) 33 Hopper Installation up to 250mm (10 inches) 34 Hopper Instalation up to 330mm (13 inches) 35 Hopper Installation up to 400mm (16 inches) Wetted Parts 316SS and TFE (CS Inactive) 700-0029-002 0.1 bar @ 260˚C (2 PSI @ 500˚F) 316SS and TFE (CS Inactive) 700-0029-003 0.1 bar @ 260˚C (2 PSI @ 500˚F) 316SS and TFE (CS Inactive) 700-0029-004 0.1 bar @ 260˚C (2 PSI @ 500˚F) 316SS and TFE (CS Inactive) 700-0029-005 0.1 bar @ 260˚C (2 PSI @ 500˚F) 316SS and TFE (CS Inactive) Mounting Type (See separate Mounting Chart for first three digits) IL CSL IL CSL xxxA 152 mm (6") 51 mm (2") xxxH 914 mm (36") 254 mm (10") xxxB 305 mm (12") 51 mm (2") xxxJ 914 mm (36") 0 mm (0") xxxC 305 mm (12") 89 mm (3.5") xxxK 1219 mm (48") 254 mm (10") xxxD 457 mm (18") 51 mm (2") xxxL 1524 mm (60") 254 mm (10") xxxE 457 mm (18") 89 mm (3.5") A1BX IL/CSL factory set for Fly Ash xxxF 457 mm (18") 254 mm (10") xxxZ Other xxxG 457 mm (18") 0 mm (0") P T 0 Notes: (1) Available with remote electronics only (2) Use A1P mounting option (3) Choose from sanitary mounting options only (4) Available with 0-inch CSL only (5) Use P00X mounting option 3⁄4" NPT 3⁄4" NPT 3⁄4" NPT 1" NPT 1" NPT C2B C3B C4B 1" TriClamp 11⁄2" TriClamp 2" TriClamp 316SS Hastelloy C PFA 316SS Hastelloy C Sanitary TriClamps E01 EP1 EQ1 ER1 ES1 ET1 EU1 EV1 EW1 EX1 ANSI Flanges (cont.) DIN Flanges (cont.) NPT Threads A1B A1C A1P A2B A2C (6) Use A1B mounting option (7) Use A8B mounting option (1⁄4-inch NPT) (8) Choose from flange mounting only (9) FM approved with remote electronics only Not all mounting options available with all sensing elements 316SS 316SS 316SS DIN Flanges 25 mm 16bar RF 316/316L SS 25 mm 40 bar RF 316/316L SS 50 mm 16 bar RF 316/316L SS 50 mm 40 bar RF 316/316L SS 80 mm 16 bar RF 316/316L SS 80 mm 40 bar RF 316/316L SS 100 mm 16 bar RF 316/316L SS 100 mm 40 bar RF 316/316L SS 150 mm 16 bar RF 316/316L SS 150 mm 40 bar RF 316/316L SS E02 EP2 EQ2 ER2 ES2 ET2 EU2 EV2 EW2 EX2 25 mm 25 mm 50 mm 50 mm 80 mm 80 mm 100 mm 100 mm 150 mm 150 mm 16 bar 40 bar 16 bar 40 bar 16 bar 40 bar 16 bar 40 bar 16 bar 40 bar RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel ANSI Flanges DA1 DB1 DC1 DD1 DE1 DF1 DG1 DH1 DI1 1" 11⁄2" 2" 21⁄2" 1" 11⁄2" 2" 21⁄2" 3" 150# 150# 150# 150# 300# 300# 300# 300# 150# RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS 3 DJ1 DK1 DL1 DM1 DN1 DA2 DB2 DC2 DD2 DE2 DF2 DG2 DH2 DI2 DJ2 DK2 DL2 DM2 DN2 3" 4" 4" 6" 6" 1" 11⁄2" 2" 21⁄2" 1" 11⁄2" 2" 21⁄2" 3" 3" 4" 4" 6" 6" 300# 150# 300# 150# 300# 150# 150# 150# 150# 300# 300# 300# 300# 150# 300# 150# 300# 150# 300# RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF 316/316L SS RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel RF Carbon Steel The Point™ Series 1.4 Introduction Housing Dimensions 4.5" (114mm) 6.5" (165mm) 4.75" (121mm) Figure 1-3 Compartment Housing Detail Equipotential Terminal (CENELEC Systems) 4 The Point™ Series SECTION 2: 2.1 Introduction INSTALLATION Unpacking Carefully remove the contents of the shipping carton and check each item against the packing list before destroying any packing material. If there is any shortage or damage, immediately report it to the factory at 1-800-527-6297 (US and Canada) or + 215-674-1234 (International). 2.2 Mounting and Installation Guidelines WARNING: ThePoint equipment is rated explosion-proof. When installing in explosion hazardous areas [rated “potential hazardous” (EU) or “hazardous classified” (USA)] observe all national and local regulations as well as specifications in the certificate. CAUTION: ThePoint instrument must be powered after it is installed in the application and with material below the sensing element. ThePoint instrument can be mounted vertically, horizontally, or at an angle. Mounting location should be as free as possible from vibration, corrosive atmospheres, and any possibility of mechanical damage. Ambient temperatures at electronics should be between -30 to 70ºC (-22 to 158ºF). NOTE: To reduce possibility of damage caused by water in conduit, install drip loop and breather drain in conduit to purge any accumulating moisture as shown in Figure 2-1. Figure 2-1 Recommended Conduit Connection Cable fittings supplied are weatherresistant. They are NOT certified as explosionproof (XP) or flameproof (d) unless they are specifically marked. 5 ThePoint™ Series 2.2 Installation Mounting and Installation Guidelines (continued) The Point RF instrument is rated Intrinsically Safe (I.S.) when power is provided from and I.S. supply. After system is installed and level is below sensing element, apply power. ThePoint series instrument does not require any calibration or setpoint adjustments and is ready to detect change in level. If properly installed, the green LED will light when power is applied. Neither the green nor red LED should be flashing. If either of the LEDs are flashing, refer to, Section 4, Troubleshooting, Mount sensing element per guidelines in Figure 2-2. Best Wall build-up does not extend past first insulator. Figure 2-2 Installation Considerations Cote-shield must extend through nozzle and wall build-up by 2". Best No Nozzle Wrong Nozzle too long; Cote-shield too short. NOZZLE Good Long Nozzle NOZZLE Factory-supplied Cote-shield extends through nozzle and wall build-up. • When installing ThePoint instrument, ambient temperature at electronics must not exceed 70°C (158°F). • When installing flange-mounted sensing elements, keep mating surfaces and bolts free of paint and corrosion to ensure proper electrical contact with vessel. Avoid using excessive amounts of TeflonTM tape when installing threaded sensing elements. • Locate sensing element to avoid enhancing electrostatic discharge from process medium, as is good practice with any thermowell, displacer, or sampler. This includes correct bonding to tank or silo wall. 6 ThePoint™ Series 2.2 Installation Mounting and Installation Guidelines (continued) • If installation area is rated explosion-proof and requires conduit seal fittings, they should be used in accordance with company standards and local codes. • Mounting sensing element inside a pipe is not recommended. • Do not mount a Cote-Shield sensing element through a nozzle that exceeds length of first insulator. • Ensure that there are no obstructions or agitator blades to interfere with sensing element. • Rigid sensing elements can be mounted at any angle. 2.3 Input Wiring WARNING: If ThePoint instrument is located in a hazardous environment, do not open enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that wiring, electrical fittings, and conduit connections conform to electrical codes for the specific location and hazard level. Figure 2-3 Input Wiring 1 2 3 G L1 L2 GND 7 Loop 13-30Vdc ThePoint™ Series 2.4 Installation Output and LED Status There are two status LEDs located on top of the Electronic Unit. The green LED is used to indicate that the unit has power. The red LED is used to indicate the output condition. See Figure 2-4. Figure 2-4 Output/LED Status Tank Condition LED Output Status Power GREEN RED LED On LED Off Power GREEN RED LED On LED On Power GREEN RED LED On LED On Power GREEN RED LED On LED Off High Level FailSafe Tank Empty High Level FailSafe Tank Full Low Level FailSafe Tank Empty Low Level FailSafe Tank Full 8 ThePoint™ Series 2.5 Installation Electronic Unit Remove housing lid to access status LEDs, time delay adjustment, and configuration jumpers. See Figure 2-5. FAILSAFE JUMPER Right�= High Level Left� = Low Level TIME DELAY ADJUSTMENT 0-60 SEC. TIME DELAY JUMPER Right�= Forward Acting Left� = Reverse Acting RED LED - ALARM OUTPUT Right = 8mA Alarm/16 mA Normal Left = 8mA Normal/16 mA Alarm Figure 2-5 Electronic Unit Adjustments GREEN LED - POWER VIEW RESET/RECAL BUTTON NOTE: Do NOT push the Recal button without first ensuring that the material being measured is below the sensing element. 2.5.1 Time Delay Time delay adjustment is used to avoid an oscillating output due to agitation or waves in the vessel. The time delay adjustment can be field adjusted from 0 to 60 seconds. Unit is shipped with time delay setting at zero seconds. 2.5.2 Time Delay Action Time delay action describes whether the output is delayed from going into the alarm state or recovering from an alarm state. • FWD: Delays system from coming out of alarm. • REV: Delays system from going into alarm. • The instrument is supplied with time delay action set in forward mode (FWD) position. • Time delay action is field-selectable using a jumper located on top of Electronic Unit. See Figure 2-5. 2.5.3 Current Output Assignment The output current can be configured using the jumpers as follows: • Jumper on pin #1 and #2 creates: 8mA - Normal 16mA - Alarm • Jumper on pin #2 and #3 creates: 8mA - Alarm 16mA - Normal 9 ThePoint™ Series Installation 2.5.4 Failsafe Failsafe describes the level condition that causes the transmitter to go into alarm. • High Level FailSafe (HLFS) is the condition when the probe is covered, the unit goes into alarm. • Low Level FailSafe (LLFS) is the condition when the probe is uncovered, the unit goes into alarm. • Instrument is supplied with failsafe jumper set in high level (HLFS) position. • Failsafe is field-selectable using a jumper located on top of the Electronic Unit. See Figure 2-5. 2.5.5 RECAL CAUTION: ThePoint instrument must be powered after it is installed in the application and with material below the sensing element. If system is powered on the bench prior to installation, or moved from one tank to another, RECAL is necessary to allow software to capture the air capacitance generated by sensing element in tank. Merely press RECAL (shown in Figure 2-5). Both LED's flash for 60 seconds before reset occurs. [Remove power from the system while the LED's are flashing and recalibration will occur immediately]. NOTE: Do Not Push the Recal Button without first ensuring that the material being measured is below the sensing element. The system is now ready for installation. 10 ThePoint™ Series 2.6 Installation Spark Protection Applications involving insulating granulars and insulating liquids may produce a static discharge that can damage the electronics. The RF series instrument is supplied with integral heavy-duty spark protection to prevent static discharges from damaging the electronic circuits. 2.7 Sensing Element Connection The sensing element connects to rear side of circuit board and is factory-installed. If sensing element must be removed from housing due to mounting requirements during installation, or because a different insertion length is discovered to be needed, use these following steps: MODEL NUMBER LABEL Figure 2-6 Sensing Element Connection (Integral Housing) 11 ThePoint™ Series 2.7 Installation Sensing Element Connection (Continued) To remove sensing element: Disconnecting sensing element froma. Remove power from system. integrally mounted transmitter is not b. Remove lid from housing. usually necessary. c. Remove two retaining screws that hold the electronic unit in place. d. Remove Electronic Unit by gently pulling it up and out of its housing [it unplugs from board-mounted interconnect receptacle]. e. Disconnect cable connector (wire harness on remote units) from circuit board in bottom of housing. f. Remove sensing element by rotating it counterclockwise. To reinstall sensing element: a. Insert cable connector (wire harness on remote units) into housing through bottom process entry. b. Apply thread sealant to 3⁄4-inch NPT threads on sensing element. c. Install sensing element by threading it clockwise into housing. e. Connect cable connector (wire harness on remote units) to circuit board at bottom of housing. f. Carefully align the four pins and place Electronic Unit into housing, taking care that board-mounted connector is reseated into interconnect receptacle. g. Install the two retaining screws. h. Install lid on housing. i. Apply power. 12 ThePoint™ Series 2.7 Installation Sensing Element Connection (Continued) For ThePoint instruments mounted remotely from sensing element, cable connections from sensing element to Electronic Unit are made to terminals beneath the Electronic Unit. See Figure 2-7. EQUIPOTENTIAL TERMINAL COTE-SHIELD (RED) GROUND (GREEN) CENTER WIRE (BLUE) + REMOVE ELECTRONIC UNIT TO ACCESS SENSOR HARNESS (2.5mm Hex-Head Screws) Cable Fitting (M20 AdapterOptional) SHIELD WIRE MUST BE CLIPPED BY USER NOTE: CLIPPED SHIELD WIRE MUST NOT TOUCH CONDULET HOUSING NOTICE Coaxial or Triaxial Cable Figure 2-7 Sensing Element Connection (Remote Housing) 13 ThePoint™ Series SECTION 3: Troubleshooting TROUBLESHOOTING WARNING: If ThePoint instrument is located in a hazardous environment, do not open enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that wiring, electrical fittings, and conduit connections conform to electrical codes for the specific location and hazard level. 3.1 Testing Sensing Element To test the sensing element, first disconnect the integral cable as shown in Figure 3-1. CAP & ELECTRONIC UNIT REMOVED FOR ACCESS TO EXPOSE INTEGRAL CABLE REMOVE CABLE TO EXPOSE TOP OF SENSING ELEMENT Figure 3-1 Testing Sensing Element Expect the following measurements: For Three-terminal Probes: under sensor side of integral cable... When tank level is known to be below the sensor, minimum acceptable values are: Center Wire - Ground Center Wire - Shield Shield - Ground Center Wire Shield 1000 Ohms. 600 Ohms. 300 Ohms. If the readings are less than the minimum acceptable values: 1. Check to see if tank is full, or if a severe coating is present. 2. Clean sensor and re-measure the sensor resistances. Ground Note: Low resistance readings are acceptable if the sensor is covered with a conductive liquid. Also, low resistance readings can be the result of material lodging in a long mounting nozzle. Refer to Figure 2-2. Measured Resistance (Sensor dry and clean): Ohms Center Wire - Ground Center Wire - Shield Ohms Ohms Shield - Ground Note: A reading of zero (0) Ohms usually indicates a metal-to-metal short circuit. Check for contact with tank wall, mounting nozzle, or other tank structure. Resistance readings must be taken using an analog ohmeter set to Rx1000 scale. 15 ThePoint™ Series 3.2 Installation Testing Electronic Unit Use the following steps to test the electronic unit: 1. Be sure environment is safe before removing lid from housing. 2. Observe failsafe jumper on circuit board on top of electronic unit (shown in Figure 2-5). Move jumper from current setting to alternate setting [HLFS to LLFS or vice versa]. Output should change state. 3. If it is possible to access sensing element (with material below sensing element), or remove ThePoint from vessel, touch tip of sensing element with your finger, while holding any bare metal portion of instrument housing with other hand. Output should change state. 4. If ThePoint changes state while moving jumper, but not while touching sensing element, in most cases, integral cable is faulty. Refer to Section 3.5 Testing Integral Cable. 5. If ThePoint is stuck in one state: a. Remove power. b. Disconnect coax cable that joins sensing element to electronic unit. Refer to Section 2.7 Sensing Element Connection. c. Apply power. d. Repeat step 2. e. If ThePoint changes state with sensing element disconnected, in most cases, sensing element is faulty. Refer to Section 3.1 Testing Sensing Element. 6. If there was no Change of state in either step 2 or step 3 and unit appears dead: a. Remove and then reapply power. b. Press reset (shown in Figure 2-5). c. Observe the two LEDs flashing for about 60 seconds. d. Green LED should be lit after 60 seconds. e. Touch sensing element with your finger. f. Output should change state. If so, circuit board is working properly. g. Reinstall instrument and press reset. 7. If ThePoint fails all of above tests, in most cases instrument is faulty. Use replacement electronic unit to determine the fault. Consult factory. 16 ThePoint™ Series Troubleshooting 3.3 Over Range 3.4 Under Range 3.5 Testing Integral Cable If the Green LED is flashing, the instrument has detected the uncovered sensing element capacitance exceeds the limits of the transmitter. Consult factory instructions. If the Red LED is flashing, the instrument has detected the sensing element capacitance is too small. Consult factory for sensing element capacitor values. Ohmmeter CAP & ELECTRONIC UNIT REMOVED FOR ACCESS TO EXPOSE INTEGRAL CABLE REMOVE CABLE TO EXPOSE TOP OF SENSING ELEMENT Shield Center Wire Center Wire Shield Figure 3-2 Testing Integral Cable Ohmmeter Shield Shield Center Wire Center Wire Ohmmeter Shield Center Wire 17 Shield Center Wire ThePoint™ Series 3.6 Troubleshooting Testing Remote Cable CHECK FOR SHORTS OHMMETER 8 CENTER - SHIELD SHIELD - GROUND 8 8 8 CENTER - GROUND 0 OHMS OHMS OHMS Correct Reading = OPEN Circuit Figure 3-3 Testing Remote Cable No Connection CHECK FOR CONTINUITY OHMMETER CENTER - GROUND 8 0 CENTER - SHIELD 0 0 0 OHMS OHMS OHMS SHIELD - GROUND Shorted wires should read 0 ohms Short out two conductors 3.7 Factory Assistance AMETEK Drexelbrook can answer any questions about ThePoint series instrument. Call Customer Service at 1-800-553-9092 (US and Canada) or +1- 215-674-1234 (International). If you require assistance and attempts to locate the problem have failed: • Contact your local Drexelbrook representative, • Call the Service department toll-free at 1-800527-6297 US and Canada) or +1-215-674-1234 (International), • FAX the Service department at 215-443-5117, or • E-Mail to drexelbrook.service@ametek.com Please provide the following information: • • • • • • • • • Instrument Model Number Sensing Element Model Number and Length Original Purchase Order Number Material being measured Temperature Pressure Agitation Brief description of the problem Checkout procedures that have failed 18 ThePoint™ Series Troubleshooting 3.8 Field Service 3.9 Customer Training Trained field servicemen are available on a time-plusexpense basis to assist in start-ups, diagnosing difficult application problems, or in-plant training of personnel. Contact the service department for further details. Periodically, AMETEK Drexelbrook instrument training seminars for customers are held at the factory. These sessions are guided by Drexelbrook engineers and specialists, and provide detailed information on all aspects of level measurement, including theory and practice of instrument operation. For more information write to: AMETEK Drexelbrook, Communications/ Training Group or call 215674-1234. 3.10 Equipment Return In order to provide the best service, any equipment being returned for repair or credit must be pre-approved by the factory. In many applications, sensing elements are exposed to hazardous materials. • OSHA mandates that our employees be informed and protected from hazardous chemicals. • Material Safety Data Sheets (MSDS) listing the hazardous materials to which the sensing element has been exposed MUST accompany any repair. • It is your responsibility to fully disclose all chemicals and decontaminate the sensing element. To obtain a return authorization (RA#), contact the Service department at 1-800-527-6297 (US and Canada) or +1-215674-1234 (International). Please provide the following information: • • • • • • • • Model Number of Return Equipment Serial Number Original Purchase Order Number Process Materials to which equipment has been exposed MSDS sheets for any hazardous materials Billing Address Shipping Address Purchase Order Number for Repairs Please include a purchase order even if the repair is under warranty. If repair is covered under warranty, you will not be charged. Ship equipment freight prepaid to: Ametek-drexelbrook. 205 Keith Valley Road Horsham, Pa 19044-1499 COD shipments will not be accepted. 19 ThePoint™ Series SECTION 4: Specifications SPECIFICATIONS Technology: RF/ Capacitance Calibration: None Modes of Operation: High and Low level Repeatability: 2mm (0.08 inch) conductive liquids Response Time: less than 1 second Time Delay: 0 to 60 seconds forward and reverse acting Ambient Electronics: -40 to 70°C (-40 to 158°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Indicators: LEDs Green Power Red Alarm Power supply: 13 to 30 Vdc Power consumption: 1 watt maximum Loop Current: 8mA Alarm, 16 mA Normal or (Field-Selectable) 8mA Normal, 16 mA Alarm Housing (electronics): Powder-coated aluminum with two cable entries Cable entry: M20 x 1.5 or 3⁄4-inch NPT Ingress Protection: IP66 NEMA 4X Approvals Pending: 21 Pending ThePoint™ Series SECTION 5: Approvals Available APPROVALS AVAILABLE Equipment Ratings Intrinsically Safe for use in Class I, II, and, III, Division 1, Groups A, B, C, D, E, F and G in accordance with Entity requirements and Control Drawing 420-0004-220-CD; Nonincendive for use in Class I, Division 2, Groups A, B, C, and D; Suitable for use in Class II and III, Division 2, Groups F and G; Explosionproof for use in Class I, Division 1, Groups A, B, C, and D; Dust-Ignition proof for Class II and III, Division 1, Groups E, F, and G; Indoor and Outdoor, (Type 4, 4X, IP66) Hazardous (Classified) locations with Intrinsically Safe Connections to Class I, II, and III, Division 1, Groups A, B, C, D, E, F, and G Hazardous (Classified) Locations in accordance with Entity requirements and Control Drawing 420-0004-220-CD. Ui = 30U Ii = 140mA Pi = 1w Ci = 0 Li = 159uH 205 KEITH VALLEY RD. HORSHAM, PA 19044 U.S.A. +1-215-674-1234 WWW.DREXELBROOK.COM TM PXTX 2 -INTEGRAL SERIES ThePoint MODEL NUMBER LOCATED INSIDE HOUSING SERIAL NO.: ACR-XXXXXX INPUT VOLTAGE: 13-30 VDC POWER: 1W ENCLOSURE TYPE: IP 66 -300 C <_ Tamb <_ +700C YEAR OF MANUFACTURE: SEE INSIDE 270-0101-837 ATEX - NEMKO 04ATEX1233X -30°C < _ T Amb < _ +70°C Ui = 30V Ii = 140mA Pi = 1W Ci = 0 Li = 159uH II 1 GD EEx ia IIC T5,...T2 T900C NEMKO 04 ATEX 1233X INSTALL PER 420-0004-221-CD Install Per 420-0004-221-CD 0344 Ui = 30U Ii = 140mA Pi = 1w Ci = 0 Li = 159uH DO NOT OPEN WHEN AN EXPLOSIVE WARNING GAS/DUST ATMOSPHERE MAY BE PRESENT REFERENCE INSTRUCTION MANUAL FOR LIVE MAINTENANCE PROCEDURES POSSIBLE SHOCK HAZARD WITH COVER REMOVED 205 KEITH VALLEY RD. HORSHAM, PA 19044 U.S.A. +1-215-674-1234 WWW.DREXELBROOK.COM TM PXTX 2 -REMOTE SERIES MODEL NUMBER LOCATED INSIDE HOUSING SERIAL NO.: ACS-XXXXXX INPUT VOLTAGE: 13-30 VDC POWER: 1W ENCLOSURE TYPE: IP 66 -300 C <_ Tamb <_ +700C YEAR OF MANUFACTURE: SEE INSIDE 270-0101-840 DREXELBROOK ThePoint II 1 GD EEx ia IIC T90°C T5...T2 Ui = 30V Ii = 140mA Pi = 1W Ci = 0 Li = 159uH II 1 GD EEx ia IIC T5, 900C 0344 NEMKO 04 ATEX 1233X INSTALL PER 420-0004-221-CD DO NOT OPEN WHEN AN EXPLOSIVE WARNING GAS/DUST ATMOSPHERE MAY BE PRESENT REFERENCE INSTRUCTION MANUAL FOR LIVE MAINTENANCE PROCEDURES POSSIBLE SHOCK HAZARD WITH COVER REMOVED DREXELBROOK 23 0344 ThePoint™ Series SECTION 6: 6.1 Control Drawings CONTROL DRAWINGS FM Control Drawings 25 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 26 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 27 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 28 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 29 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 30 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 31 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 32 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 33 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 34 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 35 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 36 ThePoint™ Series 6.1 Control Drawings FM Control Drawings (Continued) 37 ThePoint™ Series 6.2 Control Drawings ATEX Control Drawings 39 ThePoint™ Series 6.2 Control Drawings ATEX Control Drawings (Continued) 40 ThePoint™ Series 6.2 Control Drawings ATEX Control Drawings (Continued) 41 ThePoint™ Series 6.2 Control Drawings ATEX Control Drawings (Continued) 42 ThePoint™ Series 6.2 Control Drawings ATEX Control Drawings (Continued) 43 ThePoint™ Series Appendix A Shortening or Lengthening Sensing Element CAUTION: The insulation length of either Flush Sensing Elements or Insulated Sensing Elements can Not be changed. Cable Sensing Elements can only be shortened. Instructions are included with each unit. The Need Sometimes your application calls for probe lengths other than the standard 18-inch or longer insertion lengths supplied. Shortening the sensing element is quite simple and can be done in the field. Lengthening the sensing element, however, is more difficult because the metal rod, typically 304SS or 316SS, must be welded. Before making any Adjustments: 1. 2. 3. 4. 5. Insulators Note: Cote-Shield element must NEVER be modified. Read the following instructions thoroughly. Remove power. Disconnect the electronics. Protect electronics from any static discharge. Protect electronics from any heat. Shortening The bare metal center rod of the sensing element can be shortened with a hacksaw. Be careful not to cut either of the two insulators. See Figure on this page. In applications using conductive or water-based materials, shortening is not a problem. Leave a minimum bare metal center rod length of two (2)inches. For dry granular materials, such as powder, sand, corn, clinker, etc., you must leave a minimum bare metal center rod length of eight (8)inches. Consult the factory Insertion Length before shortening beyond this point. (18" or 36" std.) Lengthening Center Rod Note: Any changes to probe length after calibration requires recalibration to ensure proper operation. To lengthen the sensing element,an extension rod can be welded onto the end of the bare metal center rod. Make sure that the extension rod is the same metal as the sensing element. An alternate option is to add a pipe coupling and a section of metal pipe after threading the tip of the sensing element. In this case, the metal pipe need not be identical to the metal of the sensing element. A1 An ISO 9001 Certified Company 205 Keith Valley Road, Horsham, PA 19044 US and Canada: 1-800-553-9092 International: +1 215-674-1234 24-Hour Service: +1 215-527-6297 Fax: +1 215-674-2731 E-mail: drexelbrook.info@ametek.com Website: www.drexelbrook.com